Loadbearing framed systems

Metsec SFS
Site fixed light gauge steel infill systems

This section includes updated information, added

! since it was first published in July 2009. Please see


the WHITE BOOK update document for details.
Last updated 25/05/2012

Opal Court, Birmingham

Metsec MetFRAME
Loadbearing structural steel frame systems

Chessington
World of Adventure

Timber systems

George Wimpey,
Pembroke Grange, Caversham
424
Loadbearing - steel framing systems

Loadbearing - steel framing systems


Lightweight cold-rolled galvanised walling systems

Metsec Site Fixed System (SFS) and MetFRAME are high


precision, light gauge steel framing systems that are suitable
for virtually all types of structure. When used in conjunction
Key facts
with British Gypsum internal linings and Isover insulation,
l Fully engineered and tested
they provide fast-track solutions in keeping with the demands
solutions
of modern methods of construction. Metsec provides a full
pre-contract service, including structural calculations, which l Versatility to aid freedom of design
is underwritten by Professional Indemnity Insurance cover,
l High precision components and
and is backed up with full technical support throughout the
ease of build
project.
l A complete pre-contract service,
including structural calculations,
which is underwritten by
Professional Indemnity Insurance
cover

l Guaranteed performance and


project support

l Proven loadbearing systems in


conjunction with high performance
British Gypsum internal linings

About Metsec
Synonymous with fast-track steel frame buildings,
Metsec pioneered this construction technique in the UK
and their track record extends to over 1,000 installations.

Metsec operates strict design and


quality control procedures and is
registered to BS EN ISO 9001, covering
both the design and manufacture of
its steel framing systems.

Metsec Framing Division Support Team


Tel: 0121 601 6000 Fax: 0121 601 6126 FAST TRACK STEEL BUILDING SYSTEMS
E-mail: framing@metsec.com WITH BRITISH GYPSUM INTERNAL LININGS
12
Website: www.metsec.com

425
Loadbearing - Metsec SFS
Site fixed light gauge steel infill systems

O2 Arena, London
426
SFS
dB Plus
Loadbearing - Metsec SFS 48
Rw dB
62 0.30
W/m2K
0.25 60
mins

- Metsec
RAPID and RAPID
Metsec’s SFS is a fast-track, pre-galvanised steel framing system,
which is fixed as infill between the main structural frame members
Key facts

Loadbearing
and provides a carrier for insulation, exterior cladding and interior
Gyproc plasterboards. SFS frames are designed and manufactured
l Pre-engineered off-site
to suit the dimensions, loading and deflection criteria for each floor
for quick installation
height panel.
l Early weather protection

GypWall
Head and base tracks, vertical studs and window trimming sections to the structure
are all manufactured from lightweight, cold-rolled galvanised steel
l Lightweight, dry
sections, cut to length and barcoded ready to be screwed together construction
on site. It is ideal for projects where the speed of construction
and / or a lightweight frame is required. l Wind posts not
required

l Provides lateral support


B for external cladding

l Easy to insulate
A
thermally and
acoustically

l Unique slotted head


track for ease and
speed of installation

A B
Metsec Metsec Slotted
Stud Section Head Track

Applications
A wide range of applications.

Sector
3 Office / commercial 3 Retail 3 Sport and leisure
3 Education 3 Healthcare 3 Industrial
3 Custodial 3 Housing 3 Apartment buildings
3 High-rise multi-occupancy 3 Auditoria 12
3

427
www.british-gypsum.com

System components
Loadbearing - Metsec SFS

Metsec framing components Fixing and finishing products

Stud Section Gyproc Jack-Point Screws


70M15, 100M12, 100M15, 100M20, 150M12, 25mm, 35mm, 41mm and 60mm for fixing boards to
150M20, 200M12, 200M15, 200M20, 250M16, stud framing.
250M20, 300M20, 300M29.
Gyproc Sealant
Available in lengths up to 16m. Sealing air paths for optimum sound insulation.

Strap Depth
38VB09 38mm
Gyproc jointing materials
100VB12 100mm
For seamless jointing.

