COOP 2021 15 D 3 FF HR 02 - Rev03
COOP 2021 15 D 3 FF HR 02 - Rev03
COOP 2021 15 D 3 FF HR 02 - Rev03
: COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 1 of 18
Date : 13/03/2022
TABLE OF CONTENTS
1. INTRODUCTION
2. DEFINITION
3. REFERENCES
4. UNITS
5. CALCULATION BASIS
8. ATTACHMENTS
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 3 of 18
Date : 13/03/2022
1. INTRODUCTION
This calculation report covers the foam solution demand estimating for firefighting system to protect
equipment and facilities installed in CO-OPERATION Petroleum Company Suez Tank Farm, Arab
Republic of Egypt.
2. DEFINITIONS
3. REFERENCES
4. UNITS
Unless otherwise specified, metric, Celsius, kilogram and kg/cm2g units will be applied as the
measurement system However, nominal sizes of piping components will be in accordance with inch
system.
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 4 of 18
Date : 13/03/2022
5. CALULATION BASIS
Foam solution velocity in pipe including deluge valve manifold pipe taken from firewater main shall
not exceed 6 m/sec although 3.5 m/sec (block case 4 m/sec) for firewater main network pipe.
Foam Demand
The largest foam demand of one of the fire risk areas will be the maximum foam demand based on a single
major fire breaking out in one fire risk area in any one time.
The used foam shall be FP “Fluoroprotein” of 6% concentration” for storage tanks foam chambers only, all
remaining facilities in process areas shall use AFFF “Aqueous Film Forming Foam” of 3% concentration
including fire monitors.
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 5 of 18
Date : 13/03/2022
The following table in Attachment#1 “Fire Scenarios and Application Rates”, summarizes different fire
scenarios for fire that could develop in equipment/separate areas and the firefighting equipment used to protect
this equipment/area showing the application flow rates that will be used for the burning equipment as well as
any other adjacent equipment in fire radiation section as detailed in COOP-2021-15-D-3-FF-FP-01 Fire
Fighting Systems Philosophy
Calculation Result
Maximum Foam Demand for 3% AFFF foam type is Scenario # 1 “Storage Tank S-10 same as K-1 & K2” is
maximum foam demand case of maximum capacity of 20 m3 of concentrated foam required for 3 hrs of
operation to cover tank S-10 dike area with 2 fire monitors at 6.5 lpm/m2 application rate.
Maximum Foam Demand for 6% FP foam type is Scenario # 2 “Storage Tank S-10 same as K-1 & K2” is
maximum foam demand case of maximum capacity of 6.5 m3 of concentrated foam required for 60 min to
operate the foam chambers of the burning tank.
This manual calculation result and its required fire main size will be verified by Hydraulic Calculation Report
using (“PIPENET” programmed by SUNRISE SYSTEM LTD.) for flow analysis in pipe network in Hydraulic
Calculation Report.
