Professional Documents
Culture Documents
Read and Follow All Safety Instructions! Save These Instructions and Deliver To Owner After Installation
Read and Follow All Safety Instructions! Save These Instructions and Deliver To Owner After Installation
• To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and
other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
• Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
• Installation and service of luminaires should be performed by a qualified licensed electrician.
• Maintenance of the luminaires should be performed by person(s) familiar with the luminaires’ construction and operation
and any hazards involved. Regular fixture maintenance programs are recommended.
• It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient
dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm
water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly
become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary.
• DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been
damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
• Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov.
• These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency
to meet in connection with installation, operation, or maintenance. Should further information be desired or should
particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be
referred to Acuity Brands Lighting, Inc.
WARNING WARNING
RISK OF ELECTRIC SHOCK RISK OF BURN
✓ Disconnect or turn off power before ✓ Allow lamp/fixture to cool before handling.
installation or servicing. Do not touch enclosure or light source.
✓ Verify that supply voltage is correct by ✓ Follow all manufacturer’s warnings,
comparing it with the luminaire label recommendations and restrictions for: driver
information. type, burning position, mounting
✓ Make all electrical and grounded locations/methods, replacement and
connections in accordance with the National recycling.
Electrical Code (NEC) and any applicable
local code requirements.
✓ All wiring connections should be capped
with UL approved recognized wire
connectors.
CAUTION CAUTION
RISK OF INJURY RISK OF FIRE
✓ Wear gloves and safety glasses at all times ✓ Keep combustible and other materials that
when removing luminaire from carton, can burn, away from lamp/lens.
installing, servicing or performing ✓ Do not operate in close proximity to
maintenance. persons, combustible materials or
✓ Avoid direct eye exposure to the light source substances affected by heat or drying.
while it is on.
1|Page
IM-440-E
LED IMPORTANT SAFETY INSTRUCTIONS
Please see product specific installation instructions for additional warnings or any applicable FCC or other regulatory
statements.
Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and
Conditions, please visit www.acuitybrands.com.
Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.
ABL LED General Warnings, Form No. 503.203
2|Page
IM-440-E
INSTRUCTIONS DE SÉCURITÉ IMPORTANTES SUR LES DEL
✓ Porter des gants et des lunettes de protection à tout ✓ Maintenir toutes matières combustibles ou
moment pour sortir le luminaire de la boîte, l’installer, susceptibles de brûler à l’écart des lampes et
le réparer ou en faire l’entretien. des optiques.
✓ Éviter le contact direct des yeux avec la source de ✓ Ne pas l’utiliser à proximité des personnes,
lumière lorsqu’elle est allumée. des substances ou des matériaux
combustibles affectés par la chaleur ou le
séchage.
INSTRUCTIONS DE SÉCURITÉ IMPORTANTES SUR LES DEL
ATTENTION : RISQUE
D’ENDOMMAGEMENT DU PRODUIT
4|Page
IM-440-E
HOLOPHANE® Petrolux® LED Low Bay Installation and
Wet Location Luminaire Maintenance
Manual
Figure 1-A
2 Installation
2.1 Tools and Materials Required.
1 Introduction
1.1 Product Description. Light Emitting Diode (LED)
luminaire. (Max Fixture Weight: 30 lbs without substation
arm)
1.2 Alternate Information Sources.
Holophane
Field Service Department
P.O. Box 3004
Newark, OH 43058-3004
(740) 345-9631
5|Page
IM-440-E
3 Applying Thread Sealant (Figures 2 and 3)
3.1 Apply thread sealant to all used entries. On used
entries, remove plug and apply thread sealant to entry
threads, then install conduit and wipe off any excess
thread sealant.
