Professional Documents
Culture Documents
120EE1098 - Vennela Medaboina - Merged BEE Report-Compressed
120EE1098 - Vennela Medaboina - Merged BEE Report-Compressed
APPARATUS REQUIRED:
1 Voltmeter 0-300(MI) 3
2 Ammeter 0-3A(MI) 1
3 Voltmeter 0-600(MI) 1
4 Rheostat 0-110Ω 1
THEORY:
1.Energy Meter:
It is used to calculate energy (kilowatt hour) at each instant of time. So this type of
instrument is called integrating type instrument. It is used for both household & industrial
purposes. It has two coils i.e. current coil & pressure coil. Current coil measures the
current through the circuit & pressure coil measures the voltage. And the arrangements of
the instrument can measure also the power factor. Thus this meter measure the energy
(power X time) with the help of gears arrangement.
For testing, we need two phases that is 240degrees displaced. Here R phase and B
phase are 240degrees displaced. In the arrangement given in the circuit diagram pressure
coil of energy meter is always taking voltage from R phase only and current coil of
energy meter has the provision for taking current from R phase and B phase
simultaneously or individually.
Case-1:-
When Vrn =0 and Vbn has some voltage then current coil of energy meter will take
current from B phase. So power factor angle=60degrees as shown below in the phasor
diagram.
Power factor=cos60degrees=0.5
Case-2:-
When Vbn has equal voltage with Vrn then current coil of energy meter will take current
from B phase and R phase equally. So power factor angle=30degrees as shown below in
the phasor diagram.
Power factor=cos30degrees=0.866
Case-3:-
When Vbn =0 and Vrn has some voltage then current coil of energy meter will take
current from R phase.
So power factor angle=0degrees as shown below in the phasor diagram.
Power factorcos0degrees=1
CIRCUIT DIAGRAM :
PROCEDURE:
1) Let’s begin by arranging the circuit as per the figure shown.
2) Start by keeping single-phase variac at zero volt position and switch on power supply.
4) According to Case-1, keeping the R-phase variac at zero potential, vary the B-phase
variac up to 60V, 70V and 80V respectively.
5) We need to note down all meter readings and calculate the R.P.M of the disc using a
stopwatch carefully.
6) Calculate the theoretical value of power (P1) and the practical value of power (P2)
and also find their percentage error.
9) Then again repeat from step-5 to step-7 for the next cases.
10) Now, let’s test the energy meter at 1.0 power factor and repeat from step-5 to step-7
again as mentioned.
11) Finally we need to plot a graph between Percentage Error (y-axis) vs Power factor (x-
axis) to record the conclusions.
OBSERVATION:
Below values are the recorded observations through the experiment .
SL. cos∅ V1 VRN VBN VPC I R.P.M R.P.H VPCICos∅=P1 R. P. H × 1000 Percentage
NO. (in (in (in (in (in (In watt.) 1500 error=
volt) volt) volt) volt) amp) =P2 (in watt) (P1−P2)×100
P1
1. 0.5 413 0 60 235 0.8 1.97 118.2 94 78.8 16
2. 0.5 413 0 70 234 0.88 2.21 132.7 102.96 88.49 14
3. 0.5 413 0 80 234 1.0 2.48 148.9 117 99.29 15
4. 0.866 413 60 60 235 1.32 6.03 361.8 268.63 241.2 10
5. 0.866 413 70 70 235 1.52 7.17 430.2 309.33 286.8 7
6. 0.866 413 80 80 235 1.74 8.02 481.2 354.10 320.8 9
7. 1.0 413 60 0 235 0.8 4.37 262.2 188 174.8 7
8. 1.0 413 70 0 235 0.86 5.18 310.8 202.1 207.2 2
9. 1.0 413 80 0 235 0.98 5.88 352.8 230.3 235.2 2
GRAPH:
--The End--
BEE Laboratory – Experiment No. 2
APPARATUS REQUIRED:
THEORY:
The performance of a transformer can be calculated on the basis of its
equivalent circuit which contains four main parameters:
• The equivalent resistance R01 as referred to primary( or secondary R02),
• The equivalent leakage reactance X01 as referred to primary,
• The core-loss conductance G0 and
• The magnetizing susceptance B0.
