SIRIM QAS International Sdn. Bhd.

(410334-X)
No.1, Persiaran Dato' Menteri, P.O.BOX 7035, Section 2,
40700 Shah Alam, Selangor Darul Ehsan, Malaysia
Tel: 03-55446386
Fax: 03-55446381
www.sirim-qas.com.my

TEST REPORT
REPORT NO : 2018MA0771 PAGE : 1 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or
forms (including but not limited to advertising purposes) without written approval from the Managing Director, SIRIM QAS International
Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.

THIS TEST REPORT IS ISSUED IN SECURED PDF SOFTCOPY

Applicant : ITHAD ENGINEERING SDN BHD


No.37, Jalan Taming 7,
Taman Taming Jaya, Balakong,
43300 Seri kembangan,
Selangor, Malaysia.
Manufacturer : ITHAD ENGINEERING SDN BHD
No.37, Jalan Taming 7,
Taman Taming Jaya, Balakong,
43300 Seri kembangan,
Selangor, Malaysia.
Product : 19" DATA CENTRE SERVER RACK
Reference Standard / : MANUFACTURER'S SPECIFICATION
Method of Test - Load Test
Description of sample / : Brand: Primestar
Description of Test Model: 42U Server Rack
Specimen Overall Dimension: 600(W)X1000(D)X2000(H) - mm
Sample Quantity: 1 unit
Date Received of : 04 September 2018
Complete Application
Job No. : J20181390652
Description of Test : The test result of the submitted test sample is described on page 3&4 of
Results / Overall Test this test report.
Result
Issued Date : 27 September 2018

Approved Signatories;

...................................................... ......................................................
(MOHD HAFIZOL BIN SHAARI) (MOHD FAIZAR BIN MUSTAFA)
Testing Executive Head
Mechanical & Automotive Section
Testing Services Department
REPORT NO. : 2018MA0771 PAGE: 2 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please
refer the last page for Conditions Relating to the Use of Test Report.

TEST INFORMATION
19” DATA CENTRE SERVER RACK

Test Item : Load Test

Test Description : 1. Safe working load (SWL): 1500 kg


2. Safety factor (SF): 1
3. Total load: 1500 kg
4. Load for each tray: 150kg/tray
5. Test duration: 24 hours
6. Record the dimension between tray:
i. Before test
ii. Immediately after full test load is applied (0 hours)
iii. At 3 hours after load applied
iv. At end of the full test load period (24 hours)
v. At 1 hour after relaxation period (after load remove from
tray)

Test Requirement : Record the deflection at each period of test and make the visual
observation on each tray and any relative part of racking systems

Figure 1: 19” Data Centre Server Rack


REPORT NO. : 2018MA0771 PAGE: 3 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please
refer the last page for Conditions Relating to the Use of Test Report.

TEST RESULT
19” DATA CENTRE SERVER RACK

Dimension (mm) Deflection


Orientation After (Before and after load)
Before 0 hours 3 hours 24 hours
Relaxation mm %
L1-1 196 195 195 194 196 2 1.02
L1-2 155 154 154 153 155 2 1.29
L1-3 196 195 195 194 195 2 1.02
L1-4 152 151 151 150 151 2 1.32
L2-1 147 146 146 146 147 1 0.68
L2-2 147 146 146 145 147 2 1.36
L2-3 148 147 147 146 147 2 1.35
L2-4 148 147 147 146 148 2 1.35
L3-1 147 146 146 145 147 2 1.36
L3-2 147 146 146 145 147 2 1.36
L3-3 147 146 146 145 147 2 1.36
L3-4 148 147 147 146 147 2 1.35
L4-1 148 147 147 146 148 2 1.35
L4-2 146 145 145 144 146 2 1.37
L4-3 147 146 146 145 147 2 1.36
L4-4 147 146 146 145 147 2 1.36
L5-1 147 146 146 145 147 2 1.36
L5-2 147 146 146 145 146 2 1.36
L5-3 149 148 148 147 148 2 1.34
L5-4 148 147 147 145 148 3 2.03
L6-1 192 191 191 190 191 2 1.04
L6-2 192 191 191 190 192 2 1.04
L6-3 192 191 191 191 192 1 0.52
L6-4 192 191 191 190 192 2 1.04
L7-1 148 147 147 146 148 2 1.35
L7-2 147 146 146 145 147 2 1.36
L7-3 147 145 145 144 147 3 2.04
L7-4 147 146 146 145 147 2 1.36
L8-1 147 146 146 145 147 2 1.36
L8-2 147 146 146 145 147 2 1.36
L8-3 148 147 147 146 148 2 1.35
L8-4 147 146 146 145 147 2 1.36
L9-1 148 147 147 146 148 2 1.35
L9-2 147 146 146 146 147 1 0.68
L9-3 149 148 148 147 149 2 1.34
L9-4 148 147 147 147 148 1 0.68
L10-1 147 146 146 145 147 2 1.36
L10-2 147 146 146 145 147 2 1.36
L10-3 149 148 148 147 148 2 1.34
L10-4 147 146 146 145 137 2 1.36
REPORT NO. : 2018MA0771 PAGE: 4 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please
refer the last page for Conditions Relating to the Use of Test Report.

TEST RESULT
19” DATA CENTRE SERVER RACK

Maximum Deflection (%) 2.04 L7-3

Minimum Deflection (%) 0.52 L6-3

Average Deflection (%) 1.28 -

Note: Please refer Appendix I for drawing orientation of dimension measurement and appendix II for test
pictures.

Overall Observation

Upon the completion of the load test, the product (19” Data Centre Server Rack) was found in
satisfactory condition. No physical damage was observed on racking systems part assembly such as
tray, frame and mounting during or after the loading test. All critical dimensions and parts were remained
intact after test was performed.
REPORT NO. : 2018MA0771 PAGE: 5 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please
refer the last page for Conditions Relating to the Use of Test Report.

APPENDIX I
DRAWING ORIENTATION OF DIMENSION MEASUREMENT

4 3 2

1
L10

L9

L8

L7

L6

L5

L4

L3

L2

L1

Figure 2: Drawing orientation of dimension measurement


REPORT NO. : 2018MA0771 PAGE: 6 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please
refer the last page for Conditions Relating to the Use of Test Report.

APPENDIX II
PICTURES OF THE LOAD TEST SETUP

Figure 3-5: Load Test setup