Professional Documents
Culture Documents
Types of Loads
Types of Loads
At any time load takes constant power irrespective of voltage changes. If the voltage decreases, the
current increases thereby consuming same power and vice versa.
Eg: - Induction Motor
Vi ₌ 415V V ₌ 414V
Pi ₌ 105.3KW P ₌ 105.3*(414/415)⁰ = 105.3KW
PF ₌ 0.9 PF ₌ 0.9
Pi ₌ 117Kva P ₌ 117Kva
Qi ₌ P*tan (ɸ) = 51Kvar Q ₌ P*tan (ɸ) = 51Kvar
I ₌ P/√3*Vi*Cosɸ I ₌ P/√3*V*Cosɸ
162.9A 163.2A
So the voltage decreases, the current increases thereby consuming same power and vice versa.
Constant Current Load
Vi ₌ 415V V ₌ 414V
Pi ₌ 105.3KW P ₌ 105.3*(414/415)¹ = 105KW
PF ₌ 0.9 PF ₌ 0.9
Pi ₌ 117Kva P ₌ 116.7Kva
Qi ₌ P*tan (ɸ) = 51Kvar Q ₌ P*tan (ɸ) = 50.9Kvar
I ₌ P/√3*Vi*Cosɸ I ₌ P/√3*V*Cosɸ
162.9A 162.9A
It will maintain the constant impedance of the connected load with respective of change in square of the
voltage.
Vi ₌ 415V V ₌ 414V
Pi ₌ 105.3KW P ₌ 105.3*(414/415)² = 104.7KW
PF ₌ 0.9 PF ₌ 0.9
Pi ₌ 117Kva P ₌ 116.4Kva
Qi ₌ P*tan (ɸ) = 51Kvar Q ₌ P*tan (ɸ) = 50.7Kvar
Combination of ZIP Load (30% Constant Power load, 50% Constant Current Load, 20% Constant
Impedance Load)
Vi ₌ 415V V ₌ 414V
Pi ₌ 105.3KW P ₌ 105.3*(0.2*(V/Vi)²+0.5*(V/Vi)¹+0.3*(V/Vi)⁰) = 105KW
PF ₌ 0.9 PF ₌ 0.9
Pi ₌ 117Kva P ₌ 116.7Kva
Qi ₌ P*tan (ɸ) = 51Kvar Q ₌ P*tan (ɸ) = 50.9Kvar