All these constants or parameters can be easily determined by two tests
i.e. open circuit test and short circuit test.
These are very economical and convenient, because they furnish the required
information without actually loading the transformer.
1. O.C. Test:-
• The purpose of O.C. test is to determine no load loss or core loss and no load I0 which
is helpful in finding X0 and R0.
• One winding of the transformer whichever is convenient but usually high voltage
winding is left open and the other is connected to its supply of normal voltage and
frequency.
• A wattmeter (W), Voltmeter (V) and ammeter (A) are connected in the low voltage
winding i.e. primary winding in the present case.
• With normal voltage applied to the primary, normal flux will be setup in the core,
hence normal iron loss will occur which are recorded by the wattmeter.
• As the primary no load current I0 is small, Cu loss is negligibly small in primary and nil
in secondary.
• Hence, the wattmeter reading represents practically the core loss under no load
condition.
2. S.C. Test:-
• For short circuit test, one winding usually the low voltage winding, is solidly short-
circuited by a thick conductor (or through an ammeter which may serve the additional
purpose of indicating rated load current).
• A low voltage (usually 5 to 10% of normal primary voltage) at rated frequency
(though for Cu losses it is not essential) is applied to the primary and is cautiously
increased till full- load current is flowing both in primary and secondary (as indicated
by the respective ammeters).
• Since, in this test, the applied voltage is a small percentage of the normal voltage, the
mutual flux ɸ produced is also a small percentage of its normal value.
• Hence, core loss is very small with the result that the wattmeter reading represents the
full load Cu loss or I2R loss for the whole transformer i.e. both primary Cu loss and
secondary Cu loss. If Vsc is the voltage required to circulate rated load current, then
Z01= Vsc/I.
A two winding transformer can be represented by means of an equivalent
circuit as shown below:
Circuit diagram :
✓ Single phase auto transformer must be kept at minimum potential point before
switch on the experiment.
PROCEDURE:
Here are the methods for both OC and SC tests.
V1 I0 Wi Im= cos ∅0 =
Wi
(in volt) (in amp) (in watt) Iw= √I02-I 2
Wi/V1I0
𝑉 w
• Wi=V1I0cos∅0
Wi
• Iw= , Im= √(I02-I 2)
𝑉 w
I0 : No-load current
• Let the total equivalent resistance of primary and secondary referred to primary
side be R01 ohms and the total equivalent leakage reactance referred to primary
side be X01 ohms.
• Wc = Isc2R01
Wi = VI0 cos∅0
IW = W/V = 0.0608 A
IM = √(I02-Iw2 ) = 0.242A
R0 = V/IW = 3782.8 Ω
X0 = V/IM = 950.41Ω
cos∅0 = 0.243
Wc = ISC2R01
= V/ISC = 1.692 Ω
CONCLUSION:
• In open circuit test the primary no load current I0 is small, Cu loss is negligibly
smallin primary and nil in secondary. Hence, the wattmeter reading represents
practicallythe core loss under no load condition.
• In short circuit test core loss is very small with the result so the wattmeter
reading represents the full load Cu loss or I2R loss for the whole transformer i.e.
both primary Cu loss and secondary Cu loss.
• By performing open and short circuit test we can find voltage regulation and
efficiency.
DISCUSSION QUESTIONS:
1. Why iron is chosen as the material for the core of the transformer? Why not
we usealuminum?
A: The soft iron core has high permeability and it provides a complete linkage
of the magnetic flux of the primary coil with the secondary coil. Soft iron are
ferromagnetic materials made of iron which can be magnetized and demagnetized
easily. This is an advantage in transformers because in transformers, we are
constantly varying magnetism of the core. This is important because without the
change of magnetism of the core, there wouldn't be any voltage induced in the
second circuit.
A: The rating is the load carrying capability of the machine. It shows the
maximum value of the voltage at which the machine is designed, and the current
consumption occurs at that voltage. The machines are always rated in watts. But
the alternator and the transformer are the only machines which are rated in volt-
amp (VA).
