PowerSuite 26-Aug-2020 Loads and Steps Detail Report (CHICO)
PowerSuite 26-Aug-2020 Loads and Steps Detail Report (CHICO)
Project - CHICO
Comments -
Project Requirements
Emissions : No Preference
Step01 Light Load 1 1 15.0 15.79 15.0 15.79 None None 35.0 10.0 0.0
Step Summary 15.0 16.0 15.0 16.0 None None 35.0 10.0 0.0
Step02 Intake Pump Motor 1 25.0 27.78 25.0 27.78 None None 35.0 10.0 10.0
Step02 High Lift Pump Motor 1 146.67 162.97 146.67 162.97 None None 35.0 10.0 10.0
Step Summary 172.0 191.0 172.0 191.0 None None 35.0 10.0 10.0
Step03 Back Wash Pump 1 41.57 46.19 36.09 97.55 None None 35.0 10.0 0.0
Motor
Step03 Air Blowers 1 21.02 23.62 21.46 48.77 None None 35.0 10.0 0.0
Step Summary 63.0 70.0 58.0 146.0 None None 35.0 10.0 10.0
Project
Running Max Starting Cumulative Step Cumulative Peak
VTHD%
Project Summary
kW kVA kW kVA kW kVA kW kVA Limit
Emissions : No Preference
Running kVA : 276.4 Max. Step kVA : 190.8 In Step 2 Cumulative Step kVA : 352.9
Running NLL kVA : 190.8 Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 317.93
Step1
Running kVA : 16.0 Starting kVA : 16.0 Cumulative Step kVA : 16.0
Alternator kW : 15.0
Running Amps : 22.82 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step2
Running kVA : 191.0 Starting kVA : 191.0 Cumulative Step kVA : 207.0
Category : Motor
Running Amps : 40.14 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 35.0
Category : Motor
Running Amps : 235.51 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 205.34
Step3
Running kVA : 70.0 Starting kVA : 146.0 Cumulative Step kVA : 353.0
Alternator kW : 62.59
Category : Motor
Running Amps : 66.75 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Shaft kW : 37.0
Category : Motor
Running Amps : 34.13 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Shaft kW : 18.5