This is to certify that the report entitled structural analysis and design of G+4 building of a gen-
uine work done and submitted by the students of fifth year Civil Engineering, at RIFT VALLEY
UNIVERSITY.
NAME ID
Date_________________
Page | iii
FINAL YEAR PROJECT 2020
Acknowledgment
We have to thank the almighty God for the endless blessings and being with us in every step we
made to complete this project.
Next we would like to express our deepest gratitude to AMIT department of civil engineering for
arranging this academic program. And we owe a great debt to our advisor Mr. AZMACH
LOLE for his valuable guidance and appreciation.
Finally we would like to acknowledge all individuals who invested their time, their effort and
continuous encouragement throughout the time.
Group members
Page | iv
FINAL YEAR PROJECT 2020
Executive summary
In any aspect, knowledge of construction engineering should be supported with practical experi-
ence. This course strengthens student’s knowledge regarding structural design and analysis of
buildings.
The content of the report is divided into six chapters. The first chapter is introduction part. It
gives introduction to construction, design data and materials and loadings. The second chapter
focuses on analysis and design of roof. The project holds both truss type and slab type roof. De-
termination of EGA sheet, analysis and design of purlin, truss design are included.
On the third chapter of the project report, it explains about slab design and analysis. This in-
cludes moment distribution and adjustment for each panel. Next, the fourth chapter describes
frame analysis. On this topic, weight of each load, center of mass, base shear forces are calcu-
lated and distributed on each floor.
The fifth chapter describes beam and column design. This design is held by using ETABS out-
put. And finally on chapter six foundation designs takes place. In each parts of the chapter, we
tried our best to make every single point clear. And finally, general conclusions and recommen-
dation are described. This report includes some figures and tables from EBCS.
Page | v
FINAL YEAR PROJECT 2020
Table of Contents
Acknowledgment........................................................................................................................................iii
Executive summary.....................................................................................................................................iv
Table of Figures.........................................................................................................................................viii
List of Tables...............................................................................................................................................ix
CHAPTER ONE..............................................................................................................................................1
1. INTRODUCTION.......................................................................................................................................2
1.1 Design data and material properties.................................................................................................2
1.2 Design method and Design aids.........................................................................................................4
1.3 Loading..............................................................................................................................................4
CHAPTER TWO.............................................................................................................................................6
2. ANALYSIS AND DESIGN OF ROOF.........................................................................................................7
2.1 Truss type Roof..................................................................................................................................7
2.1.1 Wind Load...................................................................................................................................7
2.1.2 Design of EGA sheet..................................................................................................................14
2.1.3 Analysis and design of purlin....................................................................................................19
2.1.4 Analysis and design of truss......................................................................................................27
2.2 Slab type roof..................................................................................................................................32
CHAPTER THREE........................................................................................................................................38
3. SLAB ANALYSIS AND DESIGN.................................................................................................................39
3.1 Requirements for effective depth....................................................................................................39
3.2 First floor Slab Design......................................................................................................................39
3.2.1 Load determination..................................................................................................................42
3.2.2 Moment Calculation.................................................................................................................47
3.2.3 Determination of moment distribution....................................................................................50
3.2.4 Moment adjustment for support and field using moment distribution method......................63
3.2.5 Field moment adjustment........................................................................................................67
3.2.6 Reinforcement work.................................................................................................................74
3.2.7 Load transfer to beam..............................................................................................................81
3.3 Second floor slab design..................................................................................................................86
Page | vi
FINAL YEAR PROJECT 2020
3.3.1 Effective depth of the panels for 2nd floor...............................................................................86
3.3.2 Load determination of second floor.........................................................................................87
3.3.3 Determination of moment for 2nd Floor Slab...........................................................................88
3.3.4 Moment adjustment for 2nd floor slab....................................................................................92
3.3.5 Adjustment of field moment for 2nd floor...............................................................................95
3.3.6 Reinforcement work.................................................................................................................96
3.3.7 Load transfer to beam for 2nd floor.........................................................................................98
3.4 Third floor slab design...................................................................................................................102
3.4.1 Effective depth of the panels for 3rd floor..............................................................................102
3.4.2 Design load of the panels for 3rd floor...................................................................................103
3.4.3 Determination of moment for 3rd floor.................................................................................104
3.4.4 Moment adjustment for 3rd floor..........................................................................................107
3.4.5 Reinforcement work...............................................................................................................111
3.4.6 Load transfer to beam............................................................................................................113
3.5 Fourth floor slab design.................................................................................................................115
3.5.1 Effective depth of the panels..................................................................................................115
3.5.2 Design load of the panels........................................................................................................116
3.5.3 Determination of Moment......................................................................................................117
3.5.4 Moment adjustment for 4th floor..........................................................................................121
3.5.5 Adjustment of field moment for 4thfloor...............................................................................124
3.5.6 Reinforcement work...............................................................................................................125
3.5.7 Load transfer to beam............................................................................................................127
3.6 Roof slab........................................................................................................................................131
3.6.1 Determination of moment for Roof Slab................................................................................131
3.6.2 Moment adjustment for Roof slab..........................................................................................132
3.6.3 Adjustment of field moment for roof slab..............................................................................132
3.6.4 Reinforcement work...............................................................................................................133
3.6.5 Load transfer to beam............................................................................................................134
3.6 Stair Analysis and Design...............................................................................................................135
3.6.1 Loading...................................................................................................................................137
3.6.2 Design Loads...........................................................................................................................139
Page | vii
FINAL YEAR PROJECT 2020
3.6.4 Loading For sec B-B.................................................................................................................146
3.6.5 Design Loads for sec B-B.........................................................................................................148
CHAPTER FOUR........................................................................................................................................160
4. FRAME ANALYSIS.................................................................................................................................161
4.1 Introduction...................................................................................................................................161
4.2 Mass center calculation.................................................................................................................162
4.2.1 Weight of ground floor...........................................................................................................163
4.2.2 Weight of first floor................................................................................................................174
4.3.3 Weight second floor...............................................................................................................184
4.3.4 Weight of 3rd floor.................................................................................................................194
4.3.6 Weight of roof........................................................................................................................213
CHAPTER FIVE..........................................................................................................................................220
5.1 BEAM DESIGN................................................................................................................................221
5.2 COLUMN DESIGN...........................................................................................................................237
5.2.1 Check for Sway Mode.................................................................................................................237
CHAPTER SIX............................................................................................................................................264
6.1 Introduction...................................................................................................................................265
6.2 Structural Design of Isolated Footing.............................................................................................265
6.2.1 Design of Group 1 Footing......................................................................................................267
6.2.2 Design of Group 5 footings.....................................................................................................274
6.2.3 REINFORCEMENT....................................................................................................................280
Conclusion...............................................................................................................................................282
Recommendation....................................................................................................................................283
REFERENCE..............................................................................................................................................283
Appendix.................................................................................................................................................284
Page | viii
FINAL YEAR PROJECT 2020
Table of Figures
Figure 2. 1Elevation of Mono pitch roof at 180o...........................................................................11
Figure 2. 2 Dead load on truss.......................................................................................................30
Figure 2. 3Live load on truss.........................................................................................................31
Figure 2. 4 Horizontal component Wind load...............................................................................31
Figure 2. 5 Vertical component wind load....................................................................................32
Figure 2. 6Roof zone.....................................................................................................................35
Figure 2. 7Roof slab Detail............................................................................................................37
List of Tables
Page | ix
FINAL YEAR PROJECT 2020
Table 1. 1 load combinations...........................................................................................................5
Page | xi
FINAL YEAR PROJECT 2020
Page | xii
CHAPTER ONE
INTRODUCTION
FINAL YEAR PROJECT 2020
1. INTRODUCTION
Construction of a reliable building requires numerous techniques and in depth knowhow of Civil
Engineering. The objective of this project is to be able to make the structural design of a building
based on what we have studied in the past academic years. This paper consists of structural anal-
ysis and design of building of hospital which is G +4 reinforced concrete building located in
ADAMA with site altitude of 1712m.
The structural design of this building involves design of slab type and truss type roof, stairs and
landings, beams, columns, floor slabs, foundation, and analysis of frames.
Concrete
Class I workmanship and ordinary loading condition is used.
Sub structure
Concrete grade C-25 Class I
Partial safety factor, γC
γC = 1.5 (Ordinary loading) [EBCS – 2, 1995 table 3.1]
Characteristic strength [compression], fck
fck = 0.8*25 = 20Mpa
0.8∗f ck
fcd = γC
= 11.33Mpa
Characteristic [Tension]
fctk = 0.21* fck2/3
=0.21*202/3
=1.55MPa
fctd = 0.21* fck2/3/1.5
= (0.21*202/3)/1.5
= 1.0315MPa
Page | 2
FINAL YEAR PROJECT 2020
From EBCS – 2, 1995 table 2.4 & 2.5 Ecm = 29Gpa
Super structure
fctk = 1.55Mpa
Ecm = 29Gpa
f ctk 1.55
fctd = γ C = 1.5 =1.03 Mpa
Reinforcement steel
fyk =300Mpa
γs = 1.15Mpa
f yk 300
fctd = γ s = 1.15 =260.87Mpa
Design load
Design load
Fd=ᵧ*fk
Where: - Fk= Characteristic load
ᵧ= Partial safety factor for loads
1.6 For live load …………. EBCS – 2, 1995 Table 3.3
Page | 3
FINAL YEAR PROJECT 2020
1.3 For dead load
1.3 Loading
Since the sit e is located in ADAMA, according to EBCS-8/95, in addition to vertical loading
earth quake loading was considered. The major loading considered are:
Vertical loading: Dead load (DL) – (self - weight, wall load and finishing load roof load-
ing)
Live load:
Lateral loading: Earth quake load in X &Y direction
Wind load
In general the total loadings make up different combinations which are listed below.
