Professional Documents
Culture Documents
Maindocument-1 (23M-03-072) - Original - 0 Extendid-ICT PEP PLN 2022 - Bus Voltage Control Final
Maindocument-1 (23M-03-072) - Original - 0 Extendid-ICT PEP PLN 2022 - Bus Voltage Control Final
2, XX-YY (2019)
ASTESJ
www.astesj.com
ISSN: 2415-6698
Minimum Static VAR Compensation Capacity for Bad Voltage Drop Buses in Power Systems
Corresponding Author*, ABC1, ABC2, ABC3 (Use this style, Time New Roman, Font 10, Normal) (Use complete Author’s name not
abbreviated)
1
Author’s Affiliation, Department, Institute, City, ZIP Code, Country
2
Author’s Affiliation, Department, Institute, City, ZIP Code, Country
3
Author’s Affiliation, Department, Institute, City, ZIP Code, Country
𝜕𝐵𝐶𝑆𝑉𝐶−𝑖 =
𝐵𝑆𝑉𝐶−𝑖
𝜕𝑄𝐶𝑆𝑉𝐶−𝑖 system losses is shown in Fig. 3. Increasing the voltage 𝑉𝑗 in (14)
𝑄𝐶𝑆𝑉𝐶−𝑖
will reduce losses significantly.
Voltage/Losses
Voltage
From (9) and (10), the value of the voltage change is obtained,
Vmax.
𝑉𝑖
∆𝑉𝑖 = ∆𝐵𝐶𝑆𝑉𝐶−𝑖 Vop.
V Control
2𝐵𝑆𝑉𝐶−𝑖
When the bus voltage drops below the minimum security limit, Losses
it must be increased at least to the lower limit to maintain the
quality of the power flow. In this paper, the voltage increase is Vmin.
limited to the lower limit so that a minimum SCV capacity is Pl min..
required.
𝑄𝑆𝑉𝐶−𝑖 𝜕𝑃𝑙 𝑅
∆𝑄𝑐𝑆𝑉𝐶−𝑖−𝑚𝑖𝑛 = 2 ∆𝑉𝑖−𝑚𝑖𝑛 = ∑𝑛𝑖=1 |𝑍𝑖𝑘| (−2𝑉𝑖 𝐶𝑜𝑠𝛿𝑖𝑘 + 2𝑉𝑘 )
𝑉𝑖 𝜕𝑉𝑘 𝑖𝑘
𝑖≠𝑘
𝑖∈𝑘
2.3. Effect SVC to Losses
And defined:
Calculation of the effect SVC to losses refer to [22]. The line
representation is shown in Fig.2. SCV generates reactive power in 𝑄𝐶
𝑋𝑚𝑖𝑛 = 2
= 𝑉𝑘−𝑚𝑖𝑛
the network so that it will have an impact on line losses. 𝐵𝐶
Bus-i Bus-j
Then obtained ∆𝑋 through Equations 18, 19 and 20, namely:
Rij+jXij
𝑜𝑙𝑑 𝑛𝑒𝑤
∑ 𝑃𝐺𝑖 −∑ 𝑃𝐺𝑖
𝛥𝑋 = 𝑅 𝑉
∑ 𝑖𝑘 (1− 𝑖 𝐶𝑜𝑠𝜕𝑖𝑘 )
|𝑍𝑖𝑘 | √𝑋
So for power system with n-buses, the total losses in power While the minimum limit voltage is obtained from (17), namely:
systems is,
𝑅𝑖𝑘
∑𝑛
𝑖=1|𝑍 |𝑉𝑖−𝑚𝑖𝑛 𝐶𝑜𝑠𝛿𝑖𝑘
𝑅𝑖𝑗 𝑖≠𝑘 𝑖𝑘
𝑃𝑙 = ∑𝑛𝑖=1 ∑𝑛𝑗=1 (𝑉𝑖2 − 2𝑉𝑖 𝑉𝑗 𝐶𝑜𝑠𝛿𝑖𝑗 + 𝑉𝑗2 ) 𝑉𝑚𝑖𝑛 = 𝑖∈𝑘
|𝑍𝑖𝑗|
𝑗>𝑖 𝑛𝑘
Network data
SVC Data Load C
4.1 Simulation
From bus To R(pu) X(pu) 1/2Y(pu)
The proposed method has been tested through simulations on 1 2 0 0.0625 1.000
electric power systems with the following explanation. 2 8 0 0.0625 1.000
3 6 0 0.0586 1.000
A. Data system
4 5 0.0085 0.0720 0.0745
This simulation uses an IEEE 9-bus system with a one-line 4 9 0.0320 0.6110 0.1530
diagram in Fig. 5. The data for this system are presented in Tables 5 6 0.0170 0.0920 0.0790
1 and 2. In particular, Table 1 is the result of load flow based on 6 7 0.0170 0.0920 0.0790
the IEEE standard and is used as a basis for calculations. While 7 8 0.0170 0.0920 0.0790
Table 2 shows the line characteristics. 8 9 0.0320 0.6110 0.1530
B. Simulation results
The comparison of the results of the base case simulation
without the SCV device is shown in Table 1. This table indicates
the need for compensation for buses 5, and 8 because low voltage.
