VAV1507 VAV Controller BACnet Protocol

Implementation Conformance Statement

JC-VAV1507-0

Building Technologies & Solutions LIT-12013604


www.johnsoncontrols.com
2020-08-13
2 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement
Contents
Document Introduction................................................................................................................................. 5
Contents
Annex A - Protocol Implementation Conformance Statement (Normative)........................................... 5
Product Description............................................................................................................................. 5
BACnet Standardized Device Profile (Annex L)........................................................................................... 5
BACnet Interoperability Building Blocks (BIBBs) (Annex K)..................................................................... 6
Segmentation Capability............................................................................................................................... 6
Standard Object Types Supported............................................................................................................... 7
Analog Input........................................................................................................................................ 8
Analog Value........................................................................................................................................ 9
Binary Input........................................................................................................................................ 10
Binary Output..................................................................................................................................... 11
Binary Value....................................................................................................................................... 13
Device.................................................................................................................................................. 14
File....................................................................................................................................................... 17
Multistate Value................................................................................................................................. 17
Network Port...................................................................................................................................... 19
Data Link Layer Options.............................................................................................................................. 20
Device Address Binding............................................................................................................................... 20
Networking Options.................................................................................................................................... 20
Character Sets Supported........................................................................................................................... 21
Communication Gateway (Annex H)......................................................................................................... 21
Network Security Options........................................................................................................................... 21

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 3


4 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement
Document Introduction
This document contains the Protocol Implementation Conformance Statement (PICS) and BACnet®
Interoperability Building Blocks (BIBBs) for the VAV1507 VAV Controller, JC-VAV1507-0, as required
by the ANSI/ASHRAE® Standard 135 for BACnet protocol.
The PICS is a written document created by the manufacturer of a device to identify the particular
options specified in the BACnet standard and implemented in the device.
BIBBs are collections of one or more BACnet services. This document includes a listing of the BIBBs
currently supported by the VAV1507.

Annex A - Protocol Implementation Conformance


Statement (Normative)
Table 1: BACnet Protocol Implementation Conformance Statement
Date August 2020
Vendor Name Johnson Controls
Product Name VAV1507 VAV Controller
Product Model Numbers JC-VAV1507-0
Application Software Version 10.5
Firmware Revision 9.0
BACnet Protocol Revision Version 1, Rev. 18

Product Description
The VAV1507 is a variable air volume controller that runs a single-duct, cooling-only software
application. The controller features an integral digital differential pressure transducer and an
integral damper actuator.
The VAV1507 operates as a BACnet® Application Specific Controller (B-ASC) and integrates into
Johnson Controls® and third-party BACnet systems.

BACnet Standardized Device Profile (Annex L)


BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Other (B-Other)

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 5


BACnet Interoperability Building Blocks (BIBBs)
(Annex K)
The following table lists all BIBBs that are supported. The table is divided into BIBBs required for
the Controller (B-ASC) profile, followed by additional BIBBs that are supported, but not required, for
the profile.
Table 2: BACnet B-ASC BIBBs Support
BIBB Name (A = Initiates and B = Executes) Designation
Required for the B-ASC profile
Data Sharing - Read Property - B DS-RP-B
Data Sharing - Write Property - B DS-WP-B
Device Management - Dynamic Device Binding - B DM-DDB-B
Device Management - Dynamic Object Binding - B DM-DOB-B
Device Management - Device Communication Control - B DM-DCC-B
Not required for the B-ASC profile
Data Sharing - Read Property - A DS-RP-A
Data Sharing - Read Property Multiple - B DS-RPM-B
Data Sharing - Write Property - A DS-WP-A
Data Sharing - Write Property Multiple - B DS-WPM-B
Data Sharing - Change Of Value - B DS-COV-B
Data Sharing - Change Of Value Property - B DS-COVP-B
Data Sharing - Change Of Value Unsubscribed - B DS-COVU-B
Executes ReadRange Executes ReadRange
Device Management - Dynamic Device Binding - A DM-DDB-A
Device Management - Time Synchronization - B DM-TS-B
Device Management - UTC Time Synchronization - B DM-UTC-B
Device Management - Reinitialize Device - B DM-RD-B
Device Management - Restart - B DM-R-B
Device Management - List Manipulation - B DM-LM-B