Page | 4
FINAL YEAR PROJECT 2020
Page | 5
FINAL YEAR PROJECT 2020
CHAPTER TWO
ANALYSIS AND DESIGN OF ROOF
Page | 6
FINAL YEAR PROJECT 2020
Wind act directly on the external surfaces of enclosed structures, through porosity of the external
surface, internal surface through opening. Wind pressure act on areas of the surfaces producing
forces perpendicular to the surface of the structure or on individual cladding or covering compo-
nents.
The effect of wind on structures is significant on light and dynamic structures. It does have con-
siderable effect on vertically standing walls, columns and beams etc. Therefore; its effect can be
easily studied on roof structures such as truss structures and flat slabs. Therefore, our analysis on
wind load actions and its design will focus on roofs analysis and design and calculation of wind
forces on flat roofs.
The building is located in ADAMA city where there are some buildings around and it’s
categorized to suburban city.
According to EBCS-1, 1995, it is belongs to terrain category Iv.
The variables for terrain category III are:
Terrain factor, KT = 0.22
Minimum height, Zmin = 8m
Roughness length, Zo = 0.3m
Structural design of a G+6 building at ADAMA the area where the building is going to be placed
has an altitude of 1284.5m, for which its air Density is,
ρ =1.026 Kg/m3 by interpolation ……………. from (table 3.1, EBCS-1, 1995)
Page | 7
FINAL YEAR PROJECT 2020
i. External wind pressure
External pressure is the wind pressure acting on the external surface of a structure.
According to EBCS-1, Art 3.5.2, the wind pressure acting on the external surface of a structure
shall be:
We = qref*Ce(ze)*Cpe
Wi = qref*Ce(zi)*Cpi
7∗Kt
Ce(ze) = Cr2(z) Ct2(z) [1+ Cr∗Ct ]
ρ ρ
∗¿ q ref = V 2
qref = 2 vref2 2 ref
= Ctem*Calt*Cdir* vref,
= 22 m/s
Page | 8
FINAL YEAR PROJECT 2020
Since the building is going to be build in ADAMA therefore ρ =1.026kg/m3
ρ
qref = 2 ∗¿ (Vref)2
= 1/2*1.026*(22)2
= 248.292 N/m2
Exposure coefficient
7 Kt
C e=Cr 2 C t ( z) [1+ ]
C r Ct
-for the building no escarpments or hills are located around and therefore Ct(Z) =1.00
KT = 0.22
Zmin = 8
Zo = 0.3
h=17.5
lnZ
Cr(Z)=KT Zo , for 8 ≤ 17.5 ≥ 200
ln 17.5
=0.22*
0.3
= 0.89
Page | 9
FINAL YEAR PROJECT 2020
Since the topographic of our site is flat,
¿H
, Ct = 1
Lu≈ 0
7∗0.22
Ce(ze) = 0.892 12*[1+ 0.89∗1 ]
= 2.2163
Pressure coefficients
To calculate the external and internal pressure coefficients, Cpe and Cpei, we divide the roof into
the following zones. The magnitude of the coefficient s depends on the loaded area of the roof.
Different zones of the loaded area are subjected to different magnitude.
The roof has two mono pitch with in deferent dimension (in three wind direction 0 o, 90o, and
180o) but we do for smaller one for considering more wind pressure effect which is governing
one because in large cover area expected pressure is lower than to that of smaller one.
b = 20m
Page | 10
FINAL YEAR PROJECT 2020
e = min (b, 2h)
= 20m
mi
e
=20/4 =5m
4
e
= 20/10 =2m
10
e
= 20/2 = 10m
2
Page | 11
FINAL YEAR PROJECT 2020
For 180o, α =9.96o
For 0o , α = 9.96o
Page | 12
FINAL YEAR PROJECT 2020
15o -0.9 -2.0 -0.8 -1.5 -0.3 -0.3
Page | 13
FINAL YEAR PROJECT 2020
From the above three cases the maximum We value is -1320.695N/m2 = -1.3207KN/m2
For closed buildings with internal partitions and openings windows, the extreme values of inter-
nal pressure coefficients are
Wnet1 = We - Win
= -1320.695-429.6445 = 1750.34N/m2
Wnet2 = We - Win
From the above three cases the maximum Wnet = -1.75034 KN/m2
Page | 14
FINAL YEAR PROJECT 2020
Thickness=0.5mm
Width=782mm
Effective width=712mm
Weight=3.92Kg/m(for uncoated sheet)
Moment of inertia=74452mm4
Section modulus=2720mm3
Ixx=101295
Sx=3701
Purlin =0.9m
L L
Truss spacing can be taken to where L is the shorter side of the
5 3
roof
9.4 9.4
= 1.88m or = 3.13m
5 3
Take c/c spacing of truss member as 2.5m
Note: Weight of each coated sheet (galvanized sheet) is at least 0.38Kg/m2 (max 0.76Kg/m2)
heavier than the weight of uncoated sheet. Load on EGA-sheet per meter.
3.92 kg
Gk =
m
s2
∗9.81 m
+ (
m2 m2 )
0.38 kg 0.76 kg 9.81 m
+ ∗
s2
0.712 2
Page | 15
FINAL YEAR PROJECT 2020
As per EBCS-11995 roofs not accessible except for normal repair, maintenance painting and mi-
nor repairs. Therefore, roof category is H. (Table 2.13, EBCS-1, 1995) and for this roof category
the live loads on the sloping roofs are (from Table 2.14, EBCS-1, 1995):
Qk = 0.25KN/m2 (UDL)
0.25 KN
Over a meter length of the purlin: Qk = ∗0.9m = 0.225KN/m
m2
QK= 1KN (concentrated load)
Effective length of the truss is taken to be the spacing of the truss, i.e. 2.5 m. purlin spacing 0.9m
1 KN
Therefore Qk = = 1.279KN/m
0.782m
Gk = 0.0596KN/m2*cos9.960 = 0.0587KN/m2
Gk = 0.0596KN/m2*sin9.960 = 0.0103KN/m2
( 1.3∗0.0587 ) KN ( 1.6∗1.26 ) KN
Pd = +
m2 m
= 0.0763KN/m2 + 2.016KN/m
KN KN
= 0.0763 *(0.782m) + 2.016 *(0.782m)
m2 m
Pd = 0.059KN/m + 1.576 KN
KN
wl 2 Pl ∗( 0.9 m ) 2 0.9 m
M = 8 + 4 = 0.074 m + 1.576KN¿ 4
8
=0.0075KN.m +0.3546KN.m
= 0.362KN.m
Pd = Gk +1.6Wk
Pd = 0.0587KN/m2 +1.6*(-1.75034KN/m2)
= (0.0587KN/m2 -2.8KN/m2)*0.782m
= -2.14KN/m
Page | 17
FINAL YEAR PROJECT 2020
Wl2
M= =−2.152 KN /m∗(0.9 m)2/8
8
= -0.218KN.m
= 0.059 KN /m + 1.33 KN
wl 2 Pl
M= 8 + 4 =
−1.7986(KN
m
∗( 0.9 m ) 2
+ )
1.33 KN ∗0.9 m
4
8
= 0.1173 KN.m
= 0.12 KN.m
Page | 18
FINAL YEAR PROJECT 2020
Check capacity of EGA sheet
= 133.09 Mpa
= 900mm / 200
= 4.5 mm
= 0.0193mm + 0.891mm
= 0.91mm
Height of truss=1.65m
Page | 19
FINAL YEAR PROJECT 2020
A. Wind load
B. Live load
Roof is not accessible for serviceability except for normal maintenance, repair, and painting
& minor repair. Therefore, roof category is H. (Table 2.13, EBCS-1, 1995).
And for this roof category the live loads (Imposed load) on the sloping roofs are (from
LL (distributed)=0.25*0.9 =0.225KN/m
LL (Concentrated)=1 KN
Effective length of the purlin is taken to be the spacing of the truss, i.e. =3m.
wl 2
M=
8
= (0.225 KN / m2 * (3m)2) /8
= 0.253KN.m
For Concentrated live load
pl
M=
4
= 1KN*3 / 4
= 0.75KN.m
The governing live load is the concentrated live load. Thus, LL= 1 KN
C. Dead Load
Page | 20
FINAL YEAR PROJECT 2020
Dead load of the purlin: From the Kaliti Steel manual take ST-60 (Square Tube: 60 mm*60
I=39.56 cm4
S=13.18 cm3
R= 2.28 cm
=0.0585 KN/m
= 0.0277KN
To determine per meter load the weight is divided by width of the sheet
=0.0354 KN/m
=0.0939KN/m
NB: The wind pressure acts perpendicular to the surface while the DL and LL are acting
vertically downward.
