L 5102 - L 5103 Guía de Selección

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

L-JS

L-5102
L-JS1CONTROL
L-5102 - FEATURES
DAMPER

DAMPERS
L-JS
L-5103
L-JS1CONTROL
L-5103 - FEATURES
DAMPER

DAMPERS
L-JS
L-5102 L-5103
CONTROL DAMPER
L-JS1 - FEATURES

The L-5102 and L-5103 offers sturdy, STANDARD CONSTRUCTION


gavanized steel construction with - Blades: 0,048" (18) formed galvanized
heavy frame desing. steel.
- Frame: 0,06" (16) formed galvanized

DAMPERS
Blades are galvanized steel
construction. steel.
- Finish: Mill
Axles positively lock to blades with
- Minimum Size: 12"X12"
screws. noncorrosive bearings assure
- Maximum Size: single section
long life and ease of operation. 48"X48".
- Temperature limits: - 40°F to +
240°F.
NOTE: Maximum section width varies
with static pressure. Consult Laminaire
if application involves pressures in
excess of 2,4" w.g. or ir velocities in

L-5102 L-5103
Damper Maximum system Maximun System Leakage without seals
width preassure Velocity % of max CFM/sq. Ft
flow
48" 2,4" w.g. 1500 FPM 2,67 40
36" 2,7" w.g. 1500 FPM 2,67 40
24" 3,8" w.g. 1500 FPM 3,33 50
12" 4,8" w.g. 1500 FPM 4,33 65

The L-5102 and L-5103 are Conservative ratings are presented


structurally designed for velocities intentionally in an effort to avoid
to 2.000 fpm and above. Turbulence misapplication. Consult Laminaire
may produce objetionable noise in when a damper is to be applied in
some conditions with velocities conditions exceeding recommended
above 1.500 fpm. maximums.
Dampers may tolerate higher
pressures and velocities than those
listed here. conservative ratings are
L-JS
L-5102 L-5103
CONTROL DAMPER
L-JS1 - FEATURES

PRESSURE DROP

DAMPERS
DETERMINING PRESSURE DROP 3. Enter the pressure drop chart at the
determined area factor and proceed up
Use the area factor table and pressure to appropriate conversion velocity (CV)
drop chart to determine pressure drop lines. Then, read across to static pressure
through Laminaire 5102 - 5103 control drop at left side of chart.
dampers.
1. Determine area factor for damper by
entering the Area factor table through
duct width ang height.
2. Find the conversion velocity (CV) by
multiplying the selected size damper´s
area factor by the flow rate in CFM:
L-JS
L-5102 L-5103
CONTROL DAMPER
L-JS1 - FEATURES

PRESSURE DROP CHART

DAMPERS
EXAMPLE:
Find the pressure drop across a 24" Wide
x 24" high for 5102 and 5103 control
damper handling 5500 CFM. From the
area factor table. the area factor is
determined to be 0.364
Area Factor x CFM = CV
Therefore, CV = 5500 CFM x 0,364 =
2000. Using the pressure drop chart,
pressure drop = 0.055 inches w.g