Slotted Head Track


Gyproc edge and angle beads
74M12, 74M20, 104M12, 104M15, 104M20, 154M12,
Protecting and enhancing board edges and corners.
154M20, 204M12, 204M20, 254M12, 254M20,
304M16, 304M20, 306M29.

Available in 3m and 4m lengths. Thistle Multi-Finish or Thistle Board Finish


To provide a plaster skim finish.
Track Section
74M12, 74M20, 104M12, 104M15, 104M20, 154M12, or
154M20, 204M12, 204M20, 254M12, 254M20, Thistle Durafinish
304M16, 304M20, 306M29. To provide improved resistance to accidental damage.
Available in lengths up to 6m.
or
Tek Screw
Thistle Spray Finish
5.5mm x 19mm low profile head Tek Screw.
Gypsum finish plaster for spray or hand application.

Tek Screw Insulation products


5.5mm x 38mm low profile head Tek Screw.
Isover APR 1200
Gypframe framing components 25mm, to achieve thermal and acoustic performance.

RB1 Resilient Bar Length


3000mm Isover Modular Roll
100mm, to achieve thermal and acoustic performance.

Board products
Isover Acoustic Slab
Gyproc WallBoard1 50mm, for improved thermal and acoustic
Thickness 12.5, 15mm performance.
Width 1200mm
Isover Steel Frame Batt (SF1)
Gyproc SoundBloc1 50mm, for thermal and acoustic insulation.
Thickness 12.5, 15mm
Width 1200mm
Isover Steel Frame Infill Batt (SF2)
Gyproc DuraLine1 50mm and 100mm, for thermal and acoustic
Thickness 15mm insulation.
Width 1200mm
Isover Cavity Barrier – Self Adhesive Grade
Gyproc Plank Cavity closure in external walls.
Thickness 19mm Available in widths to suit.
Width 600mm

Gyproc FireLine1 Rigid Foam Insulation (by others)


Thickness 12.5, 15mm Foil faced rigid PIR insulation board.
Width 1200mm

Insulated external render system (by others)


12 1 Moisture resistant boards are specified in intermittent wet use areas,
e.g. shower cubicles. For building envelope and thermal performance.
ECSURE
SP

Always use genuine branded British Gypsum components to qualify for SpecSure® lifetime warranty
ANTY
LIFETIM

RR
E

SY
STEM W

428
T 0844 800 1991 F 0844 561 8816 E bgtechnical.enquiries@bpb.com

Loadbearing - Metsec SFS


Installation overview

Metsec Site Fixed Infill System (SFS) Where components need to be cut on site, this should only be done
It is the installer’s responsibility to produce a cutting list and order with a chopsaw with a TCT blade and not an abrasive disk. Care
Metsec materials. should be taken to cut the components square where they are used
in right-angled connections, or as required for an angular fit
l Section sizes should be taken from the project specific design /
against abutting members.
drawings.
l A site survey should be conducted to establish the ‘as built’ Splices in sections are not permitted without consent from Metsec.
dimensions of the main frame to enable material to be ordered
in the most economic manner. Fixing of components shall be with self-tapping screws, as specified
l The orders should be co-ordinated to suit the desired by Metsec for the project. All screw fixings must be installed
construction programme. perpendicular to the surface unless advised otherwise.

Sections are delivered to site in bundles on an articulated lorry. No holes are to be cut or formed in SFS steelwork without prior
Give consideration to the method of offloading material and the reference to Metsec. 72mm deep x 32mm wide service slots can be
need for an accessible designated safe storage area. provided 600mm from each end of studs / joists on request.