The above loads (DL & LL) shall be resolved parallel (x direction) and perpendicular to the
Page | 21
FINAL YEAR PROJECT 2020
I. Load parallel to the rafter (i.e. x direction)
DLx = 0.0939KN/m*sin9.96°
=0.016KN/m
LLx = 1KN*sin9.96°
=0.173KN
DLy = 0.0939KN/m*cos9.96°
=0.0925KN/m
LLy = 1KN*cos9.96°
=0.985KN
Safety factors for favorable and unfavorable load conditions indicated below are adopted from
X- Direction
= 1.3*0.016KN/m + 1.6*0.173 KN
=0.021KN/m + 0.2768 KN
wl 2 Pl
Mx = 8 + 4
W= 0.021 KN /m
P= 0.2768 KN
Page | 22
FINAL YEAR PROJECT 2020
L=3m
= 0.024 + 0.2076
= 0.232 KN.m
wl 2 P
Vx = 2
+ 2
= 0.0315 + 0.1384
= 0.1699 KN
Y- Direction
Governing live load: Concentrated live loading (determined earlier) Therefore, unfavorable con-
= 0.1203KN/m + 1.576KN
wl 2 Pl
My = 8 + 4
= 0.135 + 1.182
= 1.317 KN.m
wl P
Vy = 2 + 2
Page | 23
FINAL YEAR PROJECT 2020
= ((0.1203 KN / m * 3m) / 2 ) + 1.576 KN / 2
= 0.18 KN + 0.788 KN
= 0.968 KN
= 0.0833 + 2.52
= -2.437KN/m
wl 2
Mx= 8
= -2.742KNm
wl
Vy = 2
= -2.437 KN * 3m / 2
= -3.656 KN
V max=-3.656KN
Flange section
C = B- 3tw
Page | 24
FINAL YEAR PROJECT 2020
= 60-3(3.5)
= 49.5 mm
Tf = 3.5 mm
ε = √ 235 / fy
Use steel grade Fe430 and for t<40mm, yield stress fy = 275 N/mm2 …EBCS3, 1995 Table 3.1
ε= √ 235 /275
= 0.9244
C / tf = 49.5/3.5
d / tw = H-3tf / tw
= 60 – 3(3.5) / 3.5
= 3.295 KN.m
Page | 25
FINAL YEAR PROJECT 2020
Mmax= (-2.742KNm) < Mpl,Rd (3.92)…………OK
fy / √ 3
Vpl.Rd = (A( )
γm
=7.59 cm 2∗100 ¿ cm 2 ¿ ¿
=109.55KN
Vd −3.656
Vpl . Rd
= 109.55
= 0.0334 since , 0.0334 ¿ 0.5 ok! ! !
δ = 5/384 * WL2/EI
δ = p.l2/48EI
Wx = 0.021KN/m + 0.2768KN
3
0.2768∗3
5
δx = ∗0.021∗¿ ¿ + 48∗210 KN −8
384 2
∗39.56∗10
mm
= 8.91 * 10-4 m
= 0.891mm
Page | 26
FINAL YEAR PROJECT 2020
Case -1. Wy = 0.1203KN/m + 1.576 KN
5
∗0.1203∗34 1.576∗3
2
384
δ y 1= + 210 KN ∗48∗39.56∗10−8 mm4
210 KN −8 4
∗39.56∗10 mm mm2
mm2
= 5.1mm
5
∗2.437∗34
384
δ y2 =
210 KN
2
∗39.56∗10−8 mm4
mm
= -0.0131m
= 13.1mm
√
δ total = ( δ x2 ¿ + √ δ y2 )¿
= √¿¿
δ total = 13.13mm
The recommended limiting value for deflection as per EBCS-3195 for roofs generally
= 15mm
Page | 27
FINAL YEAR PROJECT 2020
2.1.4 Analysis and design of truss
Load: Load the purlin are
Wind load: WL = -1.75034 KN/m2 * 0.9m
= -1.575 KN/m
Rwl = WL / 2
This load will be resolved into components in horizontal and vertical plane to make easier com-
putation by SAP 2014. The sign are provided in accordance with global co-ordinate.
= -0.409KN
= -2.327KN
Governing live load on the purlin LL = 1KN acting at the mid span.
RLL = 1KN / 2
= 0.5KN
Page | 28
FINAL YEAR PROJECT 2020
3. Dead load transferred to intermediate truss from purlin
= 0.141 KN
= 0.192KN
= 6 battens
Page | 29
FINAL YEAR PROJECT 2020
= 16 battens
= 102m
= 1.224KN
= 0.192 KN + 1.224 KN
= 1.42 KN
= 0.203KN
= 0.71KN
Page | 30
FINAL YEAR PROJECT 2020
Page | 31
FINAL YEAR PROJECT 2020
Page | 32
FINAL YEAR PROJECT 2020
Roof qk(KN/m2) Qk(KN)
Flat roof 0.5 1.0
Sloping roof 0.25 1.0
qk = 0.5KN/m= uniformly distributed load
qref =1/2ῥ*Vref2
Where ῥ is the air density and for an altitude of 1284m (our building is found at ADAMA)
=1.026Kg/m3
Vref=Cdir*Ctemp*Calt* Vref, 0
Taking the three factor which is the directional, temperature and altitude factors unity and given
as Vref, 0=22m/s.
= 1*1*1*22m/s
= 22m/s
Page | 33
FINAL YEAR PROJECT 2020
Reference wind pressure
qref =1/2ῥ*Vref2
=248.292Kg/m2s2
Exposure coefficient
Since ADAMA is sub- urban area with regular cover of vegetation, building or with isolatedob-
stacles:-
KT =0.22
Zmin=8m
Zo =0.3m
Page | 34
FINAL YEAR PROJECT 2020
Reference height (Ze) = h + hp = 16.65
= 15.00 + 1.65
= 16.65m
= 0.884
Since topography of our site is that, Ø = H/Lu≈0. This is less than 0.05 so, Ct = 1.0
= 0.8842*1.02*[1+7*0.22/0.713*1]
=0.5084*3.356
=1.706
Ce (16.65) = 2.143
Since our roof is flat (slab) type roof load exerted in wind direction 0o, 90o, 180o
G H I
Page | 35
FINAL YEAR PROJECT 2020
Area calculation
-0.47
G -0.8 -1.4 -0.39 -1.19
+0.11
H -0.7 -1.2 -0.7 -1.5
-0.2
I -1.2 -1.02 -1.2 -2.0
-0.7
Page | 36
FINAL YEAR PROJECT 2020
= -0.97
= 248.29N/m2*2.143 (-2.0)
= -1064.17
Dead load
All unit weights are taken from EBCS-1, 1995, Art 2.4.2
Page | 37
FINAL YEAR PROJECT 2020
CHAPTER THREE
SLAB ANALYSIS AND DESIGN
Page | 38
FINAL YEAR PROJECT 2020
le- is the effective span, for two-way slabs, the shorter span
Page | 39
FINAL YEAR PROJECT 2020
Ly
≥ 2One-way Slab
Lx
Ly
<2Two-way Slab
Lx
[
d= 0 . 4+0 . 6 ]
f yk L e
400 β a
f yk =300 Mpa
[
d= 0 . 4+0 . 6 ]
300 L e
400 β a
Le
d=0 . 85
βa
Sample calculation
Panel 1
Page | 40
FINAL YEAR PROJECT 2020
LX =6m
Ly =6m
Le=6m
Ly 6m
= =1< 2, two way slab
Lx 6m
βa
For span ration of 1 (end span)
βa
=40
[
d= 0 . 4+0 . 6 ]
300 L e
400 β a
Le
d=0 . 85
βa
6000
d=0 . 85 =127 .5 mm
40
Panel 19
Page | 41
FINAL YEAR PROJECT 2020
βa
=10
Le=1.76
[
d= 0 . 4+0 . 6 ]
300 L e
400 β a
Le
d=0 . 85
βa
1760
d=0 . 85 =149. 6 mm
10
The effective depth determination for the rest of the panels are tabulated below
Panel
number Ly Lx Ly/Lx Ba dmin
1 6 6 1 40 127.5
2 6 3 2 30 85
5 6 3 2 30 85
6 6 3 2 30 85
7 3 3 1 45 56.67
10 3 3 1 40 63.75
11 6 3 2 30 85
Page | 42
FINAL YEAR PROJECT 2020
12 6 3 2 30 85
13 6 3 2 30 85
14 9 3 3 25 102
15 4 4 1 45 75.56
16 4.5 4.5 1 45 85
17 4.5 4.5 1 45 85
20 3.4 1 3.4 10 85
dmax = 149.6mm, using Ø10 bar and 15mm concrete cover so the overall depth D=149.6+15+5
=169.6mm so we use D=170mm
Pd=1.3DL + 1.6 LL
Self weight
Finishing material
Partition wall
For Panel 1
Page | 43
FINAL YEAR PROJECT 2020
=0.170m * 25 kN/m3
= 4.25 kN/m2
Finishing material
Partition wall
Type 1
5.8∗0.15∗3∗14
Height of the building (h)=3m =
(6∗6)
Partition wall
Type 2
3.31∗0.1∗3∗14
Height of the building (h)=3m p.wall = (6∗6)
Page | 44
FINAL YEAR PROJECT 2020
Unit weight of the wall=14 KN/m3
1.401
Pd=1.3DL + 1.6 LL
Pd = (1.3*7.75) + 1.6(2)
Pd =13.275 KN/m2
For Panel 2
=0.170m * 25 kN/m3
=4.25 kN/m2
Finishing material
Page | 45
FINAL YEAR PROJECT 2020
Partition wall
Type 1
5.8∗0.15∗3∗14
Height of the building (h)=3m =
(3∗6)
= 8.024
Pd=1.3DL + 1.6 LL
=1.6(2) + 1.3(8.024)
= 13.63
Page | 46
FINAL YEAR PROJECT 2020
8
9 4.25 2.04 0.852 7.142
10 4.25 2.04 2.5 8.79
11 4.25 2.04 0 5.79
12 4.25 2.04 0 5.79
13 4.25 2.04 0 5.79
14 4.25 2.37 0.89 6.12
15 4.25 2.37 0 6.12
16 4.25 2.04 2.583 8.87
17 4.25 2.04 3.3 9.6
18 4.25 2.04 0.303 6.59
19 4.25 2.04 1.107 7.4
20 4.25 2.04 0 5.79
Page | 47
FINAL YEAR PROJECT 2020
14 6.12 3 12.76
15 6.12 3 12.76
16 8.87 2 14.74
17 9.6 2 15.68
18 6.59 4 13.36
19 7.4 4 14.42
20 5.79 4 12.33
3.2.2Moment Calculation
Coefficient Method
Maximum moments for individual slab panels with edges either simply supported or fully fixed
are calculated as
1. The ratio of the actual support moment to the bending moment of fully fixed slab, or the
ratio of the width of fixed to the width of the simply supported part of the edge is
evaluated.