Segmentation Capability
Segmented requests supported Window Size: 1
Segmented responses supported Window Size: 1

6 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Standard Object Types Supported
The following is a list of the standard object types as defined by ASHRAE that are supported. See the
appropriate supported object type section in this document for details.

• Analog Input

• Analog Value

• Binary Input

• Binary Output

• Binary Value

• Device

• File

• Multistate Value

• Network Port

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 7


Analog Input
Dynamically Creatable: No
Dynamically Deletable: No
Table 3: Analog Input
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
1
PRESENT_VALUE X 85 X

1
STATUS_FLAGS X 111
EVENT_STATE X 36
OUT_OF_SERVICE X 81 X
UNITS X 117 X 0 to 65,535 value
COV_INCREMENT X 22 X any value > = 0
40 characters
DESCRIPTION X 28 X
max
20 characters
DEVICE_TYPE X 31 X
max
MIN_PRES_VALUE X 69 X
MAX_PRES_VALUE X 65 X
1
RELIABILITY X 103 X

RESOLUTION X 106
UPDATE_INTERVAL X 118 X 0 to 1,000,000
ALARM_STATE X 1006 Enumerated
DISPLAY_PRECISION X 661 Enumerated X 0 to 12
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
OFFLINE X 913 Boolean
SAB_MAC_ADDR X 3645 Unsigned
SLOT X 519 Unsigned
STATUS X 512 Enumerated
USE_COV_MIN_SEND_TIME X 3930 Boolean X
FILTER_SETUP X 3407 Enumerated X 0 to 4
ANTI_SPIKE X 722 Boolean X
LOWPASS_FILTER_ENABLE X 3542 Boolean X
MINUS_20_DB_FREQ X 3543 Real X 0.01 to 0.30
PROCESS_ID X 3422 Enumerated X 0 to 20
SPIKE_FRACTION X 725 Real X 0.0001 to 1.0
TIME_CONSTANT X 3164 Real X
ENDPOINT_TOLERANCE X 3544 Real X 0.0 to 100.0
FIELD_OFFSET X 2179 Real X
INPUT_RANGE_HIGH X 1294 Real X any value > = 0
INPUT_RANGE_LOW X 1293 Real X any value > = 0

8 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Table 3: Analog Input
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OFFSET X 956 Real X
OUTPUT_RANGE_HIGH X 1296 Real X
OUTPUT_RANGE_LOW X 1295 Real X
FIELD_UNITS X 2180 Enumerated
HARDWARE_VALUE X 1433 Real
SETUP X 518 Enumerated X
Character
USER_NAME X 2390
String
1 Writable when Out_Of_Service is true.

Analog Value
Dynamically Creatable: No
Dynamically Deletable: No
Table 4: Analog Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
OUT_OF_SERVICE X 81
STATUS_FLAGS X 111
EVENT_STATE X 36
PRESENT_VALUE X 85 X
UNITS X 117 X 0 to 65,535
RELINQUISH_DEFAULT X 104 X
PRIORITY_ARRAY X 87
CURRENT_COMMAND_PRIORITY X 431
1
COV_INCREMENT X 22 X any value > = 0
1
40 characters
DESCRIPTION X 28 X
max
MIN_PRES_VALUE X 69 X
MAX_PRES_VALUE X 65 X
1
RELIABILITY X 103 X

DISPLAY_PRECISION X 661 Enumerated X 0 to 12


ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
ALARM_STATE X 1006 Enumerated
2
ATTRIBUTE_ID X 3365 Enumerated
2
2
COMMAND_SIGNATURE X 3366 Unsigned
2
DEFAULT_ATTRIBUTE_VALUE X 3633 Boolean
2
LAST_RELIABLE_CMD_SIG X 3362 Unsigned