Health and Safety issues must be agreed with the main contractor, For technical advice relating to the specification, design and
prior to works commencing. installation of Metsec systems, contact the Metsec Framing Division
Support Team - tel: 0121 601 6000, email: framing@metsec.com
Installation
Base and head tracks should be set out as the project specific Gyproc plasterboards are screw-fixed to Metsec stud sections to form
drawings and fixed in place. If the set out of the main frame results in the lining. Screw-fix boards to framing members at 300mm centres,
the Metsec overhanging, refer to Metsec for guidance. using Gyproc Jack-Point Screws. All board joints should be taped and
finished in accordance with the guidance set out in the British Gypsum
In all infill applications, a deflection head detail should be used at the SITE BOOK, available to download from www.british-gypsum.com
top of the stud. Metsec recommends the use of the slotted head track
wherever possible. For advice on the specification and installation of British Gypsum
linings, contact the British Gypsum Drywall Academy on
Studs shall be plumbed, aligned and securely attached / located tel: 0844 800 1991, or email: bgtechnical.enquiries@bpb.com
within the base and head tracks.

Openings should be formed to suit the project specific design and


architectural set-out, including any tolerances required.

Refer to bracing / blocking requirements shown on the project


specific design.

12
For further details, visit the Metsec website www.metsec.com or email framing@metsec.com
429
www.british-gypsum.com

Performance ( Refer to section 3 - Basic principles of system design)


Loadbearing - Metsec SFS

BS Table 1 – Non-loadbearing steel frame system - protecting loadbearing structural steel


Solutions to satisfy the requirements of BS 476: Part 20: 1987 (loadbearing capacity)

Board linings to one side of Metsec framework, forming an


independent lining to structural steel columns. Linings as in table.

Board Lining thickness Fire protection Section factor1


type mm mins A/V (Hp/A) m-1

FireLine 1 x 12.5 30 Up to 300

FireLine 1 x 12.5 60 Up to 165

FireLine 1 x 15 30 Up to 300

FireLine 1 x 15 60 Up to 195

WallBoard or SoundBloc 2 x 12.5 30 Up to 300

WallBoard or SoundBloc 2 x 15 60 Up to 300

FireLine 2 x 12.5 60 Up to 300

FireLine 2 x 12.5 90 Up to 200

FireLine 2 x 15 90 Up to 300
1 Based on four-sided exposure. Protection is afforded to universal column sections as described in BS 4: Part 1. Based on critical temperature 550°C
(information on other critical temperatures is available).
NB The fire resistance and sound insulation performances are for imperforate walls incorporating boards with all joints taped and filled, or skimmed according to British Gypsum’s
recommendations. The quoted performances are achieved only if British Gypsum components are used throughout, and the Company’s fixing recommendations are strictly observed.
Any variation in the specifications should be checked with British Gypsum.

NB For improved durability and impact resistance, the outer layer of board can be replaced with a layer of Gyproc DuraLine.
NB The above table is based on a minimum 10mm airspace between the back of the inner lining board and the structural steel, with no vertical board joints aligning with the
structural steel.

ECSURE
SP

BS Table 2 – Loadbearing steel frame system - external walls

ANTY
LIFETIM
Solutions to satisfy the requirements of BS 476: Part 21: 1987

RR
E

A
SY
STEM W

1 2 3

103mm brickwork, 50mm low emissivity clear cavity, low Rainscreen cladding, well vented clear cavity, insulation, Insulated external render system (unbridged), 12mm
emissivity faced insulation, insulation between Metsec insulation between Metsec 100M12 studs at 600mm sheathing board, insulation between Metsec 100M12
100M12 studs at 600mm centres. Board linings as in table. centres. Board linings as in table. studs at 600mm centres. Board linings as in table.

Detail Board Lining Load bearing R-value of insulation Combined R-value of insulation external side of U-value2 Metsec
type thickness ratio between studs studs and low emissivity cavity (where applicable) system
mm % m2K/W m2K/W W/m2K reference

60 minutes fire resistance 1 BS


1 WallBoard 2 x 15 67 1.39 2.13 0.29 MFD380

1 WallBoard 2 x 15 67 2.78 2.13 0.25 MFD380

2 WallBoard 2 x 15 67 2.78 1.56 0.30 MFD383

2 WallBoard 2 x 15 67 2.78 2.17 0.26 MFD383

3 WallBoard 2 x 15 67 1.39 1.88 0.29 MFD395

3 WallBoard 2 x 15 67 2.78 1.88 0.25 MFD395

1 Exposed to fire on the room side.


2 Thermal performance values assume normal exposure conditions.

12 NB Performance data applies to loadbearing construction details, contact Metsec for all performance substantiation.
NB A vapour control layer may be required in all solutions.

