Release / Revision: NW Blvd. & Plum Street VINELAND, NJ 08360
Release / Revision: NW Blvd. & Plum Street VINELAND, NJ 08360
LIGHT HAZARD WET PIPE SYSTEM FOR NFPA 13 AREAS AS INDICATED ON PLANS AND AS REQUIRED BY CODE: 5. COORDINATE INSTALLATION OF ALL SYSTEMS WITH MECHANICAL (HVAC), PLUMBING,
SPRINLKER PIPE RETURN BEND AND ELECTRICAL SYSTEMS. CEILING CAVITY SPACE IS RESTRICTED AND INSTALLTION
OCCUPANCY CLASSIFICATION: LIGHT HAZARD OF DUCTWORK SHALL TAKE PRIORITY OVER ALL OTHER TRADES. NO EXTRA
ACCEPTABLE LOCATIONS SYSTEM TYPE: WET PIPE COMPENSATION WILL BE ALLOWED TO COVER THE COST OF RELOCATING SYSTEMS
FOR SPRINKLER PLACEMENT DESIGN DENSITY: 0.10 GPM/SQ. FT. FOUND ENCROACHING ON SPACE REQUIRED BY MECHANICAL, PLUMBING, OR
HYDRAULIC REMOTE AREA: 1,500 SQ. FT. ELECTRICAL SYSTEMS.
1' - 0" 1' - 0"
WALL WALL SPRINKLER ORFICE SIZE: 1/2"
DURATION OF SUPPLY: 60 MINUTES 6. PROVIDE SPRINKLERS ABOVE AND BELOW WIDE DUCTS (48" AND WIDER INCLUDING
FIRE MAIN INSULATION) PER NFPA 13 REQUIREMENTS. REFER TO HVAC DRAWINGS FOR
MAXIMUM COVERAGE/SPRINLER HEAD: 225 SQ. FT.
ADDITIONAL INFORMATION.
1' - 0"
1' - 0"
HOSE STREAM ALLOWANCE: 100 GPM
CEILING 7. PIPING ARRANGEMENT ARE DIAGRAMMATIC AND ARE PROVIDED FOR THE
STORAGE, KITCHENS, LAUNDRIES, MECHANICAL, ELECTRICAL ROOMS AND SIMILAR AREAS:
CONTRACTOR'S INFORMATION. EXACT ROUTING OF PIPING AND FINAL SIZING AND
1' - 0"
LOCATION OF SPRINKLERS SHALL BE SELECTED BY THE CONTRACTOR TO ACCOUNT
INTERIOR NON-RATED INTERIOR RATED WALL OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
ORDINARY HAZARD GROUP 1
WET PIPE
FOR ACUTAL FIELD CONDITIONS. ALL AREAS SHALL BE PROTECTED UNLESS
2'X2' CEILING TILE 2'X4' CEILING TILE 1' - 0" SPECIFICALLY NOTED OTHERWISE. COORDINATE INSTALLATION WITH CEILING HEIGHTS
WALL SLEAVE DETAIL PIPE SLEAVE DETAIL SPRINKLER
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
0.15 GPM/SQ. FT.
1,500 SQ. FT.
AND SOFFITS. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
SPRINKLER ORFICE SIZE: 1/2" 8. EXTENDED COVERAGE SPRINKLERS MAY BE UTILIZED. THE USE OF EXTENDED
DURATION OF SUPPLY: 60 - 90 MINUTES COVERAGE SHALL BE CONFIRMED BY HYDRAULIC CALCULATIONS.
MAXIMUM COVERAGE/SPRINLER HEAD: 130 SQ. FT.
HOSE STREAM ALLOWANCE: 250 GPM
3
PIPE SLEEVE DETAIL 4
RETURN BEND DETAIL 5
SPRINKLER HEAD PLACEMENT 9. PIPING SHALL BE CONCEALED IN ALL FINISHED AREAS.
SCALE: NONE SCALE: NONE SCALE: NONE LIGHT HAZARD DRY PIPE SYSTEM FOR NFPA 13 AREAS AS INDICATED ON PLANS: 10. COORDINATE ALL UNDERGROUND AND TAP-IN WORK WITH LOCAL WATER COMPANY.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ASSOCIATED FEES.
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
SYSTEM TYPE: DRY PIPE 11. THIS BUILDING SHALL BE CONSIDERED LIGHT/ORDINARY HAZARD OCCUPANCY WITH
DESIGN DENSITY: 0.10 GPM/SQ. FT. EXCEPTIONS PER NFPA 13, STATE, AND LOCAL CODES. DESIGN DENSITIES SHALL BE IN
HYDRAULIC REMOTE AREA: 1,950 SQ. FT. ACCORDANCE WITH THE OWNER'S INSURANCE UNDERWRITER.
SPRINKLER ORFICE SIZE: 1/2"
DURATION OF SUPPLY: 60 MINUTES 12. INSTALL SPRINKLER MAINS AS HIGH AS POSSIBLE IN CEILING CAVITIES. SOME BRANCH
SUPERVISED SECTIONAL
MAXIMUM COVERAGE/SPRINLER HEAD: 225 SQ. FT. LINES WILL REQUIRE ARM OVERS TO SUPPLY SPRINKLERS BELOW DUCTWORK. REFER
CONTROL VALVE
HOSE STREAM ALLOWANCE: 100 GPM TO MECHANICAL DRAWINGS AND COORDINATE WITH THE MECHANICAL CONTRACTOR.
NOTE: ATTIC SHALL NOT BE ACCESSIBLE FOR OR UTILIZED FOR STORAGE. SPECIAL APPLICATION 13. SPRINKLER PIPING SHALL BE SCHEDULE 10 STEEL FOR PIPING THAT IS 2-1/2" OR
SPRINKLERS MAY BE UTILIZED IN THE ATTIC SPACE IF INSTALLED IN ACCORDANCE WITH THEIR LISTING. LARGER. PROVIDE SCHEDULE 40 STEEL PIPING FOR 2" AND SMALLER UNLESS
OTHERWISE NOTED. THINWALL, LIGHTWALL, PRO-PRESS TYPE PIPING/FITTINGS WILL
FLOW SWITCH
NOT BE ALLOWED.
SUPPORT STEEL 14. PROVIDE PIPE LABELS FOR ALL SPRINKLER PIPING. LABELS SHALL READ "FIRE
PROTECTION PIPING".
TO SPRINKLER SYSTEM 15. PAINT ALL SPRINKLER PIPING THAT IS EXPOSED IN PUBLIC SPACES. COORDINATE WITH
FROM STANDPIPE
WATER STOP AND ALL TRADES. COLOR TO BE SELECTED BY OWNER/ACRHITECT.
ANCHOR COLLAR LOCKNUT & RETAINING
CLIP, CLAMP SIZE &
SLEEVE ROD AS REQUIRED THREAD-O-LET
HEX NUTS CHECK VALVE
MECHANICAL MECHANICAL
SEAL SEAL CLEVIS HANGER
PIPE PIPE PIPING SIZED FLOW TEST DATA
PER NFPA 13
9
EXTERIOR PIPE SLEEVE DETAIL 6
UNINSULATED PIPE SUPPORT DETAIL 7
FLOOR CONTROL VALVE ASSEMBLY
SCALE: NONE SCALE: NONE SCALE: NONE
1"
FROM END OF
REMOTE 9 11 13
BRANCH LINE
9 11
B
E
9
-
2
5
3
CLOSET
204A
QUIET VIEWING STAIR DASHED LIINE INDICATES AREA TO
B
E
9
-
5
2
3
E 1
-1 0
5
4
ROOM MEZZANINE 150 ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
PIPE SLEEVE THRU WALL, 206 207 BE PROTECTED BY AN AUTOMATIC
SEAL WATERTIGHT SPRINKLER SYSTEM PER NFPA 13, RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
STATE, AND LOCAL CODES
MAX. 7' - 0"
B E
9 -2
5 5
2
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B
E
9
-
2
5
3
CORRIDOR
SMOOTH BORE CORROSION 202 STAIR VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
124 BE SUBJECT TO LEGAL PROSECUTION.
RESISTANT OUTLET GIVING
B
E
9
-
2
5
3
E 1
-1 0
5
4
SPRINKLER 202C
FLOOR
SPLASH BLOCK
STAIR
G c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
3
5
2
-
9
E
B
CORRIDOR
5
2
-
9
E
124
B
TOILET
PANTRY 000
202B ROOM
205
DASHED LIINE INDICATES AREA TO
G
STORAGE
DAY
3
5 5
BE PROTECTED BY AN AUTOMATIC
9 -2
200A
E
B
1 4
0 5
-
E 1
F MONITORED
F
4" STANDPIPE-DN
VALVE
MONITORED VALVE Manders Merighi Portadin Farrell Architects, LLC
STORAGE 1138 East Chestnut Avenue Vineland, New Jersey 08360
DINING GYM IT 001
200 p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
004
E 1 4
5
-1 0
3
2
5
KITCHEN
-
9
E
B
ROOM
201 002
David G. Manders AIA AI-07220
Lawrence J. Merighi AIA AI-07473
Ronald P. Portadin AIA AI-13038
3
5
2
-
9
E
B
5
2
-
9
E
B
1 4
0 5
-
E 1
E 1
- 1
0 5
4
B 9
E -5
2 5
3 B 9
E -2
5 3
5
B 9
E -2
5 2
5
B 9
E -2
5 3
5
E 1
- 1
0 5
4 E 1
- 1
0 5
4
B 9
E -2
5 3
5 B 9
E -2
5 3
5
B 9
E -2
5 2
5
B E
9 -2
5 5
3
E 1
- 1
0 5
4 E 1
- 1
0 5
4
B E
9 -2
5 5
3 B E
9 -2
5 5
3
B E
9 -2
5 5
2
B E
9 -2
5 5
3
E 1
- 1
0 5
4 E 1
- 1
0 5
4
B E
9 -2
5 5
3 B E
9 -2
5 5
3
B E
9 -2
5 5
2
B E
9 -2
5 5
3
E 1
- 1
0 5
4
E E
FLOW GPM
450 500
0 200 400 600 800 1000 1200 1400
140
130
120
110
100
PRESSURE PSI
90
80
70
60
SYSTEM FLOW
50
40
30
20
10
ESTIMATED FLOW
OCCUPANCY ORDINARY I
1500 SF x 0.15 GPM/FT2 x 1.3 292.5 GPM
COMBINED HOSE 150 GPM
TOTAL FLOW 442.5 GPM
REDUCED PRESSURE
BACKFLOW PREVENTER
P 4"FP-UP
CB
YARD FILL/HOSE 155 STATE, AND LOCAL CODES
STORAGE
E 1 4
5
-1 0
3
5
2
-
9
E
B
EQUIP/ 152
ELECTRICAL
M FLAM. HAZMAT
CB
ROOM STORAGE 153
156 151
? EQUIPMENT/
3
5
2
-
9
E
B
?
E 1 4
5
-1 0
PARTS
154
N
3
UNDER MEZZANINE FIRE PROTECTION PLAN
SCALE: 1/8" = 1'-0"
6 7 8 9 10 11 12 13 14
?
N
?
?
?
? REDUCED PRESSURE
? BACKFLOW PREVENTER
FIRE MOUNTED IN VERTICAL
SPRINKLER
PUMP 4"FP-UP
160
?
?
WATER L
COMPRESSOR HEATER
ROOM 159 1
157 F0.2
STORAGE
MEZZANINE
158 FIRE PUMP
M
CONTROLLER
FIRE DEPARTMENT
TEST HEADER
FIRE DEPARTMENT
CONNECTION
?
N
2
CONT. FIRST FLOOR FIRE PROTECTION PLAN ?
4"FP-UP
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
K RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
STAIR
4 5 150
OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
1 2 3 BE SUBJECT TO LEGAL PROSECUTION.
WOMEN'S MEN'S
J
DASHED LIINE INDICATES AREA TO
BE PROTECTED BY AN AUTOMATIC
TOILET
ROOM
TOILET
ROOM
H c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3
BUNK
141
B E
9 -2
5 5
2
E 1
- 1
0 5
4 E 1
- 1
0 5
4
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4
E 1 4
5
-1 0 4
5
-1 0
E 1 4
5
-1 0
E 1 E 1 4
5
-1 0 4
5
-1 0
E 1 4
5
-1 0
E 1
5
2 -
9
E B 5
2 -
9
E B 5
2 -
9
E B 4
5
-1 0
E 1 5
2 -
9
E B E 1 4
5
-1 0 4
5
-1 0
E 1 5
2 -
9
E B 4
5
-1 0
E 1
DECON
G
3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B
3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B 3
5
2 -
9
E B
GEAR
ROOM BUNK
STOR. 149 140
148
CLOSET TOILET
118A DEPUTY
ROOM
FIRE CHIEF STAIR 147
SECRETARIES 119 124
MARSHAL 111
107 4" SPRINKLER
CODE JANITOR Manders Merighi Portadin Farrell Architects, LLC
ENFORCEMENT CHIEF RISER UP&DN
FIRE EVIDENCE 118 CLOSET 125
108 DIRECTOR 119A CORRIDOR TOILET 1138 East Chestnut Avenue Vineland, New Jersey 08360
INVESTIGATOR STORAGE 114 117 ROOM
109 109A p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
145
BUNK
F David G. Manders AIA AI-07220
139
Lawrence J. Merighi AIA AI-07473
Ronald P. Portadin AIA AI-13038
CORRIDOR BUNK
E 1 4
5
-1 0
3
5
2
-
9
E
B
5
2
-
9
E
B
103 DAYTIME
LIEUTENANT
CAPTAIN 122
LOBBY 121
100
E 1 4
5
-1 0
TOILET
3
5
2
-
9
E
B
ROOM
FIRE 144 BUNK
PREVENTION CONFERENCE 137
106 TOILET
ROOM ROOM
101 DAY
CAPTAIN 143 CORRIDOR
LIEUTENANT 123 127
120 TOILET
TOILET
ROOM
ROOM
134
E
104 3
5
2 -
9
E B
4
5
-1 0
E 1
5
2 -
9
E B
3
5
2 -
9
E B
5
2 -
9
E B
3
5
2 -
9
E B 3
5
2 -
9
E B
4
5
-1 0
E 1 4
0 5
1 -
E 1
E -2
9 3
5 5 B
5
2 -
9
E B
3
5
2 -
9
E B
5
2 -
9
E B
3
5
2 -
9
E B 3
5
2 -
9
E B
4
5
-1 0
E 1
TRAINING
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
2
B E
9 -2
5 5
3 B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
2
B E
9 -2
5 5
3 B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
2
B E
9 -2
5 5
3 B E
9 -2
5 5
3
E 1
- 1
0 5
4
LAUNDRY
135 BUNK Project
136
113
BREAK
4
5
-1 0
4
5
-1 0
E 1
E 1
3
5
2
3
5
2
-
-
9
E
9
E
B
ROOM OFFICE
105 113A TOILET
D VINELAND FIRE DEPT.
3
5
2
5
2
-
-
9
E
9
E
B
B
3
5
2
5
2
ROOM
-
9
E
-
9
E
B
B
142
HEADQUARTERS
3
5
2
-
9
E
B
E 1 4
5
-1 0
E 1 4
5
-1 0
3
5
2
-
9
E
B
E 1
4
5
-1 0
-1 0
E 1
5
4
3
5
2
E
9
-
-
9
E
2
5
3
B
C
B
3
5
2
E
9
-
-
9
E
2
5
3
B
E 1
4
5
-1 0
-1 0
E 1
5
4
3
5
2 -
9
E B
4
5
-1 0
E 1 5
2 -
9
E B
3
5
2 -
9
E B 3
5
2 -
9
E B
E 1 4
5
-1 0
3
5
2 -
9
E B
4
5
-1 0
E 1
5
2 -
9
E B
3
5
2 -
9
E B 3
5
2 -
9
E B
4
5
-1 0
E 1
OFFICE
0 5
1 4
E -
1
E -5
9
B 5
2 3
N 113C
B
PRINTED: 7/19/2022 9:21:44 AM
2
5
3
-
9
E
E - 0
5
1 1 4
OFFICER OFFICER
E - 0
5
1 1 4
1 BUNK BUNK
131 132 133
Scale Job Sheet
SCALE: 1/8" = 1'-0" 128 129
A
B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4
B E
9 -2
5 5
3
E 1
- 1
0 5
4 B E
9 -2
B
5 5
2
E
9 -2
5 5
3
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B 9
E -5
B
2 2
5
9
E -5
2 3
5 B 9
E -5
2 3
5
E -
1 0
1 4
5
1/8" = 1'-0" 20.026
Drawn Date F1.1
Author 07/11/2022
RELEASE / REVISION
No. Date Description
A 07-11-22 RELEASED FOR BIDDING
SHT, # WHERE
SECTION IS DRAWN
FLEX DUCT MAX. 12"
LENGTH STRAIGHT LOW VELOCITY RECTANGULAR SUPPLY DUCT. SHEET METAL D
DIM., 1ST NUMBER WIDTH, 2ND NUMBER DEPTH. HVAC SYMBOLS AND ABBREVIATIONS LEGEND GENERAL NOTES:
14"x12"
10"ø SYMBOLS A. CONTRACTOR SHALL PROVIDE MANUFACTURER'S RECOMMENDED ACCESS TO
ALL EQUIPMENT, TERMINAL UNITS AND VALVES. ACCESS SHALL BE REMOVABLE
14"x12"
SUPPLY DIFFUSER 3D 2D
8"ø 8"ø SEE SCHEDULE CEILING TILES OR CEILING ACCESS PANELS. COORDINATE LOCATION OF
O.A. OUTSIDE AIR MECHANICAL EQUIPMENT WITH OTHER TRADES TO AVOID CONFLICT.
45° LATERAL THERMOMETER
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF
10"x12"
TAKE-OFF S.A. SUPPLY AIR
PROVIDE ADDITIONAL BALANCING
NOTE 2 GRILLES AND DIFFUSERS.
DAMPERS WITH ALL DIFFUSERS, M
16"x12"
MED. VELOCITY FLAT OVAL, ROUND, OR RECTANGULAR 8"ø 8"ø REGISTERS, AND GRILLES R.A. RETURN AIR
SUPPLY DUCT, 1ST NUMBER WIDTH, 2ND NUMBER AUTOMATIC DAMPER C. FOR ALL WALLS THAT ARE EXTENDED TO STRUCTURE PROVIDE SLEEVES FOR
DEPTH 00/00 OR 00 Ø (MOTOR OPERATED) CAP. CAPACITY PIPING AND DUCTWORK PENETRATING WALLS (REFERENCE SPECIFICATIONS).
VARIABLE AIR VOLUME
TERMINAL UNIT MANUAL DAMPER D. DRAWINGS ARE DIAGRAMMATIC. PROVIDE ADDITIONAL OFFSETS, TRANSITIONS,
LOW VELOCITY ROUND DUCT PRESS. PRESSURE
ETC. AS REQUIRED TO AVOID INTERFERENCE'S ENCOUNTERED. FULL
TEMP. TEMPERATURE COORDINATION DRAWINGS WITH OTHER TRADES ARE REQUIRED.
AT ALL (ROUND INTO RECTANGULAR) DUCT AUTOMATIC AIR VENT E. PROVIDE FIRE DAMPERS AT ALL DUCT FLOOR PENETRATIONS NOT CONCEALED
CONNECTIONS PROVIDE TAPERED TYPE FITTING MIN. MINIMUM
WITH DAMPER. SEE DETAIL. WITHIN A FIRE RATED CHASE.