Figure 2
Figure 3
6|Page
IM-440-E
4 Pendant Luminaire Installations (Figure 4) 4.2.3 Close luminaire housing and tighten closure screw
4.1 Mounting to torque specified in Figure 1-A.
4.1.1 Loosen closure screw and open electrical housing.
(See Figure 1-A) 5 Ceiling Luminaire Installations (Figure 5)
4.1.2 Un-hinge top cover from luminaire. 5.1 Mounting
4.1.3 Back out the pendant set screw far enough to 5.1.1 Loosen closure screw and open electrical housing.
ensure that it will not interfere with the pipe threads. (See Figure 1-A)
4.1.4 Remove top ¾” plug on threaded entry, if present 5.1.2 Un-hinge top cover from luminaire.
4.1.5 Pull supply wires through pendant entry and thread 5.1.3 Remove 1-11.5 NPT plugs as needed for supply
electrical cover onto pipe at least (5) full turns until wire access.
secure. 5.1.4 Customer shall provide two 3/8” diameter fasteners
4.1.5.1 A suitable mounting structure must be with washers suitable for supporting the luminaire.
provided that supports the full weight of the luminaire in 5.1.4.1 A suitable mounting structure must be
accordance with local codes. provided that supports the full weight of the luminaire in
4.1.6 Tighten pendant set screw, per torque specified in accordance with local codes.
Figure 5. 5.1.5 Install top cover to suitable building structure using
4.1.7 Proceed to Section 4.2 the fasteners.
5.1.6 Re-attach luminaire to top cover.
Figure 4 – Pendant Mount 5.1.7 Proceed to Section 5.2
5.2 Wiring
5.2.1 Use supplied zip tie to secure supply wires and
ensure they cannot be pinched when closing the
housing. Customer supplied zip ties should be rated
90°C minimum.
PM Mounting Option 5.2.2 Make appropriate supply and ground connections
to the luminaire wires in accordance with local codes.
5.2.4 Close luminaire and tighten closure screw to
torque specified in Figure 1-A.
4.2 Wiring
4.2.1 Hang the luminaire on the top cover. Make 6 Wall Luminaire Installations (Figure 6)
appropriate supply and ground connections to the 6.1 Mounting
luminaire wires in accordance with local codes. 6.1.1 Loosen closure screw and open electrical housing.
4.2.2 Use supplied zip tie to secure supply wires and (See Figure 1-A)
ensure they cannot be pinched when closing the 6.1.2 Un-hinge top cover with mounting arm from
housing. Customer supplied zip ties should be rated luminaire. If not attached, attach mounting arm to top
90°C minimum cover using two supplied 5/16-18 bolts as specified in
7|Page
IM-440-E
Figure 9. Alternatively, mounting arm can be attached to Figure 7 – Stanchion Mount
mounting structure prior to attaching to top cover.
6.1.3 Provide 2X 5/16-18 diameter fasteners suitable for
supporting the luminaire and install the top cover with
mounting arm to the structure.
6.1.4 Remove 1-11.5 NPT plugs from the mounting arm
as needed for supply wires.
6.1.5 Remove mounting arm plate. (See Figure 9)
6.1.6 Re-attach luminaire to top cover.
6.1.7 Proceed to Section 6.2.
7.2 Wiring
7.2.1 Feed supply wires and mounting arm ground lead
from the mounting arm through the entry hole of the top
cover and into the wiring chamber. Use supplied zip ties
or customer supplied wire ties rated 90°C minimum to
secure the supply wires to the top cover such that they
cannot be pinched when closing the housing. Re-attach
mounting arm plate with 4 screws provided, per torque
specified in Figure 9.
7.2.2 Make appropriate supply and ground connections
to the luminaire wires in accordance with local codes.
7.2.4 Close luminaire and tighten closure screw to
6.2 Wiring torque specified in Figure 1-A.
6.2.1 Feed supply wires and mounting arm ground lead
from the mounting arm through the entry hole of the top 8 Gasket Hook Installations (Figure 8)
cover and into the wiring chamber. Use supplied zip ties 8.1 Mounting
or customer supplied wire ties rated 90°C minimum to 8.1.1 Hang luminaire from a suitable structure.
secure the supply wires to the top cover such that they 8.1.1.1 A suitable mounting structure must be
cannot be pinched when closing the housing. Re-attach provided that supports the full weight of the luminaire in
mounting arm plate with 4 screws provided, per torque accordance with local codes.
specified in Figure 9. 8.1.2 Tighten hook screw until the head is flush with the
6.2.2 Make appropriate supply and ground connections hook.
to the luminaire wires in accordance with local codes. 8.1.3 Cords provided by factory are pre-wired to
6.2.3 Close luminaire and tighten closure screw to luminaire.
torque specified in Figure 1-A. 8.1.4 Insert plug into appropriate electrical receptacle.
