AVR MODEL: CT-100A

POWER INPUT ANALOG INPUT


415 VAC (V-N), 50/60 Hz 10 Vdc max from isolated device for ± 10%
SENSING INPUT variation in generator output
415 VAC (U-V) EXTERNAL VOLTAGE ADJ.
50/60Hz ±10% using 2 KΩ pot
OUTPUT FREQUENCY SELECTION
Voltage: 100 VDC max at 240VAC power input 50 Hz or 60 Hz (Jumper selectable)
Current: continuous 100 Amp dc RESIDUAL MAGNETISM
Intermittent 120 Amp dc for 20s 3 VAC min (V-N)
Resistance (exc. field) 2 Ω min. PROTECTIONS
VOLTAGE ADJUSTMENT LC networks
415 VAC ±10% POWER DISSIPATION
TYPICAL SYSTEM RESPONSE 10 W max
Machine volt to 97% in 500 ms OPERATING TEMPERATURE
REGULATION -20°C to +60°C amb.
±1% with 3% engine governing Thermal drift @ 0.05% per deg.C.
UFRO FUSE
Set point 47Hz 100A/120V or 50A/240V
DROOP SIZE
±5% max with 5A Signal from CT in “B” phase 155 X 140 X 85 mm
UFRO WEIGHT
Set point 47Hz 1.2 Kg approx

CONTROL FUNCTION DIRECTION


VOLT TO ADJUST GENERATOR OUTPUT VOLTAGE CLOCKWISE INCREASES OUTPUT VOLTAGE

STAB TO PREVENT VOLTAGE HUNTING CLOCKWISE INCREASES DAMPING EFFECT

UFRO TO SET THE UNDER FREQUENCY KNEE POINT CLOCKWISE REDUCES THE KNEE POINT
FREQUENCY. UF LED GLOWS WHEN
GENERATOR FREQUENCY DROPS BELOW
SET POINT

DROOP TO SET THE GENERATOR DROOP UPTO 5% CLOCKWISE INCREASES THE DROOP

ANLG I/P TO OPTIMISE ANALOG INPUT SENSITIVITY CLOCKWISE INCREASES THE GAIN OR
SENSITIVITY
WIRING DIAGRAM
AVR CT-100A
5A Droop CT in B phase (1A option also available)

S2
S1
DROOP

AVR VOLT
STAB

CT-100A UFRO

ANLG I/P

60HZ 60Hz
C
50 HZ 50Hz
A2 Analog
A1 Input
R2

Remove Link to fit 2KΩ Pot


R1
UF LED
+

WARNING!
DO NOT KEEP THE AVR INSIDE ANY BOX OR POLETHENE AFTER INSTALLING.
OVERHEATING OF THE AVR MAY DAMAGE IT.
FIT IT INSIDE THE TERMINAL COVER OF THE A.C.GENERATOR OR INSIDE THE PANEL.