10"ø END CAP
MAX. MAXIMUM
FLEX CONNECTION F. IF THE CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT
VAV-XXX LOW VELOCITY DUCT SURE OF THEIR MEANING. HE SHOULD OBTAIN THE ARCHITECTS WRITTEN
SIM. SIMILAR
WITH ASSOCIATED TAPS AND ADJUSTABLE ROOM THERMOSTAT EXPLANATION AND INTERPRETATION PRIOR TO SUBMITTING HIS BID, SINCE THE
BALANCE DAMPERS T
20"x16"
AUTO. AUTOMATIC CONTRACTORS WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE
ROOM SENSOR, ADJUSTABLE AT BMS ONLY ARCHITECT.
LOW VELOCITY FLEX. DUCT TS
FD EX EXISTING
(5'-0" MAX. LENGTH) G. PROVIDE BALANCING DAMPERS FOR ALL S.A., R.A., AND E.A. DUCT BRANCH
CARBON MONOXIDE SENSOR
CO TAKEOFFS AND RUNOUTS TO GRILLES, DIFFUSERS, ETC.
CONC. CONCRETE
INDICATES ROOM CARBON DIOXIDE SENSOR
FIRE DAMPER SERVED BY UNIT/LOCATION CO2
AHU AIR HANDLING UNIT H. USE RADIUS ELBOWS. IF SPACE ISN'T AVAILABLE, MITERED ELBOWS ARE
OF THERMOSTAT
H HUMIDITY SENSOR ACCEPTABLE. PROVIDE TURNING VANES IN ALL RECTANGULAR MITERED
SF SUPPLY FAN ELBOWS, SUPPLY AND RETURN DUCTWORK.
DETAIL # POINT OF CONNECTION - I. INSTALL FLEX DUCTS FULLY EXTENDED, DO NOT BEND DUCTS ACROSS SHARP
PROJECT INSTALLED TO EXISTING RF RETURN FAN
X CORNERS. BENDS OF FLEX DUCTS SHALL NOT EXCEED A MINIMUM OF 1 DUCT
RETURN OR EXHAUST GRILLE SEE BTUH BTU/H DIAMETER. AVOID CONTACT OF FLEX DUCT WITH METAL FIXTURES, WATER LINES,
SCHEDULE
X PIPES, OR CONDUITS. MAX FLEX DUCT LENGTH OF 5' 0".
SHT. # WHERE A.F.F. ABOVE FINISHED FLOOR
VIEW IS DRAWN
R- OR E- EF EXHAUST FAN
XXX XXX
AT ALL (ROUND INTO RECTANGULAR) DUCT LOW VELOCITY RECTANGULAR EXHAUST OR TYP. TYPICAL
CONNECTIONS PROVIDE TAPERED TYPE RETURN DUCT. SHEET METAL DIM., 1ST
FITTING WITH DAMPER. SEE DETAIL. NUMBER WIDTH, 2ND NUMBER DEPTH. CONN. CONNECTION
INSULATION NOT REQ'D ON EXHAUST OR
RETURN DUCT
FD FIRE DAMPER
HTR HEATER 2. UPON COMPLETION OF THE DUCT INSTILLATION, RECORD FINAL AIR FLOW
RATES WITHIN THE PROJECT AREA, AT THE AIR HANDLING UNIT AND EXHAUST
VAV VARIABLE AIR VOLUME FAN(S). TOTAL AIR FLOWRATES WITHIN THE PROJECT AREA AND AT THE
SOURCE EQUIPMENT SHALL BE WITHIN 10% OF DESIGN FLOW RATES.
VARIABLE AIR VOLUME CLG. CEILING
TERMINAL UNIT
T.C. TEMPERATURE CONTROL
DN. DOWN
REF. REFERENCE
UH UNIT HEATER
SP SETPOINT
ISOMETRIC VIEW
HVAC DUCT LEGEND
SCALE: NONE
NOTES:
1. ALL DUCTWORK DIMENSIONS ARE EXTERIOR DIMENSIONS OF DUCT.
2. ALL MEDIUM PRESSURE TAKEOFFS TO HAVE 45° LATERAL OR SIMILAR EVEN IF NOT
SPECIFICALLY SHOWN IN DRAWINGS.
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
3. PROVIDE BALANCING DAMPERS IN TAKEOFF TO ALL GRILLES/DIFFUSERS. RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
4. DUCTWORK INSTALLATION SHALL MEET ALL REQUIREMENTS OF NFPA 90A/SMACNA. STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
BE SUBJECT TO LEGAL PROSECUTION.
Project
MECHANICAL LEGEND
PRINTED: 7/19/2022 9:29:21 AM
SCBA
YARD
FILL/HOSE
EQUIP/ EQUIPMENT/ MAINTENANCE
ELECTRICAL STORAGE
FLAM. 152 PARTS OFFICE
ROOM STORAGE HAZMAT 154 155
156 151 153
GARAGE
'B'
146B
GARAGE
'A'
146A
2
FIRST FLOOR ZONING PLAN PART 2
SCALE: 1/8" = 1'-0"
STAIR
150
BUNK
DECON 141
GEAR ROOM
WOMEN'S MEN'S 149 ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
STOR.
TOILET TOILET 148 RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
FILE ROOM ROOM TOILET BUNK
115 116 DEPUTY ROOM 140 MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
STORAGE CLOSET 147 STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
110 118A CHIEF
119 COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
EVIDENCE OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
STAIR
FIRE FIRE STORAGE 124 VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
MARSHAL CODE INVESTIGATOR 109A DIRECTOR
ENFORCEMENT SECRETARIES CHIEF BE SUBJECT TO LEGAL PROSECUTION.
107 109 114 118 CLOSET JANITOR
108 111 119A 125
TOILET DAYTIME
ROOM LOBBY DAY CAPTAIN TOILET
103 100 121 LIEUTENANT ROOM
CONFERENCE LIEUTENANT 122
120 144
FIRE ROOM
PREVENTION 101
106 TOILET TOILET
ROOM ROOM
104 143
CAPTAIN BUNK Manders Merighi Portadin Farrell Architects, LLC
123 137
1138 East Chestnut Avenue Vineland, New Jersey 08360
LAUNDRY CORRIDOR p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
TOILET 135 127 BUNK
TRAINING ROOM 136
113 134 David G. Manders AIA AI-07220
BREAK
OFFICE TOILET Lawrence J. Merighi AIA AI-07473
ROOM H 113A
105 ROOM Ronald P. Portadin AIA AI-13038
142
Peter W. Farrell AIA AI-13618
CORRIDOR
127
STORAGE
113B
Project
OFFICE
113C
OFFICER OFFICER BUNK BUNK BUNK BUNK
BUNK 130 131 132 133
BUNK
128 129
VINELAND FIRE DEPT.
HEADQUARTERS
NW BLVD. & PLUM STREET
VINELAND, NJ 08360
Drawing
WATER
FIRE
COMPRESSOR HEATER
STORAGE SPRINKLER
ROOM ROOM
157 MEZZANINE 159 PUMP
158 160
2
SECOND FLOOR ZONING PLAN (MEZZ.)
SCALE: 1/8" = 1'-0"
E 1
-1 0
5
4
B
E
9
-
2
5
3
QUIET VIEWING
B
E
9
-
2
5
3
E 1
-1 0
5
4
ROOM MEZZANINE STAIR
206 207 150
B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
B 9
E -5
2 2
5
E -
1 0
1 4
5 E -
1 0
1 4
5
E 1
-1 0
5
4
B
E
9
-
2
5
3
B
E
9
-
2
5
3
E 1
-1 0
5
4
E 1 4
5
-1 0
3
5
2
-
9
E
B
PANTRY CORRIDOR
202C 204
3
5
2
-
9
E
B
5
2
-
9
E
B
PANTRY TOILET
202B
PANTRY ROOM DAY
STAIR 205
9 -2
E
B 3
5 5
1 4
0 5
-
E 1
CORRIDOR 124 ROOM
202 203
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
PANTRY STORAGE
202A 200A RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
BE SUBJECT TO LEGAL PROSECUTION.
E 1 4
5
-1 0
3
5
2
-
9
E
B
KITCHEN DINING
201 200
CORRIDOR
000 c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
3
5
2
-
9
E
B
5
2
-
9
E
B
9 -2
E
B 3
5 5
1 4
0 5
-
E 1
STORAGE
GYM 001
004
B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5
IT
RADIO ROOM
Manders Merighi Portadin Farrell Architects, LLC
TECH/ 002 1138 East Chestnut Avenue Vineland, New Jersey 08360
SCBA p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
003
David G. Manders AIA AI-07220
Lawrence J. Merighi AIA AI-07473
Ronald P. Portadin AIA AI-13038
Peter W. Farrell AIA AI-13618
3
BASEMENT ZONING PLAN Project
SCALE: 1/8" = 1'-0"
1
SECOND FLOOR ZONING PLAN VINELAND FIRE DEPT.
SCALE: 1/8" = 1'-0"
HEADQUARTERS
NW BLVD. & PLUM STREET
VINELAND, NJ 08360
Drawing
KEYED NOTES:
5. DRYER VENT DUCT: PROVIDE EXHAUST VENT DUCT FROM DRYER AND TERMINATE
THROUGH NEAREST OUTSIDE WALL WITH MANUFACTURE SIDE WALL TERMINATION.
DUCT SHALL BE RIGID GALVANIZED OR ALUMINUM. MALE END OF DUCTWORK AT
OVERLAPPING JOINTS SHALL EXTEND IN THE DIRECTION OF AIRFLOW. DUCT SHALL NOT
EXCEED 24'-0. DUCT SHALL NOT BE CONNECTED WITH SHEET METAL SCREWS OR
FASTENERS THAT MAY OBSTRUCT AIRFLOW. VERIFY SIZE WITH MANUFACTURE DRYER
VENT TO PENETRATE TO EXTERIOR. PROVIDE WITH DRYER VENT CAP.
CB
11. 4" FLUE UP THROUGH ROOF. REFER TO DETAIL ON M4.0
UH-2 L-1 12. CONTRACTOR TO PROVIDE MOUNTING PLATFORM FOR FLAMMABLE STORAGE EXHAUST
6"ø
FAN. EXHAUST TO BE PROVIDED WITH VIBRATION ISOLATION.
12"ø
HEATERS. RADIANT HEATERS SHALL NOT BE INSTALLED DIRECTLY BELOW LIGHT
UP TO VEF-1 FIXTURES.
18 14
18. VEHICAL EXHASUT DUCT TO BE ROUTED TIGHT TO STRUCTURE UP TO DUCT DROPS
FOR VEHICAL EXHASUT RAILS.
L-1
L-1 19. 10'X10" UP TO EF-15
10"ø
6"ø 6"ø
PLYMOVENT STR 80-2 6"ø 6"ø PLYMOVENT STR 80-2
3
M3.0
10"ø
L-1
L-1
? CONNECT TO GARAGE
? 'A'
VEHICLE EXHAUST
RAIL TYP. 146A
6"ø 6"ø
12"ø
13
PLYMOVENT STR 80-2 6"ø 6"ø PLYMOVENT STR 80-2
CO PLYMOVENT STR 80-1 RH-1
10 10
RH-1
10 11 10
11 11 17 RH-1 11 17
RH-1 17 17
8"ø
L-1
L-1
6"ø 6"ø
18 14 CONNECT TO VEHICLE
6"ø 6"ø
PLYMOVENT STR 80-2 EXHAUST RAIL TYP.
17 17
UP TO VEF-2 RH-1
RH-1 PLYMOVENT STR 80-1
10 11 11 RH-1 10
10 11 CO 11 10
RH-1 17 17
VEHICAL EXHAUST
4"ø 16 16 SS-3
1 SS-3 PANEL
15 EF-13
SS-1
12 REFRIGERANT
SUPPLY / RETURN EQUIPMENT/ MAINTENANCE
YARD FLAMMABLE PARTS OFFICE
EQUIP/ STORAGE SCBA HAZMAT 154 155
FILL/HOSE 153
FLAM. CABINET
STORAGE STORAGE REFRIGERANT
151 EF-14 152 L-1
SUPPLY / RETURN 16
12 E-2
15 UH-2 UP TO CU-1
200
8"ø 8"ø
TG-1 TG-1 6"ø 6"ø
150 150
17 PLYMOVENT STR 80-1 17
10 RH-1 RH-1
10
2
FIRST FLOOR HVAC PLAN (CONT.) CO 11 11
1 2 3 2 UH-1
M3.0
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
3 RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
VAV-BUNK MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
6"ø STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
H FSD
GEAR
E-1
550
E-1
400
S-1
100 COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
2 DECON BUNK OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
FSD STOR. 6 141 VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
148 ROOM
E-1 E-1 S-2 149
S-2 8"ø 8"ø 12"x12" BE SUBJECT TO LEGAL PROSECUTION.
150 220
14"x12"
150
10"x10"
235 6"ø 6"ø S-2 S-2 S-2 WOMEN'S S-2 TOILETE-2 8"ø
8"x8"
8"ø
22"x24"
8"ø 8"ø SS- 4
12"ø
8"ø S-2 8"ø S-2 S-1 S-1 200 200 200 TOILET 180 ROOM 110 VAV-148 4"ø 6"ø BUNK
VAV-111 8"ø STAIR 147 8"ø
225 VAV-108 215 50 50 ROOM CLOSET CONDENSATE
124 S-1 VAV-BUNK 140
8"ø
6"x10"
MARSHAL ENFORCEMENT VAV-109 109 STORAGE 10"ø 8"x10" 111 119 E-2 7
107 108 109A S-1 ROOM S-1 CHIEF S-2
6"ø 116 8"ø 70
R-1 90 90 118 8"ø S-2 S-2 225
22"x16" FILE 20"x12" DIRECTOR 6"ø
R-1 114 200 CLOSET R-1 225 225 VAV-BUNK
STORAGE R-1
6"ø
18"x20"
110 220 180 10"ø CORRIDOR 8"x10" 14"x14" 18"x16" S-1
235 6"ø 200 JANITOR
12"ø
8"ø 117
6"ø
10
R-1 S-3
14"ø
VAV-123 BUNK
8"ø
400 11"x10" S-1 9 10"x10" 300 139
8"ø
8"ø
8"ø
8"ø
8"ø
10"ø
100 R-1
10"x10"
40"x16" 22"x16" 18"x12" 12"ø R-1 CORRIDOR 10"x10" TOILET
VAV-114 225
600 112 8"ø 10"ø ROOM
14"ø
S-1
10"ø
6"ø
10"ø
VAV-101
10"ø
300 600 10"x12" 138
R-1 14"ø VAV-105
R-1
14"ø
R-1
14"ø
R-1 10"x12" 14"x12" VAV-126 S-2 VAV-BUNK Manders Merighi Portadin Farrell Architects, LLC
14"x12"
R-1 CONFERENCE 800 800 R-1 8"ø R-1
26"x20"
12"ø S-3 800 R-1 R-1 R-1 225
10"ø
600 ROOM DAY TOILET 1138 East Chestnut Avenue Vineland, New Jersey 08360
E-1 840 280 LOBBY 110 300 DAYTIME 300 300 500
8"ø
12"ø
10"ø
8"x10"
100 p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
10"ø
10"ø
TOILET 75 120 CAPTAIN E-2 144
ROOM 20"x16" 121 24"x14" 22"x12" 8"ø 110
103 FULL SIZE UP 10"ø David G. Manders AIA AI-07220
8"x12"
10"ø
6"ø
10"ø TO RTU-1 10"ø 127 4"ø 6"ø S-1 Lawrence J. Merighi AIA AI-07473
10"ø
12"ø
6"ø TOILET
14"x14"
8"ø
10"x10"
6"ø 4"ø 6"ø
10"ø
10"ø 10"ø
C 300 12"ø Project
10"ø
14"x12" 8"x10"
300 300 50
4"ø
4"ø
4"ø
4"ø
4"ø
4"ø
VAV-BUNK S-1 VAV-BUNK VAV-BUNK
STORAGE
113B 125 VAV-BUNK VAV-BUNK
S-3
300
VINELAND FIRE DEPT.
VAV-BUNK
10"ø 10"ø
S-3 S-3
HEADQUARTERS
6"ø
300
6"ø
6"ø
6"ø
300
6"ø
6"ø
S-3 OFFICE
300 113C
R-1 S-1 OFFICER OFFICER
BUNK
S-1 S-1 BUNK BUNK S-1 S-1 BUNK BUNK NW BLVD. & PLUM STREET
300 BUNK 130 131 132 133
100
128 129 100 100 100 100
S-1
VINELAND, NJ 08360
100
Drawing
6. 10"X10" UP TO EF - 16
7. 10"X10" UP TO EF - 17
8 9 9 8
RH-1 RH-1
RH-1
RH-1
8 9 9 8
5 5
TG-2 5 UH-2 1 1
16"x16" 1500 TG-2
1500 UH-2 TG-2
FULL SIZE
UP TO EH-1 WATER FIRE 1500
M COMPRESSOR
ROOM
HEATER
ROOM
159
6
7
SPRINKLER
PUMP
160
157
UP TO CU-2
3 SS-3
9 9
8 8
RH-1 RH-1
8 RH-1 9 9 RH-1 8
3
M3.0
2
SECOND FLOOR HVAC PLAN (MEZZ.)
SCALE: 1/8" = 1'-0"
8 RH-1 9 9 RH-1 8
8"x12"
10"ø 8"ø
E 1
-1 0
5
4
B
E
9
-
2
5
3
S-3 R-1
300 VAV-206
300
2 VIEWING
QUIET 10"ø
B
E
9
-
2
5
3
E 1
-1 0
5
4
MEZZANINE
ROOM M3.0 207
206
9 11
FULL SIZE E -
1 0
1 4
5
B 9
E -5
2 3
5 B 9
E -5
2 3
5
B 9
E -5
2 2
5
B 9
E -5
2 3
5
E -
1 0
1 4
5
E 1
-1 0
5
4
B
E
9
-
2
5
3
5 RTU-3 RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
12"ø
M3.0 MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
10"ø
FSD S-3
B
E
9
-
2
5
3
E 1
-1 0
5
4
STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
300
EF-10 COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
E 1 4
5
-1 0
3
5
2
-
9
E
B
FSD S-2 R-1 OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
600
20"x18"
200
K VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
BE SUBJECT TO LEGAL PROSECUTION.
3
5
2
-
9
E
B
5
2
-
9
E
B
DAY
16"x16" TOILET 12"ø
R-1 ROOM
600 STAIR ROOM 203
124 STORAGE 205 CORRIDOR EF-11
200A
9 -2
E
B 3
5 5
PANTRY
4
0 5
204
1 -
E 1
UP TO S-3 c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
CORRIDOR MAU-1 E-2
10"ø
202 120 300
E-2
4 70 R-1
12"ø VAV-203
6"ø
J UH-1 18"x20"
M3.0 600
10"ø
12"ø
8"ø
UP
14"x14"
10"x12" 12"ø CU-3
THROUGH S-3
FSD AT CHASE 10"x10" VAV-200 10"ø
CHASE R-1 300
PENETRATION KITCHEN S-3 S-3
18"x16"
450 10 201 12"ø
300 300
16"x16"
S-4 UP TO R-1
24"x16"
4
5
-1 0
EF-3
E 1
3
5
2
-
9
E
B
400 10"ø 600
G
12"x12"
"ø
S-6
12
S-3 12"ø UP TO
Manders Merighi Portadin Farrell Architects, LLC
10"ø
14"x14"
10"x12" 600
275 EF-12 10"ø R-1
S-6 S-4 DINING
22"x16"
3
5
2
-
9
E
B
5
2
1138 East Chestnut Avenue Vineland, New Jersey 08360
-
9
E
B
12"ø
14"x14"
600 400 200 600
18"x10"
10"ø VAV-201 10"ø p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
2 S-6 12"ø 12"ø
VAV-004 S-3
10"ø
VAV-003 600
8"ø S-3 S-3 R-1 300 David G. Manders AIA AI-07220
9 -2
E
B 3
5 5
0 5
1 4
S-6
-
E 1
STORAGE 12"ø
10"ø
12"x10"
SS-4 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
0"
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5
"x1
4
GYM
004
12"x12"
R-1 11
12"ø
8"ø
8"ø
150 IT
ROOM
002
S-2 S-2
S-2
225 225 Project
RADIO
TECH/ 150
SCBA
S-3 003
275
E VINELAND FIRE DEPT.
