Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

MTAP 2 – Motor Test Access Panel

Offers
Increased Safety For Testing
Energized AC
Electric Motors

Reduces
Testing
time per
motor

Reduces
labour
cost

Increases
Savings

Avenir Technologies/Iqbal Ibrahim


NFPA 70E
2

For making connections on


live electrical circuits as per
NFPA 70E you have to wear
these PPE

Avenir Technologies/Iqbal Ibrahim


Spider Bite Near Ankle
3

Thermal Image of the


temperature of the ankle
after a spider bite

No body loves to be
bitten by a spider

Avenir Technologies/Iqbal Ibrahim


Why are we afraid of this?
4

Avenir Technologies/Iqbal Ibrahim


But not this?
5

Picture of a Low Voltage


Metering panel after Arc
flash.

Avenir Technologies/Iqbal Ibrahim


And not this?
6

Fingers burnt by Arc flash

Avenir Technologies/Iqbal Ibrahim


Arc Flash Explosion Damage
7

Result of an Arc
Flash Explosion

Avenir Technologies/Iqbal Ibrahim


Arch Flash: Clothes Burned
8

Think about the


person who
was in it

Avenir Technologies/Iqbal Ibrahim


Arc Flashes
9

• Mainly occur in electrical devices that are


480 volt and up.

• Motor control centers and substations are a


great source of faults.

Avenir Technologies/Iqbal Ibrahim


Arc Flash Explosion
10

• Vaporized metal and ionized • – Forms the arc path through air
air: • – Expands to form blast wave

• Temperatures reach 35,000°F+

• Energy levels can reach 20-100


Cal/cm2

• Duration is less than 7/10ths of


a second

• Proportional to energy and


distance.

Avenir Technologies/Iqbal Ibrahim


Damages from Arc Flash
11

• High temperatures burns to skin

• Melting of synthetic clothing to skin

• UV and IR burns to eyes and skin

• Temporary or permanent blindness

• Pressure Wave can knock you down

• Decibel can reach 160 DB

• Neurological effect of a magnetic field

• Temporary or permanent personality changes

UETS/ AVERNR/Iqbal Ibrahim


The End Results
12

Avenir Technologies/Iqbal Ibrahim


Solution: Install MTAP
13

Time consuming tag


out and lock out
procedures are
eliminated and in
seconds you can
connect and collect
accurate data to
determine your motor
health.

MTAP2 meets both OSHA and NFP 70E


definitions for safe voltage
Avenir Technologies/Iqbal Ibrahim
No More Direct Connection
14

Tester Voltage Leads and


current probes direct
connections

Avenir Technologies/Iqbal Ibrahim


No More Direct Connection
15

Voltage Leads

Current
Probes

MCC

Avenir Technologies/Iqbal Ibrahim


MTAP 2 – Motor Test Access Panel
16

MTAP 2 Board

Avenir Technologies/Iqbal Ibrahim


PdMA’s Answer to Safe Testing
Voltage connections

CT Cable Connections

Port connection
Direct connection to MCEmax Tester / MTAP2 One time Installation
Avenir Technologies/Iqbal Ibrahim
PdMA’s Answer to Safe Testing

Without MTAP2 With MTAP2 Installed


MTAP 2 Installation
19

All MTAP 2 Installed in a separate panel

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Installation
20

MTAP 2 Installed in a
separate panel

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Provides protection from Arc Flash
21

Before MTAP2 you need PPE to protect against Arc Flash


while connecting test leads & current probes

After installing MTAP2 there is no need to open the MCC door to make connections.
Test cable is connected to the connector installed on MCC Door

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Installation
22

MTAP 2 Test Port


to connect
MCEmax

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Specifications
23

Specifications

 Voltage at MCC test port: 30V RMS nominal, <50V peak

 Input voltages (select one when ordering): 120, 240, 480, 600 VAC

 Motors rated over 600V, require the 120V/5A model and existing metering
PT’s and CT’s

 Current input terminal strip (0-3V RMS input), current represented by voltage
Signal

 MCC test port: Circular military style, 1-inch diameter, extends out ½ inch

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Specifications
24

Physical Dimensions

 Size: 7.25 x 5.6 inches x 3.5 inches deep

 Weight: less than 3 lbs.