8|Page
IM-440-E
Figure 9 – Universal Mount
9|Page
IM-440-E
10.7 Next, Mount the Luminaire(s) to the Arm. Using
Figure 11 – Mounting to Substation Arm Accessory
Section 3 for directions, apply thread sealant to the
pendant entry of the luminaire and to the nipple of the
arm.
10.7.1 Using Section 4.1 for directions, separate the
top cover from the luminaire.
10.7.2 Pull supply wires through pendant entry and
thread top cover onto pipe at least (5) full turns until
secure.
10.7.3 Tighten pendant set screw, per torque
specified in Figure 4.
10.7.4 Route the arm supply wires through pendant
entry of luminaire and into top cover wiring chamber.
10.7.5 Make appropriate arm supply wire connections
to the luminaire wires in accordance with local codes.
10.7.6 Re-attach luminaire to electrical cover and
tighten closure screw to torque specified in Figure 1-
A.
10.7.7 Repeat these instructions to install the second
luminaire onto a double substation arm.
WARNING
FOR A LUMINAIRE THAT POINTS UP TOWARD THE
10.2 Disconnect power to arm location. SKY, THE LUMINAIRE IS NOT HELD CAPTIVE ONTO
10.3 Provide and install a suitable mounting structure THE HINGE OF THE ELECTRICAL COVER.
that supports the full weight of the substation arm and up EXERCISE CAUTION AND FIRMLY GRASP THE
to two luminaires in accordance with local codes. LUMINAIRE WHEN OPENING AND CLOSING THE
10.3.1 The Single Substation Arm with one PXLW LUMINAIRE ONTO THE COVER. FAILURE TO
luminaire weighs 35 lbs. FIRMLY GRASP THE LUMINAIRE DURING OPENING
10.3.2 The Double Substation Arm with two PXLW AND CLOSING CAN CAUSE THE LUMINAIRE TO
luminaires weighs 62 lbs. SEPARATE FROM THE COVER AND FALL CAUSING
10.4 Install the single or double arm onto the mounting DEATH, INJURY OR SERIOUS PROPERTY DAMAGE.
structure. Installer shall provide suitable 3/8” diameter SEE FIGURE 13
fasteners to mount the arm to the mounting structure.
10.5 Route supply wires into the side entries of the arm AVERTISSEMENT
and into the arm wiring chamber. (See Figure 12)
10.6 Make appropriate supply and ground connections POUR UN LUMINAIRE QUI POINTE VERS LE CIEL, LE
to the arm wires in accordance with local codes. LUMINAIRE N’EST PAS MAINTENU DANS LA
CHARNIÈRE DE LA COUVERTURE ÉLECTRIQUE.
Figure 12 – Supply Wire Connections at Substation Arm FAIRE ATTENTION ET SOUTENIR FERMEMENT LE
LUMINAIRE AU MOMENT D’OUVRIR ET DE FERMER
LE LUMINAIRE DANS LA COUVERTURE
ÉLECTRIQUE. NE PAS MAINTENIR LE LUMINAIRE
FERMEMENT PENDANT L’OUVERTURE ET LA
FERMETURE PEUT PROVOQUER LA SÉPARATION
DU LUMINAIRE DE LA COUVERTURE ÉLECTRIQUE,
IL PEUT AINSI TOMBER ET CAUSER DES
ACCIDENTS MORTELS, DES BLESSURES OU DE
SÉRIEUX DOMMAGES AUX BIENS. Voir schéma 13
10 | P a g e
IM-440-E
Figure 13 – WARNING Figure 15 – Single Luminaire With Sensor
11 | P a g e
IM-440-E
Figure 16 – Twin Luminaire Without Sensor Figure 17 – Twin Luminaire With Sensor
12 | P a g e
IM-440-E
11 Dimming Option (See Figure 18)
11.1 Dimming Option
Figure 19 – Emergency Battery Option
11.1.1 Remove un-used NPT plug and provide and
install separate conduit and water tight connection to
luminaire for dimming supply wires.