NBS work section K10 - Plasterboard drylinings / partitions / ceilings


430
T 0844 800 1991 F 0844 561 8816 E bgtechnical.enquiries@bpb.com

Loadbearing - Metsec SFS


ECSURE
SP

BS Table 3 – Loadbearing steel frame system - internal walls

ANTY
LIFETIM
Solutions to satisfy the requirements of BS 476: Part 21: 1987

RR
E

A
SY
STEM W

1 2

Metsec stud at 600mm centres. Metsec stud at 600mm centres, with Gypframe
Stud size, insulation and linings as in table. RB1 Resilient Bar to both sides. Stud size,
insulation and linings as in table.

Detail Board Stud Lining Insulation Load bearing Sound insulation2 Metsec
type size thickness type ratio Rw (Rw + Ctr) system
mm mm % dB reference

60 minutes fire resistance 1 BS

1 FireLine 100 2 x 12.5 100mm Isover Modular Roll 67 55 MFD351

1 WallBoard 100 2 x 15 50mm Isover Acoustic Slab 67 48 MFD371

2 SoundBloc 70 2 x 15 25mm Isover APR 1200 67 59 (51) MFD362

2 SoundBloc 100 2 x 15 50mm Isover Acoustic Slab 67 61 (54) MFD374

1 Estimated 90 minutes in non-axial loaded wall situations (non-loadbearing, BS 476: Part 22).
2 Sound insulation values are for airtight constructions in the absence of flanking sound transmission.

NB Performance data applies to loadbearing construction details, contact Metsec for all performance substantiation.

ECSURE
SP

BS Table 4 – Loadbearing steel frame system - joisted floors

ANTY
LIFETIM
Solutions to satisfy the requirements of BS 476: Part 21: 1987

RR
E

A
SY
STEM W

18mm chipboard, battened floating floor,


19mm Gyproc Plank, 15mm plywood to one
side of 200mm Metsec joists at 600mm
centres. 75mm Isover Steel Frame Infill Batt
(SF2) in the cavity. Gypframe RB1 Resilient
Bars and two ceiling linings as in table.

Detail Board Ceiling Load bearing Sound insulation Metsec


type lining ratio Airborne Impact system
thickness Rw (Rw + Ctr) Lnw reference
mm % dB dB

60 minutes fire resistance BS

1 FireLine 2 x 12.5 80 62 (52) 51 MFD384

NB Ceiling and floating floor details used in conjunction with joisted floors will vary to suit site requirements.

NB Contact Metsec for all performance substantiation.

12
NBS work section K10 - Plasterboard drylinings / partitions / ceilings
431
www.british-gypsum.com

Design
Loadbearing - Metsec SFS

General
Metsec’s SFS fast-track building system is designed using the
FrameSPEC software program, developed by Metsec, which optimises
the stud sections, spacing and anchorage according to the required
floor-to-floor heights, deflection criteria and lateral wind pressures.
Being pre-engineered off-site, Metsec’s SFS is lighter and quicker to
install than other construction methods.

Services
All Metsec SFS stud sections feature a 72mm x 32mm slot, which
is located 600mm from either end of the section. This aperture
allows for the easy routing of services through the frame at the
time of installation without any resultant loss of internal space.

Cavity barriers
Properly constructed cavity barriers must be provided in
accordance with the requirements of the relevant Building
Regulations. The nature of these cavity barriers will vary according
to the design requirements of each particular project.

Electrical
The installation of electrical services should be carried out in
accordance with BS 7671. The cut-outs in the stud sections are
suitable for routing electrical services.