The transformer consumes the power regarding losses. The copper and iron are
the two type of losses occur in the transformer. The copper loss depends on the
current (ampere) flows through the windings of the transformer while the iron
loss depends on the voltage (volts). i.e., the rating of the transformer is in kVA.
3. What is the difference between Hysteresis loss & Eddy current loss?
A: Difference between the Eddy current and Hysteresis loss is that the eddy
current loss occurs because of the relative motion between the conductor and the
magnetic field whereas the hysteresis loss occurs because of the reversal of the
magnetism. Due to these eddy currents, some energy will be dissipated in the form
of heat. Hysteresis loss depends upon the volume and grade of the iron, frequency
of magnetic reversals and value of flux density.
4. What is the difference between step up & step down transformer?
A:
Out of these losses core loss is constant whereas copper loss is variable. The
reason behind core loss being constant is that hysteresis loss and eddy current
loss both are dependent on the magnetic properties of the material used in the
construction and design of the core of the transformer. So these losses are
constant and do not depend on the value of load current.
BEE Laboratory - Experiment No.3
To study load test of single phase transformer and determine its efficiency and voltage
regulation.
APPARATUS REQUIRED:
THEORY:
Efficiency of a Transformer:
Efficiency is defined as the ratio of output power to the input power of the
transformer. It varies with the power factor at different loads.
As the output power is always less than the input power due to losses in the
transformer, practically the transformer efficiency is always between 0 and 1 i.e. 0%
and 100% but it can never be 1 or 100%.
• Load test for the calculation of efficiency and voltage regulation is completely
different from finding them through OC and SC test of transformer.
• In this method secondary of the transformer is connected to the load. When
the secondary is loaded the secondary current I2 is set up.
• The magnitude and phase of I2 with respect to terminal voltage V2 depends
on the type of load.
• If the load is resistive then I2 will be in phase with V2 for inductive I2 will lag
behind V2 and for they capacitive load it will lead the voltage.
• Because of this secondary current I2 there is a drop in terminal voltage V2.
• Drop in voltage depends on the impedance of the load and pf.
• For leading pf, the voltage drop may be negative and for lagging pf it will be
always positive.
• Since the flux passing through the core is the same from no load to full load
conditions, core losses remain the same.
• But the copper losses depend on the square of the current, they vary with the
load current.
Circuit diagram
PRECAUTIONS:
PROCEDURE:
Case 1:
Efficiency = W2 X 100 = 0
W1
Voltage Regulation= V1–V2 X 100 = 0
V1
Case 2:
when load=100W
V1=230 V ; V2=229 V
I1=0.53 A ; I2=0.43 A ; W1=120 W ; W2=98 W
Efficiency = W2 X 100
W1
= (98/120) X 100 = 81.66
Case 3:
when load=200W
V1=230 V ; V2=227 V
I1=0.96 A ; I2=0.87 A ; W1=221 W ; W2=198 W
Efficiency = W2 X 100
W1
= (198/221) X 100 = 89.59
when load=1000W
V1=230 V ; V2=215 V
I1=4.24 A ; I2=4.18 A ; W1=990 W ; W2=901 W
Efficiency = W2 X 100
W1
= (901/990) X 100 = 91.01
OBSERVATION TABLE:
V1 I1 W1 V2 I2 W2 𝐄𝐟𝐟𝐢𝐜𝐢𝐞𝐧𝐜𝐲
𝐖𝟐
=
Voltage Regulation=
LOAD ×100
Sl.No. (in (in (in (in (in (in
𝐖𝟏
𝑽𝟏−𝑽𝟐
𝑿𝟏𝟎𝟎
(in watt) 𝑽𝟏
Volt) amp) watt) Volt) amp) watt)
Theoretical Graph
• The experiment was performed and seen that as load current increases, the
voltage drop in the transformer secondary winding was also increasing,
hence voltage regulation was increased up to 6.52%
• The ideal voltage regulation is 0%. It should be as low as possible for proper
operation of the electrical devices.