HEADQUARTERS
NW BLVD. & PLUM STREET
VINELAND, NJ 08360
P 2
1
EF-15
2 2
EF-9
1 1
2 2
1 EF-8 1
2 2
1 1
EF-7
VEF-2
1
2 2
1 3
CU-1
EF-16
EH-1
EF-17
CU-2
3
2
1 2 1
VEF-1
EF-6
1 2 2 1
EF-5
1 2 2 1
1 EF-4 2 2 1
1 2 2 1
EF-10
MAU-1
EF-11
1
ROOF HVAC PLAN
SCALE: 1/16" = 1'-0"
Project
RETURN MAIN
E1- 1054
B E9- 2553
SUPPLY MAIN
DIFFUSER
E9- 1015
CEILING
LIGHT FIXTURE
B E9- 2556
CONFERENCE EVIDENCE
ROOM CORRIDOR STORAGE
101 102 109A
E9- 1015
B E9- 2556
E9- 1015
B E9- 2579
B E9- 2578
1
OFFICE SECTION
SCALE: 1/4" = 1'-0"
5
M3.0
SUPPLY BRANCH LINE
SUPPLY
LIGHTS
JOISTS RISER
HW/CW PIPE CEILING
TOILET
S-6 S-6 S-6 S-6 ROOM
600 600 600 600 147 JANITOR CORRIDOR CAPTAIN
SUPPLY MAIN CHASE 125 117 123
LIGHT
CEILING RETURN
PANTRY RISER
CEILING
PANTRY
CORRIDOR PANTRY
KITCHEN 202 202A
PANTRY PANTRY PANTRY 201 LAMINAR
202C 202B 202A
FLOW
DIFFUSERS
5
KITCHEN SECTION 4
PANTERY SECTION 2
CHASE / OFFICE SECTION
SCALE: NONE SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
LIGHT
OA INTAKE EXHAUST FLUE VEHICLE DOMESTIC COMPRESSED AIR NATURAL
EXHAUST MAIN WATER PIPING PIPING GAS PIPING
OA INTAKE
Manders Merighi Portadin Farrell Architects, LLC
1138 East Chestnut Avenue Vineland, New Jersey 08360
RADIANT HEATER p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
VEHICLE EXHAUST
HOSE RAIL David G. Manders AIA AI-07220
GARAGE DOOR Lawrence J. Merighi AIA AI-07473
Ronald P. Portadin AIA AI-13038
Peter W. Farrell AIA AI-13618
GARAGE
VEHICLE 'A'
146A
EXHAUST HOSE
VEHICLE
EXHAUST HOSE
Project
FLOOR
VINELAND FIRE DEPT.
HEADQUARTERS
NW BLVD. & PLUM STREET
VINELAND, NJ 08360
Drawing
3
GARAGE SECTION
SCALE: 1/4" = 1'-0"
HVAC SECTION CUTS
PRINTED: 7/19/2022 9:31:21 AM
5
RTU DETAIL 3
RETURN/EXHAUST GRILLE CONNECTION DETAIL 1
SUPPLY DIFFUSER CONNECTION DETAIL
SCALE: NONE SCALE: NONE SCALE: NONE
7
VOLUME DAMPER TAPERED FITTING W/ DAMPER DETAIL 8
DUCT HANGER DETAIL 4
EXHAUST FAN DETAIL (DOWNBLAST)
SCALE: NONE SCALE: NONE SCALE: NONE
WALL
LIQUID LINE
VAPOR LINE
MINI-SPLIT UNIT
GRILLE DUCT CONNECTION
METAL STRAPS
(SEE NOTES)
TRANSITION TO
CONCRETE PAD UNIT HEATER
UNIT INLET SIZE
(SEE DETAIL) CONDENSATE DRAIN
LOW PRESSURE
DUCTWORK
6
MINISPLIT/HEAT PUMP PIPING (PAD) ELBOW'S) p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
EXTERIOR WALL
10'-0"
WALL CAP. COLOR WALL SLEEVE RAIN CAP W/BIRDSCREEN
BY ARCHITECT
EXHAUST/DRYER DUCT/O.A. SILICONE SEALANT
INTAKE
STORM COLLAR
24"MIN. TALL CONE SLOPPING
36"MIN. ROOF FLASHING
4" SHEET METAL DUCT
LOCATED AS SHOWN ON Project
PLANS. SEAL JOINTS WITH
SEALANT. NO SCREWS IN SEALANT (ALL AROUND)
DUCT. ROOF
ROOF DECK
NOTES:
1. FOR DRYER EXHAUST PROVIDE WALL CAP WITH BACKDRAFT DAMPER.
CLOTHES
1" CLEARANCE DOUBLE WALL
VINELAND FIRE DEPT.
DRYER
FOR BATHROOM EXHAUST AND O.A. INTAKE PROVIDE WALL CAP WITH
INSECT SCREEN IN LIEU OF BACKDRAFT DAMPER.
VENT, TYPE B. HEADQUARTERS
VERIFY VENT SIZE WITH
FURNACE MANUFACTURER.
2. PROVIDE FLASHING AND WEATHER TIGHT SEAL AROUND DUCT WHERE FLOOR
DUCTWORK PENETRATES EXTERIOR WALL. NW BLVD. & PLUM STREET
NOTES: VINELAND, NJ 08360
FLEXIBLE ROUND SHEET METAL COLLAR
CONNECTION TO FULL SIZE OF DRYER OUTLET 1. INSTALL FURNACE VENT AS RECOMMENDED BY
DRYER VENT CONNECTING INTO TEE RISER VENT MANUFACTURER AND IN COMPLIANCE Drawing
WITH ALL APPLICABLE NFPA CODES.
9
SIDEWALL EXHAUST/DRYER DETAIL NOTE:
2. INSTALLATION SHALL BE COMPLETELY
SCALE: NONE 1. PROVIDE DRYER PLACARD, PERMANENT LABEL ON WALL BEHIND HVAC DETAILS
WATER-TIGHT.
DRYER. SHALL LIST ACTUAL NET EQUIVALENT LENGTH OF DRYER
DUCT.
PRINTED: 7/19/2022 9:31:24 AM
WALL
SMOKE
PARTITION GASKET
1
FIRE / SMOKE DAMPER DETAIL (Horizontal) 2
FIRE / SMOKE DAMPER DETAIL (Vertical) 3
SIDEWALL GRILLE MOUNTING DETAIL
SCALE: NONE SCALE: NONE SCALE: NONE
OUTLET SHALL BE
7'-0"
ABOVE ROOF OR 4
TIMES THE DIAMETER
(D), WHICHEVER IS
4D D+1" GREATER
10'-0" MIN.
NOTES:
DUCT SUPPORT
1. APPLICABLE FOR ALL COOLING COILS, HUMIDIFIER SECTIONS, AND FOR AHU
INTAKE SECTION ON 100% OUTSIDE AIR UNIT, ETC. CAP OTHER UNIT DRAIN
OPENINGS WITH REMOVABLE CAPS.
2. IF FLOOR DRAIN USED, COVER SHALL REMAIN READILY ACCESSIBLE.
7
CONDENSATE DRAIN DETAIL - BLOW-THRU UNITS 6
EXHAUST FAN DETAIL (UTILITY SET)
SCALE: NONE SCALE: NONE
NOTES:
1. INSTALL WATER HEATER VENT AS RECOMMENDED BY
VENT MANUFACTURER AND IN COMPLIANCE
WITH ALL APPLICABLE NFPA CODES.
2. INSTALLATION SHALL BE COMPLETELY
WATER-TIGHT.
Project
HVAC DETAILS
PRINTED: 7/19/2022 9:31:25 AM
NET COOLING CAP NET COOLING CAP NET HEATING CAP CLG. DB CLG. WB CLG. DB CLG. WB SUPPLY MOTOR T.S.P. E.S.P. SOUND
MARK MANUFACTURER MODEL No. CFM MIN OA CFM SENSIBLE (MBh) TOTAL (MBh) (MBh) NET GAS CAP E.A.T. E.A.T. L.A.T. L.A.T. HTG. E.A.T. HTG. L.A.T. H.P. FRPM (IN H20) (IN H2O) DATA VOLTAGE PHASE MCA NOTES
RTU-1 TRANE YHC072E4RHA 2400 700 48.1 67.6 120.0 150000.0 Btu/h 80 °F 67 °F 60 °F 57 °F 70 °F 117 °F 1 980 1.56 in-wg 1.25 in-wg NA 460 ALL 3 15
RTU-2 TRANE YHD180G4RHD 5000 1500 92.5 136.1 200.0 250000.0 Btu/h 80 °F 67 °F 60 °F 57 °F 70 °F 107 °F 5 901 1.86 in-wg 1.50 in-wg 84 dB 460 3 38 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
RTU-3 TRANE YCH330B4 10500 3150 236.9 321.3 480.0 600000.0 Btu/h 80 °F 67 °F 60 °F 57 °F 70 °F 112 °F 10 733 2.43 in-wg 1.50 in-wg 83 dB 460 3 72.85 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
SCHEDULE OF EXHAUST FANS SS-4 TRANE TPKA0A0361KA70A 36000.0 Btu/h 0.0 Btu/h 810 208 1 1 ALL
NOTES:
1. PROVIDE WITH BACKDRAFT DAMPER AND DISCONNECT SWITCH.
2. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED. SCHEDULE OF CONDENSING UNITS / HEAT PUMPS
ELECTRICAL
STATIC CHARACTERISTICS FAN NOTES:
1. DIVISION 26 SHALL PROVIDE DISCONNECT SWITCH.
MARK AREA SERVED MANUFACTURER MODEL No. SIZE HP FRPM CFM PRESSURE VOLTAGE PHASE MOUNTING NOTES 2. PROVIDE SINGLE POINT WIRING KIT AND ALL DAMPERS, SENSORS, AND CONTROL COMPONENETS AS REQUIRED FOR SEQUENCE OF OPERATION INDICATED.
EF-1 OFFICE BATHROOM GREENHECK G 080-VG 1/10 1725 150 0.50 in-wg 120 1 ROOF ALL 3. SLOPE SUCTION LINE TOWARD EVAPORATOR.
EF-2 OFFICE BATHROOM GREENHECK G 090-VG 1/10 1716 320 0.50 in-wg 120 1 ROOF ALL 4. FURNISH WITH LOW AMBIENT CONTROLS WITH NON-BLEED TXV AND MECHANICAL A/C CONDENSER ROOF SUPPORT (SIMILAR TO MIR MODEL LD).
EF-3 SECOND FLOOR GREENHECK G 080-VG 1/10 1537 220 0.50 in-wg 120 1 ROOF ALL 5. REFRIGERANT LINES SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS WITH LONG LINE KITS AND OTHER ACCESSORIES AS REQUIRED.
6. PROVIDE UNIT WITH COMMUNICATION INTERFACE. CONTRACTOR TO COORDINATE WITH TEMP CONTROL PROVIDER TO CONNECT TO BMS.
EF-4 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL
7. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED. ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
EF-5 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL
RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
EF-6 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
EF-7 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL MINIMUM MINIMUM STARTING ELECTRICAL CHARACTERISTICS
STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
EF-8 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL EFFICIENCY AND OPERATING MCA/MOP COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
EF-9 GARAGE GREENHECK AER 20-VGD 3/4 1151 4000 0.21 in-wg 480 3 ROOF ALL MARK MANUFACTURER MODEL No. CAPACITY (EER/SEER) TEMPERATURE VOLTAGE PHASE (AMPS) NOTES OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
EF-10 DECON GREENHECK G 095-VG 1/6 1725 400 0.75 in-wg 120 1 ROOF ALL CU-1 TRANE NTXMPH24A132AA 22200.0 Btu/h 11.75 0 °F 208 1 30.5 ALL VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
CU-2 TRANE NTXMPH24A132AA 22200.0 Btu/h 11.75 0 °F 208 1 30.5 ALL BE SUBJECT TO LEGAL PROSECUTION.
EF-11 GENERAL GREENHECK G 120-VG 1/2 1725 1520 1.00 in-wg 120 1 ROOF ALL
EF-12 KITCHEN GREENHECK CUE 140-VG 1 1725 2800 0.71 in-wg 480 3 ROOF ALL CU-3 TRANE TRUYA0361KA70BA 36000.0 Btu/h 11.75 0 °F 208 1 25 ALL
EF-13 FLAMABLE STORAGE CABINET FANAM CBI 160 1/4 1725 50 1.00 in-wg 120 1 PLATFORM ALL
EF-14 HAZMAT FANAM CBI 160 1/4 1725 200 0.50 in-wg 120 1 PLATFORM ALL c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
EF-15 ELEC 157 GREENHECK G 090-VG 1/10 1716 320 0.50 in-wg 120 1 ROOF ALL SCHEDULE OF GAS RADIANT HEATERS
EF-16 WATER HEATER ROOM GREENHECK G 080-VG 1/10 1725 150 0.50 in-wg 120 1 ROOF ALL NOTES:
EF-17 FIRE SPRINKLER ROOM GREENHECK G 080-VG 1/10 1725 150 0.50 in-wg 120 1 ROOF ALL 1. PROVIDE WITH REMOTE THERMOSTAT.
2. PROVIDE UNIT WITH DISCONNECT SWITCH AND OVERLOAD PROTECTION.
3. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
SCHEDULE OF VEHICLE EXHAUST SYSTEM 4. RADIANT HEATER SHALL BE 40' IN LENGTH.
NOTES: ELECTRICAL
1. PROVIDE WITH BACKDRAFT DAMPER AND DISCONNECT SWITCH. NET GAS HEATING CHARACTERISTICS
2. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
MARK MANUFACTURER MODEL No. CAPACITY CAPACITY VOLTAGE PHASE MCA NOTES Manders Merighi Portadin Farrell Architects, LLC
ELECTRICAL RH-1 REZNOR VPT60A 60000.0 Btu/h 50000.0 Btu/h 120 1 3 ALL 1138 East Chestnut Avenue Vineland, New Jersey 08360
STATIC CHARACTERISTICS FAN p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
MARK AREA SERVED MANUFACTURER MODEL No. SIZE HP FRPM CFM PRESSURE VOLTAGE PHASE MOUNTING NOTES David G. Manders AIA AI-07220
VEF-1 VEHICLE EXHAUST PLYMOVENT TEV 585 7.5 3450 3500 5.00 in-wg 480 3 ROOF ALL SCHEDULE OF MAKE UP AIR UNIT Lawrence J. Merighi AIA AI-07473
VEF-2 VEHICLE EXHAUST PLYMOVENT TEV 745 10 3535 4000 10.00 in-wg 480 3 ROOF ALL Ronald P. Portadin AIA AI-13038
NOTES: Peter W. Farrell AIA AI-13618
1. CONTRACTOR SHALL COORDINATE ROOF CURB CONSTRUCTION WITH SLOPE OF STRUCTURAL STEEL.
2. PROVIDE UNIT WITH 85% (MERV08) FILTERS.
3. PROVIDE UNITS WITH FIXED PITCH V-BELT DRIVES SELECTED FOR A SERVICE FACTOR OF 2.0.
SCHEDULE OF LOUVERS 4. CONTRACTOR SHALL PROVIDE ONE ADDITIONAL SET OF BELTS AND SHEAVES FOR FINAL AIR BALANCING, COORDINATE WITH BALANCE CONTRACTOR.
5. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
NOTES:
6. PROVIDE UNIT WITH MODULATING GAS HEAT.
1. DESIGN SHALL BE DRAINABLE TO PREVENT INFILTRATION OF WIND DRIVEN RAIN.
2. PROVIDE WITH BIRDSCREEN.
3. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
ELECTRICAL
4. MOUNTING LOCATION TO BE COORDINATED WITH ARCHETETURAL. REFER TO ARCH DRAWINGS FOR DETAILS.
5. MOTORIZED DAMPER OPERATION TO BE INTERLOCKED WITH GARAGE EXHAUST FANS GAS SUPPLY FAN CHARACTERISTICS
MARK MANUFACTURER MODEL No. CAPACITY CFM E.S.P. FRPM H.P. FAN TYPE VOLTAGE PHASE NOTES
MAU-1 TRANE GRAA-30 300000.0 Btu/h 2400 1.00 in-wg 1070 2 BLOWER 460 3 ALL Project
PRESSURE
MARK MANUFACTURER MODEL No. CFM DROP VELOCITY FREE AREA SIZE MOUNTING NOTES
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL SCHEDULE OF EXHAUST HOOD VINELAND FIRE DEPT.
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL NOTES: HEADQUARTERS
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL 1. PROVIDE WITH GRAVITY BACKDRAFT DAMPER.
2. SHOP DRAWINGS MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL STATIC HOOD
NW BLVD. & PLUM STREET
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL MARK AREA SERVED MANUFACTURER MODEL No. SIZE CFM PRESSURE MOUNTING NOTES VINELAND, NJ 08360
L-1 GREENHECK ESD-435 3000 0.02 in-wg 320 FPM 9 SF 14' X 18" MASONERY ALL EH-1 COMPRESSOR ROOM GREENHECK GRSR 16 1530 0.12 in-wg ROOF ALL Drawing
HVAC SCHEDULES
PRINTED: 7/19/2022 9:31:35 AM
CONTROLS LEGEND
BO BI
ABBREVIATIONS T C
BMS = BUILDING MANAGEMENT SYSTEM DUCT TEMPERATURE SENSOR COOLING COIL T WELL TEMPERATURE SENSOR CT
BI
AHU = AIR HANDLING UNIT C
ADJ = ADJUSTABLE VALUES M
NO = NORMALLY OPEN H MD SP
HEATING COIL FAN/PUMP
NC = NORMALLY CLOSED AVERAGING
OA = OUTSIDE AIR TEMPERATURE SENSOR C
TCC = TEMPERATURE CONTROL CONTRACTOR
OAT = OUTDOOR AIR TEMPERATURE T
MAT = MIXED AIR TEMPERATURE 2-WAY CONTROL VALVE
AUTOMATIC DAMPER
DAT = DISCHARGE AIR TEMPERATURE
RADIANT HEAT PANEL SEQUENCE OF OPERATION
AI ANALOG INPUT POINT
LOW LIMIT 3-WAY CONTROL VALVE EXHAUST FANS CONTROL DIAGRAM 1. ROOM TEMPERATURE SETPOINT SHALL BE SET AT THE THERMOSTAT. WHERE THERMOSTATS HAVE NO
THERMOSTAT MS MOTOR STARTER SCALE: NONE SETPOINT ADJUSTMENT, THE SETPOINT SHALL BE SET THROUGH THE BMS. THE ROOM TEMPERATURE
SETPOINT MAXIMUM AND MINIMUM SHALL BE ADJUSTABLE REMOTELY THROUGH THE BMS.
