Offer N° SebastianGonzalez-2022-000063 Date 28-11-2022

Designed by Sebastián Gonzalez

Customer Hospital Policial


To the kind attention of
Town

Following your kind request, we thank you for contacting our company and reply with the following offer based on the
information you provided.
Air handling unit WZ-E920
Order reference
Unit reference AC-1 a AC-4
Supply air flow rate 3000 m³/h Model Box MB1
Return air flow rate // m³/h RH operating range 0 - 90 %
Supply air velocity on filter cross-section 1.38 m/s AHU operating temperature -20/+45 °C
Return air velocity on filter cross-section // m/s Altitude 0 masl
Winter outdoor temperature: 0.0 °C Air density 1.204 kg/m³
Absorbed power factor 0.95
Eurovent summer application
Dry bulb temperature - °C Dew temperature - °C
Wet bulb temperature - °C Absorbed power factor -

Length 3500 mm Height + base 800 + 100 mm


Depth 1020 mm Approximate weight 457 Kg
Connection side Right Inspection side Right
The dimensions are indicative and will be optimised in the production phase

Mechanical characteristics of structure according EN1886


Mechanical srength Leakage Thermal trasmittance Thermal bridging
D1(M) L1(M) T2 TB2

CONSTRUCTIONAL CHARACTERISTICS
Self-supporting frame with extruded section bars in double-wall aluminium camera for recessed screws.
Thermal cold break bridge section bar thickness 60 mm
Double-wall sheet metal thermal break panels thickness 62 mm:
internal in galvanised steel thickness 0.5 mm, external in pre-painted steel thickness 0.6 mm. Insulation in injected polyurethane
average density 45 kg/m³.
Internal face for floor panels in galvanised steel
All filters installed on unit
Without weather protection (indoor installation only)
With aluminium profile base frame
Carpentry material with galvanised sheet. Slides for container transport
Installation and service manual language: English

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 1/8
PrzRev Ag5.0 28/11/2022 11:56:21
Damper section
galvanised sheet damper size N° 1 900x680 mm - 3000 mc/h - Enginia
Without servomotor
Total section pressure drop = 2 Pa
Damper Class 1 – Aluminum blades, galvanized steel frame

Synthetic filter
Pleated synthetic filter efficiency ISO Coarse 55% - ISO 16890 (G4 - EN 779:2012) N°1 490 x 592 x 48 mm + N°1 287 x 592 x 48 mm
Filter pressure drop: clean filter 51 Pa, project pressure drop 76 Pa, dirty filter 101 Pa
Velocity in AHU filter cross section: 1.81 m/s
Total section pressure drop = 76 Pa
With side withdrawal

Cooling coil.
AIR TEMPERATURE AND HUMIDITY DATA FLUID: Water
Air flow standard 3000 m³/h Flow rate 6632 dm³/h
Face velocity 2.63 m/s Fluid speed 1.59 m/s
Inlet temperature 35 °C Inside volume 12.69 dm³
Inlet RH 50 % Inlet temperature 7 °C
Outlet temperature 15.48 °C Outlet temperature 12 °C
Outlet RH 99 %
Capacity 38.56 kW
Wet pressure drop 190 Pa Pressure drop 42.00 kPa
Dry pressure drop 155 Pa
Condensate 25.43 dm³/h
Sensible heat/Total heat 0.53 -
Geometry P40 - Tubes material Copper -
Number of rows 6 - Tube diameter 16.45 mm mm
Fins spacing 2.5 mm Tube thickness 0.4 mm mm
Tubes number 12 - Fins material Aluminium -
Circuits number 6 - Fins tickness 0.12 mm mm
Frame material Galvanized -
Manifolds material Iron -
Coil width 840 mm
Manifold inlet 1 1/2' -
Manifold outlet 1 1/2' -
3S P40 6 rows p.a 2.5 Cu/Al 12T 660A 6c 1 1/2'
Accessories:
Drain pan in galvanised sheet
Drop separator in Aluminium Pa 108
Total section pressure drop = 297 Pa

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 2/8
PrzRev Ag5.0 28/11/2022 11:56:21
Heating coil
AIR TEMPERATURE AND HUMIDITY DATA FLUID: Water
Air flow standard 3000 m³/h Flow rate 3597 dm3/h
Face velocity 2.63 m/s Fluid speed 1.29 m/s
Inlet temperature 0 °C Inside volume 5.14 dm3
Inlet RH 0 % Inlet temperature 45 °C
Outlet temperature 20.41 °C Outlet temperature 40 °C
Outlet RH 0 %
Capacity 20.91 kW
Pressure drop 37 Pa Pressure drop 15.93 kPa
Condensate 0 dm3/h
Geometry P60 - Tubes material Copper -
Number of rows 3 - Tube diameter 16.45 mm mm
Fins spacing 2.5 mm Tube thickness 0.4 mm mm
Tubes number 8 - Fins material Aluminium -
Circuits number 4 - Fins tickness 0.12 mm mm
Frame material Galvanized -
Manifolds material Iron -
Coil width 835 mm
Manifold inlet 1 1/4' -
Manifold outlet 1 1/4' -
3S P60 3 rows p.a 2.5 Cu/Al 8T 660A 4c 1 1/4'
Accessories:
Total section pressure drop = 37 Pa

Fan Supply (single fan)