8. ATTACHMENTS
Attachment # 1 “Foam System Scenarios and Application Rates”
Attachment #2 “Foam System Manual Calculation & Foam Solution Lines Sizing”
Attachment #3 “Spray Nozzles Catalogues”
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 6 of 18
Date : 13/03/2022
Attachment # 1
“Foam System Fire Scenarios and Application Rates”
Fire Water Demands Scenarios
Fire Water Demand Total Foam Total Foam
FP Concentrated AFFF Concentrated Foam
Equipment on Fire Fixed Foam System Solution Solution
Fire Scenarios Firefighting Equipment Water Spray System Fire Monitor (*) Fire Hydrant Foam Demand Demand as Per NFPA 11 Remarks
Tag Activation (Spray / Champer) (6%FP) (3%AFFF)
Activation Device
Method
m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr
(*) 2 X Foam Monitors will be used for S-10 dike spillage control (application
1 S-10 Foam Champer (**) FDV-0009 & FDV-0014 Automatic N/A 112 228 57 112 228 6.72 20.52
rate 666 m3/hr/m2) for approximate 3 hrs with AFFF Foam
(*) 1 X Foam Monitors will be used for K-1 (or) K2 dikes spillage control
2 K-1 (OR) K-2 Foam Champer (**) FDV-0003 & FDV-0015 Automatic N/A 112 114 57 112 114 6.72 6.84
(Application rate I 222 m3/hr/m2) for approximate 2 hrs with AFFF Foam
FDV-0012 Automatic
3 LOADING ARMS Water/Foam Spray System N/A 514.08 114 57 N/A 628 N/A 18.8424
FDV-0013 Automatic
P-1A
P-1B
P-2
P-3A
P-3B
P-3C FDV-0010 Automatic
P-3D
P-3E
P-5
P-6
4 P-7 Water/Foam Spray System N/A 642.60 114 57 N/A 680.60 N/A 20.418
P-8
P-9
P-9A
P-9B
P-9C
FDV-0011 Automatic
P-10A
P-10B
P-10C
P-11
P-12
5 15ص Foam Champer (**) FDV-00025 Automatic N/A 18 114 57 18 114 0.54 6.84
6 16ص Foam Champer (**) FDV-00028 Automatic N/A 50 114 57 50 114 1.5 6.84
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 8 of 18
Date : 13/03/2022
Attachment #2
“Foam System Manual Calculation & Foam Solution Lines Sizing”
Foam Solution Manual Hydraulic Calculatuion Sheet
Equipment Data
Spray Nozzles Data Ring Pipe Data Foam Data
Minimum Minimum
Total Flow rate
Minimum Water Water Concentrated Foam
required per
Height Surface Application Rate Demand Demand Volume
Zone No. Deluge Valve No. Diameter Length Width Minimum No. of Total Total Total Maximum Actual Pipe Foam Equipment Foam Type
(2) Area (3) Required Required No. of Rings / Nozzle Flow Horz. Distance overlap % Actual Velocity Concentrated
Equipment Type Equipment Tag Equipment Description Spray Nozzle Model Spray Angle K-Factor (4) Discharge Nozzles Per Number of Nozzles Nozzles Ring Circumfrance Velocity Diameter Application
Branches (6,9) Rate (4) Between Nozzles (8) inside Pipe Foam Volume
Pressure (5) Ring (7) Nozzles Flow rate Flow rate Inside Pipe Used Duration (10)
(Meters) (Meters) (Meters) (Meters) (m2) (lpm) (lpm) (m3/h) Type (Degrees) (lpm/barg) (barg) (EA) (EA) (lpm) (EA) (lpm) (m3/h) (m) (m) (%) (m/s) (inches) (m/s) (min) (m3) (m3/h) (m3)
1"
Laoding Arms Shed LA-3D Gas Oil Loading Arm N/A 65 12 N/A 780 6.5 5070 304.2 Pendent / Upright 43.2 2.1 22 4 63 88 5544 332.64 N/A 3 66.7 4 8 2.9 30 4.9896 332.64 4.9896
FOAM/WATER SPRAY NOZZLE
Water/Foam Spray
3% AFFF
System LA-3E Calibration Unit Loading Arm
1"
Common Metering Skids All All loading Arms N/A 6 1 1 12 6.5 78 56.16 Pendent / Upright 43.2 2.1 2 2 63 4 252 181.44 N/A 3 66.7 4 2 2.1 30 2.7216 181.44 2.7216
FOAM/WATER SPRAY NOZZLE
FDV-0001 FOAM CHAMPER TFC-0001 S-1 Bunker Gas Oil Storage Tank 20 N/A N/A 7.5 314 4.1 1287.4 77.244 N/A N/A Vendor to Confirm 3.5 N/A N/A 1287.4 1 1287.4 78 N/A N/A N/A 4 4 2.7 30 2.34 78 2.34
FDV-0002 FOAM CHAMPER TFC-0002 S-2 Bunker Gas Oil Storage Tank 20 N/A N/A 7.5 314 4.1 1287.4 77.244 N/A N/A Vendor to Confirm 3.5 N/A N/A 1287.4 1 1287.4 78 N/A N/A N/A 4 4 2.7 30 2.34 78 2.34
