Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

Date 13/10/2022

zapateria

Created with DIALux


zapateria

Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


1096647 lm 21452.0 W 51.1 lm/W 1096647 lm 22490.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

173 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

2
zapateria

Product data sheet

SYLVANIA - Sylproof Superia Polycarbonate diffuser T8 2x58W Electronic Emergency (1 Hours)

Article No. 0056170

P 124.0 W

PEmergency lighting 130.0 W

ΦLamp 10400 lm

ΦLuminaire 6339 lm

ΦEmergency lighting 6339 lm Polar LDC

η 60.96 %

ELF 100 %

- Moisture and Dust Protection to IP65


- Polycarbonate housing with polycarbonate diffuser with internal
prism system
- Surrounding seal made from polyurethane
- New 'push push' stainless steel clips for convenient access during
maintenance
- T8 versions, high frequency electronic or magnetic ballast or T5
energy efficient electronic ballast
- Newly developed interchangeable gear tray holding clips
- Emernency with 1 hour battery

Polar LDC

3
zapateria

Product data sheet

SYLVANIA - Sylproof Superia Polycarbonate diffuser T8 2x58W Electronic Emergency (1 Hours)

Luminous emittance 1

Fitting 2x 58W T8

P 124.0 W

ΦLamp 10400 lm

ΦLuminaire 6339 lm

η 60.96 %

Luminous efficacy 51.1 lm/W

CCT 3000 K

CRI 83

Polar LDC

UGR diagram (SHR: 0.25)

4
zapateria

Product data sheet

SYLVANIA - Sylproof Superia Polycarbonate diffuser T8 2x58W Electronic Emergency (1 Hours)

Luminous emittance 2

Fitting 2x 58W T8

PEmergency lighting 130.0 W

ΦEmergency lighting 6339 lm

CCT 3000 K

CRI 83

ELF 100 %

Polar LDC

UGR diagram (SHR: 0.25)

5
zapateria

Product data sheet

SYLVANIA - Sylproof Superia Polycarbonate diffuser T8 2x58W Electronic Emergency (1 Hours)

γ C0° C90° C0°- C360°

0°-180° 1472.12 1375.92 1472.12

60°-90° 1116.96 530.92 1116.96

Glare valuation table [cd]

6
zapateria

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area: 31.64 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 7
zapateria

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 124 lx ≥ 100 lx WP1

g1 0.38 - - WP1

Consumption values Consumption 240 kWh/a max. 1150 kWh/a

Room Lighting power density 3.92 W/m² - -

3.16 W/m²/100 lx - -

Utilisation profile: Places of public assembly - General areas, Entrance halls

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

8
zapateria

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


6339 lm 124.0 W 51.1 lm/W 6339 lm 130.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

9
zapateria

Building 1 · Storey 1 · Room 1 (Light scene 1)


Working plane (Room 1)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 1) 124 lx 46.8 lx 305 lx 0.38 0.15 WP1


Perpendicular illuminance (adaptive) (≥ 100 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas, Entrance halls

10
zapateria

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Ground area: 179.12 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.800 m | Mounting height: 2.800 m 11
zapateria

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 678 lx ≥ 500 lx WP2

g1 0.34 - - WP2

Consumption values Consumption 10250 kWh/a max. 6300 kWh/a

Room Lighting power density 20.77 W/m² - -

3.06 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

12
zapateria

Building 1 · Storey 1 · Room 2


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


190170 lm 3720.0 W 51.1 lm/W 190170 lm 3900.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

13
zapateria

Building 1 · Storey 1 · Room 2 (Light scene 1)


Working plane (Room 2)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 2) 678 lx 231 lx 1205 lx 0.34 0.19 WP2


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

14
zapateria

Building 1 · Storey 1 · Room 4 (Light scene 1)


Summary

Ground area: 40.45 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 15
zapateria

Building 1 · Storey 1 · Room 4 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 369 lx ≥ 200 lx WP4

g1 0.55 - - WP4

Consumption values Consumption 410 kWh/a max. 1450 kWh/a

Room Lighting power density 12.26 W/m² - -

3.32 W/m²/100 lx - -

Utilisation profile: General areas inside buildings - Rest, sanitation and first aid rooms, Cloakrooms, washrooms, bathrooms, toilets

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

16
zapateria

Building 1 · Storey 1 · Room 4


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


25356 lm 496.0 W 51.1 lm/W 25356 lm 520.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

17
zapateria

Building 1 · Storey 1 · Room 4 (Light scene 1)


Working plane (Room 4)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 4) 369 lx 204 lx 532 lx 0.55 0.38 WP4


Perpendicular illuminance (adaptive) (≥ 200 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Rest, sanitation and first aid rooms, Cloakrooms, washrooms, bathrooms, toilets