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 9


Table 4: Analog Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
2
PEER_REFERENCE X 748 Complex X
2
DIRECTION X 746 Boolean
2
ERROR_STATUS X 576 Boolean
2
FAILSOFT X 2567 Boolean X
2
IN_TEST X 3368 Boolean
2
CURRENT_CMD_SIG X 3378 Unsigned
2
CURRENT_RELIABILITY X 3377 Enumerated
2
STANDARD_NAME X 3670 Enumerated
RESTORE_COMMAND_PRIORITY X 721 Bit String X
BACNET_EXPOSED X 3807 Boolean X
2
LAST_RELIABLE_VALUE X 3369 Real
2
DEFAULT_VALUE X 3113 Real X
2
TEST_VAL X 3371 Real
2
INPUT X 513 Real
2
OUTPUT X 663 Real
2
CURRENT_VALUE X 3376 Real
2
OFFLINE X 913 Boolean
STATUS X 512 Enumerated
2
USE_COV_MIN_SEND_TIME X 3930 Boolean X
Character
USER_NAME X 2390
String
1 Not writable in all instances.
2 Not Present in all instances.

Binary Input
Dynamically Creatable: No
Dynamically Deletable: No
Table 5: Binary Input
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
OUT_OF_SERVICE X 81 X
STATUS_FLAGS X 111
EVENT_STATE X 36
1
PRESENT_VALUE X 85 X
1
POLARITY X 84 X
40 characters
INACTIVE_TEXT X 46 X
max
40 characters
ACTIVE_TEXT X 4 X
max
COS_TIME X 16

10 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Table 5: Binary Input
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
0 to
COS_COUNT X 15 X
4,294,967,295
STATE_COUNT_RESET X 115 X
0 to
ELAPSED_ACTIVE_TIME X 33 X
4,294,967,295
ACTIVE_TIME_RESET X 114 X
40 characters
DESCRIPTION X 28 X
max
20 characters
DEVICE_TYPE X 31 X
max
1
RELIABILITY X 103 X

ALARM_STATE X 1006 Enumerated


ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
OFFLINE X 913 Boolean
STATUS X 512 Enumerated
SAB_MAC_ADDR X 3645 Unsigned
SLOT X 519 Unsigned
STATES_TEXT X 931 Enumerated X
Character
USER_NAME X 2390
String
1 Writable when Out_Of_Service is true.

Binary Output
Dynamically Creatable: No
Dynamically Deletable: No
Table 6: Binary Output
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
OUT_OF_SERVICE X 81 X
STATUS_FLAGS X 111
EVENT_STATE X 36
POLARITY X 84 X
PRESENT_VALUE X 85 X
RELINQUISH_DEFAULT X 104 X
PRIORITY_ARRAY X 87
CURRENT_COMMAND_PRIORITY X 431
40 characters
ACTIVE_TEXT X 4 X
max
40 characters
INACTIVE_TEXT X 46 X
max

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 11


Table 6: Binary Output
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
COS_TIME X 16
0 to
COS_COUNT X 15 X
4,294,967,295
STATE_COUNT_RESET X 115 X
0 to
ELAPSED_ACTIVE_TIME X 33 X
4,294,967,295
ACTIVE_TIME_RESET X 114 X
MIN_OFF_TIME X 66 X 0 to 604,800
MIN_ON_TIME X 67 X 0 to 604,800
40 characters
DESCRIPTION X 28 X
max
20 characters
DEVICE_TYPE X 31 X
max
1
RELIABILITY X 103 X

1
ALARM_STATE X 1006 Enumerated
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
OFFLINE X 913 Boolean
RESTORE_COMMAND_PRIORITY X 721 Bit String X
STATUS X 512 Enumerated
SAB_MAC_ADDR X 3645 Unsigned
SLOT_A X 990 Unsigned
SLOT_B X 991 Unsigned
STATES_TEXT X 931 Enumerated X
Character
USER_NAME X 2390
String
HEAVY_EQUIP_DELAY X 516 Unsigned X 0 to 255
HED_CONTROLLER X 517 Unsigned X 1 to 5
MINIMUM_CYCLE_TIME X 2199 Unsigned X 0 to 65,535
SETUP X 518 Enumerated
PULSE_WIDTH X 600 Real X 0 to 100
OUTPUT X 663 Boolean
1 Writable when Out_of_Service is true.