2. The bending moments of the slab are then computed by interpolating between different
conditions……………………. [EBCS-2, 1995, Art 3.3.1]
Page | 48
FINAL YEAR PROJECT 2020
Page | 49
FINAL YEAR PROJECT 2020
Mys= αysPdlx2
Mxf= αxfPdlx2
Myf= αyfPdlx2
Strip Method
Advantages:
The strip method gives results on the safe side, which is certainly preferable in practice.
The strip method is a design method by which the needed reinforcement can be calcu-
lated.
In this project, we have used strip method for panels with irregular shapes but approximately
changed to rectangle.
Page | 50
FINAL YEAR PROJECT 2020
3.2.3Determination of moment distribution
Sample calculations
Panel 1
LX =6m
Ly =6m
Le=6m
Ly 6m
= =1:1
Lx 6m
αxs= 0.047
αxf=0.036
αys=0.047
αyf=0.036
For one way slab the structural element is designed by assuming the section as a seriously con-
nected rectangular beam.
Page | 51
FINAL YEAR PROJECT 2020
Pd∗l s2
max=
8
2
12.76∗3
Max=
8
Mmax=14.35
M resistance=0.8fcd*B*d2*ρmax*m (1-0.4ρmax*m)
de=ts-(cover+ Dmin/2 )
ρmax= 0.75 ρb
ρ b=¿εcu/ εcufyd/εs*1/m ]
m=fyd/0.8fed =34.54
Page | 52
FINAL YEAR PROJECT 2020
Mcap= 61.952 KNm> 14.35 KNm ……… OK
Panel 15
Quadrant area
Approximate rectangle
A=4*4 = 16m2
Panel 16 and 17
Page | 53
FINAL YEAR PROJECT 2020
Page | 54
FINAL YEAR PROJECT 2020
For middle strip
Mxy=
4 8( )
wa 3 a wa a
+ ( )
8 8
2 2
3 wa wa
Mxy= +
32 64
2
7 wa 7 ( 12.76 )∗4
2
Mxy= =
64 64
Page | 55
FINAL YEAR PROJECT 2020
At side strip
Cantilever
( )( )
2
w a
2
∗
wl 2 4
Mx= =
2 2
wa2 12.76∗4 2
Mx= =
64 64
Mx=3.19 KN m/m
Page | 56
FINAL YEAR PROJECT 2020
At middle strip
2
7 wa 7 ( 15.68 )∗4.5
2
Mxy= = =34.75KN m/m
64 64
Page | 57
FINAL YEAR PROJECT 2020
At side strip
2
wa2 ( 15.68 )∗4.5
Mx= = =4.96 KN m /m
64 64
Page | 58
FINAL YEAR PROJECT 2020
Panel 19
Panel 20
Determination of moment for the rest of the panels are tabulated below
Page | 59
FINAL YEAR PROJECT 2020
α ys= 0.037 Mys= 4.54
Page | 60
FINAL YEAR PROJECT 2020
α ys= 0.032 Mys= 17.42
αxs=
α ys=
Lift α xf=
α yf=
12.48
14.63
10.727
Page | 61
FINAL YEAR PROJECT 2020
panel-11 α xf= 0.05 Mxf= 4.83
Mxs=9.58
Panel-14 One way slab
Mys=4.79
Middle stripSide strip
Panel-15 Using strip method
Mxs=14.88 Mxs=2.126
Mys=14.88 Mys=2.126
Mxf=7.44 Mxf=1.06
Myf=7.44 Myf=1.06
Middle strip Side strip
Panel-16&17 Using strip method
Mxs=23.159 Mxs=3.306
Mys=23.159 Mys=3.306
Mxf=11.57 Mxf=1.653
Myf=11.57 Myf=1.653
M =20.69
Panel-18 Cantilever slab
M =22.33
Panel-19 Cantilever slab
M =6.165 Page | 62
Panel-20 Cantilever slab
FINAL YEAR PROJECT 2020
Two methods of different accuracy are given for treating the effect of this redistribution on mo-
ments away from the support. EBCS 2, 1995 article A.3.3.1 No.3 and 4
Page | 63
FINAL YEAR PROJECT 2020
If the difference between initial support moments are less than 20%of the larger moment only
EBCS 2, 1995 article A.3.3.2 No.1
Sample calculation
Panel S1&S2
22.46−8.22
= *100 = 63.4% >20% use moment distribution
22.46
I /8
Distribution factor Df1 = I = 0.27
+ I /3
8
I /3
Df2 = I =0.73
+ I /3
8
S1 Df S2
0.27 0.73
Page | 64
FINAL YEAR PROJECT 2020
-10.66 7.17
(22.46-8.22)*0.27 (22.46-8.22)*0.73
=-3.845 = -10.395
S2 = (-8.22-10.395) =-18.615kNm
Panel S3 &S4
14.17−12.73
= ∗¿1009.79% < 20% take averaging
14.17
The support moment adjustments for the rest of the panel are tabulated below
Page | 65
FINAL YEAR PROJECT 2020
S2 3 0.3333 0.333 22.46 17.713
Page | 66
FINAL YEAR PROJECT 2020
S10 3 0.3333 0.5 4.57 4.080
Page | 67
FINAL YEAR PROJECT 2020
9 S17 1.76 0.5682 0.281 23.15 22.740
Panel 1
Since the support moment Mxs = 22.46 and Mys = 22.46 then the adjusted moment it needs
adjustment in the larger and the shorter side respectively.
Page | 68
FINAL YEAR PROJECT 2020
Larger side (Mxs)
Ly/Lx=6/6=1
Cx=0.280
Cy=0.380
ΔM=22.46-18.615=3.845
Cx=0.380
Cy=0.280
ΔM=22.46-17.3=5.16
Page | 69
FINAL YEAR PROJECT 2020
ΔMxf=5.16 (0.38) = 1.9608
Panel 2
Lx/Ly=2
Cx=0.238
Cy=0.055
ΔM=4.54-4.15=0.39
Mxf=6.13+0.092=6.22
Myf=3.43+0.021=3.45
Panel 3
Ly/Lx=1.33
ΔM=12.73-10.024=2.706
Page | 70
FINAL YEAR PROJECT 2020
ΔMyf=2.706(0.344) =0.93
Mxf=9.55+1.03=10.58
Myf=6.86+0.93=7.79
Panel 4
Along Mxs1
Along Mxs2
Along Mys
ΔM=1.83,ΔMxf=0.59,ΔMyf=0.23, Mxf=12.25,Myf=8.8
Panel 6
Along Mxs
Page | 71
FINAL YEAR PROJECT 2020
Ly/Lx=2, Cx=0.484, Cy=0.248
Along Mys
Cx=0.238, Cy=0.055
ΔM=0.005,ΔMxf=0.00119,ΔMyf=0.000275
Mxf=5.337, Myf=2.96
Panel 10
Along Mxs
ΔM=0.34,ΔMxf=0.095,ΔMyf=0.13
Along Mys
Cx=0.380, Cy=0.280,ΔM=0.49,ΔMxf=0.1862,ΔMyf=0.1372
Mxf=4.101, Myf=3.96
Panel 12 & 13
ΔM=0.48,ΔMxf=0.234,ΔMyf=0.12
Mxf=5.784, Myf=3.23
Page | 72
FINAL YEAR PROJECT 2020
Panel 16
Mxs223.15 to 22.74
ΔM=4.38,ΔMxf=1.22,ΔMyf=1.66
ΔM=0.41,ΔMxf=0.11,ΔMyf=0.16
Mxf=12.9, Myf=13.4
Panel 17
Mys123.15 to 18.77
Mys223.15 to 22.79
Along Mxs
ΔM=10.32,ΔMxf=2.89,ΔMyf=3.92
Along Mys
Cx=0.38, Cy=0.28
ΔM=4.38,ΔMxf=1.66,ΔMyf=1.23
ΔM=0.41,ΔMxf=0.16,ΔMyf=0.12
Mxf=16.28, Myf=16.89
Page | 73
FINAL YEAR PROJECT 2020
8Adjustment of field moment for First Floor Slab
Table 3.