FDV-0005 FOAM CHAMPER TFC-0003 S-3 Gas Oil Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-0006 FOAM CHAMPER TFC-0004 S-4 Gas Oil Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-0007 FOAM CHAMPER TFC-0005 S-5 Summer Diesel Storage TanK 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-0008 FOAM CHAMPER TFC-0008 S-11 Gasoline 95 Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
Water/Foam Champers
6% FP
(12)
FDV-0009 FOAM CHAMPER TFC-0009 S-10 Gasoline 92 Storage Tank 24 N/A N/A 15 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
3.36
FDV-0014 FOAM CHAMPER TFC-0009 S-10 Gasoline 92 Storage Tank 24 N/A N/A 15 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-0003 FOAM CHAMPER TFC-0006 K-1 Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
3.36
FDV-0015 FOAM CHAMPER TFC-0006A K-1 Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-0004 FOAM CHAMPER TFC-0007 K-2 Bunker Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
3.36
FDV-0016 FOAM CHAMPER TFC-0007A K-2 Bunker Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
Foam Solution Manual Hydraulic Calculatuion Sheet
Equipment Data
Spray Nozzles Data Ring Pipe Data Foam Data
Minimum
Total Flow rate
Minimum Application Water Minimum Water Concentrated
required per
Height Rate Demand Demand Required Horz. Foam Volume
Zone No. Deluge Valve No. Diameter Length Width Surface Area (3) Minimum Maximum Equipment Foam Type
(2) Required No. of Rings / No. of Nozzles Per Nozzle Flow Rate Total Number Total Nozzles Flow Total Nozzles Flow Distance Actual Pipe Actual Velocity Foam Application Concentrated
Equipment Type Equipment Tag Equipment Description Spray Nozzle Model Spray Angle K-Factor (4) Discharge Ring Circumfrance overlap % (8) Velocity Inside
Branches (6,9) Ring (7) (4) of Nozzles rate rate Between Diameter Used inside Pipe Duration (10) Foam Volume
Pressure (5) Pipe
Nozzles
(Meters) (Meters) (Meters) (Meters) (m2) (lpm) (lpm) (m3/h) (Degrees) (lpm/barg) (barg) (EA) (EA) (lpm) (EA) (lpm) (m3/h) (m) (m) (%) (m/s) (inches) (m/s) (min) (m3) (m3/h) (m3)
FDV-0017 FOAM CHAMPER TFC-0010 1ص Oil Storage Tank Roof 6 N/A N/A 7.5 28.26 4.1 115.866 6.95196 N/A N/A Vendor to Confirm 3.5 N/A N/A 115.866 1 115.866 7 N/A N/A N/A 4 2 1.5 30 0.21 7 0.21
FDV-00018 FOAM CHAMPER TFC-0011 2ص Oil Storage Tank Roof 6 N/A N/A 7.5 28.26 4.1 115.866 6.95196 N/A N/A Vendor to Confirm 3.5 N/A N/A 115.866 1 115.866 7 N/A N/A N/A 4 2 1.5 30 0.21 7 0.21
FDV-00019 FOAM CHAMPER TFC-0012 6ص Oil Storage Tank Roof 9.5 N/A N/A 8.85 70.84625 4.1 290.469625 17.4281775 N/A N/A Vendor to Confirm 3.5 N/A N/A 290.469625 1 290.469625 18 N/A N/A N/A 4 3 1.5 30 0.54 18 0.54
FDV-00020 FOAM CHAMPER TFC-0013 7ص Oil Storage Tank Roof 6 N/A N/A 7.5 28.26 4.1 115.866 6.95196 N/A N/A Vendor to Confirm 3.5 N/A N/A 115.866 1 115.866 7 N/A N/A N/A 4 2 1.5 30 0.21 7 0.21
FDV-00021 FOAM CHAMPER TFC-0014 8ص Oil Storage Tank Roof 6 N/A N/A 7.5 28.26 4.1 115.866 6.95196 N/A N/A Vendor to Confirm 3.5 N/A N/A 115.866 1 115.866 7 N/A N/A N/A 4 2 1.5 30 0.21 7 0.21
Oil Tanks
Water/Foam Champers FDV-00022 FOAM CHAMPER TFC-0015 12ص Oil Storage Tank Roof 9.5 N/A N/A 7.5 70.84625 4.1 290.469625 17.4281775 N/A N/A Vendor to Confirm 3.5 N/A N/A 290.469625 1 290.469625 18 N/A N/A N/A 4 3 1.5 30 0.54 18 0.54 6% FP
(12)
FDV-00023 FOAM CHAMPER TFC-0016 13ص Oil Storage Tank Roof 9.5 N/A N/A 7.5 70.84625 4.1 290.469625 17.4281775 N/A N/A Vendor to Confirm 3.5 N/A N/A 290.469625 1 290.469625 18 N/A N/A N/A 4 3 1.5 30 0.54 18 0.54
FDV-00024 FOAM CHAMPER TFC-0017 14ص Oil Storage Tank Roof 9.5 N/A N/A 7.5 70.84625 4.1 290.469625 17.4281775 N/A N/A Vendor to Confirm 3.5 N/A N/A 290.469625 1 290.469625 18 N/A N/A N/A 4 3 1.5 30 0.54 18 0.54
FDV-00025 FOAM CHAMPER TFC-0018 15ص Oil Storage Tank Roof 9.5 N/A N/A 10 70.84625 4.1 290.469625 17.4281775 N/A N/A Vendor to Confirm 3.5 N/A N/A 290.469625 1 290.469625 18 N/A N/A N/A 4 3 1.5 30 0.54 18 0.54
