Following your kind request, we thank you for contacting our company and reply with the following offer based on the
information you provided.
Air handling unit WZ-E920
Order reference
Unit reference AC-1 a AC-4
Supply air flow rate 3000 m³/h Model Box MB1
Return air flow rate // m³/h RH operating range 0 - 90 %
Supply air velocity on filter cross-section 1.38 m/s AHU operating temperature -20/+45 °C
Return air velocity on filter cross-section // m/s Altitude 0 masl
Winter outdoor temperature: 0.0 °C Air density 1.204 kg/m³
Absorbed power factor 0.95
Eurovent summer application
Dry bulb temperature - °C Dew temperature - °C
Wet bulb temperature - °C Absorbed power factor -
CONSTRUCTIONAL CHARACTERISTICS
Self-supporting frame with extruded section bars in double-wall aluminium camera for recessed screws.
Thermal cold break bridge section bar thickness 60 mm
Double-wall sheet metal thermal break panels thickness 62 mm:
internal in galvanised steel thickness 0.5 mm, external in pre-painted steel thickness 0.6 mm. Insulation in injected polyurethane
average density 45 kg/m³.
Internal face for floor panels in galvanised steel
All filters installed on unit
Without weather protection (indoor installation only)
With aluminium profile base frame
Carpentry material with galvanised sheet. Slides for container transport
Installation and service manual language: English
Synthetic filter
Pleated synthetic filter efficiency ISO Coarse 55% - ISO 16890 (G4 - EN 779:2012) N°1 490 x 592 x 48 mm + N°1 287 x 592 x 48 mm
Filter pressure drop: clean filter 51 Pa, project pressure drop 76 Pa, dirty filter 101 Pa
Velocity in AHU filter cross section: 1.81 m/s
Total section pressure drop = 76 Pa
With side withdrawal
Cooling coil.
AIR TEMPERATURE AND HUMIDITY DATA FLUID: Water
Air flow standard 3000 m³/h Flow rate 6632 dm³/h
Face velocity 2.63 m/s Fluid speed 1.59 m/s
Inlet temperature 35 °C Inside volume 12.69 dm³
Inlet RH 50 % Inlet temperature 7 °C
Outlet temperature 15.48 °C Outlet temperature 12 °C
Outlet RH 99 %
Capacity 38.56 kW
Wet pressure drop 190 Pa Pressure drop 42.00 kPa
Dry pressure drop 155 Pa
Condensate 25.43 dm³/h
Sensible heat/Total heat 0.53 -
Geometry P40 - Tubes material Copper -
Number of rows 6 - Tube diameter 16.45 mm mm
Fins spacing 2.5 mm Tube thickness 0.4 mm mm
Tubes number 12 - Fins material Aluminium -
Circuits number 6 - Fins tickness 0.12 mm mm
Frame material Galvanized -
Manifolds material Iron -
Coil width 840 mm
Manifold inlet 1 1/2' -
Manifold outlet 1 1/2' -
3S P40 6 rows p.a 2.5 Cu/Al 12T 660A 6c 1 1/2'
Accessories:
Drain pan in galvanised sheet
Drop separator in Aluminium Pa 108
Total section pressure drop = 297 Pa
Inspection section
Inspection section for filters
Ecodesign
Manufacturer Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A.
Unit model WZ-E920
Typology NRVU;UVU
SFPint [W/(m³/s)] 89
Nominal flow rate [m³/s] 0.83
Face velocity [m/s] 1.38
Type of HRS /
Thermal efficiency of heat recovery /
Maximum external leakage rate (-400Pa) [%] 0.39
Maximum external leakage rate (+400Pa) [%] 0.19
Maximum internal leakage rate (+250Pa) [%] /
CAL (R) class at -400 Pa L3 (R)
CAL (R) class at +700 Pa L2 (R)
SUPPLY
Nominal flow rate [m³/s] 0.83
Type of drive for var. speed inverter installed
120
60
1 1/2' 1 1/4'
680
800
900
1 1/2' 1 1/4'
60
100
1"
120
S.1 L 3500
60
1020
S.1 3600 1150 1050 457
900
1 1/2' 1 1/4'
Flow rate Flow rate
Working head Working head
60
MS MS
Motor Motor
Mains Mains
1 1/2' 1 1/4' Supply Fan Exhaust Fan
Notes