From the results of the simulations carried out to increase the
voltage on buses 5 and 8, the minimum compensation values are
obtained as shown in Table 3.
www.astesj.com 4
H. David et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 5, No. 5, XX-YY (2020)
Table 3: Minimum compensation 5. Conclusion
Bus Before Compensation After Compensation The method of calculating the minimum compensation in the
V BSCV Q V BSCV Q electric power system has been presented in this paper.
(pu) (pu) (MVar) (pu) (pu) (MVar) Formulation validation has been tested through simulation of
5 0.872 0 0 0.9 0.1978 21.0 electric power systems in section 4 of this paper.
8 0.884 0 0 0.9 0.0942 10.0 This work uses the IEEE 9-bus power system, based on the
base case there are bad voltages on buses 5 and 8. SCV capacities
The load flow simulation results after compensation are of 0.19 and 0.9 pu are required to increase the voltage to the
presented in Table 4. The gain from this compensation is that the minimum safety level (0.9 pu) on bus 5 and 8 respectively. The
system loss drops by 1.37 MW. effect of compensation is to increase the voltage across all buses.
It should be noted that the voltage increase at the bus does not
Table 4: Power flow after compensation exceed the maximum security limit. The addition of compensating
capacity must be stopped if the bus voltage reaches its maximum
No V Pg Qg Pd Qd safety limit.
bus. [pu] [MW] [MVAR] [MW] [MVAR]
1 0.961 0 0 0 0 The advantage of compensation is the reduction of system
2 1.025 163.00 112.77 0 0 losses. This is caused by a decrease in reactive flow in the network
3 1.025 85.00 179.83 0 0 so that the amount of current decreases. From the simulation
4 0.965 0 0 0 0 results obtained a power saving of 1.37 MW to increase the
5 0.900 0 0 200.0 79.0 voltage to the minimum limit level (0.9), where the voltage on bus
6 0.921 0 0 90.0 30.0 5 and 8 is 0.872 pu and 0.884 pu.
7 1.040 390.47 180.21 0 0
8 0.900 0 0 150.0 85.00 References
9 0.923 0 0 180.0 130.0 [1] T. Gonen, Electrical Power Distribution System Engineering, McGrow-
Total 638.47 472.81 620.0 324.0 Hill,Inc, 1986.
[2] X. Ye, J. Le, Y. Liu, et al. “A coordinated consistency voltage stability
4.2 Discussion control method of active distribution grid”, Int. J. of Modern Power Systems
and Clean Energy. 6(1), 85-94, 2018, doi: 10.1007/s40565-017-0294-z.
The proposed method has successfully simulated the IEEE 9 [3] Juan dixon, senior member, IEEE, “Reactive Power Compensation
bus system, which is presented in Tables 3 and 4. Table 3 presents Technologies: State-of-the-ArtReview” Proceedings of the IEEE, 93(12),
the results of the minimum compensation on buses 5 and 8. The december 2005, doi: 10.1109/JPROC.2005.859937
previous voltages (based on the base case) were below the [4] P. Kundur, Power System Stability and Control, McGraw Hill, New York,
minimum safety limits of 0.872 and 0.884 pu, all marked in bold. 1994.
In the simulation using voltage security 0.9-1.1 pu, so the voltage [5] Q. Hung and Y. Mishra, “Voltage fluctuation mitigation: fast allocation and
on the bus becomes bad. To increase the voltage on buses 5 and 8 daily local control of DSTATCOMs to increase solar energy harvest”, IET
installed SCV. The SCV capacities required to increase the Renew. Power Generation, 13, 2558–2568, 2019, doi: 10.1049/iet-
rpg.2019.0223.
voltage to the minimum safety level (0.9 pu) are 0.1978 pu and
[6] M. Alrashidi, “Community Battery Storage Systems Planning for Voltage
0.0942 pu, respectively. Regulation in Low Voltage Distribution Systems,” Applied Sciences,
12(18), 9083, 2022, doi: 10.3390/app12189083.
The effect of Compensation is to increase the voltage, not only
[7] M. Aybar-Mejía, J. Villanueva, D. Mariano-Hernández, F. Santos and A.
at the bus being compensated but also at other buses. For example Molina-García,”A Review of Low-Voltage Renewable Microgrids:
Bus-1 has a voltage of 0.95 pu before compensation increasing to Generation Forecasting and Demand-Side Management Strategies,”
0.961 after compensation. Electronics, 10(17), 2093, 2021, doi: 10.3390/electronics10172093
[8] R. Anilkumar, G. Devriese and A.K. Srivastava, “Voltage and Reactive
This increase in voltage needs to be watched out for when it Power Control to Maximize the Energy Savings in Power Distribution
exceeds its maximum limit. If there is an overvoltage due to System with Wind Energy”, IEEE Transactions on Industry Applications,
compensation, the compensation capacity is stopped until August 2017, 1(1), doi: 10.1109/TIA.2017.2740850.