AO ANALOG OUTPUT POINT
LOCAL S
P
START/STOP
SWITCH
SEQUENCE OF OPERATION
1. KITCHEN EXHAUST HOOD SHALL BE STARTED AND STOPPED FROM CONTROL SWITCHED MOUNTED IN
KITCHEN. COORDINATE LOCATION WITH OWNER.
2. MAKE-UP AIR UNIT SHALL BE ACTIVATED WHEN KITCHEN HOOD EXHAUST FAN IS TURNED ON TO SUPPLY AIR
FOR KITCHEN HOOD.
3. MAKE-UP AIR UNIT DIRECT GAS FIRED HEATER SHALL STAGE ON/OFF AS REQUIRED TO MAINTAIN LEAVING AIR
TEMP.
4. CONTRACTOR SHALL PROVIDE ALL INTERCONNECTING WIRING, MATERIALS, COMPONENTS, ETC. AS
TYPICAL ROOM REQUIRED FOR EXHAUST HOOD FAN/MAKE-UP AIR SYSTEM OPERATION AND SHALL COORDINATE ALL
CONNECTION TO REQUIREMENTS WITH EQUIPMENT SUPPLIER AND ALL OTHER CONTRACTORS FOR SYSTEM OPERATION.
CONTROL NETWORK 5. ACTIVATION OF HOOD FIRE SUPPRESSION SHALL SHUT OFF THE MAKE-UP AIR AS REQUIRED FOR CODE
TERMINAL UNIT COMPLIANCE.
TRANSFORMER
PACKAGED
BMS SOFTWARE P.C. IN ROOFTOP AIR T
MECHANICAL ROOM HANDLING UNIT E
BASEMENT PC PRIMARY AIR TO
FROM AHU ROOM
E
O.A. TEMP SENSOR
COMMUNICATION PACKAGED
CONTROLLER BMS SOFTWARE P.C. IN ROOFTOP AIR
TEMP. (COMM4) LINK WIRE
STATIC PRESS. SENSOR MECHANICAL ROOM HANDLING UNIT
CONTROL BASEMENT PC
(LOCATED IN DUCTWORK)
PANEL IN
MECH.
SUPPLY AIR TEMP SENSOR ROOM XXX
O.A. TEMP SENSOR
RETURN AIR TEMP SENSOR
COMMUNICATION
TEMP. (COMM4) LINK WIRE
ECONOMIZER STATIC PRESS. SENSOR
CONTROL
(ACTUATOR WITH RTU) (LOCATED IN DUCTWORK)
XFMR PANEL IN
MECH.
277/24 VAC TRANSFORMER TO SUPPLY AIR TEMP SENSOR
TERMINAL ROOM XXX
LOCATED ON EACH DDC
UNIT
TERMINAL UNIT SHALL T RETURN AIR TEMP SENSOR
(TYP.)
RECEIVE 120/24
VAC TRANSFORMER. THERMOSTAT ECONOMIZER
(ACTUATOR WITH RTU) ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
PACKAGED ROOFTOP UNIT SEQUENCE OF OPERATION - RTU - 2, 3 RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
VAV PACKAGED ROOFTOP UNIT
1. THE RTU SHALL BE CONTROLLED BY DDC FOR OCCUPIED AND UNOCCUPIED OPERATION AND
TERMINAL UNIT TEMPERATURE CONTROL DIAGRAM STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
OPTIMUM RUN TIME SEQUENCES. THE RTU SHALL START AS REQUIRED TO ACHIEVE ZONE SETPOINTS
BEFORE OCCUPIED CYCLE BEGINS. DURING OCCUPIED OPERATION RTU FAN SHALL RUN
AND SEQUENCE OF OPERATION OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
CONTINUOUSLY. 1. THE DISCHARGE AIR TEMPERATURE LEAVING THE TERMINAL UNIT SHALL BE MONITORED. BE SUBJECT TO LEGAL PROSECUTION.
2. STATIC PRESSURE SENSOR SHALL BE INSTALLED IN THE DUCTWORK APPROXIMATELY 2/3 2. ROOM TEMPERATURE SETPOINT SHALL BE SET AT THE THERMOSTAT. TEMPERATURE SETPOINT SINGLE ZONE ROOFTOP UNIT SEQUENCE OF OPERATION - RTU - 1
DOWNSTREAM OF THE SUPPLY FAN TO MAINTAIN OPERATIONAL SYSTEM PRESSURE. VFD CONTROL MAXIMUM AND MINIMUM AND THE AIRFLOW MAXIMUM AND MINIMUM SHALL BE ADJUSTABLE
SHALL MODULATE AIRFLOW THRU THE SUPPLY AIR FAN BASED ON SYSTEM AIR FLOW REMOTELY THROUGH THE BMS. c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
REQUIREMENTS. RTU SEQUENCE OF OPERATIONS
3. PRESSURE INDEPENDENCE: A DIFFERENTIAL PRESSURE SENSOR IN THE TERMINAL UNIT SHALL
3. INSTALL A HIGH LIMIT, MANUAL RESET, STATIC PRESSURE SENSOR AT THE FAN DISCHARGE THAT MEASURE THE AIRFLOW ENTERING THE TERMINAL UNIT. THE DAMPER SHALL MODULATE TO 1. THE DISCHARGE AIR TEMPERATURE LEAVING THE RTU SHALL BE MONITORED.
WILL SHUTDOWN THE FANS WHEN TRIPPED AND SEND AN ALARM TO DDC. MAINTAIN THE AIRFLOW SETPOINT, SO THAT THE AIRFLOW IS INDEPENDENT OF FLUCTUATIONSIN
THE SUPPLY DUCT STATIC PRESSURE. 2. ROOM TEMPERATURE SETPOINT SHALL BE SET AT THE THERMOSTAT. TEMPERATURE SETPOINT
4. MORNING START-UP SEQUENCE THE DDC SHALL START FAN, MODULATE THE GAS HEATING OR DX MAXIMUM AND MINIMUM AND THE AIRFLOW MAXIMUM AND MINIMUM SHALL BE ADJUSTABLE
COOLING TO MAXIMUM SETPOINT, PROVIDE 100% RETURN AIR, MAINTAIN CLOSED POSITION OF 4. EACH TERMINAL UNIT SHALL HAVE AN ASSOCIATED THERMOSTAT OR TEMPERATURE SENSOR REMOTELY THROUGH THE BMS.
OUTSIDE AND RELIEF AIR DAMPERS, OPEN ALL VAV TERMINAL UNITS TO FULL FLOW UNTIL SETPOINT WITHIN THE ZONE SERVED BY THE TERMINAL UNIT. MOUNT THERMOSTATS IN LOCATION
IS REACHED. DURATION OF START-UP SHALL BE AS REQUIRED TO ACHIEVE SPACE SET-POINT AT INDICATED ON HVAC PLAN. 3. ROOFTOP UNIT SHALL HAVE AN ASSOCIATED THERMOSTAT OR TEMPERATURE SENSOR WITHIN THE
START OF OCCUPIED MODE. ZONE SERVED BY THE ROOFTOP UNIT. MOUNT THERMOSTATS IN LOCATION INDICATED ON HVAC
5. ROUTE LOW VOLTAGE CONTROL POWER FROM THE CONTROL TRANSFORMER MOUNTED ON PLAN.
5. WHEN IN ITS NORMAL OCCUPIED MODE, THE MINIMUM OUTSIDE AIR DAMPER SHALL BE MINIMUM EACH UNIT. Manders Merighi Portadin Farrell Architects, LLC
POSITION WITH RELIEF AND RETURN AIR DAMPER MODULATING TO MAINTAIN STATIC SETPOINT. GAS 4. THERE SHALL BE A DEADBAND OF 2°F (ADJ) BETWEEN THE COOLING SETPOINT AND THE HEATING 1138 East Chestnut Avenue Vineland, New Jersey 08360
HEAT SHALL BE OFF AND ELECTRIC RE-HEAT TERMINAL UNITS SHALL PROVIDE SPACE HEATING. SETPOINT. THE COOLING SETPOINT SHALL BE EQUAL TO THE ROOM SETPOINT.
VARIABLE AIR VOLUME REHEAT ROOM p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
6. WHEN INDEXED TO UNOCCUPIED MODE BY DDC, THE RTU SHALL CYCLE TO MAINTAIN ROOM 5. WHEN THE ROOM TEMPERATURE RISES ABOVE THE COOLING SETPOINT, THE RTU SHALL MODULATE David G. Manders AIA AI-07220
TEMPERATURE AND HUMIDITY, THE OUTSIDE AIR DAMPERS SHALL CLOSE. IF THE OUTSIDE AIR TEMPERATURE CONTROL TO MAINTAIN THE CALCULATED AIRFLOW SETPOINT, WHICH IS BETWEEN THE MINIMUM AND MAXIMUM Lawrence J. Merighi AIA AI-07473
TEMPERATURE IS BELOW 50°F AND THE DISCHARGE AIR RISES ABOVE SETPOINT, THE OUTSIDE AIR AIRFLOW. WHEN THE ROOM TEMPERATURE FALLS BELOW THE COOLING SETPOINT, THE RTU SHALL Ronald P. Portadin AIA AI-13038
TERMINAL UNITS WITH DIFFERENT MAXIMUM AND MINIMUM AIRFLOWS SHALL FOLLOW MODULATE TO MAINTAIN THE MINIMUM AIRFLOW. THE HEATER ELEMENT SHALL REMAIN INACTIVE Peter W. Farrell AIA AI-13618
DAMPER SHALL MODULATE IN ECONOMIZER OPERATION. THE DDC SHALL CONTINUE TO MONITOR THE THISSEQUENCE.
THE SPACE TSTAT READINGS. WHENEVER THE ROOM TEMPERATURE IS ABOVE THE HEATING SETPOINT.
THERE SHALL BE A DEADBAND OF 2°F (ADJ) BETWEEN THE COOLING SETPOINT AND THE HEATING 6. WHEN THE ROOM TEMPERATURE FALLS BELOW THE SETPOINT, THE ELECTRIC HEATER ELEMENT
7. CONTROL SYSTEM SHALL HAVE REMOTE COMMUNICATIONS THROUGH AREA LOCAL AREA NETWORK SETPOINT. THE COOLING SETPOINT SHALL BE EQUAL TO THE ROOM SETPOINT.
AND VENDOR SPECIFIC SOFTWARE TO ROOM 157 WITH A REMOTE SITE CONNECTION TO THE SHALL STAGE TO MAINTAIN THE ROOM TEMPERATURE AT THE HEATING SETPOINT, WHILE
NETWORK, THE OPERATION OF THE CONTROL SYSTEM SHALL BE UNAFFECTED. ALARMS SHALL THEDAMPER MODULATES TO MAINTAIN THE MINIMUM AIRFLOW.
WHEN THE ROOM TEMPERATURE RISES ABOVE THE COOLING SETPOINT, THE DAMPER SHALL
CONTINUE TO BE PRINTED AND LOGGED TO THE DATABASE. MODULATE OPEN TO MAINTAIN THE CALCULATED AIRFLOW SETPOINT, WHICH IS BETWEEN THE 7. WHEN THE ROOM HUMIDITY RISES ABOVE SET POINT, THE DEHUMIDIFICATION CYCLE SHALL RUN
MINIMUM AND MAXIMUM AIRFLOW. WHEN THE ROOM TEMPERATURE FALLS BELOW THE COOLING USING HOT GAS RE-HEAT TO MAINTAIN SPACE TEMPERATURE SET POINT.
8. HUMIDISTAT (BUILDING) SHALL MAINTAIN SETPOINT (50% ADJ.) BY ENERGIZING AHU/FAN DURING SETPOINT, THE DAMPER SHALL MODULATE TO MAINTAIN THE MINIMUM AIRFLOW. THE ELECTRIC
NIGHT SETBACK PERIODS. HEATER ELEMENT SHALL REMAIN CLOSED WHENEVER THE ROOM TEMPERATURE IS ABOVE THE RTU SAFETIES AND NIGHT SETBACK
HEATING SETPOINT.
9. THERMOSTAT (BUILDING) SHALL MAINTAIN 68°F TO 78°F RANGE BY ENERGIZING AHU/FAN DURING
NIGHT SETBACK PERIODS. 1. SMOKE DETECTOR SHALL SHUT DOWN THE SUPPLY FAN AND CLOSE OUTSIDE AIR DAMPER ANYTIME Project
WHEN THE ROOM TEMPERATURE FALLS BELOW THE SETPOINT, THE ELECTRIC HEATER ELEMENT SMOKE IS DETECTED. SMOKE DETECTOR SHUTDOWN SHALL BE HARDWIRED CONNECTED, NOT
SHALL MODULATE TO MAINTAIN THE ROOM TEMPERATURE AT THE HEATING SETPOINT, WHILE SOFTWARE CONTROLLED. TEMPERATURE CONTROL, ELECTRICAL AND FIRE ALARM CONTRACTORS
RTU SAFETIES AND NIGHT SETBACK THEDAMPER MODULATES TO MAINTAIN THE MINIMUM AIRFLOW.
1. SMOKE DETECTOR SHALL SHUT DOWN THE SUPPLY FAN AND CLOSE OUTSIDE AIR DAMPER ANYTIME SHALL COORDINATE SMOKE DETECTOR TYPE, LOCATION, ETC.
SMOKE IS DETECTED. SMOKE DETECTOR SHUTDOWN SHALL BE HARDWIRED CONNECTED, NOT
SOFTWARE CONTROLLED. TEMPERATURE CONTROL, ELECTRICAL AND FIRE ALARM CONTRACTORS 2. THE ROOFTOP UNIT SHALL BE PROVIDED WITH MANUAL RESET RELAY TO MANUALLY RESET AND VINELAND FIRE DEPT.
SHALL COORDINATE SMOKE DETECTOR TYPE, LOCATION, ETC.
CONSTANT VOLUME COOLING ONLY ROOM
START THE ROOFTOP UNIT FANS AND COMPRESSOR UPON LOSS OF POWER OR SMOKE DETECTOR
SHUT DOWN. HEADQUARTERS
2. THE ROOFTOP UNIT SHALL BE PROVIDED WITH MANUAL RESET RELAY TO MANUALLY RESET AND
START THE ROOFTOP UNIT FANS AND COMPRESSOR UPON LOSS OF POWER OR SMOKE DETECTOR TEMPERATURE CONTROL 3. SET POINT. NIGHT SETBACK: THE SPACE THERMOSTATS SHALL INCORPORATE A NIGHT SETBACK. ALL
SHUT DOWN. THERMOSTATS SHALL OPERATE THE ASSOCIATED TERMINAL UNIT IF THE SPACE TEMPERATURE NW BLVD. & PLUM STREET
COOLING ONLY TERMINAL UNITS WITH EQUAL MAXIMUM AND MINIMUM AIRFLOWS SHALL FOLLOW
THIS SEQUENCE.
DIFFERS FROM ITS NORMAL SETPOINT (INITIAL SETBACK POINT OF ± 15°F (ADJ.)). OUTSIDE AND/OR VINELAND, NJ 08360
3. SET POINT. NIGHT SETBACK: THE SPACE THERMOSTATS SHALL INCORPORATE A NIGHT SETBACK. ALL RELIEF AIR DAMPERS SHALL REMAIN CLOSED IF THE OUTSIDE AIR TEMPERATURE IS ABOVE 50°F. THE
THERMOSTATS SHALL OPERATE THE ASSOCIATED TERMINAL UNIT IF THE SPACE TEMPERATURE WHEN TEMPERATURE SETPOINT CALLS FOR COOLING THE DAMPER SHALL MODULATE TO MAINTAIN
SPACE HUMIDISTAT SHALL MAINTAIN 50% RH (ADJ.) DURING UNOCCUPIED PERIODS. Drawing
DIFFERS FROM ITS NORMAL SETPOINT (INITIAL SETBACK POINT OF ± 15°F (ADJ.)). OUTSIDE AND/OR THE SAME AIRFLOW SETPOINT AT ALL TIMES IN ORDER TO PROVIDE CONSTANT PRESSURIZATION
RELIEF AIR DAMPERS SHALL REMAIN CLOSED IF THE OUTSIDE AIR TEMPERATURE IS ABOVE 50°F. THE AND AIR CIRCULATION IN THE ROOM. WHEN ROOM TEMPERATURE SETPOINT IS SATISFIED, DAMPER
SPACE HUMIDISTAT SHALL MAINTAIN 50% RH (ADJ.) DURING UNOCCUPIED PERIODS. SHALL MODULATE CLOSED. HVAC TEMP CONTROL
PRINTED: 7/19/2022 9:31:38 AM
ARROWS INDICATE EGRESS EXIT SIGNAGE CHEVRON(S) REQUIRED. WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. MOUNT 18" INTERCOM STATION WITH VIDEO CAMERA. MOUNT AT 44" A.F.F TO F. COORDINATE LIGHTING FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
I
A.F.F. TO BOTTOM, UNLESS NOTED OTHERWISE. BOTTOM, UNLESS NOTED OTHERWISE. SUBSCRIPT M INDICATES MASTER
SYMBOL INDICATES FIXTURE TYPE WHEN SHOWN ON LIGHTING PLANS SPEAKER TYPE STATION WITH VIDEO MONITOR. G. PROVIDE FIRE INTUMESCENT PUTTY PAD BEHIND / AROUND ALL ELECTRICAL BACKBOXES INSTALLED WITHIN FIRE
A ADJACENT TO FIXTURE. RATED WALLS. PUTTY PADS SHALL BE SPECIFIED TECHNOLOGIES, INC SERIES SSP. INSTALL PER MANUFACTURER'S
WALL OUTLET WITH 20A, 125V DOUBLE DUPLEX (QUADRAPLEX) A
1 RECOMMENDATIONS. REFERENCE ARCHITECTURAL RATINGS DETAIL KEY PLAN FOR RATED WALL LOCATIONS.
RECEPTACLE. MOUNT AT 18" A.F.F. TO BOTTOM UNLESS NOTED S CEILING OUTLET AND RECESSED CEILING MOUNTED PUBLIC ADDRESS
LOWER CASE LETTERS AT OUTLETS INDICATES SWITCHING OTHERWISE. SYSTEM SPEAKER COMPLETE WITH MOUNTING HARDWARE,
"a,b,c" ZONE
ARRANGEMENT. SPEAKER TYPE
BRACKETS/TILE BRIDGES, BAFFLES AND, BACKBOXES. H. EACH BRANCH CIRCUIT SHALL INCORPORATE A DEDICATED NEUTRAL CONDUCTOR WHERE NEUTRAL IS REQUIRED.
WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE FOR TV 1 THE NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS, UNLESS SPECIFICALLY INDICATED FOR
SINGLE POLE 20A, 120V/277V SWITCH. MOUNT 48" A.F.F. TO TOP, UNLESS TV DISPLAY. VERIFY MOUNTING HEIGHT WITH A/V PROVIDER BEFORE S WALL OUTLET AND WALL MOUNTED PUBLIC ADDRESS HORN TYPE CIRCUITS SERVING SYSTEMS FURNITURE.
NOTED OTHERWISE. ROUGH-IN. ZONE SPEAKER COMPLETE WITH ALL MOUNTING HARDWARE AND BRACKETS.
SUBSCRIPT: I. EACH CONDUIT CONTAINING BRANCH CIRCUITS SHALL CONTAIN A GREEN EQUIPMENT GROUND CONDUCTOR.