Page | 74
FINAL YEAR PROJECT 2020
Fi
gure 3 4first floor moment after adjustment
3.2.6Reinforcement work
Since there is no loading to applied other than live load (0.5kn/m 2) and dead load compensated
by, excavated soil, the floor designed for minimum reinforcement. The minimum reinforcement
provided for shrinkage and temperature requirement i.e.
Use D= 100mm
Page | 75
FINAL YEAR PROJECT 2020
Ø 8 mm reinforcement bar
Use d= 80mm
as∗b π 8 2 /4∗1000
Spacing, S = = =369.60 mm
As 136
fcd =11.33 N /m
b =1000 mm
√ √
6
d= msd 22.74∗10
=
µsd∗fcd∗b 0.295∗11.33∗1000
d =82.49<150 mm … … … … … … … ok !!!
Slab reinforcement
Minimum reinforcement
Page | 76
FINAL YEAR PROJECT 2020
0.5
ρ min = =0.00167
300
2
π∗10 ∗1000
as∗b
S= = 4
As
250.5
S calculated =313.53
Smax=300
{
∅ main ¯¿ 10
Smin> ∅+ 5 mm=20
20 mm=20
Smin=20 mm
d=170−15−5=150 mm
Msd 9.58∗10
6
µsd = 2= =0.03758
fcd∗b∗d 11.33∗1000∗1502
d
Zs=
2
(1+√ 1−2 µsd
Page | 77
FINAL YEAR PROJECT 2020
150
Z=
2
(1+√ 1−2(0.03758)
Z =147.126
6
Msd 9.58∗10
As= =
Zfyd 147.126∗260.87
2
π∗10 ∗1000
αs∗b 78539.81
Spacing S= As = 4 = 250.5 = 313.53
250.5
In one way slab bar ratio of the secondary reinforcement to the main reinforcement shall be at
least equal to 0.2
Aρ=20 % (250.5)
Aρ=50.1 ¿ Asmin=250.5
π∗82∗1000
as∗b
S= = 4 50265.48 =200.66
As
250.5 250.5
Use ∅ , 8 c / c200mm
From EBCS-2-1995
Use ∅ , 8 c /c 200 mm
Page | 78
FINAL YEAR PROJECT 2020
d = 150 mm
Msd 4.79∗106
µsd= 2 = =0.0188
fcd∗b∗d 11.33∗1000∗1502
d
Z=
2
(1+√ 1−2 µsd
150
Z=
2
(1+√ 1−2(0.018)
Z =148.57
Msd 4.79∗106
As= = =
Zfyd 148.57∗260.87
Use = Asmin=250.5 mm 2
π∗82∗1000
as∗b
S= = 4 = 200.66
As
250.5
Use ∅ 8c/c200 mm
The Reinforcement work for the rest of the panel are tabulated below
Page | 79
FINAL YEAR PROJECT 2020
Page | 80
FINAL YEAR PROJECT 2020
Support reinforcement
panel between ρ ρmin Ac [sq.mm]S.calc[mm] S.final [mm]
S1 & S2 M= 17.713 0.0031 0.0017 469.607 107.037 Ø 8c/c 100
S1 & S6 M= 17.300 0.0031 0.0017 458.243 109.692 Ø 8c/c 100
S3 & S2 M= 10.024 0.0017 0.0017 261.423 192.276 Ø 8c/c 190
S2 & S7 M= 4.150 0.0007 0.0017 106.937 470.047 Ø 8c/c 300
S3 & S4 M= 13.450 0.0024 0.0017 353.315 142.268 Ø 8c/c 140
S4 & S5 M= 12.190 0.0021 0.0017 319.361 157.394 Ø 8c/c 150
S4 & S9 M= 8.650 0.0015 0.0017 224.947 223.455 Ø 8c/c 220
S5 & S10 M= 4.800 0.0008 0.0017 123.848 405.863 Ø 8c/c 300
S6 & S11 M= 6.720 0.0012 0.0017 174.065 288.774 Ø 8c/c 280
S6 & S7 M= 3.800 0.0007 0.0017 97.849 513.702 Ø 8c/c 300
S9 & S10 M= 4.080 0.0007 0.0017 105.119 478.179 Ø 8c/c 300
S9 & S17 M= 12.830 0.0022 0.0017 336.584 149.340 Ø 8c/c 140
S11 & S12 M= 6.950 0.0012 0.0017 180.107 279.087 Ø 8c/c 270
S12 & S13 M= 7.430 0.0013 0.0017 192.736 260.800 Ø 8c/c 260
S13 & S20 M= 7.114 0.0012 0.0017 184.419 272.561 Ø 8c/c 270
S13 & S18 M= 20.690 0.0037 0.0017 552.162 142.240 Ø 10c/c 140
S15 & S17 M= 18.770 0.0033 0.0017 498.789 157.461 Ø 10c/c 150
S15 & S16 M= 18.770 0.0033 0.0017 498.789 157.461 Ø 10c/c 150
S16 & S19 M= 22.740 0.0041 0.0017 609.682 128.821 Ø 10c/c 120
S16 & S17 M= 23.150 0.0041 0.0017 621.253 126.422 Ø 10c/c 120
S17 & S19 M= 22.740 0.0041 0.0017 609.682 128.821 Ø 10c/c 120
S14 & S15 M= 14.880 0.0026 0.0017 392.078 200.317 Ø 10c/c 200
S14 & S16 M= 23.150 0.0041 0.0017 621.253 126.422 Ø 10c/c 120
S14 & S11,12&13 M= 9.580 0.0017 0.0017 249.613 314.646 Ø 10c/c 300
Page | 81
FINAL YEAR PROJECT 2020
Table 3. 10TableSpan reinforcement
of span moment reinforcement
panel no. ρ ρmin Ac [sq.mm]S.calc[mm] S.final [mm]
S1 Mxf= 20.220 0.0036 0.0017 539.053 145.700 Use Ø 10c/c 140
span moment Myf= 20.220 0.0042 0.0017 581.465 135.072 Use Ø 10 c/c 130
S2 Mxf= 6.220 0.0011 0.0017 160.949 312.306 Use Ø 8c/c 300
span moment Myf= 3.450 0.0007 0.0017 95.213 527.926 Use Ø 8 c/c 300
S3 Mxf= 10.580 0.0018 0.0017 276.244 181.960 Use Ø 8c/c 180
span moment Myf= 7.740 0.0015 0.0017 215.764 232.965 Use Ø 8 c/c 230
S4 Mxf= 12.250 0.0021 0.0017 320.974 156.603 Use Ø 8c/c 150
span moment Myf= 8.800 0.0018 0.0017 245.935 204.385 Use Ø 8 c/c 200
S5 Mxf= 3.370 0.0006 0.0017 86.702 579.748 Use Ø 8c/c 300
span moment Myf= 6.940 0.0014 0.0017 193.097 260.312 Use Ø 8 c/c 260
S6 Mxf= 5.340 0.0009 0.0017 137.932 364.423 Use Ø 8c/c 300
span moment Myf= 2.960 0.0006 0.0017 81.598 616.013 Use Ø 8 c/c 300
S7 Mxf= 2.820 0.0005 0.0017 72.472 693.581 Use Ø 8c/c 300
span moment Myf= 2.820 0.0006 0.0017 77.714 646.803 Use Ø 8 c/c 300
S9 Mxf= 4.490 0.0008 0.0017 115.777 434.156 Use Ø 8c/c 300
span moment Myf= 2.700 0.0005 0.0017 74.386 675.736 Use Ø 8 c/c 300
S10 Mxf= 4.100 0.0007 0.0017 105.638 475.827 Use Ø 8c/c 300
span moment Myf= 3.960 0.0008 0.0017 109.417 459.394 Use Ø 8 c/c 300
S11 Mxf= 4.830 0.0008 0.0017 124.630 403.318 Use Ø 8c/c 300
span moment Myf= 2.700 0.0005 0.0017 74.386 675.736 Use Ø 8 c/c 300
S12 Mxf= 5.784 0.0010 0.0017 149.535 336.146 Use Ø 8c/c 300
span moment Myf= 3.230 0.0006 0.0017 89.096 564.169 Use Ø 8 c/c 300
S13 Mxf= 5.784 0.0014 0.0017 207.911 241.764 Use Ø 8c/c 240
span moment Myf= 3.230 0.0006 0.0017 89.096 564.169 Use Ø 8 c/c 300
S14 Mxf= 4.790 0.0008 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment
S15 Mxf= 7.440 0.0013 0.0017 192.999 260.444 Use Ø 8c/c 260
span moment Myf= 7.440 0.0015 0.0017 207.254 242.531 Use Ø 8 c/c 240
S16 Mxf= 12.900 0.0023 0.0017 338.471 148.508 Use Ø 8c/c 140
span moment Myf= 13.400 0.0027 0.0017 378.712 132.728 Use Ø 8 c/c 130
S17 Mxf= 16.280 0.0029 0.0017 430.268 116.824 Use Ø 8c/c 110
span moment Myf= 16.840 0.0034 0.0017 480.062 104.706 Use Ø 8 c/c 100
Page | 82
FINAL YEAR PROJECT 2020
3.2.7Load transfer to beam
According to EBCS-2/1995, the design loads on supporting beam and the design shear force of
two-way slab subjected to a uniformly distributed load considering torsion at corners may be de-
termined using the following equation.