• When load current was increased, the efficiency of the transformer increased
up to a specific limit (92.45% in the case), after that, efficiency decreases with
an increase in load current.
• Most of the transformers have full load efficiency between 95% to 98.5% .
DISCUSSION QUESTIONS:
The voltage regulation is defined as the change in the magnitude of receiving and
sending voltage of the transformer.It determines the ability of the transformer to
provide the constant voltage for variable loads.
When the transformer is loaded with continuous supply voltage, the terminal
voltage of the transformer varies. The variation of voltage depends on the load and
its power factor.The value of the voltage regulation should always be less for the
better performance of the transformer.
When a DC voltage is applied to the primary winding of a transformer due to the low
resistance, the winding acts as a short circuit between the terminals of the DC
source, resulting in a large current flow through the winding, which leads to
overheating of the winding.
Hysteresis losses can be reduced by using material that has less area of the
hysteresis loop. Hence, high grade or silica steel can be used for designing the core
within a transformer because it has extremely less area of the hysteresis loop.
Study of power factor at different loads i.e. resistive, inductive & capacitive.
APPARATUS REQUIRED:
THEORY:
Reactive power:
Power merely absorbed and returned in load due to its reactive properties
is referred to as Reactive Power. Reactive Power is symbolized by the letter Q
and is measured in the unit of Volt-Amps- Reactive (VAR). Simply the power
consumed in reactive load called reactive power. Q = I2 X
Reactive Power (Q)= V x I sinΦ = VIsinΦ
Power Triangle:
CIRCUIT DIAGRAM:
PRECAUTIONS:
PROCEDURE:
Case – 1 : Case – 2:
Case – 3 : Case – 4 :
Case – 7 :
Passive element : R1 + C1 + C2
Observation table:
CALCULATION:
CONCLUSION:
1. How does the reactive power vary with the variation of power factor?
When power factor is equal to 0, the energy flow is entirely reactive and stored
energy in the load returns to the source on each cycle. When the power factor is 1,
all the energy supplied by the source is consumed by the load. Higher the power
factor less is the angle between voltage and current . So reactive power is inversely
proportional to power factor .
2. What is the power factor of purely resistive, inductive & capacitive load?
For inductive load , power factor will be zero(lagging) ,since current will lag voltage
by some angle ,it depends on the reactance offered by the inductor.
For capacitive load, power factor will be zero(leading), since current will lead
voltage by some angle.
We know that in pure inductive circuit, current is lagging by 90 degree from voltage
(in other words, Voltage is leading 90° from current) i.e the phase difference
between current and voltage is 90 degrees. If current and voltage are 90° out of
phase from each other the total power of the circuit would be 0
Pure capacitive load even follows the same condition. In case of pure capacitive
circuit also, the total power of the circuit would be zero (as cos 90° = 0).
4. Draw the phasor diagram for purely resistive, inductive & capacitive
load.
APPARATUS REQUIRED:
1 Voltmeter 0-150V(MI) 3
2 Voltmeter 0-75V(MI) 1
7 Capacitor 42uF 3
THEORY:
CIRCUIT DIAGRAM:
Circuit connection
Circuit Description:
Before Resonance:
The capacitive reactance(Xc) dominates the inductive reactance(XL)
i.e.,(XC > XL) and due to which the series RLC circuit behaves like a
capacitive circuit.
Beyond Resonance:
At Resonance:
Quality Factor:
The quality factor of the RLC circuit is the voltage magnification in the
circuit at resonance.
Voltage Magnification (Q) = Voltage across L or C = VL
Supply voltage VS
Q = ƒr /BW.