12 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Binary Value
Dynamically Creatable: No
Dynamically Deletable: No
Table 7: Binary Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
OUT_OF_SERVICE X 81
STATUS_FLAGS X 111
EVENT_STATE X 36
PRESENT_VALUE X 85 X
40 characters
INACTIVE_TEXT X 46 X
max
40 characters
ACTIVE_TEXT X 4 X
max
1
COS_TIME X 16
1
1 0 to
COS_COUNT X 15 X
4,294,967,295
1
STATE_COUNT_RESET X 115
1 0 to
ELAPSED_ACTIVE_TIME X 33 X
4,294,967,295
1
ACTIVE_TIME_ RESET X 114
1
MIN_OFF_TIME X 66 X 0 to 604,800
1
MIN_ON_TIME X 67 X 0 to 604,800
1
PRIORITY_ARRAY X 87
1
RELINQUISH_DEFAULT X 104 X
CURRENT_COMMAND_PRIORITY X 431
40 characters
DESCRIPTION X 28 X
max
2
RELIABILITY X 103 X
2
ALARM_STATE X 1006 Enumerated
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
ATTRIBUTE_ID X 3365 Enumerated
COMMAND_SIGNATURE X 3366 Unsigned
DEFAULT_ATTRIBUTE_VALUE X 3633 Boolean
LAST_RELIABLE_CMD_SIG X 3362 Unsigned
PEER_REFERENCE X 748 Complex X
DIRECTION X 746 Enumerated
ERROR_STATUS X 576 Enumerated
FAILSOFT X 2567 Boolean X
IN_TEST X 3368 Boolean
CURRENT_CMD_SIG X 3378 Unsigned

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 13


Table 7: Binary Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
CURRENT_RELIABILITY X 3377 Enumerated
STANDARD_NAME X 3670 Enumerated
BACNET_EXPOSED X 3807 Boolean X
LAST_RELIABLE_VALUE X 3369 Boolean
DEFAULT_VALUE X 3113 Boolean X
TEST_VAL X 3371 Boolean
INPUT X 513 Boolean
OUTPUT X 663 Boolean
CURRENT_VALUE X 3376 Boolean
OFFLINE X 913 Boolean
RESTORE_COMMAND_PRIORITY X 721 Bit String X
STATUS X 512 Enumerated
STATES_TEXT X 931 Enumerated
Character
USER_NAME X 2390
String
1 Not present in all instances.
2 Not writable in all instances.

Device
Dynamically Creatable: No
Dynamically Deletable: No
Table 8: Device
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
APPLICATION_SW_VERSION X 12 X 5 characters
1
NUMBER_OF_APDU_RETRIES X 73 X 2 to 10
1
1
APDU_TIMEOUT X 11 X 1,000 to 65,535
MAX_APDU_LENGTH_ACCEPTED X 62 X Any value >50
LOCATION X 58 X 56 characters
1
APDU_SEGMENT_TIMEOUT X 10 X 1,000 to 65,535
DAYLIGHT_SAVINGS_STATUS X 24
40 characters
DESCRIPTION X 28 X
max
LOCAL_DATE X 56
LOCAL_TIME X 57
UTC_OFFSET X 119 X -900 to 900
LAST_RESTART_REASON X 196
TIME_OF_DEVICE_RESTART X 203
RESTART_NOTIFICATION_RECIPIENTS X 202 X
MAX_INFO_FRAMES X 63 X 1 to 255
MAX_MASTER X 64 X 4 to 127