11.1.2 Route 0-10V DC dimming supply wires, rated
90°C minimum, to the luminaire for the dimming option.
Use wire ties rated 90°C minimum to secure the supply
wires to the electrical cover such that they cannot be
pinched when closing the housing.
11.1.3 Connect DC supply wires to purple and pink or
grey capped leads coming out of the driver.
11.1.4 Close luminaire and tighten closure screw to
torque specified in Figure 1-A.
15 Maintenance
15.1 Gasket Joint Surfaces
15.1.1 Check the condition of gaskets and gasket joint
surfaces. Optical or electrical gaskets that show signs of
damage or wear and gasket joint surfaces that have
debris may affect seal integrity.
12.1 Energize Luminaire
12.1.1 Energize luminaire and check for correct CONTACT YOUR LOCAL HOLOPHANE
operation. REPRESENTATIVE FOR HOLOPHANE APPROVED
12.1.1.1 A few second delay before the LED’s turn REPLACEMENT PARTS
on is typical for this luminaire.
COMMUNIQUEZ AVEC VOTRE REPRÉSENTANT
13.1 Emergency Battery Option HOLOPHANE LOCAL POUR DES PIÈCES DE
13.1.1 Bring 4 conductor power – 3 conductors switched, RECHANGE APPROUVÉES PAR HOLOPHANE.
1 conductor un-switched -- into fixture via chosen
conduit opening in top cover
13.1.2 Connect switched power line to white, black, and 15.2 Cleaning
green conductors as per electrical code 15.2.1 Disconnect power to the unit prior to opening and
13.1.3 Connect un-switched power line to black lead performing any maintenance.
label “UNSWITCHED LINE” 15.2.2 Wipe off exterior dirt and debris using a soft clean
13.2 For Corded Fixtures cloth. A mild detergent and water may be used if
13.2.1 Connect switched power line to white, black, and necessary.
green conductors as per electrical code
13.2.2 Connect un-switched power line to red conductor CAUTION
13.3 Power fixture, ensure emergency test switch shown DO NOT USE ABRASIVE CLEANERS ON OPTICAL
in Figure 19 is lit (red/green). Reference PS1055MCP SURFACES. THEIR USE MAY RESULT IN THE LOSS
spec sheet for emergency test switch color code. OF OPTICAL EFFICIENCY
MISE EN GARDE
NE PAS UTILISER DE NETTOYANT ABRASIF SUR
DES SURFACES OPTIQUES. LEUR UTILISATION
13 | P a g e
IM-440-E
PEUT ENTRAÎNER UNE PERTE D’EFFICACITÉ 15.4.1 Disconnect power to the luminaire location before
OPTIQUE. maintenance. Loosen closure screw and open electrical
housing. See Figure 1-A.
15.3 Optic Replacement (Figure 20) 15.4.2 Tag leads before disconnecting.
15.3.1 Disconnect power to the luminaire. 15.4.3 Replace components using Holophane approved
15.3.2 Remove luminaire and set on a work surface for replacement parts.
optic replacement. 15.4.4 Examine the condition of electrical cover gasket
15.3.3 Remove the four fasteners holding the ring and and gasket joint surfaces. See Section 15.1
glass optical assembly using a T-20 Torx screwdriver. 15.4.5 Re-connect electrical components
15.3.4 Replace with new optical assembly into heatsink 15.4.6 Close luminaire and tighten closure screw to
using the drip edge as a guide. Inspect optical gasket torque specified in Figure 1-A.
surface and remove debris that may affect seal integrity.
15.3.5 Partially thread each ring fastener into the heat 16 Antenna Installation – rIO / rSBG
sink. 16.0.1 Remove antenna tape and discard (see figure 21)
15.3.6 Then drive each ring fastener, one by one, further 16.0.2 Fasten female end of antenna to protruding male
down in a sequential pattern until the ring is seated connector on the sensor housing (see figure 21)
against the heat sink.
15.3.7 Tighten each ring fastener to between 25 and 35
Figure 21 – rIO / rSBG Antenna Installation
inch pounds.