Vx = βvx * Pd * Lx
Vy = βvy * Pd * Lx
For analysis to use in ETABS the dead load and live load should transfer separately.
Page | 83
FINAL YEAR PROJECT 2020
Live
Table Load
3. 11 live Transfer TotoBeam
load transfer beam
Panel Support Shear Aspect RatioLL Lx βVx βVy Vx Vy 0.914Vx 0.914Vy
1 Vxc 0.40 4.80 4.39
Vxd 0.26 3.12 2.85
1.00 2.00 6
Vyc 0.40 4.80 4.39
Type 4 Vyd 0.26 3.12 2.85
2 Vxc 0.52 3.12 2.85
Vxd 0.00 0.00
2.00 2.00 3
Vyc 0.36 2.16 1.97
Type 2 Vyd 0.24 1.44 1.32
Vxc 0.44 3.96 3.62
Vxd 0.00 0.00 0.00
3 1.33 2.00 4.5
Vyc 0.36 3.24 2.96
Type 2 Vyd 0.24 2.16 1.97
Vxc 0.44 3.96 3.62
Vxd 0.00 0.00 0.00
4 1.33 2.00 4.5
Vyc 0.36 3.24 2.96
Type 2 Vyd 0.24 2.16 1.97
Vxc 0.52 3.12 2.85
Vxd 0.00 0.00 0.00
5 2.00 2.00 3
Vyc 0.40 2.40 2.19
Type 4 Vyd 0.26 1.56 1.43
Vxc 0.40 2.39 2.19
Vxd 0.00 0.00 0.00
6 2.00 2.00 3
Vyc 0.36 2.16 1.97
Type 2 Vyd 0.24 1.44 1.32
Vxc 0.33 1.98 1.81
7 1.00 2.00 3
Type 1 Vyc 0.33 1.98 1.81
8
Vxc 0.45 2.70 2.47
9 1.50 2.00 3
Type 1 Vyc 0.33 1.98 1.81
Vxc 0.38 2.25 2.06
10 1.00 2.00 3
Type 1 Vyc 0.33 1.98 1.81
Page | 84
FINAL YEAR PROJECT 2020
Page | 85
FINAL YEAR PROJECT 2020
Table 3. 12 dead load transfer toDEAD
beam Load Transfer To Beam
Panel Support Shear Aspect RatioDL Lx βVx βVy Vx Vy 0.914Vx 0.914Vy
1 Vxc 0.40 18.60 17.00
Vxd 0.26 12.09 11.05
1.00 7.75 6
Vyc 0.40 18.60 17.00
Type 4 Vyd 0.26 12.09 11.05
2 Vxc 0.52 12.52 11.44
Vxd 0.00 0.00
2.00 8.02 3
Vyc 0.36 8.67 7.92
Type 2 Vyd 0.24 5.78 5.28
Vxc 0.44 13.54 12.38
Vxd 0.00 0.00 0.00
3 1.33 6.84 4.5
Vyc 0.36 11.08 10.13
Type 2 Vyd 0.24 7.39 6.75
Vxc 0.44 15.63 14.29
Vxd 0.00 0.00 0.00
4 1.33 7.89 4.5
Vyc 0.36 12.79 11.69
Type 2 Vyd 0.24 8.53 7.79
Vxc 0.52 9.38 8.57
Vxd 0.00 0.00 0.00
5 2.00 6.01 3
Vyc 0.40 7.21 6.59
Type 4 Vyd 0.26 4.69 4.28
Vxc 0.40 7.71 7.05
Vxd 0.00 0.00 0.00
6 2.00 6.44 3
Vyc 0.36 6.96 6.36
Type 2 Vyd 0.24 4.64 4.24
Vxc 0.33 7.51 6.87
7 1.00 7.59 3
Type 1 Vyc 0.33 7.51 6.87
8
Vxc 0.45 9.64 8.81
9 1.50 7.14 3
Type 1 Vyc 0.33 7.07 6.46
Vxc 0.38 9.89 9.04
10 1.00 8.79 3
Type 1 Vyc 0.33 8.70 7.95
Page | 86
FINAL YEAR PROJECT 2020
Page | 87
FINAL YEAR PROJECT 2020
Page | 88
FINAL YEAR PROJECT 2020
3.3.2 Load determination of second floor
Load calculation
Panel Dead Load Live Load PD=1.3 DL + 1.6 LL
1 8.23 2 13.9
2 7.3 2 12.69
3 6.29 2 11.38
4 8.23 2 13.9
5 7.24 2 12.61
6 7.36 2 12.77
7 8.48 2 14.22
8
9 6.72 2 11.94
10 8.96 2 14.85
11 6.29 2 11.38
12 6.29 2 11.38
13 6.29 2 11.38
14 10.12 3 17.96
15 6.62 3 13.41
16 6.62 2 11.81
17 11.01 2 17.51
18 7.22 4 15.79
19 7.75 4 16.48
20 6.29 4 14.58
Page | 89
FINAL YEAR PROJECT 2020
3.3.3 Determination of moment for 2nd Floor Slab
oment determination
M
Page | 90
FINAL YEAR PROJECT 2020
3 12.61 axs= 0.093 Mxs= 10.55
Lift
Page | 91
FINAL YEAR PROJECT 2020
a ys= 0.037 Mys= 4.95
Page | 92
FINAL YEAR PROJECT 2020
Mxs=13.47
Panel-14 17.96 One way slab
Mxf=6.735
Middle strip Side strip
Panel-15 13.41 Using strip method
Mxs=15.65 Mxs=2.23
Mys=15.65 Mys=2.23
Mxf=7.82 Mxf=1.17
Myf=7.82 Myf=1.17
Middle strip Side strip
Panel- 17.51 Using strip method
Mxs=25.85 Mxs=3.69
16&17
Mys=25.85 Mys=3.69
Mxf=12.93Mxf=1.84
Myf=12.93Myf=1.84
M =24.45
Panel-18 15.79 Cantilever slab
M =25.52
Panel-19 16.48 Cantilever slab
M =7.255
Panel-20 14.51 Cantilever slab
Page | 93
FINAL YEAR PROJECT 2020
Page | 94
FINAL YEAR PROJECT 2020
S2 6 0.1667 0.667 7.65 18.570
Use Distri-
S1 3 0.3333 0.333 24.03 18.570
S1&S2 bution
S6 6 0.1667 0.667 7.7 17.587
Use Distri-
S1&S6 S1 3 0.3333 0.333 22.53 bution 17.587
Page | 95
FINAL YEAR PROJECT 2020
Page | 97
FINAL YEAR PROJECT 2020
3.3.6 Reinforcement work
Page | 98
FINAL YEAR PROJECT 2020
Table 3.19 Span reinforcement
Page | 99
FINAL YEAR PROJECT 2020
3.3.7 Load transfer to beam for 2nd floor
Table 3.20 live load transfer to beam
Live Load Transfer To Beam
Panel Support Shear Aspect RatioLL Lx βVx βVy Vx Vy 0.914Vx 0.914Vy
1 Vxc 0.40 4.80 4.39
Vxd 0.26 3.12 2.85
1.00 2.00 6
Vyc 0.40 4.80 4.39
Type 4 Vyd 0.26 3.12 2.85
2 Vxc 0.52 3.12 2.85
Vxd 0.00 0.00
2.00 2.00 3
Vyc 0.36 2.16 1.97
Type 2 Vyd 0.24 1.44 1.32
Vxc 0.44 3.96 3.62
Vxd 0.00 0.00 0.00
3 1.33 2.00 4.5
Vyc 0.36 3.24 2.96
Type 2 Vyd 0.24 2.16 1.97
Vxc 0.44 3.96 3.62
Vxd 0.00 0.00 0.00
4 1.33 2.00 4.5
Vyc 0.36 3.24 2.96
Type 2 Vyd 0.24 2.16 1.97
Vxc 0.52 3.12 2.85
Vxd 0.00 0.00 0.00
5 2.00 2.00 3
Vyc 0.40 2.40 2.19
Type 4 Vyd 0.26 1.56 1.43
Vxc 0.40 2.39 2.19
Vxd 0.00 0.00 0.00
6 2.00 2.00 3
Vyc 0.36 2.16 1.97
Type 2 Vyd 0.24 1.44 1.32
Vxc 0.33 1.98 1.81
7 1.00 2.00 3
Type 1 Vyc 0.33 1.98 1.81
8
Vxc 0.45 2.70 2.47
9 1.50 2.00 3
Type 1 Vyc 0.33 1.98 1.81
Vxc 0.38 2.25 2.06
10 1.00 2.00 3
Type 1 Vyc 0.33 1.98 1.81
Page | 100
FINAL YEAR PROJECT 2020
Page | 101
FINAL YEAR PROJECT 2020
Table 3.21 dead load transfer to beam
Page | 102
FINAL YEAR PROJECT 2020
Page | 103
FINAL YEAR PROJECT 2020
Page | 104
FINAL YEAR PROJECT 2020
3.4.2 Design load of the panels for 3rd floor
Table 3.23 Design load of the panels for 3rd floor
Page | 105
FINAL YEAR PROJECT 2020
Panel No Lx Pd Coefficient Moment
6 axs= 0.048 Mxs= 20.7
a ys= 0.045 Mys= 19.41
panel-1 11.98 a xf= 0.036 Mxf= 15.53
a yf= 0.034 Myf= 14.67
3 13.01 axs= 0.067 Mxs= 7.84
a ys= 0.037 Mys= 4.33
panel-2 a xf= 0.05 Mxf= 5.85
a yf= 0.028 Myf= 3.28
4.5 12.78 axs= 0.052 Mxs= 13.46
Page | 106
FINAL YEAR PROJECT 2020
panel-6 a xf= 0.05 Mxf= 5.72
Lift
Page | 107
FINAL YEAR PROJECT 2020
a yf= 0.028 Myf= 2.94
Page | 108
FINAL YEAR PROJECT 2020
Page | 109
FINAL YEAR PROJECT 2020
S2 6 0.1667 0.667 7.84 16.413
Use Distri-
S1&S2 S1 3 0.3333 0.333 20.7 bution 16.413
Page | 110