14 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Table 8: Device
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
MAX_SEGMENTS_ACCPT X 167
ACTIVE_COV_SUBSCRIPTIONS X 152
ALARM_STATE X 1006 Enumerated
ARCHIVE_DATE X 849 Date
ARCHIVE_STATUS X 1187 Unsigned
ARCHIVE_TIME X 850 Time
CPU_USAGE X 2583 Real
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
EXTENDED_PROTO_VERSION X 2291 Unsigned
FLASH_USAGE X 2584 Real
ITEM_REFERENCE X 32527 String
JCI_STATUS X 847 Enumerated
MEMORY_USAGE X 2581 Real
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
OBJECT_MEMORY_USAGE X 2582 Real
STATUS X 512 Enumerated
BACNET_BROADCAST_RECEIVE_RATE X 745 Unsigned
DEFAULT_BASE_UNITS X 2206 Enumerated
ESTIMATED_FLASH_AVAILABLE X 2395 Real
LAST_IDLE_SAMPLE X 30082 Real
MAX_MESSAGE_BUFFER X 848 Unsigned X 98 to 65,535
USER_NAME X 2390 String
PCODE X 1320 String
EVENTS_LOST X 1479 Unsigned
STANDARD_TIME_OFFSET X 1017 Signed X -900 to 900
DAYLIGHT_SAVING_TIME_OFFSET X 1093 Signed X -900 to 900
STANDARD_TIME_START X 988 Complex X
DAYLIGHT_SAVING_TIME_START X 1040 Complex X
ACCEPT_BACNET_TIME_SYNC X 4970 Boolean
LAST_BACNET_TIME_SYNC_RECEIVED X 5728 Complex
SUPERVISORY_DEVICE_ONLINE X 3653 Boolean X
SUPERVISORY_OFFLINE_TIMEOUT X 6002 Unsigned X 1 to 255
30,000,001 to
NEXT_AVAILABLE_OID X 787 Unsigned X
41,799,991
HAS_UNBOUND_REFERENCES X 767 Boolean
SURROGATE_CACHE_CNT X 571 Unsigned
SURROGATE_CACHE_MAX X 639 Unsigned
ASSET_VERSIONS X 4960 Complex
LOAD_BALANCER_LEVEL X 4722 Enumerated
TIMER_DB_SIZE X 733 Unsigned
TIMER_USED X 734 Unsigned

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 15


Table 8: Device
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
TIMER_PEAK X 735 Unsigned
TIMER_MESSAGES_ABORTED X 4959 Unsigned
BACNET_OID_ALLOCATED X 1291 Unsigned
BACNET_OID_USED X 1292 Unsigned
SIGN_PRI_DB_SIZE X 730 Unsigned
SIGN_PRI_USED X 731 Unsigned
SIGN_PRI_PEAK X 732 Unsigned
BACNET_ENCODE_TYPE X 32578 Enumerated X 0 to 3
ROUTING_MODE X 4307 Enumerated X 0 to 2
BACNET_INTEGRATED_OBJECTS X 4302 Enumerated
BACNET_COMPATIBLE X 4581 Boolean X
SEND_I_AM_RATE X 579 Unsigned X 60 to 86,400
DEFAULT_TIME_ZONE X 32583 Enumerated X 1 to 1,101
TIME_ZONE X 1403 Enumerated X 1 to 1,101
LOCAL_TIME_ZONE X 1404 Enumerated
FC_MULTICAST_RESPONDER X 3390 Unsigned X
FC_WAIT_BEFORE_POLLING X 3391 Unsigned X
SUPERVISOR_MAC_ADDRESS X 3652 Unsigned
LIBRARY_PART_ID X 3295 String
APPLICATION_CLASS_SET_VERSION X 4128 Unsigned
DEVICE_MODEL_CLASS_SET_VERSION X 4129 Unsigned
COV_MIN_SEND_TIME X 3929 Unsigned X 10 to 255
COV_TRANSMITS_PER_MINUTE X 651 Unsigned
CONTROL_SEQUENCE_IN_TEST X 3651 Unsigned X
END_OF_LINE X 603 Boolean
DEVICE_ADDRESS X 876 Unsigned
FC_BUS_COMMUNICATION_MODE X 4400 Enumerated
SYSTEM_TYPE X 3900 Unsigned
SYSTEM_CONFIGURATION X 3899 Unsigned
1 Write does not take effect until after restart.