PRECAUTIONS:
CALCULATION:
Inductance vs Current
2.55
2.5
2.45
Current (Amp)
2.4
2.35
2.3
2.25
2.2
2.15
2.1
0 20 40 60 80 100 120 140
Inductance (mH)
2.55
Impedance vs Current
2.5
2.45
2.4
Current (amp)
2.35
2.3
2.25
2.2
2.15
2.1
23 24 25 26 27 28 29
Impedance (Ohms)
CONCLUSION:
DISCUSSION QUESTIONS:
APPARATUS REQUIRED:
THEORY:
CIRCUIT DIAGRAM:
Circuit Description:
𝑉2𝑅𝐿
Power delivered to the load resistance, 𝑃 = 𝐼2𝑅𝐿 =
(Ri+RL)2
To find the maximum power, differentiate the above expression
with respect to resistance RL and equate it to zero. Thus,
𝑑𝑃
[ = 𝑉2(𝑅𝑖+𝑅𝐿)2−2𝑅𝐿(𝑅𝑖+𝑅𝐿)𝑉2]/(𝑅𝑖+𝑅𝐿)4=0⇒𝑅𝐿=𝑅𝑖
dRL
𝑅𝐿 1
ƞ = =
𝑅𝐿+𝑅𝑖 1+𝑅𝑖/𝑅𝐿
Consider three particular cases:
PROCEDURE:
CALCULATION:
VS = 12 V and VL = 8.4 V
I = 0.332A and RL = 25.3 ohms
𝑷𝑳=𝑰𝟐𝑹𝑳
= 0.332 x 0.332 x 25.3
= 2.78 W
𝑷𝑰 = 𝑽𝑰
= 12 x 0.332
= 3.984 W
Efficiency (ƞ) = (𝑷𝑳/𝑷𝑰) x 100
= (2.78/3.98) x 100
= 69.84%
VS = 12 V and VL = 6.0 V
I = 0.549A and RL = 10.9 ohms
𝑷𝑳=𝑰𝟐𝑹𝑳
= 0.549 x 0.549 x 10.9
= 3.28 W
𝑷𝑰 = 𝑽𝑰
=12 x 0.549
= 6.58 W
Efficiency (ƞ) = (𝑷𝑳/𝑷𝑰) x 100
= (3.28/6.58) x 100
= 49.84%
VS = 12 V and VL = 5.1 V
I = 0.630 A and RL = 8.09 ohms
𝑷𝑳=𝑰𝟐𝑹𝑳
= 0.630 x 0.630 x 8.09
= 3.21 W
𝑷𝑰 = 𝑽𝑰
=12 x 0.630
= 7.56 W
Efficiency (ƞ) = (𝑷𝑳/𝑷𝑰) x 100
= (3.21/7.56) x 100
= 42.46%
GRAPH:
3.5
2.5
Load Power (PL)
1.5 Series1
0.5
0
0 5 10 15 20 25 30
Load Resistance(RL)
2. Plot a graph between Load resistance & Efficiency.
80
70
60
Efficiency
50
40
30 Series1
20
10
0
0 10 20 30
DISCUSSION QUESTIONS:
Ans. Yes it is applicable to both AC and DC. The limitation is that the
load should be variable load.
Ans.
If the resistance of the load is made larger than the resistance of the
source then efficiency is higher, since a higher percentage of the source
power is transferred to the load, but the magnitude of the load power is
lower since the total circuit resistance increases.
If the load resistance is smaller than the source resistance, then most of
the power ends up being dissipated in the source, and although the total
power dissipated is higher, due to a lower total resistance, it turns out
that the amount dissipated in the load is reduced.