FDV-00026 FOAM CHAMPER TFC-0019 16ص Oil Storage Tank Roof 16 N/A N/A 7.5 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-00027 FOAM CHAMPER TFC-0020 17ص Oil Storage Tank Roof 16 N/A N/A 7.5 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
1"
Oil Tanks Mixer Shed FDV-00028 Mixer Shed All N/A N/A 28 7 N/A 196 20.4 3998.4 239.904 Pendent / Upright 43.2 2.1 16 4 63 64 4032 241.92 N/A 1.8 111.2 4 2 2.1 30 3.6288 241.92 3.6288 3% AFFF
FOAM/WATER SPRAY NOZZLE
1"
Oil Tanks Loading Arms FDV-00029 Loading Arm All N/A N/A 3.5 1 N/A 3.5 4.1 14.35 0.861 Pendent / Upright 43.2 2.1 2 1 63 2 126 7.56 N/A 1.8 90 4 2 2.1 30 0.1134 7.56 0.1134 3% AFFF
FOAM/WATER SPRAY NOZZLE
Foam Solution Manual Hydraulic Calculatuion Sheet
Equipment Data
Spray Nozzles Data Ring Pipe Data Foam Data
Minimum Minimum
Total Flow rate
Minimum Water Water Concentrated Foam
required per
Height Surface Application Rate Demand Demand Volume
Zone No. Deluge Valve No. Diameter Length Width Minimum No. of Total Total Total Maximum Actual Pipe Foam Equipment Foam Type
(2) Area (3) Required Required No. of Rings / Nozzle Flow Horz. Distance overlap % Actual Velocity Concentrated
Equipment Type Equipment Tag Equipment Description Spray Nozzle Model Spray Angle K-Factor (4) Discharge Nozzles Per Number of Nozzles Nozzles Ring Circumfrance Velocity Diameter Application
Branches (6,9) Rate (4) Between Nozzles (8) inside Pipe Foam Volume
Pressure (5) Ring (7) Nozzles Flow rate Flow rate Inside Pipe Used Duration (10)
(Meters) (Meters) (Meters) (Meters) (m2) (lpm) (lpm) (m3/h) Type (Degrees) (lpm/barg) (barg) (EA) (EA) (lpm) (EA) (lpm) (m3/h) (m) (m) (%) (m/s) (inches) (m/s) (min) (m3) (m3/h) (m3)
N/A FM-0001 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0002 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0003 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0004 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0005 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0006 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
FDV-0010
N/A FM-0007 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0008 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0009 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0010 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0011 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
Water/Foam Spray 1"
Pumps Shed N/A 58 9 N/A 522 20.4 10648.8 638.928 Pendent / Upright 43.2 2.1 43 4 63 170 10710 642.6 N/A 1.348837209 148.3 4 2 3 30 9.639 642.6 9.639 3% AFFF
System FOAM/WATER SPRAY NOZZLE
N/A FM-0012 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0013 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FOAM MONITOR (11) FM-0014 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0015 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
Water/Foam Fire
3% AFFF
Monitors
N/A FM-0016 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0017 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0018 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0019 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0020 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0021 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0022 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0023 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0024 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0025 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0026 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0027 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A EFM-0001 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A ELEVATED FOAM MONITOR EFM-0002 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A EFM-0003 General Coverage N/A N/A N/A N/A 463.41463 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
General Notes
1. Due to the shortage of information provided by COOP, some data have been assumed i.e. Working Volume for some Tanks, Tanks Roof Height,….. Etc.