16 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


File
Note:

• File objects can only be modified by replacing the entire file.


• File objects must be written sequentially.

Dynamically Creatable: No
Dynamically Deletable: No
Table 9: File
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
FILE_TYPE X 43
MODIFICATION_DATE X 71
READ_ONLY X 99
FILE_ACCESS_METHOD X 41
ARCHIVE X 13 X
1
FILE_SIZE X 42 X
1
40 characters
DESCRIPTION X 28 X
max
Character
ITEM_REFERENCE X 32527
String
Character
USER_NAME X 2390
String
STATUS X 512 Enumerated
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
ALARM_STATE X 1006 Enumerated
MAX_FILE_SIZE X 3380 Unsigned
1 Can write zero (0) to file size but arbitrary truncation or expansion is not supported.

Multistate Value
Dynamically Creatable: No
Dynamically Deletable: No
Table 10: Multistate Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
OBJECT_NAME X 77
OUT_OF_SERVICE X 81
PRESENT_VALUE X 85 X
STATUS_FLAGS X 111
EVENT_STATE X 36
NUMBER_OF_STATES X 74

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 17


Table 10: Multistate Value
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
STATE_TEXT X 110 X
1
PRIORITY_ARRAY X 87

1
CURRENT_COMMAND_PRIORITY X 431
1
RELINQUISH_DEFAULT X 104 X
40 characters
DESCRIPTION X 28 X
max
RELIABILITY X 103
ALARM_STATE X 1006 Enumerated
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X 0 to 3
Character
ITEM_REFERENCE X 32527
String
OBJECT_CATEGORY X 908 Enumerated X 0 to 249
OFFLINE X 913 Boolean
STATUS X 512 Enumerated
1
ATTRIBUTE_ID X 3365 Enumerated
1
COMMAND_SIGNATURE X 3366 Unsigned
1
DEFAULT_ATTRIBUTE_VALUE X 3633 Boolean
1
LAST_RELIABLE_CMD_SIG X 3362 Unsigned
1
PEER_REFERENCE X 748 Complex X
1
DIRECTION X 746 Enumerated
1
ERROR_STATUS X 653 Boolean
1
FAILSOFT X 2567 Boolean X
1
IN_TEST X 3368 Boolean
1
CURRENT_CMD_SIG X 3378 Unsigned
1
CURRENT_RELIABILITY X 3377 Enumerated
1
STANDARD_NAME X 3670 Enumerated
BACNET_EXPOSED X 3807 Boolean X
1
LAST_RELIABLE_VALUE X 3369 Enumerated
1
DEFAULT_VALUE X 3113 Enumerated X
1
TEST_VAL X 3371 Enumerated
1
INPUT X 513 Enumerated
1
OUTPUT X 663 Enumerated
1
CURRENT_VALUE X 3376 Enumerated
Character
USER_NAME X 2390
String
RESTORE_COMMAND_PRIORITY X 721 Bit String X
STATES_TEXT X 931 Enumerated
1 Not present in all instances.