FINAL YEAR PROJECT 2020
S6 3 0.3333 0.5 4.23 age 4.115
Page | 111
FINAL YEAR PROJECT 2020
7 3 3 16 11.9 12.45
6
Page | 112
FINAL YEAR PROJECT 2020
3.4.5 Reinforcement work
Page | 113
FINAL YEAR PROJECT 2020
Table 3.28 span reinforcement
Span reinforcement
panel no. ρ ρmin Ac [sq.mm]S.calc[mm] S.final [mm]
S1 Mxf= 18.125 0.0032 0.0017 480.965 163.296 Use Ø 10c/c 160
span moment Myf= 17.310 0.0035 0.0017 494.053 158.971 Use Ø 10 c/c 150
S2 Mxf= 5.850 0.0010 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.241 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S3 Mxf= 11.180 0.0019 0.0017 292.278 171.978 Use Ø 8c/c 170
span moment Myf= 8.220 0.0016 0.0017 233.333 215.423 Use Ø 8 c/c 210
S4 Mxf= 11.790 0.0021 0.0017 308.621 162.871 Use Ø 8c/c 160
span moment Myf= 8.510 0.0017 0.0017 237.665 211.497 Use Ø 8 c/c 210
S5 Mxf= 7.260 0.0013 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.520 0.0007 0.0017 250.000 201.062 Use Ø 8 c/c 200
S6 Mxf= 5.940 0.0010 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.460 0.0007 0.0017 250.000 201.062 Use Ø 8 c/c 200
S7 Mxf= 2.900 0.0005 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.900 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S9 Mxf= 4.390 0.0008 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.860 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S10 Mxf= 3.070 0.0005 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.140 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S11 Mxf= 5.240 0.0009 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.940 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S12 Mxf= 6.660 0.0011 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 6.700 0.0013 0.0017 250.000 201.062 Use Ø 8 c/c 200
S13 Mxf= 5.180 0.0012 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.890 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S14 Mxf= 5.020 0.0009 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment
S15 Mxf= 7.820 0.0014 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 7.820 0.0016 0.0017 250.000 201.062 Use Ø 8 c/c 200
S16 Mxf= 17.960 0.0032 0.0017 476.414 105.508 Use Ø 8c/c 100
span moment Myf= 12.450 0.0025 0.0017 351.038 143.191 Use Ø 8 c/c 140
S17 Mxf= 15.340 0.0027 0.0017 404.600 124.235 Use Ø 8c/c 120
span moment Myf= 15.900 0.0032 0.0017 452.186 111.161 Use Ø 8 c/c 110
Page | 114
FINAL YEAR PROJECT 2020
3.4.6 Load transfer to beam
Page | 115
FINAL YEAR PROJECT 2020
Page | 116
FINAL YEAR PROJECT 2020
1 6 6 1 40 127.5
2 6 3 2 30 85
5 6 3 2 30 85
6 6 3 2 30 85
7 3 3 1 45 56.67
10 3 3 1 40 63.75
11 6 3 2 30 85
12 6 3 2 30 85
13 6 3 2 30 85
14 9 3 3 25 102
15 4 4 1 45 75.56
16 4.5 4.5 1 45 85
17 4.5 4.5 1 45 85
Page | 117
FINAL YEAR PROJECT 2020
20 3.4 1 3.4 10 85
Page | 118
FINAL YEAR PROJECT 2020
Page | 119
FINAL YEAR PROJECT 2020
11.52 a ys= 0.045 Mys= 4.66
Lift
Page | 120
FINAL YEAR PROJECT 2020
panel-10 a xf= 0.029 Mxf= 2.79
Mxs=10.05
Panel-14 13.41 One way slab
Mxf=5.02
Middle strip Side strip
Panel-15 13.41 Using strip method
Mxs=15.645 Mxs=2.23
Mys=15.645 Mys=2.23
Mxf=7.82 Mxf=1.17
Page | 121
FINAL YEAR PROJECT 2020
Myf=7.82 Myf=1.17
Middle strip Side strip
Panel- 14.41 Using strip method
Mxs=21.27 Mxs=3.04
16&17
Mys=21.27 Mys=3.04
Mxf=10.63 Mxf=1.52
Myf=10.63 Myf=1.52
M =22.56
Panel-18 14.57 Cantilever slab
M =25.58
Panel-19 16.52 Cantilever slab
M =7.29
Panel-20 14.58 Cantilever slab
Page | 122
FINAL YEAR PROJECT 2020
Page | 123
FINAL YEAR PROJECT 2020
Moment Moment
Page | 124
FINAL YEAR PROJECT 2020
Page | 125
FINAL YEAR PROJECT 2020
Page | 126
FINAL YEAR PROJECT 2020
3.5.6 Reinforcement work
Page | 127
FINAL YEAR PROJECT 2020
Table 3.36 span reinforcement
Span reinforcement
panel no. ρ ρmin Ac [sq.mm]S.calc[mm] S.final [mm]
S1 Mxf= 18.125 0.0032 0.0017 480.965 163.296 Use Ø 10c/c 160
span moment Myf= 17.310 0.0035 0.0017 494.053 158.971 Use Ø 10 c/c 150
S2 Mxf= 5.850 0.0010 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.241 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S3 Mxf= 11.180 0.0019 0.0017 292.278 171.978 Use Ø 8c/c 170
span moment Myf= 8.220 0.0016 0.0017 233.333 215.423 Use Ø 8 c/c 210
S4 Mxf= 11.790 0.0021 0.0017 308.621 162.871 Use Ø 8c/c 160
span moment Myf= 8.510 0.0017 0.0017 237.665 211.497 Use Ø 8 c/c 210
S5 Mxf= 7.260 0.0013 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.520 0.0007 0.0017 250.000 201.062 Use Ø 8 c/c 200
S6 Mxf= 5.940 0.0010 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.460 0.0007 0.0017 250.000 201.062 Use Ø 8 c/c 200
S7 Mxf= 2.900 0.0005 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.900 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S9 Mxf= 4.390 0.0008 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.860 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S10 Mxf= 3.070 0.0005 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 3.140 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S11 Mxf= 5.240 0.0009 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.940 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S12 Mxf= 6.660 0.0011 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 6.700 0.0013 0.0017 250.000 201.062 Use Ø 8 c/c 200
S13 Mxf= 5.180 0.0012 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 2.890 0.0006 0.0017 250.000 201.062 Use Ø 8 c/c 200
S14 Mxf= 5.020 0.0009 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment
S15 Mxf= 7.820 0.0014 0.0017 250.000 201.062 Use Ø 8c/c 200
span moment Myf= 7.820 0.0016 0.0017 250.000 201.062 Use Ø 8 c/c 200