 Mounts to DIN rail via 2 mounting brackets

 Mounting brackets provided, DIN rail not provided

 Optional Mounting: Mount circuit board directly to MCC

 4 mounting feet (must specify if required)

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Specifications
25

Circuit Protection and Isolation

 3 primary and 3 secondary fast-acting fuses on potential


transformer

 Transorbs used to limit voltage for current and voltage signals to


test port

 Electrical Isolation: potential transformer rated 2000V DC High Potential


test

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Specifications
26

Standards and Certifications

 Designed to UL508, UL845, and CSA 22.2 #14 standards

 CSAus certification

 Meets NFPA 70E guidelines for safe voltage level

Avenir Technologies/Iqbal Ibrahim


MTAP 2 Specifications – CT Information
27

CT Primary Current Rating 5A 100 A 400 A

CT Opening Size (inside 0.3 1.25 1.25


diameter in inches)
Design Iron Core Donut Iron Core Donut Iron Core Donut

Voltage Class (max continuous 600V 600V 600V


voltage)
Burden Resistor Built-in Built-in Built-in

Output (mV/A) 66.7 mV / A 3.3 mV / A 0.833 mV / A

Burden in VA at rated 0.003 0.04 0.14


current
Burden in VA at 10X rated 0.28 3.63 14.5
current
Wire Length 8 ft 8 ft 8 ft

ANSI / IEEE Standard # IEEE-C57.13 IEEE-C57.13 IEEE-C57.13

CSA Standard # CAN3-C13-M83 CAN3-C13-M83 CAN3-C13-M83

Avenir Technologies/Iqbal Ibrahim


MTAP 2 – Information Required when ordering
28

When requesting a quote for MTAP 2 or Placing order, please provide the
following information:

Specify Motor Voltage, FLA and HP

Specify input voltage and CT current rating.

Requires one external cable to connect MCC test port

Cable Part Number ASY-00321

UETS/ AVERNR/Iqbal Ibrahim


MTAP 3
29

Full range of MCEmax online tests including Power, Inrush / Start-


up, Demod, Rotor Evaluation and Eccentricity

Avenir Technologies/Iqbal Ibrahim


MTAP 3 – Current Only
30

MTAP3 offers the ability to safely capture data in many of the smallest
enclosures where the MTAP2 cannot be installed or the PT’s are not available
at the motor MCC.

FEATURES
• In seconds you are able to collect accurate data to determine your motor
health
• Eliminate time consuming tag-out and lock-out procedures
• Nomex PPE NOT required
• Full range of MCEMAX online tests including Power, In-Rush/Start-Up, Demod,
Rotor Evaluation, and Eccentricity
• Meets OSHA and NFPA 70E definition for safe voltage
• Meets UL 508 and CSA 22.2 #14 standards .

Avenir Technologies/Iqbal Ibrahim


MTAP 3 – Current Only
31

With the current-only MTAP3, you can choose from one of four standard
ranges of CT’s – MTAP 3 CT’s are ordered as a separate line item
CT Primary Current Rating 5A 100A 400A
CT Opening Size (inside
diameter in inches) 0.3 1.25 1.25

Design Iron Core Donut Iron Core Donut Split-Core


Voltage Class (max
continuous voltage) 600V 600V 600V

Burden Resistor Built in Built in Built in


Output (mV/A) 66.7 mV / A 3.3 mV / A 0.833 mV / A
Burden in VA at rated current 0.003 0.04 0.0177
Burden in VA at 10X rated
current 0.28 3.63 1.778

Wire Length 8 ft 8 ft 8 ft
ANSI / IEEE Standard # IEEE-C57.13 IEEE-C57.13 IEEE-C57.13
CSA Standard # CAN3-C13-M83 CAN3-C13-M83 CAN3-C13-M83

Avenir Technologies/Iqbal Ibrahim

You might also like