FAN GR40I-ZID.DG.CR Ziehl-Abegg MOTOR
116896/A01
Fan type Plug fan Motor type Brushless
Size 400 Motor nominal power 2.5 kW
Impeller material Zamid® composite Mains 400/3/50 V/f/Hz
Flow rate 3000 m³/h Insulation class F
Working head 254 Pa Protection IP 55
Internal pressure drops 792 Pa Shaft power 1.56 kW
Total static press. 1046 Pa Absorbed electrical Input power 1.56 kW
Dynamic pressure 5 Pa Motor efficiency Class IE5
Total pressure 1051 Pa System static efficiency 56.23
Fan speed 2246 rpm Absorbed current 2.39 A
Ufactor 9.0
Power input at shaft 1.56 kW
Calibration factor 180
Level of sound power by octave bands
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply[dB] 83 92 88 84 82 78 71 65
The fan system effect is taken into account in the fan performances.
Fan designed for wet conditions
Free supply
With microswitch on hatch
Hinge/handle with safety latch

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 3/8
PrzRev Ag5.0 28/11/2022 11:56:21
Rigid bag filter FCR
Bag filter efficiency ePM1 85% - ISO 16890 (F9 - EN 779:2012) N°1 490 x 592 x 292 mm + N°1 287 x 592 x 292 mm
Filter pressure drop: clean filter 72 Pa, project pressure drop 122 Pa, dirty filter 172 Pa
Velocity in AHU filter cross section: 1.81 m/s
Counter-frames in galvanised sheet N° 1 508x610x100 mm + N° 1 305x610x100 mm
Energy consumption of the filters (kWh/annum): 1300
Total section pressure drop = 122 Pa
with rear extraction

Inspection section
Inspection section for filters

Absolute filter FCR


Absolute filter efficiency H13 - EN 1822:2010 N°1 610 x 610 x 292 mm
Filter pressure drop: clean filter 215 Pa, project pressure drop 258 Pa, dirty filter 300 Pa
Velocity in AHU filter cross section: 2.24 m/s
Counter-frames in galvanised sheet N° 1 629x629x130 mm
Filter certificate attached to machine documentation
Total section pressure drop = 258 Pa
with rear extraction
Filter material PVC

AHU sound levels Octave band (Hz)


63 125 250 500 1000 2000 4000 8000 Tot. dB(A)
Sound power level inlet (supply side) [dB] 76 81 82 74 64 60 58 51 76
Sound power level discharge (supply side) [dB] 81 81 82 76 72 63 47 34 78
Sound power level inlet (return side) [dB]
Sound power level discharge (return side) [dB]
Airborne power level [dB] 83 81 69 68 59 37 24 75
Panel sound attenuation 9 9 7 15 14 19 34 41
Sound pressure level at 2 m 69 67 55 54 45 23 10 57
Sound pressure level defined considering semispheric propagation
Tolerance +/-3 [dB]

N°1 Mod. WZ-E920

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 4/8
PrzRev Ag5.0 28/11/2022 11:56:21
CLIMAVENETA partecipate in the ECC program for
AHU. Check ongoing validity of certificate:
www.eurovent-certification.com or www.certiflash.com

Ecodesign
Manufacturer Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A.
Unit model WZ-E920
Typology NRVU;UVU
SFPint [W/(m³/s)] 89
Nominal flow rate [m³/s] 0.83
Face velocity [m/s] 1.38
Type of HRS /
Thermal efficiency of heat recovery /
Maximum external leakage rate (-400Pa) [%] 0.39
Maximum external leakage rate (+400Pa) [%] 0.19
Maximum internal leakage rate (+250Pa) [%] /
CAL (R) class at -400 Pa L3 (R)
CAL (R) class at +700 Pa L2 (R)
SUPPLY
Nominal flow rate [m³/s] 0.83
Type of drive for var. speed inverter installed

Effective electric power input [Kw] 1.56


Nominal external pressure [Pa] 254
Internal pressure drop of ventilation components [Pa] 50
Static efficiency of fan [%] 55.9

Internet address for disassembly instructions: http://climaweb.climaveneta.it/


AHU exclusively selected for process application, out of scope of the (UE) N. 1253/2014 Regulation

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 5/8
PrzRev Ag5.0 28/11/2022 11:56:21
ARIA DI MANDATA / SUPPLY AIR

ARIA DI RINNOVO / FRESH AIR

ARIA DI RIP.-RICIRCOLO / RETURN AIR

ARIA DI ESPULSIONE / EXPULSION AIR


ISPEZIONI CON BARRE FERMA PORTA
B
INSPECTION WITH STOP BARS

120
60

1 1/2' 1 1/4'
680

800

900
1 1/2' 1 1/4'
60

100
1"

120
S.1 L 3500
60

1020
S.1 3600 1150 1050 457
900

1 1/2' 1 1/4'
Flow rate Flow rate
Working head Working head
60

MS MS
Motor Motor
Mains Mains
1 1/2' 1 1/4' Supply Fan Exhaust Fan

MITSUBISHI ELECTRIC HYDRONICS & IT COOLING SYSTEMS S.p.A.

CLIMAVENETA - CTAPRO Off. N° 22-0063/A 28/11/2022


Rel. 32.0.0 31.08.2022- Page 6/8
PrzRev Ag5.0 28/11/2022 11:56:21
CONDITIONS OF SUPPLY
Offer validity 60 days
Guarantee 12 months from commissioning, max 18 months from invoice date
Delivery term ex works loaded on truck
Delivery to be agreed
Payment to be agreed

Notes

We remain at your disposal. Kind regards.