3 = THREEWAY SPECIAL OUTLET AS NOTED. MOUNT 18" A.F.F. TO BOTTOM UNLESS SPEAKER TYPE: DESCRIPTION;
2P = TWO POLE NOTED OTHERWISE. A: INTERIOR RECESSED CEILING MTD. J. CONDUIT SHALL BE RUN WITH SMOOTH, EASY BENDS. EXPOSED CONDUIT SHALL BE RUN PARALLEL OR
MS = VACANCY SENSOR B: INTERIOR WALL MTD HORN TYPE. PERPENDICULAR TO WALLS, CEILINGS, BEAMS, AND COLUMNS. CONCEALED CONDUIT MAY BE RUN AT ANGLES
LV = LOW VOLTAGE, ACUITY nPODM OR APPROVED EQUAL. 208Y/120V SURFACE MOUNTED PANELBOARD. DASH LINE INDICATES C: EXTERIOR WALL MTD HORN TYPE. OTHER THAN PARALLEL OR PERPENDICULAR TO BUILDING LINES BUT SHALL BE GROUPED IN A NEAT AND
N.E.C. CLEARANCE. WORKMANLIKE MANNER. DISSIMILAR ANGLES AND CRISSCROSS ARRANGEMENT WILL NOT BE ACCEPTABLE.
MS OUTLET BOX IN WALL AT 44" TO BOTTOM AND DIMMER SWITCH WITH
R CEILING OUTLET AND RECESSED CEILING SPEAKER WITH RED LED LIGHT
DUAL TECHNOLOGY VACANCY SENSOR SWITCH, ACUITY WSX DPDT OR FOR FIRE DISPATCH ALARM SYSTEM COMPLETE WITH ALL MOUNTING K. EXPOSED PARALLEL OR BANKED RACEWAYS SHALL BE RUN TOGETHER TO PROVIDE A NEAT APPEARANCE. BENDS IN
APPROVED SIMILAR. S PARALLEL OR BANKED RUNS SHALL BE MADE FROM THE SAME CENTER LINE SO THAT THE BENDS ARE PARALLEL.
480Y/277V SURFACE MOUNTED PANELBOARD. DASH LINE INDICATES HARDWARE AND BRACKETS.
N.E.C. CLEARANCE. STANDARD MANUFACTURERS’ BENDS ARE ALLOWED FOR GROUPS OF 90 DEGREE BENDS IF THE CONDUITS ARE
OUTLET BOX IN WALL AT 44" TO BOTTOM AND LOW VOLTAGE DIMMER WALL OUTLET AND PUBLIC ADDRESS SYSTEM VOLUME CONTROL CLOSE TO THE SAME SIZES. THIS SHALL REQUIRE THAT THERE BE A CHANGE IN THE PLANE OF THE RUN, SUCH AS
MS
LV SWITCH WITH DUAL TECHNOLOGY VACANCY SENSOR SWITCH, ACUITY V STATION. MOUNT 44" A.F.F TO BOTTOM, UNLESS NOTED OTHERWISE. FROM WALL TO CEILING, AND THE RACEWAYS OF THE SAME SIZE. IN OTHER CASES, PARALLEL RACEWAYS SHALL BE
NWSX PDT LV OR APPROVED SIMILAR. FUSIBLE DISCONNECT SWITCH. MOUNT 4'-6" A.F.F. TO CENTER, FIELD-BENT.
UNLESS NOTED OTHERWISE. DASH LINE INDICATES N.E.C. OUTLET BOX IN WALL WITH DATA JACKS AND DEVICE PLATE. PROVIDE
CEILING OUTLET AND DUAL TECHNOLOGY MOTION SENSOR FOR CLEARANCE. 1" CONDUIT FROM OUTLET BOX TO ACCESSIBLE CEILING AND BUSH END. L. ALL RECEPTACLES LOCATED WITHIN 6 FEET OF A SINK OR WATER SOURCE SHALL INCLUDE INTEGRAL GROUND
MS LIGHTING CONTROL, ACUITY nCM PDT 9 OR APPROVED SIMILAR. 2D PROVIDE CABLE FROM EACH JACK IN OUTLET BOX TO FAULT CIRCUIT INTERRUPTER, (GFI)
MOTOR CONTROLLER AND FUSIBLE DISCONNECT SWITCH TO SUIT TELECOMMUNICATIONS SYSTEM EQUIMENT AT RACK IN IT ROOM AND
OUTLET BOX MOUNTED MOTION LOW VOLTAGE SENSOR POWER PACK MOTOR. MOUNT 4'-6" A.F.F. TO CENTER, UNLESS NOTED OTHERWISE. TERMINATE. MOUNT 18" A.F.F TO BOTTOM, UNLESS NOTED OTHERWISE. M. CONDUITS SHALL NOT BE EMBEDDED IN FLOOR SLABS
PP WITH DIMMING OUTPUT, ACUITY nPP16 D EPF OR APPROVED SIMILAR.
ENCLOSED CIRCUIT BREAKER. MOUNT 4'-6" A.F.F. TO CENTER, #D: NO. OF DATA JACKS N. THE ELECTRICAL INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE 2017 NATIONAL ELECTRICAL CODE
CB
LIGHTING CONTROL DAYLIGHT SENSOR. SUBSCRIPT INDICATES THE UNLESS NOTED OTHERWISE. (NEC) AND THE NEW JERSEY UNIFORM CONSTRUCTION CODE.
DS
a LIGHTING SWITCH LEG LETTER OF THE FIXTURES THAT IT SHALL OUTLET BOX WITH (1) DATA JACK AND DEVICE PLATE FOR WIRELESS
CONTROL. ACUITY nCM ADCX OR APPROVED SIMILAR H POLYMER CONCRETE HANDHOLE AS INDICATED. ACCESS POINT. PROVIDE 1" CONDUIT FROM OUTLET TO J-HOOK SYSTEM
AP IN CORRIDER. PROVIDE CABLE FROM JACK IN OUTLET BOX TO
SITE LIGHTING FIXTURE AS SCHEDULES COMPLETE WITH REINFORCED MOTOR. TELECOMMUNICATIONS SYTEM EQUIPMENT AT RACK IN IT ROOM AND
CONCRETE BASE AND ALL REQUIRED MOUNTING ACCESSORIES. TERMINATE. WIRELESS ACCESS POINT DEVICE SHALL BE PROVIDED BY
HD OUTLET BOX FOR HAND DRYER. COORDINATE MOUNTING HEIGHT THE OWNER.
SITE LIGHTING BOLLARD OR PATHWAY LIGHTING FIXTURE AS J
WITH HAND DRYER PROVIDER.
SCHEDULED COMPLETE WITH REINFORCED CONCRETE BASE AND ALL WALL OUTLET AND TELEVISION SIGNAL JACK. COORDINATE LOCATION
REQUIRED MOUNTING ACCESSORIES. MANUAL MOTOR CONTROLLER WITH PILOT LIGHT TO SUIT MOTOR. TV AND MOUNTING HEIGHT WITH TELEVISION PROVIDER BEFORE ROUGH-IN.
P MOUNT 44" A.F.P TP BOTTOM, UNLESS NOTED OTHERWISE PROVIDE 1" CONDUIT FROM OUTLET BOX TO ACCESSIBLE CEILING CAVITY
FLOODLIGHT TYPE LIGHTING FIXTURE AS SCHEDULED. PROVIDE AND BUSH END.
COMPLETE WITH ALL MOUNTING HARDWARE AND CONCRETE BASE.
B EMERGENCY BATTERY INVERTER IIS 550 I. RATED FOR 550W FIRE ALARM SYSTEM
EMERGENCY POWER.
FIRE ALARM SYSTEM VISUAL UNIT. WALL MOUNT AT 80" A.F.F. TO STROBE.
MS
WALL OUTLET AND DUAL TECHNOLOGY MOTION SENSOR FOR LIGHTING ST
CONTROL, ACUITY nCM PDT 9 OR APPROVED SIMILAR. INTERIOR RATED WALL
FIRE ALARM AUDIO UNIT. MOUNT 80" A.F.F. TO BOTTOM, OR 6" BELOW CEILING
F TO TOP, WHICHEVER IS LOWER. SUBSCRIPT C: CEILING MOUNT. MINERAL
WOOD (4PCF)
F FIRE ALARM SYSTEM AUDIO/VISUAL UNIT. MOUNT 80" A.F.F. TO STROBE. FIRE STOPPING
F MANUAL FIRE ALARM ADDRESSABLE PULL STATION. MOUNT 48" A.F.F. TO TOP. STEEL SLEEVE
GENERAL DEVICE SUBSCRIPTS FIRE ALARM ADDRESSABLE CONTROL MODULE.
FIRE STOPPING
C MIN. 1/2" THICK
"1,2,3" NUMBER AT OUTLET INDICATES CIRCUIT ARRANGEMENT. FIRE ALARM ADDRESSABLE MONITOR MODULE. CONDUIT
M
"NL" SUBSCRIPT INDICATED LIGHTING FIXTURE IS NON-SWITCHED AND CEILING MOUNTED SMOKE DETECTOR. SUBSCRIPT R = WITH RELAY BASE.
SERVES AS NIGHTLIGHT. SD SUBSCRIPT C=COMBINATION SMOKE DETECTOR WITH CARBON MONOXIDE
C
DETECTOR AND SOUNDER BASE
"GFI" INDICATES GROUND FAULT CURRENT INTERRUPTER DEVICE.
HD FIRE ALARM HEAT DETECTOR.
INDICATES EXISTING WHEN SHOWN ADJACENT TO SYMBOLS ON
"EX" LIGHTING, POWER, OR SYSTEMS PLANS. CEILING MOUNTED CARBON MONOXIDE DETECTOR WITH A TEMPORAL 4
CO
SOUNDER BASE.
INDICATES SURFACE MOUNTED DEVICE WHEN INDICATED ON POWER
"S" & SYSTEMS PLANS. ADDRESSABLE SMOKE DETECTOR, DUCT TYPE. PROVIDE REMOTE TEST
DD SWITCH IN READILY ACCESSIBLE LOCATION. ACTIVATION OF DETECTOR SHALL
INDICATES WEATHER PROOF WHEN SHOWN ADJACENT TO SYMBOLS CAUSE FAN TO SHUT-DOWN.
"WP" ON LIGHTING, POWER, OR SYSTEMS PLANS. PROVIDE APPROPRIATE
ENCLOSURES AND/OR COVERS. TAMPER SWITCH.
TS
INDICATES DEVICE FOR ELECTRIC WATER COOLER WHEN INDICATED FLOW SWITCH. BRANCH CIRCUIT VOLTAGE
"EWC" ON POWER & SYSTEMS PLANS. FS
DROP TABLE 2
FIRESTOP DETAIL - CONDUIT WITH SLEEVE
L
DUCT SMOKE DETECTOR REMOTE STATUS LAMP INDICATOR FLUSH MOUNTED SCALE: NONE
INDICATES RECEPTACLE IS DEDICATED FOR MICROWAVE WHEN DD IN CEILING.
"MW" WIRE SIZE MAXIMUM CIRCUIT LENGTH
SHOWN ON POWER PLANS.
FSD FIRE/SMOKE DAMPER 20A, 120V, 1P
INDICATES RECEPTACLE IS DEDICATED FOR TELEVISION WHEN
"TV" SHOWN ON POWER OR SYSTEMS PLANS. VERIFY MOUNTING HEIGHT #12 AWG 61 FEET
WITH ARCHITECTURAL ELEVATIONS BEFORE ROUGH-IN. INTERIOR RATED WALL
#10 AWG 102 FEET
INDICATES RECEPTACLE IS DEDICATED FOR FREEZER WHEN SHOWN
ONE-LINE DIAGRAM MINERAL
WOOD (4PCF)
#8 AWG 154 FEET
"FRZ" ON POWER PLANS. FIRE STOPPING
TRANSFORMER. #6 AWG 240 FEET
INDICATES RECEPTACLE IS DEDICATED FOR ICE MACHINE WHEN STEEL SLEEVE
"IM" SHOWN ON POWER PLANS. CIRCUIT BREAKER.
CONDUIT BUSHING
• LENGTHS REPRESENT THE MAXIMUM
INDICATES REFRIGERATOR. POINT OF CONNECTION TO GROUND POTENTIAL. FIRE STOPPING
"REF" CIRCUIT LENGTH BASED ON THE WIRE SIZE
PUDDY MIN. 1" THICK
AND COPPER CONDUCTORS FOR A MINIMUM
INDICATES RECEPTACLES IS DEDICATED FOR UNDERCOUNTER NON-FUSED DISCONNECT SAFETY SWITCH. CABLING
VOLTAGE DROP OF 3%
"UCR" REFRIGERATOR WHEN SHOWN ON POWER PLANS.
FUSE.
• LENGTHS SHALL BE MEASURED FROM ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
INDICATES COFFEE MAKER. PANELBOARD TO THE FARTHEST DEVICE
"CM" FUSED SAFETY SWITCH. RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
CONNECT TO CIRCUIT. MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
INDICATES RECEPTACLE IS DEDICATED FOR VENDING MACHINE WHEN
"VM" POINT OF CONNECTION TO EXISTING. STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
SHOWN ON POWER PLANS. • THE PHASE AND NEUTRAL CONDUCTORS COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
SHALL BE SIZED AS INDICATED FOR THE OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
INDICATES COPIER RECEPTACLE WITH INTEGRAL SURGE NORMALLY OPEN CONTACT.
ENTIRE LENTH OF RUN. VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
"C" SUPPRESSION.
NORMALLY CLOSED CONTACT. BE SUBJECT TO LEGAL PROSECUTION.
• IF CONDUCTORS ARE UPSIZED FOR
"SMR" INDICATES TWO-PIECE SURFACE METAL RUNWAY. VOLTAGE DROP, GROUND CONDUCTORS
SOLIDLY GROUNDED WYE CONNECTION.
SHALL ALSO BE UPSIZED PER NEC 250.122.
INDICATES DEVICE CONNECTED TO EMERGENCY POWER WHEN
DELTA CONNECTION. c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
"EM" SHOWN ADJACENT TO DEVICE.
RACEWAYS
CIRCUIT CONCEALED BENEATH FLOOR. Manders Merighi Portadin Farrell Architects, LLC
1138 East Chestnut Avenue Vineland, New Jersey 08360
CIRCUIT EXPOSED. CONDUIT p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
PHASE
CONDUCTORS FIRE STOPPING David G. Manders AIA AI-07220
CIRCUIT CONCEALED IN CEILING OR WALL. CROSSBARS INDICATE
Lawrence J. Merighi AIA AI-07473
NEUTRAL NUMBER OF CONDUCTORS REQUIRED. CONDUIT NOT SIZED IS 1/2". SECURE PIPE RING TO FLOOR Ronald P. Portadin AIA AI-13038
GROUND CONDUCTORS NOT SIZED ARE NO. 12.
PIPE RING Peter W. Farrell AIA AI-13618
H1A-1,3 SILICON
HOMERUN TO PANELBOARD INDICATED. NUMBER OF ARROWHEADS 1" MINIMUM
INDICATES CIRCUIT NUMBERS. PREFIX INDICATES PANEL NUMBER.
INSULATION
C. LOCATION OF UTILITY COMPANY PAD MOUNTED TRANSFORMER AND UTILITY METER ARE APPROXIMATE. COORDINATE FINAL
10 LOCATION WITH UTILITY
1L1- 12,14
CLEARANCE D. CONDUITS SHALL BE SLOPED TO HANDHOLE LOCATIONS TO ALLOW FOR DRAINAGE OF CONDUITS.
6
1L1- 8,10 E. BURIED CONDUITS FOR BRANCH CIRCUITS, COMMUNICATIONS, AND SECURITY CABLING SHALL BE BURIED AT 24 INCHES
TO TOP OF CONDUIT, UNLESS NOTED OTHERWISE.
CONCRETE
PAD
GENERATOR
1L1- 16
KEYNOTES
GENERATOR ANNUNCIATOR 1 CONDUIT SHALL BE BROUGHT TO APPROXIMATELY 6 INCHES ABOVE FINAL GRADE AT RISER POLE. SECURELY ATTACHED DUCTS
COMM. CABLING, IN 1"C. TO POLE TO WITHSTAND PULLING TENSION DURING INSTALLATION OF CABLE. CONDUITS SHALL BE DIRECTLY ATTACHED TO POLE
DUAL PURPOSE DOCKING STATION
HEATER WITHOUT THE USE OF STANDOFF BRACKETS. PROVIDE 5 INCHES OF SEPARATION BETWEEN THE TWO CONDUITS. THE UTILITY
DOCKING STATION SHALL COMPLETE THE CONSTRUCTION OF PRIMARY RISER UP POLE. COORDINATE REQUIREMENTS WITH THE UTILITY.
OUTLINE OF
ELECT. ROOM 156 2 PROVIDE PROTECTION BOLLARDS AROUND TRANSFORMER AND GENERATOR. BOLLARDS AROUND TRANSFORMER SHALL
N COMPLY WITH UTILITY CO. REQUIREMENTS.
3 PROVIDE LINK-SEAL AROUND CONDUIT PENETRATIONS THROUGH BASEMENT WALL. PENETRATIONS SHALL BE SEALED
2
ENLARGED GENERATOR ELECTRICAL PLAN WATERTIGHT. PROVIDE A PENETRATION SLEEVE. FASTENERS SHALL BE STAINLESS STEEL.
4 CONDUITS SHALL SLOPE TO HANDHOLE.
SCALE: 1/8" = 1'-0"
5 STUB A 1 INCH CONDUIT 5 FEET OUT FROM POLE BASE AND CAP FOR FUTURE USE.
6 COORDINATE EXACT ELECTRICAL REQUIREMENTS OF GENERATOR BLOCK HEATER WITH GENERATOR MANUFACTURER BEFORE
ROUGH-IN. PROVIDE ALL REQUIRED WIRING AND RACEWAYS. PROVIDE APPROPRIATE CIRCUIT PROTECTION.
7 PROVIDE FOB READER AND VIDEO INTERCOM STATION FOR PEDESTRIAN GATE. COORDINATE REQUIREMENTS WITH GATE
PROVIDER.
8 UTILIZE ONE CONDUIT AND THE REMAINING CONDUIT SHALL BE SPARE. PROVIDE PULL STRING IN SPARE CONDUIT. TERMINATE
SPARE CONDUIT WITHIN 1ST FLOOR ACCESSIBLE CEILING CAVITY. PROVIDE LABEL ON END OF CONDUIT IDENTIFYING "SPARE TO
SITE".
9 ROUTE UP TO 1ST FLOOR ACCESSIBLE CEILING CAVITY.
10 PROVIDE (1) 20A/1 CIRCUIT FOR GENERATOR LIGHTS AND RECEPTACLE AND (1) 20A/1 CIRCUIT FOR BATTERY CHARGER.
11 VERIFY EXACT LOCATION AND REQUIREMENTS WITH OWNER'S SECURITY VENDOR.
12 VERIFY ELECTRICAL REQUIREMENTS FOR VEHICLE GATE WITH OWNER. PROVIDE ALL REQUIRED WIRING, RACEWAYS, AND
CIRCUIT PROTECTION. PROVIDE ALL REQUIRED GROUNDING.
1H1-1
1H1-1 1H1-1 PMT
4#10.1#10G,1"C. 4#10.1#10G,1"C. 4#10.1#10G,1"C. 2 G1
PROTECTION
BOLLARDS, TYP.
