12.133
Leakage Due to
Internal Pressure
(Air Pressure
Method)
12.13.4
Leakage
Dueto
Infiltration
12.13.5
Leakage Due
to Internal
Pressure (Water
Pressure Method)
The Contractor shall plug all pipe outlets with suitable plugs, and
brace each plug securely where needed. The input air supply shall
be regulated by a pressure regulating valve so as to not exceed 5
psi gage pressure. The air test equipment is to be approved by
the Engineer prior to testing. Air shall be added slowly to the
pipe until the internal air pressure is raised to 4 psi gage
pressure, at which time the flow of air into the pipe shall be shut
off, and the input supply hose disconnected completely from the
testing equipment. After the internal pressure of 4 psi is obtained,
two (2) minutes shall be allowed for the air temperature to
stabilize within the pipe. Air may be needed only to maintain a
pressure of 4 psi. When the intemal pressure decreases to 3.5 psi,
timing shall start and the seconds counted until the pressure has
decreased to 2.5 psi. Minimum permissible pressure holding time
for sewer mains, with or without laterals, are listed in the N.C.P.I.
Air Test Tables, as published in the latest National Clay Pipe
Institute “Low Pressure Air Test for Sanitary Sewer (Procedures
and Tables)”,
If, in the construction of a section of sewer of any size, excessive
groundwater is encountered, a test for infiltration shall be
conducted if ordered by the Engineer. ‘The upper end of the sewer
shall be closed sufficiently to prevent the entrance of water, and
pumping of water shall be discontinued for at least 3 days prior to
‘the test for infiltration. The infiltration shall not exceeded 415
imperial gallons per inch diameter per mile per day of that portion
of mainline sewer in ground-water being tested, and does not
include the length of house laterals entering that section. This test
may be in lieu of , or in addition to the other tests, as determined
by the Engineer.
It would be of the advantage to the Employer in some cases to
have certain sections of sewer pipes tested by water pressure in
lieu of the Air Pressure Method. If requested by the Engineer, the
test shall be performed as follows
The pipeline to be tested shall be plugged at all pipe outlets with
suitable plugs, and each plug securely braced where needed. The
ine shall be filled with water, and sufficient time will be
permitted to elapse between the filling and testing of the line to
permit absorption of water by the pipe walls. A hose shall
connect the plug with a stand pipe (12 inches diameter
approximately). ‘The stand pipe will be filled to a level not less
than 4 feet above the level of the sewer at the upper end and
positioned to permit the addition of one additional gallon of water.
One gallon of water shall be added and the time measured for the
water level to return to the marked measured . The time so
measured shall not be less than that computed by the following
formula which provides for minimum allowable leakage of 415
imperial gallons per inch diameter per mile per day.
Minimum Time (minutes) 15,206
Diameter (inches) x Test Length (feed)
12.14