one/several bus voltages reach their maximum limit. Furthermore, [9] Kyun-Do Kim, Won-Kun Yu, Eun-Jae Lee, In-Soo Wang, Hyun-Jae Kang,
JeongHoon Shin & Heung-Jae Lee, “Development of an Intelligent Voltage
the load shedding operation needs to be considered to increase the Control System for Jeju Island in Korea,” Journal of International Council
voltage on buses that have the bad voltage. on Electrical Engineering, 1(2), 2011, doi:10.5370/JICEE.2011.1.2.156
,
Besides that, compensation has advantages because it reduces
[10] H. Van Pham and S.N. Ahmed, Multi-Agent based Approach for Intelligent
losses. The load flow simulation after compensation in Table 4 Control of Reactive Power Injection in Transmission Systems”, In Dynamic
states that total power production degrease from 639.84 MW to Vulnerability Assessment and Intelligent Control: For Sustainable Power
638.47 MW or saving 1.37 MW. When these savings are System, P. Wiley-IEEE Press. Ed., 1st., 269, 2018.
converted to costs, the value is quite large. [11] Y. Zhang and A. Srivastava, “Voltage Control Strategy for Energy Storage
System in Sustainable Distribution System Operation”, Energies-MDPI, 1-
12, 2021, doi.org/10.3390/en14040832.
[12] K. Awatef and M.S.M. Mahmoud,” Coordinated Distributed Voltage
Control Methods for Standalone Microgrids,”IJRCS, 2(2), 2022,
doi.org/10.31763/ijrcs.v2i2.612
www.astesj.com 5
H. David et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 5, No. 5, XX-YY (2020)
[13] F. Karbalaei and H. Shahbazi, “A quick method to solve the optimal
coordinated voltage control problem based on reduction of system
dimensions”, Int. J. Electric Power Systems Research. 142, 310-319, 2017,
doi: 10.24200/SCI.2021.56970.4999.
[14] H. Shahbazi and F. Karbalaei “Decentralized Voltage Control of Power
Systems Using Multi-Agent Systems”, Int. J. of Modern Power Systems and
Clean Energy, 8(2), 2020, doi: 10.35833/MPCE.2018.000628.
[15] H. Ma and D.J. Hill, “A Fast Local- Search Scheme for Adaptive
Coordinated Voltage Control”, Int. J. IEEE Transaction on Power Systems,
33(3), 2321-2330, 2018, doi: 10.1109/TPWRS.
[16] K. Alzaareer, M. Saad, H. Mehrjerdi, et al., “Development of new
identification method for global group of controls for online coordinated
voltage control in active distribution networks”, Int. J. IEEE Transactions on
Smart Grid., 11(5), 3921-3931, 2020, dio: 10.1109/ PowerAfrica
49420.2020.9219871.
[17] C.K. Wachjoe and H. Zein, “A Method for Voltage Drop Monitoring on
Load Sides in Medium Voltage Feeder”, 2020 7th International Conference
on Control, Decision and Information Technologies (CoDIT’20), Prague,
Czech Republic, une 29 - July 2, 2020, https://dblp.org/ db/conf/
codit/codit2020.html.
[18] R. Herman, C.T. Gaunt and S.W. Heunis,” Distribution Voltage Drop
CalculationProcedurs,” The transaction of the S.A. Institute of Electrical
Engineering, 54-59, June 1999, https://ieeexplore.ieee.org/ stamp/
stamp.jsp?arnumber=9487825.
[19] J.G. Jamnania and M. Pandya, “Coordination of SVC and TCSC for
Management of Power Flow by Particle Swarm Optimization “2018 5th
International Conference on Power and Energy Systems Engineering,
CPESE 2018, 19–21 Nagoya, Japan, September 2018,
doi:10.1016/j.egypro.2018.11.149.
[20] K.R.C. Mamandur and R. D. Chenoweth, “Optimal control of reactive
power flow for improvements in voltage profiles and for real power loss
minimization”, IEEE Transactions on Power Apparatus andSystems, Vol.
PAS-I1O, No. 7, pp. 3185-3194, July 1981, doi: 10.4028/
www.scientific.net/AMR.986-987.394
[21] H. Zein, “Optimal Capacitor Bank Location in the Primary Feeder with
Typical Flat Load”, Conference on Information Technology and Electrical
Engineering (CITEE) Department of Electrical Engineering, Faculty of
Engineering, Gadjah Mada University, Tuesday, August 4, 2009,
https://pdfslide.net > Documents.
[22] H. Zein, S.Saodah, T.Utami and C,K, Conny, “Static Var Compensation
Capacity for Bus Voltage Setting in Electric Power Systems,” 2022
International Conference on Technology and Policy in Energy and Electric
Power (ICT-PEP). https//ict-pep-pln.com.
www.astesj.com 6