UE
SECONDARY
PARKING ELECTRIC EM FEEDER
GROUND GRID
GROUNDING GEN. DOCKING
UE
TEST WELL ELECTRODE STATION
TO ATS-1
AND CB FP
UE
UE
2"C
12"x18" 2#10.1#10G,1"C.
HANDHOLE 3#8,1#10G.,1"C.
UE
TO THE WEST
(1) 1"C. FOR CONTROL
1H1-1 AND SECURITY CABLING
UE
1H1-3
FOB READER
PEDESTAL
3#8,1#10G.,1"C.
(GATE POWER)
UE
SIT LTG.
NORTH 4TH STREET
2#10,1#10G.,1"C.
UE
PEDESTAL UTILITY UNDERGROUND PRIMARY ELECTRIC.
3#8,1#10G.,1"C. PROVIDE (2) 4 INCH SCH. 80 PVC CONDUITS BURIED 30 INCHES
(GATE POWER) BELOW GRADE TO TOP OF CONDUIT. ALL ELBOWS SHALL BE 36
INCH RADIUS AND SHALL BE GALVANIZED RIGID STEEL CONDUIT.
PROVIDE PULL ROPE IN DUCT FOR UTILITY USE. INSTALLATION
SHALL COMPLY WITH UTILITY REQUIREMENTS.
UE
FIRE
HEADQUARTERS
P1
UE
1H1-3
SITE LTG.
2#10,1#10G.,1"C. 2#10.1#10G,1"C.
12"x18"
HANDHOLE P1 PARKING P1
UE
1H1-3 2#10.1#10G,1"C.
1H1-3
7 1H1- 47
PARKING 1"C. VIA LCP1-12,
3#10 1H1- 47
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
I
UE
PEDESTRIAN 4 8
GATE RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
FR
(1) 2"C VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
3#8,1#10G.,1"C. 12"x18" 1L3-22,24 4 4 9 BE SUBJECT TO LEGAL PROSECUTION.
(GATE POWER) HANDHOLE 3#8,1#10G.,1"C.
(GATE POWER)
UE
3#10
UE
OUTLINE OF IT ROOM
UC
002 IN BASEMENT 3 4
1H1-3 (1) 2"C FOR
COMM. CABLING
UC
P1 4
UE
UC
24"x36"
PARKING
HANDHOLE Manders Merighi Portadin Farrell Architects, LLC
UE
UC
p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
UC
2#10,1#10G.,1"C. Ronald P. Portadin AIA AI-13038
1H1-3 1H1-3 5 PROVIDE (2) 4 INCH SCH. 40 PVC CONDUITS ELECTRICAL REQUIREMENTS OF
2#10,1#10G.,1"C. Peter W. Farrell AIA AI-13618
P1 BURIED 24 INCHES BELOW GRADE TO TOP SIGNAGE
1 OF CONDUITS. PROVIDE PULL ROPE IN EACH SIGNAGE
DUCT FOR UTILITY USE. 277V, 1P
4
P1
UC
NEW UTILITY POLE.
OH
UC
EXIST. UTILITY
BY POLE 1
UTILITY CO.
Project
N
PRINTED: 7/13/2022 9:27:12 AM
1
SITE ELECTRICAL PLAN Scale Job Sheet
SCALE: 1" = 20'-0" As indicated 20.026
Drawn Date E0.2
KA 07/11/2022
RELEASE / REVISION
No. Date Description
A 07-11-22 RELEASED FOR BIDDING
GROUND GRID.
SEE NOTE 3 POLE
HANDHOLE
1-5/8" X 1-5/8" PROVIDE GROUT TO FILL SPACE
GALVANIZED BETWEEN BOLT COVER AND BASE
UNISTRUT ANCHOR BOLTS
#4 L BAR AT 1" CHAMFER
SEE NOTES 2,7 CORNERS TYP. BOLT COVER
PROVIDE HIGH QUALITY RUB FINISH
REINFORCEMENT OF 4. ON BASE
6' - 6"
TEMPORARY CO. AND INSTALLED
TO CONDUITS, ANCHOR 2'-0"
WOOD DIVIDER BY CONTRACTOR
BOLDS, STEEL MESH, AND
WIRE COIL THE LIGHTING STANDARD FINISHED
60"
SECONDARY SIDE, 2-1/2" ADJUST AIM TO PROVIDE FULL
GALVANIZED STELL GRADE ILLUMINATION OF SIGNAGE OR
PRIMARY SEE NOTE 4
PIPE FILLED WITH FLAGS
DUCTS CONDUIT ENTRY AREA CONCRETE
1'-0" 1'-3" 1'-0" MIN. FLOODLIGHT FIXTURE
GROUND LUG 2'-0" MIN. AS SCHEDULED
#1/0 CU BOND TO
GROUND GRID
CONDUIT GRADE
6"
SET SUPPORT PIPES IN CONCRETE
8" AT MIN DEPTH OF 3 FEET 6'-0"
4'-0"
(6) #5 BARS
1-1/4" GALVANIZED RIGID STEEL EQUALLY SPACED
6' - 6" CONDUIT FOR METERING LEADS GROUND ROD, 18" STANCHION
#4 HOOP TIE @ 18" MIN.
TO TRANSFORMER SECONDARY 1/2" x 8'-0"
COMPARTMENT. METERING LEADS 12" O.C.
BY UTILITY CO. CONCRETE
PLAN
CONCRETE
#6 BARE COPPER GROUND IN 1 INCH CONDUIT
MIN. 4" ABOVE GALVANIZED RIGID STEEL CONDUIT TO
END BELL FINAL GRADE TRANSFORMER SECONDARY
CONCRETE. COMPARTMENT
1" MIN. NOTE 5 NOTE 1 3" CLEAR
REINFORCEMENT 16"
FINAL GRADE • METER PEDESTAL SHALL MEET UTILITY COMPANY REQUIREMENTS 24" DIA.
8"
6"
36" SWEEP 2
ELECTRIC UTILITY METER DETAIL 3
SITE LIGHTING POLE BASE DETAIL 11
FLOODLIGHT FIXTURE FOUNDATION DETAIL
SCALE: NONE SCALE: NONE SCALE: NONE
COMPACTED GRAVEL,
SIDE NOTE 6
2. REBARRING: PROVIDE 1/2 INCH DEFORMED REINFORCING STEEL, ASTM A615 GRADE 60. MAINTAIN THREE (3) TO FOUR (4) INCHES OF CLEARANCE WITH ALL
EDGES AND A MAXIMUM SPACING OF EIGHT (8) INCHES. PLACE RODS IN CENTER OF SLAB.
3. GROUND GRID: SHALL CONSIST OF FOUR (4), 5/8 INCH BY 8 FEET COPPER CLAD GROUND RODS. LOCATED EACH ONE IN A CORNER AND APPROXIMATELY
TWELEVE (12) INCHES BELOW FINAL GRADE. BRING IN THE GROUND WIRE (#2 COPPER MINIMUM) INTO A CONDUCTOR ENTRY AREA AND LEAVE A FIFTY-SIX
(56) INCH LENGTH COIL OF THE GROUND WIRE ABOVE THE SLAB FOR UTILITY PERSONNEL TO USE FOR BONDING THE TRANSFORMER AT TWO GROUNDING
LUGS. BOND ALL METALIC CODNUIT, STRUCTURES, AND METRUC PEDESTAL TO GROUND GRID. ANY GROUND CLAMPS USED TO BOND GROUND GRID TO
GROUND RODS SHALL BE UL LISTED FOR UNDERGROUND APPLICATION AND ELECTRICAL USE.
4. CONDUCTOR ENTRY AREA: PLACE TEMPORARY WOOD DIVIDER ACROSS CONDUCTOR ENTRY AREA, AT A POINT FIFTEEN (15) INCHES FROM RIGHT-HANDED
EDGE. ALL SECONDARY CONDUITS SHALL BE LOCATED ON THE RIGHT-HAND SIDE OF THIS DIVDER. PRIMARY CONDUITS SHALL BE LOCATED A MINIMUM OF
TWELVE (12) INCHES TO THE LEFT OF THIS DIVIDER.
5. PRIMARY CONDUIT ENTRANCE: THE FLANGE SHALL EXTEND AT LEAST ONE (1) INCH AND NO MORE THAN TWO (2) INCHES ABOVE THE PAD.
6. GRADE: GRAVEL SHALL BE COMPACTED BEFORE POURING CONCRETE. TRANSFORMER SHALL AT LEAST 4" ABOVE THE FINAL GRADE.
7. APPROVAL: GROUND GRID AND REINFORCEMENT SHALL BE INSPECTED BY UTILITY ENGINEERING STAFF PRIOR TO CONCRETE BEING POURED.
POLYMER CONCRETE COVER.
LOGO AS SPECIFIED.
1
CONCRETE PAD FOR TRANSFORMER
SCALE: NONE STAINLESS STEEL HEAVY DUTY
BOLT AND WASHER, WITH
STAINLESS STEEL INSERTS, TYP.
1/2" X 2-1/2"
PULL SLOT
SKID RESISTANT
GRADE. FEATHER AND SURFACE
EXHAUST SILENCER TAMP BACKFILL TO CREATE
SHALL BE WITHIN
ENCLOSURE
FLUSH INSTALLATION
AND POSITIVE DRAINAGE COVER
AWAY FROM BOX PROVIDE GASKET
W BETWEEN COVER
L AND BOX
GENERATOR
ANCHOR GENERATOR HANDHOLE
TO PAD (SEE SPEC.) 24" MIN.
PAD SHALL EXTEND 6" PROVIDE BOX
DIMENSIONS AS
BEYOND EQUIPMENT, EXTENSIONS AS
INDICATED
ALL SIDES REQUIRED D
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
1" PAD SHALL
RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
CHAMFER BE LEVEL
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
ALL SIDES 6" ABOVE GRADE STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
BASE RAIL 6"
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
FINISHED GRADE CLEAN 3/4" CONDUIT(S) WITH OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
6" CRUSHED ROCK BELL BENDS (TYP.)
1'-0" POLYMER VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
SIZE, QUANTITY AND CONCRETE BE SUBJECT TO LEGAL PROSECUTION.
#5 BARS @ 12" O.C.
WIRING AS INDICATED SIDES WITH NO BASE
2'-11" BOTH WAYS
ON PLANS
CONCRETE PAD (3000PSI)
c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
COMPACTED GRAVEL BASE BOX
4
GENERATOR CONCRETE PAD DETAIL 5
HANDHOLE DETAIL INSTALLATION IN TURF AREAS 6
ELECTRICAL HANDHOLE DETAIL
SCALE: NONE SCALE: NONE SCALE: NONE
5' - 6"
SEE CIVIL FOR
SURFACE TYPE
MAGNETIC WARNING
12'-
GRADE
CONCRETE COVER
SELECTED EXCAVATED GROUNDING ROD
1'-0" MATERIAL TEST WELL SEE 60º
DETAIL THIS SHEET
6" PACKED CLEAN SAND GRADE
#4 REBAR
REINFORCEMENT 1-1/2" 12"Ø X 2'-0" V.C.P.
3" FROM OUTER POUR, 12'-0" Project
TYPICAL GROUND CONNECTOR
CONDUIT. NUMBER & PLAN
7.5" 2" MIN ARRANGEMENT AS TEST WELL GRADE ⅝"Ø X 10'-0"
3' - 10"
GROUND ROD
INDICATED
VINELAND FIRE DEPT.
4' - 0"
6"
#4/0 GROUND
CONCRETE ENCASED,
3'-0"
3"
CONTINUOUS THROUGHOUT
CABLE CONCRETE
HEADQUARTERS
ENTIRE LENGTH OF DUCT
3" BANK EXOTHERMIC WELD
(TYPICAL) NW BLVD. & PLUM STREET
2" MIN #4/0 GROUND
CABLE VINELAND, NJ 08360
⅝" X 10'-0" 1' - 4" DIA.
7.5" SECTION GROUND ROD Drawing
SITE DETAILS
7
SECONDARY ELECTRIC DUCTBANK DETAIL 8
GROUNDING GRID DETAIL 9
GROUNDING ROD TEST WELL 10
PROTECTION BOLLARD DETAIL
PRINTED: 7/13/2022 9:27:15 AM
GENERAL NOTES:
A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET E0.1 FOR ADDITIONAL INFORMATION.
B. ALL EXIT LIGHTS, NIGHT LIGHTS, AND BATTERY PACKS FOR EMERGENCY EGRESS LIGHTING
14 SHALL BE PROVIDED WITH UNSWITCHED PHASE CONDUCTOR.
6 7 8 9 10 11 12
KEYNOTES
1 MOUNT TYPE N AND NX LIGHTING FIXTURE AT ------ A.F.F. TO BOTTOM. PROVIDE ALL
REQUIRED MOUNTING HARDWARE AND STRUT.
2 ROUTE STAIR #1 LIGHTING CIRCUIT THROUGH JUNCTION BOX.
3 ROUTE STAIR #2 LIGHTING CIRCUIT THROUGH JUNCTION BOX.
4 ROUTE ELEVATOR LIGHTING CIRCUIT THOUGH JUNCTION BOX.
5 LOW VOLTAGE OVERRIDE SWITCH FOR AFTER HOURS LIGHTING CONTROL. PROVIDE LABEL
ETCHED IN BUTTON INDICATING AFTER HOURS LIGHTING OPERATION.
P MDP 1H1
6 WALL MOUNT SIGNAGE LIGHTING BELOW THE SIGNAGE. PROVIDE 24 INCH STAND-OFFS.
FIXTURE LENGTH SHALL MATCH LENGTH OF SIGNAGE. COORDINATE WITH SIGNAGE
ATS1 PROVIDER.
1H1- 40 1 1H1- 40 1 NL 1H1- 40 1 1H1- 40 1 1H1- 40 1 1H1- 40 1
1L1- 2 FX
ELECTRICAL 1L1 7 COORDINATE LOCATION OF LIGHT FIXTURE WITH SUN SHADE SUPPORTS.
a a a a b
ROOM
156 NX N NX N N NX
FACP1
1L1- 2 FX
1L1- 21 1L1- 2
LCP1
1L1- 2 FX 1H1-40
J
1L1-2
1H1- 40
a: VIA LCP1-1
EM T1 X2
1H1- 40
+8'
b: VIA LCP1-2
6 7 8 9 10 11 12 14
1H1- 48 1H1- 40 1 1H1- 40 1 1H1- 40 1 1H1- 40 1 1H1- 40 1
b a a a b
LV
a,b
NX N N N N W
VIA LCP1-8 +11'-6" TO CENTER
1H1- 48
1L5
T2
1H1- 42 1 1H1- 42 1 NL 1H1- 42 1 1H1- 42 1 1H1- 42 1
+16'
1H1- 48 b J a a b
1H1-42
NX N NX N NX
1H1- 42
a: VIA LCP1-3
T2 b: VIA LCP1-4
c: VIA LCP1-5
1H1- 40 1 1H1- 40 1 NL 1H1- 40 1 1H1- 40 1 1H1- 40 1 +16''
b a a b 1H1- 48
NX N NX N NX X2 W
1H1- 40
DS
b
DS
b
EM
+11'-6" TO CENTER
1H1- 48
N
TYPE W FIXTURES SHALL BE MOUNTED
B
AT SAME ELEVATION ALONG THE EAST
FACE OF BUILDING. VERIFY WITH
ARCHITECT. W
GARAGE +10' TO CENTER
'B' 1H1- 42 1 1H1- 42 1 1H1- 42 1 1H1- 42 1 1H1- 42 1 1H1- 48
146B
TYPE T2 FIXTURES SHALL BE MOUNTED b a a a b
T2
AT THE SAME ELEVATION ALONG THE N N N N N
+16' WEST FACE OF BUILDING. VERIFY WITH
1H1- 48 ARCHITECT.