Cladding support
Metsec SFS can support most external cladding systems with the
exception of heavy masonry, which should be supported off the
primary framework of the structure. The actual support details will
vary accordingly and are designed by Metsec on a project specific
basis.

Wind loading
Metsec SFS walls are designed to accommodate wind loadings and
are designed by Metsec on a project specific basis.

Window and door apertures


Allowance should be made for the plasterboard lining returns at
window and door apertures. These will vary on a project specific
basis according to the fire performance requirements of the
structure. Full details will be provided by Metsec for each project.

Movement joints
These should always be provided to coincide with the movement
joints in the main frame of the structure.

Deflection
All SFS walls require deflection head details. The Metsec Slotted
Head Track solution, removes the need for auxiliary components.

Sustainability
The excellent 94% combined re-use and recycling figure1 for
constructional steelwork ensures that sustainability objectives can
also be met.

12 1 British Constructional Steelwork Association (BCSA) publication No. 35/03.

Please refer to section 3 - Basic principles of system design for general guidance
432
T 0844 800 1991 F 0844 561 8816 E bgtechnical.enquiries@bpb.com

Loadbearing - Metsec SFS


Construction details
1 Detail SF1

3
4

1 Primary frame
2 Slotted deflection head track fixed to steel beam, additional fixings
at jamb
3 150mm length of stud fixed to jamb
4 Track
5 Additional stud for brick tie 12
6 Jamb stud
7 Base track fixed to concrete slab, additional fixings at jamb

433
Loadbearing - Metsec MetFRAME
Loadbearing structural steel frame systems

Crispin Street, London


434
MetFRAME
dB Plus
Loadbearing - Metsec MetFRAME

and RAPID
The Metsec MetFRAME building system features cold-rolled, light
gauge galvanised steel sections to create pre-fabricated panels,
Key facts

- Metsec
which can be bolted together on site to create the building
superstructure. This provides a fast-track solution for medium
l Pre-engineered off-site

GypWall RAPID
rise structures, in line with the demands of Modern Methods of
for quick installation
Construction.

Loadbearing
l Provides early weather
Each MetFRAME project is designed by Metsec’s own team of protection to the
structural engineers, and drawn in-house. Metsec approved structure

contractors pre-assemble panels within their own factories, then l Lightweight, dry
erect the structure on-site. This entire process is underwritten by construction
Metsec’s own Professional Indemnity Insurance cover.
l Wind posts not
C required

l Provides lateral support


A for external cladding

B l Easy to insulate
thermally and
acoustically

A B C
MetFRAME Metsec MetFRAME
Stud Diagonal Joists
Section Bracing Strap

Applications
A wide range of applications.

Sector
3 Office / commercial 3 Retail 3 Sport and leisure
3 Education 3 Healthcare 3 Industrial
3 Custodial 3 Housing 3 Apartment buildings
3 High-rise multi-occupancy 3 Auditoria 12
3

435
www.british-gypsum.com

System solutions
Loadbearing - Metsec MetFRAME

Metsec MetFRAME is pre-fabricated to meet project specific requirements, therefore no standard system solutions are
presented in this section. Please contact Metsec to discuss your project.

Example system components

Framing - Metsec components Fixing and finishing products

Components for MetFRAME walls, floors and roofs are designed to Gyproc Jack-Point Screws
suit specific project requirements. 25mm, 35mm, 41mm and 60mm for fixing boards to
stud framing.

Board products Gyproc Sealant


Sealing air paths for optimum sound insulation.
Gyproc WallBoard1
Thickness 12.5mm
Width 1200mm Gyproc jointing materials
For seamless jointing.
Gyproc SoundBloc1
Thickness 12.5, 15mm
Width 1200mm Gyproc edge and angle beads
Protecting and enhancing board edges and corners.
Gyproc DuraLine1
Thickness 15mm
Width 1200mm Thistle Multi-Finish or Thistle Board Finish
To provide a plaster skim finish.
Gyproc Plank or
Thickness 19mm
Width 600mm Thistle Durafinish
To provide improved resistance to accidental damage.
Gyproc FireLine1
or
Thickness 15mm
Width 1200mm Thistle Spray Finish
Gypsum finish plaster for spray or hand application.
1 Moisture resistant boards are specified in intermittent wet use areas,
e.g. shower cubicles. Insulation products

Isover APR 1200


For thermal and acoustic performance.