18 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Network Port
Dynamically Creatable: No
Dynamically Deletable: No
Table 11: Network Port
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
128 to
APDU_LENGTH X 399 X
65,535
CHANGES_PENDING X 416
LINK_SPEED X 420
NETWORK_NUMBER X 425 X 0 to 65,534
NETWORK_NUMBER_QUALITY X 426
NETWORK_TYPE X 427
OBJECT_NAME X 77
OUT_OF_SERVICE X 81
PROTOCOL_LEVEL X 482
RELIABILITY X 103
STATUS_FLAGS X 111
BACNET_COMMAND X 417 X
BACNET_MAC_ADDRESS X 423 X
DESCRIPTION X 28 X
LINK_SPEED_AUTONEGOTIATE X 422
MAX_INFO_FRAMES X 63 X 1 to 255
MAX_MASTER X 64 X 4 to 127
ACTIVE_BAUD_RATE X 2861 Enumerated
ALARM_STATE X 1006 Enumerated
CLEAR_STATISTICS X 2427 Boolean X
ENABLED X 673 Boolean X
EXECUTION_PRIORITY X 2197 Enumerated X
Character
ITEM_REFERENCE X 32527
String
JCI_NPO_APDU_RETRIES X 1851 Byte X 2 to 10
Unsigned 1,000 to
JCI_NPO_APDU_SEGMENT_TIMEOUT X 1849 X
Integer 65,535
Unsigned 1,000 to
JCI_NPO_APDU_TIMEOUT X 1850 X
Integer 65,535
JCI_NPO_CHANGES_PENDING_BITSTRING X 1852 Byte
JCI_NPO_PORT_TYPE X 1848 Enumerated
LATCH_STATISTICS X 2426 Boolean X
MULTICAST_RESPONDER X 30095 Byte X
OBJECT_CATEGORY X 908 Enumerated X
PORT_STATUS X 2866 Enumerated
PROT_ENG_OUT_RESOURCE X 2020 Unsigned
REPLY_TIMEOUT X 2865 Unsigned
SOFTWARE_ADDRESSING_ENABLED X 2863 Boolean

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 19


Table 11: Network Port
Property
Property Name Required Optional Proprietary Data Type Writable Range
ID
STATUS X 512 Enumerated
USAGE_TIMEOUT X 2864 Byte
Character
USER_NAME X 2390
String

Data Link Layer Options


BACnet IP (Annex J) __________________________________
BACnet IP (Annex J), Foreign Device __________________________________
ISO 8802-3, Ethernet (Clause 7) __________________________________
ATA 878.1, 2.5 MB ARCNET network (Clause 8) __________________________________
ATA 878.1, EIA-485 ARCNET network (Clause 8), baud rates: __________________________________
Auto (default), 9600; 19,200;
MS/TP master (Clause 9), baud rates:
38,400; 76,800
MS/TP slave (Clause 9), baud rates: __________________________________
Point-To-Point, EIA 232 (Clause 10), baud rates: __________________________________
Point-To-Point, modem (Clause 10), baud rates: __________________________________
LonTalk® protocol (Clause 11), medium: __________________________________
BACnet/ ZigBee® protocol (Annex O) __________________________________
Other: __________________________________

Device Address Binding


Is static device binding supported? (This is currently necessary for two-way
Yes No
communication with MS/TP slaves and certain other devices.)

Networking Options
Router, Clause 6: IP/MSTP MSTP/MSTP
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Does the BBMD support network address translation? Yes No

20 VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement


Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported
simultaneously.

IBM®/Microsoft® Double-Byte Character Set (DBCS)


ISO 10646 Universal Character Set-2 (UCS-2)
ISO 10646 (UCS-4)
ISO 10646 (UTF-8)
ISO 8859-1
Japanese Industrial Standard (JIS) X 0208

Communication Gateway (Annex H)


If this product is a communication gateway, describe the types of non BACnet equipment/
network(s) that the gateway supports:
None

Network Security Options


Non-secure Device - is capable of operating without BACnet Network Security
Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)
Multiple Application-Specific Keys:
Supports encryption (NS-ED BIBB)
Key Server (NS-KS BIBB)

VAV1507 VAV Controller BACnet Protocol Implementation Conformance Statement 21


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision and are subject to change without notice.