T1 1H1- 42 1H1- 42 W
X2 EM
EM
1H1- 48 X2
DS
b
1H1- 42 1 1H1- 42 1 NL 1H1- 42 1 1H1- 42 1 1H1- 42
DS
b +10' TO CENTER L
1 1H1- 48
B
b a a b
T2 NX N NX N NX
+16'
1H1- 48
GARAGE
1H1- 40 1 1H1- 40 1 1H1- 40 1 1H1- 40 1 1H1- 40 1 T2 'A'
NL
+16'' 146A
b a a b
1H1- 48
NX N NX N NX
a,b
LV LV 5
SCBA EQUIPMENT/
YARD HAZMAT MAINTENANCE
FILL/HOSE 153 PARTS
EQUIP/ 154 OFFICE
F STORAGE F 155
FLAM. 152 1L5- 2
1L5- 2
3
5
2
W
-
9
E
B
E 1 4
5
-1 0
STORAGE 1L5- 2 1L5- 2 1L5- 2 1L5- 2 1L5- 2 EM EM 1L5- 2 1L5- 2
151
MS
1L5- 2
NL NL
MS
A1 A1
M 1H1- 42 1 1H1- 42 1 1H1- 42 1 1H1- 42 1 1H1- 42 1
+10' TO CENTER
1H1- 48
b a a a b
LV
F 1L5-2 F F F F S F
S
3
5
2
PP
-
9
E
B
4
5
-1 0
PP 1L5- 2 1L5- 2
E 1
N N N N N
1L5- 2 1L5-2 1L5-2
1L5-2 1L5-2
LV MS MS MS
1L5
T2
+16''
1H1- 48
N 1H1- 42
b
1 1H1- 42
a
1 NL 1H1- 42 1 1H1- 42
a
1 1H1- 42
b
1
2
FIRST FLOOR LIGHTING PLAN (CONT.) NX N NX N NX
X2
K
1H1- 42 X2
1L2- 32 X2
1H1- 42 1H1- 42 V VX V V VX V
5 c c c c c c S
1H1- 42 1H1- 42 1H1- 42 1H1- 42 1H1- 42
LV LV
a,b,c
1H1- 46 ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
1 2 3 4 5 VIA LCP1-7 1H1- 46 U a,b,c 5 a,b,c 1L2- 32 STAIR
RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
EM LV LV 5 LV LV NL
EM
3
150
J MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
1L2- 20 1L2- 24 STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
1L2-34 1L2- 32 1L2-32 J
S 1L2- 30 NL J
X1 MS 1L2-22 x 1L2-22 1L2- 24 COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
EM 1L2- 30 LV X1
EM y
+8' 1L2- 34 OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
EM EM T1 X2 4 B1X 1L2- 20 1L2- 22 1L2- 22 1L2- 22 1L2- 22 1L2-24 1L2-22
H
4
5
-1 0
PP
E 1
3
5
2
-
9
E
B
CORRIDOR +8' 1H1- 46 A1 VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
T1 +8' T1 NL
3
5
2
112
-
9
E
B
5
2
-
9
E
B
1H1- 46
B E
9 -2
5 5
3
B E
9 -2
5 5
3
B E
9 -2
5 5
3
B E
9 -2
5 5
2
B E
9 -2
5 5
3
E 1
- 1
0 5
4
B E
9 -2
5 5
3
B E
9 -2
5 5
3
B E
9 -2
5 5
2
B E
9 -2
5 5
3
X1 X1 1L2- 20
3
5
2
-
9
E
B
E 1 4
5
-1 0
F F Q Q
G
1 4
0 5 -
E 1 9 2
5 5
E -2 B 4
5
-1 0
E 1 4
0 5
1 -
E 1 E -2
9 2
5 5 B 4
5
-1 0
E 1 1 4
0 5 -
E 1 E -2
9 2
5 5 B E 1 4
5
-1 0 4
0 5
1 -
E 1 E -2
9 2
5 5 B 4
5
-1 0
E 1 1 4
0 5 -
E 1 9 -2
E 2
5 5 B 4
5
-1 0
E 1
9 3
5 5
E -2 B 3
5 5
E -2
9 B 3
5
2 -
9
E B 9 3
5 5
E -2 B 9 3
5 5
E -2 B 3
5
2 -
9
E B E -2
9 3
5 5 B 9 3
5 5
E -2 B 3
5
2 -
9
E B E -2
9 3
5 5 B E -2
9 3
5 5 B 3
5
2 -
9
E B 3
5 5
9 -2
E B 9 -2
E 3
5 5 B 3
5
2 -
9
E B
STAIR J CORRIDOR
FIRE CODE FIRE EVIDENCE FILE 1L3- 25 X1 1L2- 20 1L2-30
124 GEAR DECON
4
5
-1 0
127
E 1
SECRETARIES
3
5
2
-
9
E
B
MARSHAL ENFORCEMENT INVESTIGATOR STORAGE STORAGE CHIEF NL
111 A1 STOR. ROOM c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
3
5
2
-
9
E
B
5
2
118
-
9
E
B
107 108 109 109A 110 B1X 148 149 1L2- 24
A1 A1 1L2- 20 B1
1L3- 25 NL 1L2- 20 B1 1L2-22 A1
1L3- 25 TOILET A1
DEPUTY
MS
1L2- 24
3
5
2
1L3- 25 1L3- 25
-
9
E
B
E 1 4
5
-1 0
A1 A1 A1 A1 ROOM 1L2- 22 1L2- 22 1L2- 22 1L2- 22 1L2- 22 BUNK
1L4-18 CHIEF 147 1L2- 20
119 1L2-20 140
1L3- 25 1L3- 25 1L3- 25 1L3- 25 A2 A2
1L2- 20
MS
A1 A1 A1 A1 A1 A1 A1 A1 MS MS A1 A1 MS MS
1L2- 20 1L2- 20 A1 JANITOR 1L2- 20 X1
y y x x
1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L3- 25 1L3-25 1L3- 25 125 B1
A1 PP A1 1L3- 25 PP PP 1L2- 20 LV CORRIDOR
1L3-25 1L3-25 EM B1 F F Q Q 127 1L2-22
1L3-25 MS 1L3- 25 CORRIDOR B1
1L4-18 1L4-18 MS 1L4-18 MS 1L4-18 MS 1L3- 25 LV B1 1L2-20 MS 1L2-20 MS S 1L2- 30 NL 1L2-20 MS 1L2- 24
4
5
-1 0
MS LV
E 1
nDTC LV
3
5
2
-
9
E
B
CORRIDOR 117 A1
112
F
3
5
2
-
9
E
B
5
2
TOILET
-
9
E
B
1L2- 20 B1
LV
3
5
2
-
9
E
B
4
5
-1 0
A1X
E 1
A1 PP B1 PP 1L3- 25 G 1L3-25 E
MS
NL G 1L3- 27 CORRIDOR B1 PP A1 A1 A1
X3 1L4-18 B1X X1 1L3- 25 NL 1L3- 25 1L2- 20 Manders Merighi Portadin Farrell Architects, LLC
4
5
-1 0
4
5
-1 0
117 1L2- 22
E 1
E 1
LV NL
3
5
2
3
5
2
-
-
9
E
9
E
B
B
1L4- 18 1L4- 18 NL 1L4- 18 1L4- 18 CORRIDOR 1L4- 18 X1 1L3- 25 1L3- 25 1L3- 25 1L3- 25 X3 1L2- 20 1L2- 20 1L2- 20 NL 1L2-20
102 1L2- 20 1L2- 22 1L2- 22 1L2- 22
LV
3
5
2
-
9
E
B
5
2
-
9
E
B
MS
TOILET y G H6X 1L3- 25 x y 1138 East Chestnut Avenue Vineland, New Jersey 08360
1L4- 18 1L4- 18 X1 WORKSPACE TOILET B1 1L2-22
ROOM 1L2 126 B1 A1 p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
1L3- 25 1L3- 25 G
5
2
-
9
E
B
1L2-20
3
5
2
MS 1L2- 20
-
9
E
B
3
5
2
-
9
E
B
E 1 4
5
-1 0
MS
a,b,c
A1 MS A1 A1 1L4- 18 A1 A1 E 138
1L3- 25 b a DAY A1 1L2- 24 Lawrence J. Merighi AIA AI-07473
3
5
2
-
9
E
MS PP
B
E 1 4
5
-1 0
LV
b
E 1 4
5
-1 0
3
5
2
143
-
9
E
A1
B
104 1L2- 20 1L2- 20 1L2- 20 CAPTAIN 1L2- 20 1L2- 20 1L2- 20 1L2- 20 CAPTAIN 1L2- 20 1L2- 22
MS
3
5
2
-
9
E
B
5
2
-
9
E
B
1L4- 18 1L4- 18 1L4- 18 1L4- 18 1L4-18 NL 121 LIEUTENANT 123 TOILET E
101 1L2- 22 BUNK
x,y
MS
A1 1L4-18 NL 1L3- 27 1L3- 27 1L3- 27 1L3- 27 1L3- 27 122 ROOM A1 B1X
1L4- 18 1L4- 18 b C b C b C 1L2- 22 1L2- 24 137
1L4- 18 CORRIDOR
FAA 1L3- 25
1L3- 25
1L3- 25 MS
a,b
134 1L2- 22
1L2- 22 E
3
5
2
-
9
E
B
1L2- 22
E 1 4
5
-1 0
102 1 4
0 5 -
E 1
9 2
5 5
E -2 B 9 2
5 5
E -2 B
4
5
-1 0
E 1 4
0 5
1 -
E 1
E -2
9 2
5 5 B
X1 E 2
5 5
9 -2 B
4
5
-1 0
E 1
1H1- 44 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3
LAUNDRY
TOILET
B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3 B E
9 -2
5 5
3
135 NL
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4
E -2
9 3
5 5 B 9 3
5 5
E -2 B 9 3
5 5
E -2 B 3
5
2 -
9
E B E -2
9 3
5 5 B 9 3
5 5
E -2 B E 3
5 5
9 -2 B 3
5
2 -
9
E B
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4
E 1 4
5
-1 0
3
5
2
-
9
E
B
TRAINING ROOM 1L2- 24
5
2
-
9
E
B
3
5
2
-
9
E
B
142
MS
A1X
B
MS A1 MS 1L4-18 113 B1 A1 B1
4
5
-1 0
4
5
-1 0
E 1
E 1
3
5
2
3
5
2
-
-
9
E
9
E
A1
B
U U E 1L2-22 A1
NL 1L4- 18 1H1- 44 1H1- 44 1L2- 20 1L2- 22 A1 1L2- 24
1L2-20 1L2- 22
3
5
2
-
9
E
B
E 1 4
5
-1 0
FIRE 1L2- 22 BUNK
LV MS MS 1L2- 22 136
D
5
2
5
2
-
-
9
E
9
E
B
A1 A1
3
5
2
3
5
2
-
-
9
E
9
E
B
PREVENTION b b b b b
MS
3
5
2
X3
-
-
9
E
9
E
B
B
4
5
-1 0
4
5
-1 0
E 1
E 1
1L4- 18
U
E 1
4
5
-1 0
-1 0
E 1
5
4
1L3- 27 1L3- 27 1L3- 27 1L3- 27 1L3- 27
3
5
2
E
9
-
-
9
E
2
5
3
B
1L4- 18 1L4- 18 1H1- 44 1H1- 44 B1X B1
MS 1L2- 24 B1 NL
C
3
5
2
E
9
-
-
9
E
2
5
3
B
NL
E 1
-1 0
4
5
-1 0
5
4
E 1
1 4
0 5 -
E 1
E -2
9 3
5 5 B 9 3
5 5
E -2
E -2
9
B
2
5 5 B
3
5
2 -
9
E B
E 1 4
5
-1 0
4
0 5
1 -
E 1
E -2
9 3
5 5 B 9 3
5 5
E -2
E -2
9
B
2
5 5 B
3
5
2 -
9
E B
4
5
-1 0
E 1
a,b B1 1L2- 24 1L2- 24 1L2- 24 1L2- 24 1L2- 24
1L2-20 A1 STORAGE
113B
D1 B1
CORRIDOR
127 B1 B1 B1 B1
CORRIDOR
127 B1 VINELAND FIRE DEPT.
1L2- 20
MS
HEADQUARTERS
1L2- 24 1L2- 24 1L2- 24 1L2- 24 1L2- 24 1L2- 24
b b b b b
E 1 4
5
-1 0
3
5
2
-
9
E
B
EM
B
3
5
2
-
9
E
B
MS
0 5
1 4
DS MS
-
E 1
9 -2
E
B 3
5 5
b a,b 1H1- 50 A1 A1
X1 A1 A1 Drawing
1L3- 27
VIA LCP1, 1L2- 20 OFFICE 1L2- 20
A1
BUNK
A1
BUNK
A1 A1
BUNK B
3
5
2
-
9
E
B
E 1 4
5
-1 0
3#10 113C OFFICER 1L2- 22 OFFICER 1L2- 22 130 131 1L2- 22 BUNK 133
3
5
2
-
9
E
B
E 1 4
5
-1 0
E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 E 1
- 1
0 5
4 B E
9 -2
5 5
2 E 1
- 1
0 5
4 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5 E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5 E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5 E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5
PLAN
B E
9 -2
5 5
3 B E
9 -2
5 5
3 B 9
E -5
2 3
5
B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
B E
9 -2
5 5
2
E 1
- 1
0 5
4 E -
1 0
1 4
5
E -
1 0
1 4
5 B 9
E -5
2 2
5 E -
1 0
1 4
5
APPROX. Y
34' IN LENGTH
PRINTED: 7/13/2022 9:27:52 AM
6 7
9 11 13
KEYNOTES
1 PROVIDE 30 DEGREE DOWNWARD ANGLE MOUNTING BRACKET TO MOUNT LIGHTING
FIXTURE IN STAIRWELL.
2 WALL MOUNT SIGNAGE LIGHTING BELOW THE SIGNAGE. PROVIDE 24 INCH STAND-OFFS.
FIXTURE LENGTH SHALL MATCH LENGTH OF SIGNAGE. COORDINATE WITH SIGNAGE
PROVIDER.
QUIET
ROOM
206
K
E 1
-1 0
5
4
B
9
-
E
2
5
3
2L1- 2
A1 2L1-2
MS PP LV
2L1- 2 2L1- 2 MS V VX V X1 STAIR
2L1- 2 2L1-2 VIEWING 150
LV
MS S
B
MEZZANINE
9
-
E
2
5
3
E 1
-1 0
NL
5
4
A1 A1 207
2L1- 2 2L1- 2 2L1- 2
MS
5 B1 B1 2L1- 2 1L2- 32
PP
E2.2 2L1-2 2L1- 2 2L1- 2 NL
X1 EM
J NL 1L2- 30 S
2L1- 2 2L1- 2 DAY
E 1
- 1
0 5
4
B 9
E -2
5 5
3 B 9
E -2
5 5
3
B 9
E -2
5 5
2
B 9
E -2
5 5
3
E 1
- 1
0 5
4
E 1
-1 0
1L2-34
5
4
B
9
-
E
2
5
3
PANTRY EM CORRIDOR X1
204 ROOM
CORRIDOR 1 A1 A1 203 S
202 b b
H 2L1- 2 1L2- 32 S
B
9
-
E
2
5
3
E 1
-1 0
5
4
PANTRY 1L2- 34 B1X MS
202C 1L2- 30
2L1- 2
E 1 4
5
-1 0
3
5
2
-
9
E
B
STORAGE FW
LV
3
200A 6
MS
NL
2L1- 2 E2.2
G B1 2L1-2 TOILET 2L1- 2 2L1- 2 S
3
5
2
-
9
E
B
5
2
-
9
E
ROOM
B
PANTRY A1 A1X
202B 2L1- 2 2L1- 2 205 b b A1 1L2- 30
c
MS
MS
ROOF S
2L1- 2 2L1
MS
E -2
9
B 3
5 5
1 4
0 5
-
E 1
B1 2L1-2 c STAIR 2L1-2 1L2- 32
124 B1
PANTRY 2L1- 2 A1X 2L1- 2 A1 A1 2ND FLOOR
202A 2L1- 2
c
2L1- 2 2L1- 2 2L1- 2
MS
c EM
LV 1L2- 30 NL S 2L1-2 A1 MS A1 1L2- 32
F B1 2L1-2
2L1-2
2L1- 2 X1
2L1- 2
a a
S
S
LV LV LV 1L2- 30
PP X3 2L1- 2 S
b 3a PP 3a 1L2- 30
c a X2
2L1- 2 2L1- 2 2L1- 2 2L1-2 1L2- 30
b PP a
2L1-2 b b a a
2L1- 2 2L1- 2
E 1 4
5
-1 0
3
5
2
-
9
E
B
A1X A1 A1 A1 2L1- 2 A1X A1X A1
a a 1L2- 32
MS 2L1- 2 2ND FLOOR
MS
a,b a,b S
MS
3
5
2
-
9
E
B
5
2
1ST FLOOR
-
9
E
B
a,b
1L2- 30
2L1- 2 2L1- 2 2L1- 2 2L1- 2 2L1-2
b b a a a S
PP MS 1L2- 32 1L2- 32
2L1- 2 2L1- 2
E -2
9
B 3
5 5
0 5
1 4
LV
3
-
E 1
A1 A1 A1X A1 A1 S X2
a A1 a A1
KITCHEN DINING 2L1- 2 1L2- 30
E E 1
- 1
0 5
4
B 9
E -2
5 5
3 B 9
E -2
5 5
3
B 9
E -2
5 5
2
201
B 9
E -2
5 5
3
E 1
- 1
0 5
4 E 1
- 1
0 5
4
B 9
E -2
5 5
3 B 9
E -2
5 5
3
B 9
E -2
5 5
2
B 9
E -2
5 5
3
E 1
- 1
0 5
4
200
E 1
- 1
0 5
4
B 9
E -2
5 5
3 B 9
E -2
5 5
3
B 9
E -2
5 5
2
B 9
E -2
5 5
3
E 1
- 1
0 5
4
c
E 1
- 1
0 5
4
B 9
E -2
5 5
3 B 9
E -2
5 5
3
B 9
E -2
5 5
2
B 9
E -2
5 5
3
E 1
- 1
0 5
4
S
BASEMENT
1ST FLOOR
Z Z
2L1- 2 2L1- 2
c c
4
STAIR #2 LIGHTING SECTION 5
STAIR #1 LIGHTING SECTION
SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0"
13
Z Z
2L1- 2 2L1- 2
c c
c c 1H1- 50
Z 2L1- 2 2L1- 2 Z VIA LCP1
N
3#10
K
J 1H1- 48
T2 1H1- 48 VIA LCP1-8 Y
2
SECOND FLOOR LIGHTING PLAN a
a
NL
2
SCALE: 1/8" = 1'-0"
LV
a
1L2- 32
NL S
1L2- 32
S APPROX.
4' IN LENGTH
Y
APPROX. 2
20' IN LENGTH
N
6
ROOF STAIR #2
SCALE: 1/8" = 1'-0"
9 11
K
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
5 MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
E2.2
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
J 1L2- 30 NL S LV
OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
EM 1L2-34 VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
1 B1X BE SUBJECT TO LEGAL PROSECUTION.
R
1L2- 34
EM BL1- 17
BL1- 17 FW BL1- 17 NL
PP BL1- 17 c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
BL1-17
BL1- 17 FX MS F
X1
G BL1- 17
MS
BL1- 17
B1
BL1
BL1- 17
STAIR BL1- 17 B1 BL1- 17
124
CORRIDOR
FX F 000
B1X BL1- 17 B1
NL
BL1- 17 BL1- 17
BL1- 17 6 7 8 9 10 11 12
X1
F BL1- 17
LV
B1
BL1- 17 F FX
BL1- 17 BL1- 17 Manders Merighi Portadin Farrell Architects, LLC
BL1-17 B1X BL1- 17 A2
BL1- 17 1138 East Chestnut Avenue Vineland, New Jersey 08360
PP
NL X1 BL1- 17 p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
F FX BL1-17
VX V 1L5-26
LV NL David G. Manders AIA AI-07220
LV MS PP
MS
Project
N N
1
BASEMENT LIGHTING PLAN 3
SECOND FLOOR POWER AND DATA PLAN (MEZZ.) VINELAND FIRE DEPT.
SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0"
HEADQUARTERS
NW BLVD. & PLUM STREET
VINELAND, NJ 08360
Drawing
RELEASE / REVISION
GENERATOR
ANNUNCIATOR
GENERAL NOTES: No. Date Description
16 A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET E0.1 FOR ADDITIONAL INFORMATION. A 07-11-22 RELEASED FOR BIDDING
PANEL 16
1L2-33 1L2-31 1L2-35 1L2-37
1L2- 31,33 B. INSTALL J-HOOKS ABOVE CEILING FOR COMMUNICATION CABLING. WHEN ENCOUNTERING
FAAP
2D AN OBSTACLE, PASS CABLING ABOVE THE OBSTACLE AND CONTINUE WITH J-HOOKS.
+44"
C
6 7 8 9 10 11 12 RC 1L2-31 C. WHERE OUTLETS ARE MOUNTED BELOW COUNTER IN KNEE-SPACE, PROVIDE MOUNTING
BRACKETS TO CENTER OUTLETS WITHIN KNEE-SPACE. SEE DETAIL ON SHEET E6.2.
1L2- 27,29 RC D. VERIFY MOUNTING HEIGHTS OF WALL MOUNTED TV DEVICES WITH TV PROVIDER
BEFORE ROUGH-IN.
2D
1L2-31 E. VERIFY MOUNTING HEIGHTS OF WALL MOUNTED TV DEVICES WITH TV PROVIDER BEFORE ROUGH-IN.
DRILL PRESS 23
2.8A, 240V, 3P 3#8,1#10G, 3/4"C. WELDER WORKSPACE
1L2 126 F. VERIFY LOCATION OF WIRELESS ACCESS POINTS WITH OWNER BEFORE ROUGH-IN.
9
P 14
GARAGE DOOR HOIST
1H1
SPD
1L1-9 1L1-11 1L1-11 1L1-11
MDP
T1
X1L1 GFI 1L1-7 GFI 1L1-9 GFI 1L1-9 GFI GFI GFI GFI 1HP, 480V,3PH
+44"
ATS1
1H1- 14,16,18 1H2
1L1 1L2-29
9
2D
1H1- 2,4,6
CB
CB FP
X1L2
1L1-7 VIA TRANS T1
1H1- 35,37,39
3#8,1#10G, 3/4"C.
17
CORD REEL
30A/3 NFDS KEYNOTES
GFI
1L1-23 FACP1 DOOR LIFT
J
J 1 PROVIDE A 30A, 250V, 1P, 4 WIRE. NEMA TYPE 14-30R. RECEPTACLE. VERIFY LOCATION WITH
CB
18 CB 1L2 1L1-19 +44" 1D +44" 1D +44"
2D
ELECTRICAL ARCHITECT.
ROOM 2 PROVIDE CONCEALED FEEDS TO RACEWAYS.