APPARATUS REQUIRED:
1. Wattmeter 500W,Digital 2
2. Voltmeter 0-300V,Digital 1
3. Ammeter 0-5A,MI 3
4. Rheostat 38Ω/5A 3
THEORY:
Phasor diagram
CIRCUIT DIAGRAM:
Circuit Description:
PRECAUTIONS:
PROCEDURE:
1. 64 81 1 1 1 50 47 48
2. 89 85 1.4 1.14 1.12 40 52 53
3. 103 90 1.5 1.4 1.12 43 47 54
4. 103 110 1.59 1.44 1.4 45 48 50
5. 103 110 1.6 1.44 1.4 44 49 50
6. 109 114 1.66 1.6 1.42 45 46 51
7. 109 127 1.72 1.64 1.6 47 47 48
8. 115 127 1.8 1.66 1.64 45 48 49
9. 121 131 1.85 1.8 1.64 46 46 50
10. 120 142 1.90 1.82 1.8 47 46 47
CALCULATION:
1 145 50 47 48 145 0
2 174 56 59.28 59.36 174.64 0.3
3 193 64.5 65.8 60.48 190.78 1.16
4 213 71.55 69.12 70 210.67 1.10
5 213 70.4 70.56 70 210.96 0.96
6 223 74.7 73.6 72.42 220.72 1.03
7 236 80.84 77.08 76.8 234.72 0.54
8 242 81 79.68 80.36 241.04 0.39
9 252 85.1 82.8 82 249.9 0.84
10 262 89.3 83.72 84.6 237.62 1.7
CONCLUSION:
DISCUSSION QUESTIONS:
A. A balanced load is a load that draws the same current from each
phase of the 3-phase system. In this system each line will produce
equal voltage magnitudes at phase angles equally spaced from each
other resulting in less power loss.
2. Explain how you will find the multiplying factor of the watt meter.
A. For Wattmeters:
Step 1: Note the voltage range.
Step 2: Note the current range.
Step3: The Multiplication Factor (MF) is:
MF = (voltage range × current range x power factor)/(range of the
wattmeter scale)
3. Verify theoretically how the two wattmeter method gives the power
measurement under both balanced and unbalanced condition.
APPARATUS REQUIRED:
THEORY:
The curve which gives the relation between field current (If) and the
generated voltage (Eg) in the armature on no load is called magnetic or
open circuit characteristic of a DC generator. The plot of this curve is
practically same for all types of generators, whether they are separately
excited or self-excited. This curve is also known as no load saturation
characteristic curve of DC generator.
Uses of OCC
Critical resistance
The maximum resistance of the field circuit above which no voltage build
up is possible is called the critical resistance.
Here field circuit resistance
Rf=Rsh+Rf,G
According to Ohms law
Rf = Eo/If
CIRCUIT DIAGRAM:
Circuit Description:
PROCEDURE:
Run I: -
Run II:
1 3000 220
2 2910 213
3 2776 202
4 2698 197
5 2612 190
6 2570 188
7 2518 184
8 2450 179
9 2400 176
GRAPHS:
(i)The curve of induced voltage versus field current for increasing and
decreasing excitation.
200
150
Series1
100
Series2
50
0
0 50 100 150 200
Field current(mA)
250
Induced voltage vs speed
200
Generated EMF(volts)
150
100
Series1
50
0
2200 2400 2600 2800 3000 3200
Speed of Generator(RPM)
CONCLUSION:
DISCUSSION QUESTIONS:
APPARATUS REQUIRED:
THEORY:
𝜙𝑍𝑁𝑃
But, Eb = = K𝜙𝑁.
60A
(𝑉−𝐼𝑎𝑅𝑎)
i.e. N = K
𝜙
It shows that:-
CIRCUIT DIAGRAM:
Circuit arrangement
PRECAUTIONS:
PROCEDURE:
• Run the motor as before and bring it to the rated speed at no load.
• Change the field resistance Rf in steps and note the speed N and
the field current If in each case . Keep the voltage across the
armature constant. Take reading for decreasing and increasing
value of field currents.
Observation table:
Case A: - Plot a graph between speed along y-axis and voltage across
armature along x-axis.
3000
2950
N in rpm
2900 Series1
2850
2800
185 190 195 200 205 210
Va in volts
Case B: - Plot a graph between speed along y –axis and field current If
along x-axis.
3100
3080
Series1
3060
3040
3020
3000
150 160 170 180 190
If in mA
CONCLUSION:
DISCUSSION QUESTIONS:
A. ADVANTAGES
Armature controlled DC motors:
• Constant field current and torque: With the armature control method,
the field current and torque levels remain constant throughout the
application. Regardless of the speed of the motor, you can rely on these
factors.
• Fast and simple speed variation: Armature controlled DC motors are
known for their exceptional speed control, which allows operators to vary
the speed as necessary in both directions.
DC shunt motor