58-404 Branch circuits for other utilization equipment 1) Separate branch circuits shall supply utilization

equipment not identified in Rules 58-400 and 58-402, however used in conjunction with equipment
identified in Rule 58-000. 2) The overcurrent devices protecting the branch circuits shall be located in
the machinery room or control room or machinery space or control space. Regenerative power 58-500
Regenerative power For passenger ropeways or passenger conveyors or material ropeways that
regenerate power back into a power source that is unable to absorb the regenerative power under
overhauling load or braking conditions, means shall be provided to absorb this power. Δ Grounding of
towers and stations 58-600 Grounding of towers and stations Each metal tower and metal station
structure of passenger ropeways, passenger conveyors, and material ropeways shall be grounded by
means of conductors installed in accordance with Rules 58-602 to 58-610. 58-602 Material for
conductors Conductors shall be not less than No. 4 AWG copper. 58-604 Support for conductors
Conductors shall be securely fastened in place and shall be permitted to be directly attached to the
supporting surface without the use of insulating supports. 58-606 Location and mechanical protection of
conductors Conductors shall be protected from corrosion and damage a) by location; or b) mechanically.
58-608 Grounding electrodes (see Appendix B) Conductors shall be connected to grounding electrodes
as specified in Section 10