2. Since the shell to shell distance between tanks complies with NFPA 30 Table # 4.3.2.2, The whole tank height was considered
3. Sufeace Area Equation used for Tanks Shell: ΠDH
Surface area Equation used for Tanks Roof: ΠRL where L is the slant height of the cone
4. K-Factor value can be obtained from the equation in NFPA 15 parag. 5.5.1.5
5. Minimum discharge pressure as per NFPA 15 of any protection nozzles at an outdoor hazard is 1.4bar, accordingly 2.1bar was used as an avarage design pressure to ensure that while including pressure
friction losses due to pipes material roughness and fitting, the nozzles pressure will always be maintane above 1.4bar
6. For estimating the required number of spray rings of each tank please refer to NFPA 15 parag. 4.5.2 and API RP 2030 sec. 7.3.13
7. In oreder to calcuate the number of nozzles per ring, please refer to NFPA 15 parag. 4.1.4
8. Nozzles overlaping shall meet the coverage distances mentioned in NFPA 15 parag. 4.1.4, parag. 4.5.2 & API RP 2030 sec. 7.3.13 with recommended overlap precentage 60%
11. Monitor minimum flow rate shall not be less than (250GPM to 500GPM) as per API RP2030 sec. 7.2.1 accordingly for High Expansion system, 500GPM is recommended (refer to Design Basis COOP-2021-
15-D-3-FF-DB-01)
12. Refer to NFPA 11 Annex B table B-1
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 03
Calculation Report Page : 12 of 18
Date : 13/03/2022
Attachment #3
“Spray Nozzles Catalogues”
Foam Top
Pourer Set Mk4
The Angus Fire Top Pourer Set (TPS) Foam Tube Length
Mk4 is designed for use in foam
The standard or minimum length of
systems for the protection of fixed roof
the foam dispersal tube projecting
flammable liquid storage tanks with
into the tank interior is shown in the
Nitrogen inerted blankets or where
below table under “E”. It is designed
tank internal pressures may reach 0.35
for pourers mounted (usually using
bar (5 psi) The Mk4 combines foam
the Angus Fire mounting kit) directly
generation, vapour sealing and foam
on to the tank wall. This positions
pouring in a robust, low-maintenance
the deflector plate at the optimum
design and represents over 35 years of
position inside the tank to spread the
product development and operating
foam evenly around the interior.
experience. Each unit is factory
Other lengths of the foam dispersal
calibrated to perform at a fixed flow
tube can be specified by the customer.
and pressure point and can perform
to the precise pressure and flow Glass Vapour Seal Disc
standards laid down by Underwriters
TPS Mk4 units are fitted with a
Laboratories (UL) and NFPA.
replaceable glass bursting disc suitable
Units without a vapour seal are available for tank internal pressures up to
for total flooding of open roof tanks. 0.34 bar (5psi).
