Professional Documents
Culture Documents
Condition Assessment of MV Switchboards: Performance of A New Sensors For Partial Discharge Monitoring
Condition Assessment of MV Switchboards: Performance of A New Sensors For Partial Discharge Monitoring
Abstract— Condition assessment of MV switchboards requires these diagnostic properties, that is also a primary cause of a
effective, but not expensive, solutions to become a common premature failure of electrical insulation, is partial discharges,
practice. On the other hand, failure of a switchboard component PD.
can cause cascade effects and outage of other apparatus, in
addition to significant economic losses due, e.g., to lack of energy Various types of PD sensors for MV switchboards are
availability. A major property to evaluate switchboard health examined in this paper, focusing on a new idea for a sensor
and reliability is partial discharges, being a direct cause of which is embedded in switchgear bushings, based on a
failure of organic insulation systems. A new type of partial capacitive coupler which is often already pre-existing in some
discharge sensoring is presented in this paper, which relies upon bushes in order measure the presence of voltage. Sensitivity to
capacitive divider embedded in switchboard bushings. Testing PD detection, also as a function of type of defect and distance
the embedded bushing sensor in factory on switchboards, in from the sensor, is investigated in comparison with other
presence of defective components as cable terminations and commonly used sensors, which couple with irradiated or
bushings, it is shown that the bushing sensor is able to provide conducted PD signals.
good sensitivity, compared to other sensors, as well as good
capability to locate the cabinet and identify the type of source II. EMBEDDED BUSHING SENSOR
generating partial discharges.
There are two coupling mechanisms for PD, which follow
Keywords – Bushing; MV switchboards; Partial discharge; up in dedicate type of sensors, that is, conduction and
Sensors. irradiation.
Regarding conduction, PD signals can propagate from the
I. INTRODUCTION source (i.e., bushings, cable terminations, etc.) to the ground
Even if it is widely thought that failure and outages of through earthing systems, so that the typical sensor is the high-
medium voltage apparatus and devices in electrical networks frequency current transformer, HFCT. Measuring conducted
do not cause severe economic losses, this may be not true in signals by HFCT offers in many cases good sensitivity, but
several industrial, transport and distribution assets. From measurements can be affected by noise. Furthermore, when
ships, to renewables, from high-tech factories to data centers, several cable lines are connected in parallel through busbars,
and considering unconventional type of electrical stress as the same PD signal can split among the earthing systems of
those involving power electronics, failure rate can become so parallel lines and be observed at different locations, although
high to affect reliability and profitability of assets. with different magnitudes and PD pulse spectral
characteristics.
Switchboards may play a significant role to ensure asset
reliability. Even if failure of one of their components is not Irradiation can be exploited through two basic coupling
per se involving expensive repair, it can cause cascade effects mechanisms, that is, near field and far field irradiation. The
that will make the cost of outage, lack or production or former corresponds to relatively low frequencies (e.g. below a
functionality of an asset a serious issue. The aspect which few hundreds MHz), at which PD signals couple in a
differs sensibly from the condition assessment of HV capacitive way with the cabinet, inducing transient earth
apparatus is that the cost of any diagnostic monitoring device voltages (TEV) on the metalclad surface. These signals can be
has to be proportioned to the cost of the switchboard, thus detected by measuring the voltage difference existing between
relatively unexpensive. Hence, the choice of sensors to be metallic surfaces separated by openings (TEV sensor) or using
used to assess switchboard health must be oriented towards capacitive probes. Far field irradiation occurs at higher
effective and low-cost solution, focusing on those degradation frequencies, at which PD signals can irradiate outside the
mechanisms that are associated with faster aging rate. One of cabinet, if they excite dielectric-aperture resonance
Authorized licensed use limited to: University of Canberra. Downloaded on May 23,2021 at 17:09:34 UTC from IEEE Xplore. Restrictions apply.