1L1-21 LCP1 156 1L2-27 1L2-27 1L2-27 1L2-29 1L2-29
3 PROVIDE A 14.25" x 14.25" IN-WALL BOX, CHIEF PAC 526 OR APPROVED EQUAL, TO HOUSE A/V
1L1-7
N EQUIUPMENT BEHIND DISPLAY. MOUNT RECEPTACLE AT THE BOTTOM OF THE BOX, (FLUSH
J
WITHIN THE BOX). A/V BOX SHALL BE WHITE WITH FLANGE AND COVER. REFER TO A/V RACEWAY
3
WORKSPACE 126 POWER AND DATA PLAN 4
DIAGRAMS ON E6.4 FOR ADDITIONAL WORK.
PROVIDE WIREMOLD V3000 SURFACE RACEWAY WITH 20A, 125V, DUPLEX RECEPTACLES
SCALE: 1/4" = 1'-0" MOUNTED 24 INCHES ON CENTER.
5 MOUNT SURFACE RACEWAY VERTICAL ABOVE GEAR RACKS PROVIDE STRUT SUPPORT AS
J
GFI
WP
GFI
1L1-6 1L1- 13,15,17 1L1-4
AP PROVIDER BEFORE ROUGH-IN. PROVIDE 20A, 250V, NEMA 6-20R RECEPTACLE.
1L1-5 7 HAND DRYER, 1000W, 120V.
GFI
WP
J
1L1-3 8 PROVIDE (2) 4 INCH CONDUIT SLEEVES THROUGH WALL FOR COMMUNICATION CABLING. PROVIDE
14 INSULATED BUSHING ON ENDS OF SLEEVES.
GFI
RC 17 17
GARAGE DOOR HOIST 9 PROVIDE A 3000VA DRY-TYPE TRANSFORMER, 480V,3PH PRIMARY TO 240V, 3PH DELTA
J
CORD REEL
J
CORD REEL
DOOR LIFT
1HP, 480V,3PH 6 7 8 9 10 11 12 13 14 SECONDARY. PROVIDE A 30A/3 FUSIBLE SECONDARY DISCONNECT SWITCH AND FUSE AT 9A/2.
MOUNT THE TRANSFORMER 'T1' AND THE SECONDARY DISCONNECT SWITCH IN THE ELECTRICAL
J
1L1-17 1L1-17 ROOM 156. PROVIDE A NEMA 15-20R RECEPTACLE AND MATCHING CORD SET FOR THE DRILL
30A/3 NFDS
PRESS.
BAY #7 10 PROVIDE (4) 4 INCH CONDUITS FOR COMMUNICATION CABLING FROM ACCESIBLE CEILING CAVITY
TO IT ROOM 002 IN BASEMENT BELOW. BUSH ENDS OF CONDUITS. CONCEAL WITHIN WALL.
COORDINATE LOCATION WITH STRUCTURE BELOW.
J
DOOR LIFT
14 11 STARTER FOR EF-1 ON THE ROOF. RECESS MOUINT. PROVIDE LABEL ON FACEPLATE.
GARAGE DOOR HOIST 12 STARTER FOR EF-2 ON THE ROOF. RECESS MOUINT. PROVIDE LABEL ON FACEPLATE.
1HP, 480V,3PH J-HOOK SYSTEM 13 STARTERS FOR EF-3, EF-10, AND EF-11 ON THE ROOF. RECESS MOUNT. PROVIDE LABEL ON
GFI
WP
AT CEILING FACEPLATE.
30A/3 NFDS
J
GARAGE
1L1-6 1L5 1L5-15 1L5-15 14 COORDINATE ELECTRICAL REQUIREMENTS WITH GARAGE DOOR PROVIDER. PROVIDE ALL
'B' GFI 1L5-15
J
GFI GFI REQUIRED WIRING AND RACEWAYS FOR POWER, SAFETY DEVICES, AND CONTROL.
146B
1L1-3
1H1- 26,28,30
N CORD REEL CORD REEL
15 REMOTE CONTROL STATION FOR ALL GARAGE BAY DOOR OPERATORS. WIRE ACCORDING TO
GARAGE DOOR MANUFACTURER'S SPECIFICATIONS. PROVIDE ALL REQUIRED WIRING AND
GFI
GFI
J BAY #4 RACEWAYS.
J J
1L5-31 1L5-31 16 PROVIDE SURFACE METAL RACEWAY FOR RADIO CHARGING EQUIPMENT. PROVIDE (2) LENGTHS
J
17 17 1L1-5 SEE E3.2 FOR OF RACEWAY AND MOUNT ONE LENGTH ABOVE EACH OF THE TWO SHELVES. REFER TO
CORD REEL CORD REEL CONTINUATION ARCHITECTURAL ELEVATIONS. PROVIDE CONCEALED POWER FEEDS RECESSED IN THE WALL.
RACEWAY SHALL BE V3000 OR APPROVED EQUAL WITH DUPLEX RECEPTACLES MOUNTED ON 24
J J
INCH CENTERS.
J
1L1-15 1L1-15
BAY #6 17 CORD REEL SHALL BE 20A, 125V, WITH A #12 SJO POWER CORD AND ADJUSTABLE RUBBER
J
DOOR LIFT DOOR LIFT
STOPS, HUBBLE 'IN REACH' INDUSTRIAL CORD REEL HBLI45123 WITH WHITE HOUSING.
14 14 COORDINATE PLUG END WITH OWNER'S TRUCK CONNECTIONS. PROVIDE ALL MOUNTING
GARAGE DOOR HOIST 1H1- 8,10,12 GARAGE DOOR HOIST HARDWARE AND STRUT SUPPORTS, AND CONNECT TO STRUCTURE ABOVE. COORDINATE
1H1- 20,22,24 1L5- 29,31
DOOR LIFT DOOR LIFT 1HP, 480V,3PH 1HP, 480V,3PH LOCATION WITH OWNER BEFORE ROUGH-IN.
J
14 18 PROVIDE (2) DATA CABLES FOR FIRE ALARM CONTROL PANEL COMMUNICATOR.
J
GARAGE DOOR HOIST 19 INTERCONNECT TO RANGE / HOOD SUPPRESSION SYSTEM. A SHUNT TRIP BREAKER SERVING
GFI
1HP, 480V,3PH 1L5-17 RC DEVICE SHALL TRIP UPON ACTIVATION OF HOOD SUPPRESSOR SYSTEM.
30A/3 NFDS 30A/3 NFDS
20 PROVIDE (1) 1-1/4" CONDUIT FOR DATA CABLING FROM FLOOR BOX TO CEILING CAVITY ABOVE.
GFI
30A/3 NFDS 14 AP 1L5-23
J
J
RC GARAGE DOOR HOIST 14 21 PROVIDE (1) 1-1/4" CONDUIT FOR A/V CABLING FROM FLOOR BOX TO A/V BOX BEHIND WALL TV IN
GFI
1HP, 480V,3PH 17
1HP, 480V,3PH 17 THE ROOM. ROUTE UP WITHIN WALL
GARAGE DOOR HOIST
1L1-5 DOOR LIFT CORD REEL CORD REEL 1HP, 480V,3PH 22 ROUTE THROUGH DUCT SMOKE DETECTOR AND RELAY. DAMPER SHALL CLOSE UPON
1L1-3
30A/3 NFDS ACTIVATION OF SMOKE DETECTOR. PROVIDE ALL REQUIRED RELAYS, WIRING AND RACEWAYS.
GFI
J J
17 1L5-29 1L5-29 23 VERIFY ELECTRICAL REQUIREMENTS OF WELDER WITH OWNER BEFORE ROUGH-IN. PROVIDE ALL
17
J
DOOR LIFT REQUIRED WIRING, RACEWAYS, AND EQUIPMENT TO CONNECT TO OWNER'S WELDER.
CORD REEL AP CORD REEL BAY #3
24 PROVIDE (1) 3 INCH CONDUIT BELOW GRADE FROM EQUIPMENT ROOM TO BASEMENT FOR
J J PASSAGE OF COMMUNICATION CABLING.
1L1-13 1L1-13
J
J-HOOK SYSTEM 25 PROVIDE POWER AND DATA FOR SECURITY CAMERA VIEWING MONITOR. VERIFY EXACT
AT CEILING LOCATION AND REQUIREMENTS WITH ARCHITECT AND OWNER BEFORE ROUGH-IN.
J
BAY #5
GARAGE
DOOR LIFT DOOR LIFT 'A'
GFI
J
14 146A
SEE E3.2 FOR 14
J
GARAGE DOOR HOIST
CONTINUATION VEHICAL EXHAUST GARAGE DOOR HOIST 1L5-23
1HP, 480V,3PH
30A/3 NFDS SCBA
PANEL 1HP, 480V,3PH L
1L5-17
J
J
1L1-1
GFI
+44" 30A/3 NFDS 17 17
1L5-5
CORD REEL CORD REEL
1L5-7
2D 2D J J
GFI 1L5-1 1L5-3 4 2 1L5-9 1L5-9 1L5-11 1L5-11 1L5-27 1L5-27
J
EQUIPMENT/ BAY #2
YARD
EQUIP/ SCBA 1L5-3 HAZMAT
PARTS
154 MAINTENANCE 1L5-13
M
GFI
2D
STORAGE STORAGE 1L5-5 155 DOOR LIFT
151 1L5-1 152
J
1L5-7 24 14 14
GFI 1L5-9 1L5-9 1L5-13 1L1-4 GARAGE DOOR HOIST 1L5- 25,27 GARAGE DOOR HOIST
1L5-1 MDP- 7 RC 1HP, 480V,3PH
1HP, 480V,3PH 30A/3 NFDS
GFI
WP
GFI
WP
RC RC
1L5-15
J
1L1-6 1L5-15 1L5-15 1L1-4
1L5
RC
GFI
GFI GFI 1L5- 9,11,13 GFI 1L5-17 30A/3 NFDS
GFI
WP
1L5- 5,7
GFI
WP
1L5- 1,3
GFI
1L5-23
1L1-6 AP
17
N
J
17
CORD REEL CORD REEL
2
FIRST FLOOR POWER AND DATA PLAN (CONT.) J
1L5-25
J
1L5-25
SCALE: 1/8" = 1'-0"
BAY #1
J
DOOR LIFT
DOOR LIFT
J
14 14
GARAGE DOOR HOIST 30A/3 NFDS GARAGE DOOR HOIST
1HP, 480V,3PH 30A/3 NFDS 1HP, 480V,3PH
SEE E3.2 FOR
CONTINUATION
J
GFI GFI
1L5-21
1L5-19
K
ALL REPORTS, PLANS, SPECIFICATIONS AND COMPUTER FILES
RELATING TO THIS PROJECT ARE THE PROPERTY OF MANDERS
MERIGHI PORTADIN FARRELL. MMPF RETAINS ALL COMMON LAW,
STAIR STATUTE AND OTHER RESERVED RIGHTS INCLUDING THE
150
1 2 3 4 5 1L5-19
GFI 1L5-21 GFI WASHER
COPYRIGHT THERETO. REPRODUCTION OF THE MATERIAL HEREIN
OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF MMPF
VIOLATES THE COPYRIGHT LAWS OF THE UNITED STATES AND WILL
1L2- 13,15,17
J BE SUBJECT TO LEGAL PROSECUTION.
STAIR 19 +44" 1L2-18
WP 124 GFI
GFI
GAS 1L2-13
GFI
1L4-19 SOLENOID
RC 1L2-14 H
GFI
VALVE 1L2-17 1L2-15 BUNK c 2018, MANDERS MERIGHI PORTADIN FARRELL ARCHITECTS, LLC
1L2- 43 1L2-4 141
GFI
WP
1L2-7 1L2-28
22 1L2- 51 RC
GFI
WP
1L3-19 4 5
WOMEN'S MEN'S 2D 1L3-17 GEAR
1L4-8 TOILET TOILET 1L3-18 STOR. DECON 1L2-16
1L4-6 1L4-8 1L3-7 FSD TOILET
G
2D
1L4-6 1L4-10 1L4-10 1L3-3 1L3-7 ROOM ROOM 148 BUNK
EVIDENCE FILE 1L3-1 FIRE ALARM ROOM ROOM
115 116 RC 140
+44"
2D
BOOSTER RC
CHIEF
2D
1L3-19 1L2- 39
25 1L3-7 119 PANEL 1L2-11 GFI
GFI
FIRE 1L3-3
2D
FIRE 1L2-13
+44"
GFI
GFI
WP
MARSHAL 1L3-17
J
INVESTIGATOR 1L4-12 1L3-17 13
107 CHIEF 1L2-41
GFI
ENFORCEMENT 109
HD
GFI
CLOSET
WP
1L3-11 1L3-13 1L3-15 JANITOR 1L2-16
GFI
WP
1L4-10
J
DIRECTOR 1L2-4
J
IM
1L3-1 C 7 1L3 1L3-17 1L3-19 GFI J AP
RC RC 1L3-3 2D VM VM VM 1L2-13 1L2-15 COAT AND BOOT
J
Manders Merighi Portadin Farrell Architects, LLC
RC
RC RC
1L4-15 1L3-5
RC RC
CORRIDOR
RC RC RC
1L2-11 RC 1L2- 7,9,11
RC
DRYER
120V,1P BUNK 1L2-28
F 1138 East Chestnut Avenue Vineland, New Jersey 08360
1L4-15 J J J J J J
2D
1L4-3 1L4- 15 AP 112 AP TOILET 139 p. 856 696 9155 l f. 856 696 9080 www.mmpfa.com
CORRIDOR AP RC 1L4- 6,8,10 1L4- 10 1L3-20 AP 8 1L3- 18,20,22 1L2-7 RC
8 1L3- 11,13,15 1L3- 7,9 RC ROOM 1L2- 26,28
1L4- 3,11 102 1L3- 1,3,5 1L3-18 8 1L3- 17,19 145
1L4-15
+44"
1L2-7 RC
J
1L3-18 J David G. Manders AIA AI-07220
GFI
J
1L4-3 J J J J J J J J J J J J J J J J J J J J J
FIRE RC AP Lawrence J. Merighi AIA AI-07473
EWC
+44"
1L4-13 1L3-12 E3.1 BUNK
GFI
126 1L2-26
J
1L3-8 RC 1H2
J
1L4-3 ROOM LOBBY ROOM 1L2-12
101 1L2-4
2D
RC 144
J
1L4- 16 1L3-20 100 3 1L2-3
3
+44" +44"
1L4-4 1L4-14
GFI
WP
GFI GFI
J
1L4-4 1L4-13 120 121 123 1L2-21
1L4-16 1L2-5 BUNK
2D
2D WASHING
2D
2D
2D
RC
J
CORRIDOR
+44"
GFI
2D
+44"
C
F1
AP
GFI
J
RC ROOM DRYER 1L2- 23,25
+44"
J
+44"
GFI
1L4- 5,7,9 1L3-2 LAUNDRY 1L2- 2,4
J
2D ROOM
1L4-7
GFI
+44"
1L4-1 P 1L3-14 1L2-41 134 135 RC
WP 1L2-26
F1
1L4-9
2D
+44"
REF
GFI BUNK
GFI
6 AP 113
J
RC RC
F1
1L4-2
1L4-9 BREAK
1L3-14
1L3-14 EWC 1L2-53
1L4-1 RC W VINELAND FIRE DEPT.
2D
J J J J J J J
GFI
+44"
GFI
WP
1L2-2 1L2-2
1L4-19
1L3-34
1L2-2 AP
C HEADQUARTERS
F1
1L3-6
A/V CORRIDOR
1L3-33 127
+44"
1L3-16
RC
1L3-16 Drawing
OFFICE
F1
1L1- 28 13
1
KEYNOTES
EF-9 1 CONNECT TO UNIT MOUNTED DISCONNECT SWITCH.
2 MOUNT RECEPTACLE ABOVE MICROWAVE SHELF. COORDINATE
LOCATION WITH CABINET PROVIDER BEFORE ROUGH-IN. PROVIDE
20A, 250V, NEMA 6-20R RECEPTACLE.
K 3 PROVIDE A 50A, 125/250V, 1P, NEMA 14-50R RECEPTACLE. VERIFY
LOCATION WITH ARCHITECT. CONTRACTOR SHALL PROVIDE A UL
E 1
-1 0
5
4
B
9
-
E
2
5
3
2L1-9 LISTED POWER CORD, (MIN. 3 FEET TO MAX 6 FEET IN LENGTH.
QUIET 6 CLOSET
2L1-9 23 6 204A 4 PROVIDE (4) 4 INCH CONDUITS FOR COMMUNICATION CABLING FROM
ROOM VIEWING
206 2L1- 25 ACCESIBLE CEILING CAVITY TO IT ROOM 002 IN BASEMENT BELOW.
1
N
B
9
-
E
2
5
3
MEZZANINE STAIR
E 1
-1 0
5
4
2D
AP 207 150 BUSH ENDS OF CONDUITS. CONCEAL WITHIN WALL. COORDINATE
EF-8 FSD 2L1-7 LOCATION WITH STRUCTURE BELOW.
2L1-9 2L1-7
J J 2L1-7 5 PROVIDE A 14.25" x 14.25" IN-WALL BOX, CHIEF PAC 526 OR
1L1- 18 APPROVED EQUAL, TO HOUSE A/V EQUIUPMENT BEHIND DISPLAY.
WP
GFI TV 2L1-3
B 9
E -5
2 3
5 B 9
E -5
2 3
5 B 9
E -5
2 3
5
J
B 9
E -5
2 2
5
E -
1 0
1 4
5 E -
1 0
1 4
5
THE BOX). A/V BOX SHALL BE WHITE WITH FLANGE AND COVER.
+86" 1D
E 1
-1 0
5
4
B
9
-
E
2
5
3
12 4 REFER TO A/V RACEWAY DIAGRAMS ON E6.4 FOR ADDITIONAL WORK.
2L1-3
CORRIDOR 6 PROVIDE (2) 4 INCH CONDUIT SLEEVES THROUGH WALL FOR
204 WALL TV COMMUNICATION CABLING. PROVIDE INSULATED BUSHING ON ENDS
7
H
B
9
-
E
5
2
5
3
E 1
-1 0
5
4
OF SLEEVES.
J
STARTERS 2L1-1
E3.2
REF
2L1-19 FOR EF-12
E 1 4
5
-1 0
7 CONDUIT SLEEVES FOR COMMUNICATION CABLING TO 2ND FLOOR.
3
5
2
1
-
9
E
B
AND MAU-1 COORDINATE WITH OTHER UTILITIES IN CHASE.
PANTRY 2L1-11
ON ROOF 2L1- 21,23 8 TELECOMMUNICATIONS GROUND BAR. PROVIDE SIZE INDICATED.
EF-7 202C
REF
2L1-17 BAR SHALL HAVE PRE-DRILLED HOLES FOR CONNECTIONS AND
J
1
2D
G
3
5
2
-
9
E
B
60A/3 FDS
5
2
-
9
E
B
13 INSULATED STAND-OFFS.
VEF-2 FUSE @40A/2 2L1-3
1H1- 11,13,15 CU-1 PANTRY TOILET RC 9 VERIFY LOCATION OF TREADMILLS WITH ARCHITECT BEFORE
10HP,480V,3PH NEMA 3R 5
REF
2L1-15 ROOM ROUGH-IN.
TV
30A,208V,1PH PANTRY CORRIDOR 2L1- 8 2L1-7 2L1-3
60A/3 FDS 202B 202 2L1 205 WALL TV
10 PROVIDE CABLE RUNWAY AROUND PERIMETER OF ROOM AND
E -2
9
B 3
5 5
1 4
0 5
-
E 1
3#8,1#10G, 3/4"C.