Four basic body sizes cover flow ranges Positive Bursting Disc Mechanism
from 75 l/min (20 US gal/min) to
When the Mk4 TPS is activated, the
3,300 l/min (870 US gal/min) at inlet
liquid foam and water mixture is driven
pressures between 3 bar (45 psi) and
up the pourer inlet pipe under full
10 bar (150 psi).
operating pressure. The liquid pressure
The discharge is enhanced by a causes the air inlet flap valves at the ANSI RF #150 inlet / outlet flange sizes*
deflector plate fitted to the outlet which base of the pourer to close. The liquid, Inlet outlet
disperses the finished foam against the still under full pressure, travels up the TPS 50 2” 4”
tank wall. This ensures a rapid spread tube, past the foam maker and bursts TPS 80 3” 6”
across the surface of the fuel, whilst the heavy duty glass vapour seal disc,
TPS100 4” 8”
lowering the application velocity, allowing access to the tank interior.
TPS150 6” 10”
reducing contamination of the foam by
the fuel and minimising splash. *ISO and DIN flanges also available
Performance Envelope
3000
400
300 1200
FLOW l.p.m.
FLOW l.p.m.
1000 2000
FLOW l.p.m.
2200
FLOW l.p.m.
200 800
100 400
0 0 0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
PRESSURE bar PRESSURE bar PRESSURE bar PRESSURE bar
Foam Top Pourer Set Mk4
Installation Options A hole is cut into the tank side. Then the need for access to the inside of
the Angus mounting kit flange is the tank. The TPS body with its foam
The Angus mounting kit allows the TPS
secured from outside by passing the deflector is then bolted on to the
to be sited without the need for access
stud nuts through the access hole. adapter kit flange in the normal way.
from inside the tank.
They are then tightened on the inside
WARNING: Before any cutting work by reaching through the access hole
is done to the tank wall, which could from outside the tank, removing
cause sparks and hot spots, it must be
ensured that the tank is empty and
purged of any flammable vapour.
Notes:
1. All inlets should be positioned equally around the circumference of the tank, but the
distance between any 2 pourers should not exceed 30m on fixed cone roof tanks.
2. Consideration may have to be given to ensuring the foam application does reach
the centre of large tanks.
Worldwide
www.tyco-fire.com
Contacts
AGITATOR
AGITATOR
7/16" 5-15/16"
(11,1 mm) 3/8" DIA. (150,8 mm)
NOMINAL (9,5 mm)
MAKE-IN
BODY
1"
(25,4 mm)
1/2" ACROSS
NPT WRENCH DEFLECTOR
WRENCHING FLATS 2-1/8" DIA.
AREA (54,0 mm)
UPRIGHT PENDENT
FIGURE 1
MODEL B-1 FOAM-WATER UPRIGHT AND PENDENT SPRINKLERS
NOMINAL DIMENSIONS
DATA KEY
WATER DISCHARGE FOAM DISCHARGE
8 or 10 INCH
RADIUS, METERS RADIUS, FEET ADJUSTABLE
3,0 2,0 1,0 0 2 4 6 8 10 WRENCH
0 0
DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS
0,5
2
CEILING, FEET
APPLY TO
1,0 WRENCH
4 FLATS
1,5 ONLY
6
2,0
8 FIGURE 2
2,5
UPRIGHT WRENCH FLATS
RADIUS, METERS RADIUS, FEET
0
3,0 2,0 1,0 0 2 4 6 8 10
0
Limited
Warranty
DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS
0,5
2
CEILING, FEET
For warranty terms and conditions, visit
1,0 www.tyco-fire.com.
4
1,5
6
Ordering
2,0
Procedure
2,5 8 Contact your local distributor for avail-
PENDENT
ability. When placing an order, indi-
GRAPH A cate the full product name, including
NOMINAL DISCHARGE PATTERNS description and part number (P/N).
(SHOWN FOR REFERENCE ONLY — NOT SUITABLE FOR DESIGN PURPOSES)
Upright Foam-Water Sprinklers
Specify: Model B-1 Upright Foam-
Care and Frequent visual inspections are recom-
mended to be initially performed for
Water Sprinkler, P/N 49-210-1-001