001 Rev 3

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Triconex TM

Documentation Update Notice


Document Title: Planning and Installation Guide for Safety Intelligent Enclosures
Document Number: 9720153-001, Rev 3.0
Release Date: May 2022

The following table identifies significant changes made in the document identified above.

Section Description of Change


Ch1 > SIE Model Configurator • In the SIE Model Code Prefix table, added the sentence “All SIE configurations
are certified for use in the following hazardous locations: Class I Division 2;
ATEX, IECEx, and China Zone2/Zone22.” to the description of TCX.
• In the Solution Selection table, removed the certification information in the
description for all SIE selections.
Ch 1> International Approvals • Moved the ATEX and IECEx certifications to be directly below the FM certification
• Added the China certification information to the list.
China Zone 2 and Zone 22
— Ex nA nC d e IIC T4 Gc
— Ex tD A22 IP66 T80°C
• Added the UKCA Mark certification to the list.
Ch 1> International Approvals • Added the new topic China Compulsory Certification (CCC)
> China Compulsory
Certification (CCC)
Ch 1 > International Approvals • Removed the sentence “The following declaration of conformity with the
> European Union CE Mark > European Union directives for explosive atmospheres, electromagnetic
Declaration of Conformity compatibility, and certain hazardous substances is provided as a convenience.”
from the topic.
• Added the revised European Union Declaration of Conformity
Ch 1 > International Approvals • Added NEW topic Great Britain UKCA Mark
> Great Britain UKCA Mark • Added the UK Declaration of Conformity
Ch 2 > Heat and Humidity • Changed the topic title from “Heat Management” to “Heat and Humidity
Management Management.”
• Changed all instances of “heat management” to “heat and humidity management”
in the introduction paragraph.
• In the Mandatory Requirements section, added the bullet item “Silica gel
(desiccant) packs are to be used inside the SIE in applications where the SIE is
not stored/installed in a humidity-controlled room. Approximately 400 grams of
silica gel are to be used in the SIE and replaced based on the lifecycle guidance
of the silica gel pack manufacturer.”
Appendix A • In the SIE Third-Party Products table, removed the SIE Certifications column.

Global Customer Support (GCS) Center


http://pasupport.schneider-electric.com

Part No. 9730153-001, Rev 3.0


June 20, 2022

Internal
2 of 2

Appendix C • In the SIE Assemblies table, replaced all instances of “ATEX and IECEx Zone
2/Zone 22” with “ATEX, IECEx, and China Zone 2/Zone 22”
Glossary • Added the terms CCC, CCCex, SITIIAS, and UKCA mark
Back page • Changed the address to

70 Mechanic Street
Foxboro, Massachusetts 02035–2040
United States of America

© 2019–2022 Schneider Electric Systems USA, Inc. All rights reserved.

Schneider Electric, EcoStruxure, Triconex, Tricon, Trident, and TriStation are trademarks of Schneider Electric SE, its subsidiaries and affiliates. All other brands may be
trademarks of their respective owners.

Documentation Update Notice June 20, 2022 Part No. 9730153-001, Rev 3.0

Internal