18
zapateria

Building 1 · Storey 1 · Room 5 (Light scene 1)


Summary

Ground area: 87.91 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 19
zapateria

Building 1 · Storey 1 · Room 5 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 533 lx ≥ 500 lx WP5

g1 0.52 - - WP5

Consumption values Consumption 4100 kWh/a max. 3100 kWh/a

Room Lighting power density 16.93 W/m² - -

3.17 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

12 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

20
zapateria

Building 1 · Storey 1 · Room 5


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


76068 lm 1488.0 W 51.1 lm/W 76068 lm 1560.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

12 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

21
zapateria

Building 1 · Storey 1 · Room 5 (Light scene 1)


Working plane (Room 5)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 5) 533 lx 276 lx 672 lx 0.52 0.41 WP5


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

22
zapateria

Building 1 · Storey 1 · Room 6 (Light scene 1)


Summary

Ground area: 296.58 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.800 m | Mounting height: 2.800 m 23
zapateria

Building 1 · Storey 1 · Room 6 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 628 lx ≥ 500 lx WP6

g1 0.22 - - WP6

Consumption values Consumption 15350 kWh/a max. 10400 kWh/a

Room Lighting power density 18.81 W/m² - -

3.00 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

45 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

24
zapateria

Building 1 · Storey 1 · Room 6


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


285255 lm 5580.0 W 51.1 lm/W 285255 lm 5850.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

45 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

25
zapateria

Building 1 · Storey 1 · Room 6 (Light scene 1)


Working plane (Room 6)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 6) 628 lx 136 lx 1070 lx 0.22 0.13 WP6


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

26
zapateria

Building 1 · Storey 1 · Room 7 (Light scene 1)


Summary

Ground area: 84.60 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 27
zapateria

Building 1 · Storey 1 · Room 7 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 698 lx ≥ 500 lx WP7

g1 0.62 - - WP7

Consumption values Consumption 5100 kWh/a max. 3000 kWh/a

Room Lighting power density 21.99 W/m² - -

3.15 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

15 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

28
zapateria

Building 1 · Storey 1 · Room 7


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


95085 lm 1860.0 W 51.1 lm/W 95085 lm 1950.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

15 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

29
zapateria

Building 1 · Storey 1 · Room 7 (Light scene 1)


Working plane (Room 7)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 7) 698 lx 436 lx 1003 lx 0.62 0.43 WP7


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

30
zapateria

Building 1 · Storey 1 · Room 8 (Light scene 1)


Summary

Ground area: 518.27 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.800 m | Mounting height: 2.800 m 31
zapateria

Building 1 · Storey 1 · Room 8 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 459 lx ≥ 500 lx WP8

g1 0.22 - - WP8

Lighting power density 12.92 W/m² - -

2.81 W/m²/100 lx - -

Consumption values Consumption 18400 kWh/a max. 18150 kWh/a

Room Lighting power density 12.92 W/m² - -

2.81 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

54 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

32
zapateria

Building 1 · Storey 1 · Room 8


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


342306 lm 6696.0 W 51.1 lm/W 342306 lm 7020.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

54 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

33
zapateria

Building 1 · Storey 1 · Room 8 (Light scene 1)


Working plane (Room 8)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 8) 459 lx 102 lx 700 lx 0.22 0.15 WP8


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

34
zapateria

Building 1 · Storey 1 · Room 9 (Light scene 1)


Summary

Ground area: 51.45 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 35
zapateria

Building 1 · Storey 1 · Room 9 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 618 lx ≥ 500 lx WP9

g1 0.58 - - WP9

Consumption values Consumption 3400 kWh/a max. 1850 kWh/a

Room Lighting power density 24.10 W/m² - -

3.90 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

10 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

36
zapateria

Building 1 · Storey 1 · Room 9


Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


63390 lm 1240.0 W 51.1 lm/W 63390 lm 1300.0 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

10 SYLVANIA 0056170 Sylproof Superia Polycarbonate diffuser 124.0 W 6339 lm 51.1 lm/W
T8 2x58W Electronic Emergency (1
Hours) 130.0 W 6339 lm (100 %) -

37
zapateria

Building 1 · Storey 1 · Room 9 (Light scene 1)


Working plane (Room 9)

Properties Ē Emin Emax g1 g2 Index


(Target)

Working plane (Room 9) 618 lx 356 lx 788 lx 0.58 0.45 WP9


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

38
zapateria

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas- discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13.3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

39
zapateria

Glossary

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be
determined anywhere in space (inside or outside). The illuminance is not a product
feature because it is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

40
zapateria

Glossary

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/m² year

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It
is the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

41
zapateria

Glossary

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

42
zapateria

Glossary

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.

43

You might also like