Fire protection systems are required in public and common areas, with some exceptions. Alarm systems must identify the initiating device, location, type, and status. Zones cannot exceed 2100 sqm and 90m in length, with each floor and device type separately zoned in high-rise buildings. Fire alarm systems must be installed and monitored according to standards, with the primary and secondary power supply, device access for inspection, and monitoring by a supervising station required.
Fire protection systems are required in public and common areas, with some exceptions. Alarm systems must identify the initiating device, location, type, and status. Zones cannot exceed 2100 sqm and 90m in length, with each floor and device type separately zoned in high-rise buildings. Fire alarm systems must be installed and monitored according to standards, with the primary and secondary power supply, device access for inspection, and monitoring by a supervising station required.
Fire protection systems are required in public and common areas, with some exceptions. Alarm systems must identify the initiating device, location, type, and status. Zones cannot exceed 2100 sqm and 90m in length, with each floor and device type separately zoned in high-rise buildings. Fire alarm systems must be installed and monitored according to standards, with the primary and secondary power supply, device access for inspection, and monitoring by a supervising station required.
Fire protection systems are required in public and common areas, with some exceptions. Alarm systems must identify the initiating device, location, type, and status. Zones cannot exceed 2100 sqm and 90m in length, with each floor and device type separately zoned in high-rise buildings. Fire alarm systems must be installed and monitored according to standards, with the primary and secondary power supply, device access for inspection, and monitoring by a supervising station required.
shall be provided in public use areas and common Exceptions:
use areas. 1. Fire alarm systems in single-story buildings Exception: Where employee work areas have less than 2100 m2 in area. audible alarm coverage, the notification appliance 2. Fire alarm systems that only include manual circuits serving the employee work areas shall be fire alarm boxes, waterflow initiating devices initially designed with not less than 20-percent and not more than 10 additional alarm- spare capacity to account for the potential of adding initiating devices. visible notification appliances in the future to accommodate hearing-impaired employee(s). 3. Special initiating devices that do not support individual device identification. 907.5.2.3.2 Groups I-1 and R-1. Group I-1 and R-1 dwelling units or sleeping units in 4. Fire alarm systems or devices that are accordance with Table 907.5.2.3.2 shall be replacing existing equipment. provided with a visible alarm notification 907.6.3.1 Annunciation. The initiating appliance, activated by both the in-room smoke device status shall be annunciated at an approved alarm and the building fire alarm system. on-site location. 907.5.2.3.3 Group R-2. In Group R-2 907.6.4 Zones. Each floor shall be zoned separately occupancies required by Section 907 to have a fire and a zone shall not exceed 2100 m2. The length of alarm system, all dwelling units and sleeping units any zone shall not exceed 90 m in any direction. shall be provided with the capability to support visible alarm notification appliances in accordance Exception: Automatic sprinkler system zones shall with Chapter 10 of ICC A117.1. Such capability not exceed the area permitted by NFPA 13. shall be permitted to include the potential for future 907.6.4.1 Zoning indicator panel. A zoning interconnection of the building fire alarm system indicator panel and the associated controls shall be with the unit smoke alarms, replacement of audible provided in an approved location. The visual zone appliances with combination audible/ visible indication shall lock in until the system is reset and appliances, or future extension of the existing shall not be canceled by the operation of an audible wiring from the unit smoke alarm locations to alarm-silencing switch. required locations for visible appliances. 907.6.4.2 High-rise buildings In high-rise 907.6 Installation and monitoring. A fire alarm buildings, a separate zone by floor shall be provided system shall be installed and monitored in for each of the following types of alarm-initiating accordance with Sections 907.6.1 through devices where provided: 907.6.6.2 and NFPA 72. 1. Smoke detectors. 907.6.1 Wiring. Wiring shall comply with the requirements of NFPA 70 and NFPA 72. Wireless 2. Sprinkler water flow devices. protection systems utilizing radio-frequency 3. Manual fire alarm boxes. transmitting devices shall comply with the special requirements for supervision of low-power wireless 4. Other approved types of automatic fire systems in NFPA 72. detection devices or suppression systems. 907.6.2 Power supply. The primary and secondary 907.6.5 Access. Access shall be provided to each power supply for the fire alarm system shall be fire alarm device and notification appliance for provided in accordance with NFPA 72. periodic inspection, maintenance and testing. Exception: Backup power for single-station and 907.6.6 Monitor ing. Fire alarm systems required multiple-station smoke alarms as required in by this chapter or by the SBC 201 shall be Section 907.2.11.6. monitored by an approved supervising station in accordance with NFPA 72. 907.6.3 Initiating device identification. The fire alarm system shall identify the specific initiating Exception: Monitoring by a supervising station is device address, location, device type, floor level not required for: where applicable and status including indication of 1. Single and multiple-station smoke alarms normal, alarm, trouble and supervisory status, as required by Section 907.2.11. appropriate. 2. Smoke detectors in Group I-3 occupancies.