Isover Modular Roll


For thermal and acoustic performance.

Isover Acoustic Slab


For thermal and acoustic performance.

Isover Steel Frame Batt (SF1)


50mm, for thermal and acoustic insulation.

Isover Steel Frame Infill Batt (SF2)


For thermal and acoustic performance.

Insulated external render system (by others)


For building envelope and thermal performance.

Rigid Foam Insulation (by others)

12 Foil faced rigid PIR insulation board.

ECSURE
SP

Always use genuine branded British Gypsum components to qualify for SpecSure® lifetime warranty
ANTY
LIFETIM

RR
E

SY
STEM W

436
T 0844 800 1991 F 0844 561 8816 E bgtechnical.enquiries@bpb.com

Loadbearing - Metsec MetFRAME


Installation overview

MetFRAME Several methods of floor construction can be used dependant upon


All MetFRAME projects are erected by Metsec approved contractors span and loading requirements:
who are experienced in the installation of loadbearing MetFRAME l Composite concrete slabs using profiled metal decking with
walls, floors and roof structure, and who can also source any
either a powerfloated or screeded finish, or with a lightweight
non-Metsec supplied items, e.g. profiled steel floor decking,
floating floor laid over. Where reinforced concrete slabs are
reinforcement.
used, they are designed by Metsec.
l Floor panels of Metsec C-section joists are detailed and
MetFRAME projects are fully detailed in advance, and all MetFRAME
supplied in a similar fashion to the wall panels. These are
components are supplied cut to length and with all holes punched.
boarded at panel assembly stage to provide a working deck as
MetFRAME walls are pre-panelized off-site by the approved installer.
soon as they are fixed into position.

Studs are typically 100mm deep at 600mm centres, but the stud l Individually installed cold-rolled steel joists, with a maximum
depth, gauge and centres can be varied to suit the exact depth of 402mm, can be used for longer spans, available from
application / loading conditions. Panels will have a base track and a the standard Metsec section range.
top track or zed ledgers where floor support is required.
If required, hot-rolled elements are incorporated into the
During panel manufacture, insulation and brick tie channels or MetFRAME structure with box section posts of the same depth as
boarding to suit a rendered or clad finish are applied. Heavier the studs built into wall panels. Long-span floor / roof support
claddings, such as brickwork, rendered blockwork or stone, should beams can be connected to either hot or cold-rolled posts / studs.
be self-supporting vertically, including at opening positions, but are
restrained laterally by the wall studs. Lighter finishes, such as Roof systems may be cold-rolled purlins, metal or timber truss
rendered board, timber shiplap cladding and profiled steel rafters, or a combination of these. Truss rafters typically span
cladding, can all be supported vertically and laterally by the system. between the front and rear walls. Cold-rolled purlins typically span
between cross walls.
By fixing rigid insulation or board onto the external panels prior to
installation on site, early weather protection of the building can be For technical advice relating to the specification, design and
achieved, allowing other internal fitting trades to work inside the installation of Metsec systems, contact the Metsec Framing Division
structure and therefore removing external cladding from the Support Team - tel: 0121 601 6000, email: framing@metsec.com
critical path.
Gyproc plasterboards are screw-fixed to Metsec stud sections to form
the lining. Screw-fix boards to framing members at 300mm centres,
using Gyproc Jack-Point Screws. All board joints should be taped and
finished in accordance with the guidance set out in the British Gypsum
SITE BOOK, available to download from www.british-gypsum.com

For advice on the specification and installation of British Gypsum


linings, contact the British Gypsum Drywall Academy on
tel: 0844 800 1991, or email: bgtechnical.enquiries@bpb.com 12
For further details, visit the Metsec website www.metsec.com or email framing@metsec.com