11kV 630A MV Switchgear Technical Specifications:

11kV, 630A, MV Switchgear (Typical):


1 – Floor standing cubicle, bottom entry control cables access, approximately
2445(H) mm x 650(W) mm x 1400(D) mm.
Circuit breaker, main bus and transformers:
1 – ABB VD4, 630A, 25 kA at 12kV, with necessary auxiliary contacts
Spring charging motor- 110 VDC
Shunt opening release- 110 VDC
Shunt closing release- 110 VDC
Truck blocking magnet
Operation counter
Auxiliary contacts (5NO+5NC)
Truck position signalling contacts
Operating mechanism blocking magnet
Additional auxiliary contacts (3NO+2NC)
Operating mechanism springs status contact

Three phase directional overcurrent protection


Three phase overvoltage, under voltage protection
Residual over voltage protection
Reverse power protection
Over/under frequency protection
Earth fault protection
Three phase thermal overload protection
Non directional earth fault protection
Negative sequence current protection

1 – Main Bus Bar rated at 630A


1 – Earth Switch 12 kV, 630A, 25 kA/3s
1 – ABB Relay (REF615- Feeder Management Relay)
3 – CT (As Required)
3 – PT (As Required)
1 – Multifunction Meter
3 – Ampere Meter
1 – Voltmeter and Selector Switch
1 – LRM Voltage Indicator
3 – Capacitive Insulator
3 – Surge Arrester 12 kV, 10 kA
1 – ES Position Indicator
1 – CB Discrepancy Switch
1 – 100W Heater & Thermostat
Controls / relay / metering compartment:
1 – Lot of VCB auxiliary contacts
1 – VCB On and OFF control
1 – Set of DIN rail auxiliary relays, MCBs, nameplates, terminal boards