PD source 1 SWITCHBOARD n°1 SWITCHBOARD n°2 SWITCHBOARD n°3
(Defective bushing)
LV/MV TEV sensors PD source 2
Transformer (Defective cable termination)
Bushing Bushing
phase 4 phase 12 HFCT sensors
IV. EXPERIMENTAL RESULTS PD (due to the peculiar pattern shape [4], [9]). Fig. 5 displays
typical PRPD patterns obtained by the bushing sensor located
Partial discharge measurements were performed (and at phase 4, switchboard 1, and phase 12, switchboard 3
monitored for times up to a few hours) in several locations of (Figure 3). Sensitivity is intermediate, for this type of defect,
the assembly of switchboards of Figure 3. Various types of between those of TEV and HFCT, but the capability of
defects, inside and outside the switchboards, were considered. recognizing the type of defect generating PD is at the same
Here, those relevant to defective MV bushing (having an level (it is noteworthy that the patters reported in these and
internal cavity), Figure 1, and defective cable termination are following figures were denoised using the T-F map approach,
reported and discussed. [1], [4], [6], endowed in the PD testing instrument).
Three types of sensors were considered, as indicated in
Figure 3. Transient earth voltage, TEV, sensors, were placed
on the outer part of the cabinet enclosure, where resistance
variation could generate an impulsive voltage drop at the
occurrence of a PD. A second sensor was a high-frequency
current transformer, HFCT, which was connected on the
ground lead of cable terminations entering into a switchgear
cabinet, see Figure 3. As mentioned, TEV and HFCT are the
most frequently used electromagnetic sensor for PD
measurements in switchboards.
The third sensor was the embedded bushing sensor Figure 4. Phase-resolved PD (PRPD) patterns obtained from sensors TEV (a)
described above. and HFCT (b) located as in Figure 2 (that is, TEV at switchboard 1 and
HFCT cable termination at switchboard 1). Defective bushing generating PD.
PD measurements were performed at various bushing
sensors farer and farer from the PD sources, and also moving
HFCT and TEV along the switchboard cabinets, in order to
evaluate sensitivity of the sensors as a function of the distance
from the PD source.
A. Defective bushing
Phase-resolved PD (PRPD) patterns were obtained while
monitoring PD from a defective bushing located on the wall
near switchboard 1 (Figure 3), through TEV, HFCT and
embedded bushing sensors.
Examples of PD patterns are reported in Figure 4 and
Figure 5. Fig. 4 shows PRPD patterns obtained by TEV (a) Figure 5. Phase-resolved PD (PRPD) patterns obtained from the bushing
and HFCT (b) sensors, located as in Figure 3 (that is, TEV at sensor located at phase 4, switchboard 1, phase 12, switchboard 3 (Figure 2).
switchboard 1 and HFCT cable termination at switchboard 1). Defective bushing generating PD.
The TEV is clearly more sensitive than HFCT, for this type of
defect, but both sensors point out the type of defect generating
Authorized licensed use limited to: University of Canberra. Downloaded on May 23,2021 at 17:09:34 UTC from IEEE Xplore. Restrictions apply.
B. Defective cable termination
A cable with defective termination was connected to the
cabinet of switchboard 3. Bushing sensors are located in
cabinet 2 of switchboard 1, cabinet 2 of switchboard 2 and in
the switchboard 3. The HFCT sensor was set in each cabinet
as in Figure 3.
Figure 6 and Figure 7 report examples of PRPD patterns
obtained by the HFCT and the bushing sensor, respectively.
Even if sensitivity of the bushing sensor is obviously lower
than that of the HFCT (the latter being very close to the defect
and, in addition, devised specifically to detect conducted
signals), it can still work to figure out the presence of PD and,
in addition, the type of defect generating them (again internal
discharges, as in the previous case). Hence, it can be
speculated that a bushing sensor can pick up also conducted
signals generated outside a switchboard, but in its vicinity.
Authorized licensed use limited to: University of Canberra. Downloaded on May 23,2021 at 17:09:34 UTC from IEEE Xplore. Restrictions apply.
REFERENCES
Authorized licensed use limited to: University of Canberra. Downloaded on May 23,2021 at 17:09:34 UTC from IEEE Xplore. Restrictions apply.