S16 Mxf= 17.960 0.0032 0.0017 476.414 105.508 Use Ø 8c/c 100
span moment Myf= 12.450 0.0025 0.0017 351.038 143.191 Use Ø 8 c/c 140
S17 Mxf= 15.340 0.0027 0.0017 404.600 124.235 Use Ø 8c/c 120
span moment Myf= 15.900 0.0032 0.0017 452.186 111.161 Use Ø 8 c/c 110
Page | 128
FINAL YEAR PROJECT 2020
3.5.7 Load transfer to beam
Page | 129
FINAL YEAR PROJECT 2020
Page | 130
FINAL YEAR PROJECT 2020
Table 3.38 dead load transfer
DEAD Load Transfer To Beam
Panel Support Shear Aspect RatioDL Lx βVx βVy Vx Vy 0.914Vx 0.914Vy
1 Vxc 0.40 16.10 14.72
Vxd 0.26 10.47 9.57
1.00 6.71 6
Vyc 0.40 16.10 14.72
Type 4 Vyd 0.26 10.47 9.57
2 Vxc 0.52 11.51 10.52
Vxd 0.00 0.00
2.00 7.38 3
Vyc 0.36 7.97 7.28
Type 2 Vyd 0.24 5.31 4.86
Vxc 0.44 14.71 13.45
Vxd 0.00 0.00 0.00
3 1.33 7.43 4.5
Vyc 0.36 12.04 11.00
Type 2 Vyd 0.24 8.02 7.33
Vxc 0.44 14.32 13.08
Vxd 0.00 0.00 0.00
4 1.33 7.23 4.5
Vyc 0.36 11.71 10.71
Type 2 Vyd 0.24 7.81 7.14
Vxc 0.52 9.98 9.13
Vxd 0.00 0.00 0.00
5 2.00 6.40 3
Vyc 0.40 7.68 7.02
Type 4 Vyd 0.26 4.99 4.56
Vxc 0.40 8.75 8.00
Vxd 0.00 0.00 0.00
6 2.00 7.31 3
Vyc 0.36 7.89 7.22
Type 2 Vyd 0.24 5.26 4.81
Vxc 0.33 6.55 5.99
7 1.00 6.62 3
Type 1 Vyc 0.33 6.55 5.99
8
Vxc 0.45 8.46 7.74
9 1.50 6.27 3
Type 1 Vyc 0.33 6.21 5.67
Vxc 0.38 7.08 6.47
10 1.00 6.29 3
Type 1 Vyc 0.33 6.23 5.69
Page | 131
FINAL YEAR PROJECT 2020
Page | 132
FINAL YEAR PROJECT 2020
Pd=1.3DL + 1.35( LL + WL )
Pd =1.3*4.73+1.35(0.5-1.064)
Pd =6.149-0.7614
Pd=5.388 kN/m2
Page | 133
FINAL YEAR PROJECT 2020
M =8.34
Panel-19 5.388 Cantilever slab
15 3.42 3.47
16 4.33 4.19
17 4.85 4.93
Page | 134
FINAL YEAR PROJECT 2020
Span reinforcement
Table 3.43 span reinforcement
Page | 135
FINAL YEAR PROJECT 2020
Page | 136
FINAL YEAR PROJECT 2020
Sec A-A
Page | 137
FINAL YEAR PROJECT 2020
From serviceability requirement:-
dmin>= (0.4+0.6fy/400)le/βa
where
= (0.4 + 0.6*300/400)*2.9/25
d = 0.0986m = 98.6mm
D= 98.6+12/2+15= 119.6mm
b= 1.1m
Page | 138
FINAL YEAR PROJECT 2020
3.6.1 Loading
Dead Load
Load on Flight
Page | 139
FINAL YEAR PROJECT 2020
A. Live Load
1. Flight=1.3DL +1.6LL
2. Landing=1.3DL +1.6LL
Page | 140
FINAL YEAR PROJECT 2020
Design moment
Design shear
Support A = 21.23 KN
Support B = 17.9 KN
Page | 141
FINAL YEAR PROJECT 2020
i. Check for Deflection
5 W L4
∆ max =
384 EI
E=29GPa
= 0.000321m = 0.321mm
4
5∗12.15∗6.15 ∗1000
∆ max = 4 9
=0.022472 m=22.472 mm According to EBCS-2 , 1995 sec. 5.2.2.
384∗29∗0.000 3 ∗10
Le
σ= Where Le effective length
200
Le= 2900 mm
2900
σ= = 10.635mm
200
Page | 142
FINAL YEAR PROJECT 2020
fctd, for C-25 f ctd =1.032MPa=1032KPa
Where, k 1 =1+50 ρ
0.5 0.5
Where ρmin = = =0.0017
f yk 300
d = 129mm
k 2=1.6−d=1.6−0.119=1.481bw=1.1m
Vc= 0.25*1032*1.085*1.471*1.1*0.129 =58.43KN
Vc=58.43KN>Vsd,max=21.23KN. . . . . . . . . . . . . . . . . . OK!
Mcap ≥ Mi
Mi=maximum moment
dreq
√ Mi
0.8∗f cd∗B∗ρmax∗m(1−0.4 ρmax∗m)
≥
Where
Mi = 14.96KNm
fcd =11.33mpa
B=1000mm
fyd 260.87
M= 0.8∗fcd = 0.8∗11.33 =28.78
Page | 143
FINAL YEAR PROJECT 2020
[( ) ]
εcu
∗1
fyd 260.87 mpa
=0.75 εcu+ εs = 200 Gpa =1.304*10-3
fyd
εs=
m Es
[
=0.75 0.0035+ 0.001304 )
(
]
0.0035
∗1
28.78
ρmax =0.0189
0.5
ρmin = fyk = 0.5/300 = 0.00167
√
6
14.96 Nmm∗10
Hence, dreq=
0.8∗11.33∗1000∗0.0189∗28.78(1−0.4∗0.0189∗28.78)
=62.27mm
Ø
D provided =D- - cover, use Ø=12 mm ¯¿
2
12
=150− −25
2
=119mm
Therefore Mcap¿MExt
Provide reinforcement
Positive(bottom) reinforcement
As = ρ *b*d
−Ø
d=D −¿Cover
2
Page | 144
FINAL YEAR PROJECT 2020
12
=150- - 25
2
=119mm
ρ=
1
2[ √
C 1− C 12−
4 Mext
C 2∗b∗d
2 ]
m =fcd/0.8fyd
2.5 2.5
C1= = =0.087
m 28.78
C2=0.32*fcd*m2
=0.32*11.33*28.782=3003.04
Mext = Mi = 14.96*106Nmm
ρ=
1
2[ √
0.087− 0.0872−
4∗14.96∗10 6
3003.04∗1000∗119
2 ]
ρ = 0.00425
ρmin ≤ ρ ≤ ρmax
=0.00425*1000*119
=505.89mm2
Spacing
as∗B π Ø 2 3.14∗122
S= As , as= = =113.04mm2
4 4
113.04∗1000
= 505.89
=223.44 ≈ 220mm
Smax=min 2*D=2*150=300,Smax=300mm
Page | 145
FINAL YEAR PROJECT 2020
350
Smin=20mm
Therefore, Smin≤S≤Smax
20mm¿S¿300mm………………………..ok
Provide Ø12mm bar @220mm c/c placed at bottom in the direction of flight.
At discontinuous support Nominal top reinforcement /steel/ about half of the positive reinforce-
ment /steel/ but using Smax
Provide Ø12mm bar @300mm c/c placed at top in the direction of flight
According to EBCS-2, 1995 sec. 7.2.2.2., the ratio of the secondary reinforcement to the main re-
inforcement shall be at least equal to 0.2.
Thus, the transverse reinforcement:
{
( 0.2∗505.89 )
0.2∗A S ( main ) /w= =91.98 mm2
1.1
AS 0.5∗( b∗d ) 0.5∗( 1000∗129 )
A S (min❑ )= = =215mm 2
fyk 300
¿
Space of bar
as∗B
S= , as for Ø10mm = 78.5mm2
As
78.5∗1000
= = 365.11 mm ≈(use 300mm)
215 mm2
Page | 146
FINAL YEAR PROJECT 2020
Sec B-B
dmin>= (0.4+0.6fy/400)le/βa
Where
le = 4.064m
Page | 147
FINAL YEAR PROJECT 2020
= (0.4 + 0.6*300/400)*4.064/25
d = 0.138m = 138 mm
D= 138+12/2+15= 159mm
To make the depth the same as the rest of the slabs and avoid tipping effect,
Load on Flight
Load on Landing
DL(self-wt.) = 0.773m*0.16*25 = 3.09 KN/m
Page | 148
FINAL YEAR PROJECT 2020
DL(wt. of 2cm cement screed) = 0.773*0.02*23 = 0.355KN/m
C. Live Load
1. Flight=1.3DL +1.6LL
2. Landing=1.3DL +1.6LL
Page | 149
FINAL YEAR PROJECT 2020
Design moment
Page | 150
FINAL YEAR PROJECT 2020
Span moment = 22.55 KN-m
Design shear
Support A = 21.25 KN
Support B = -21.25 KN
5 W L4
∆ max =
384 EI
L=length of stair = 4m
E=29GPa
= 0.00963m = 9.63mm
5∗12.15∗6.15 4∗1000
∆ max = 4 9
=0.022472 m=22.472 mm According to EBCS-2 , 1995 sec. 5.2.2.
384∗29∗0.000 3 ∗10
Le
σ= Where Le effective length
200
Le= 4000 mm
4000
σ= = 20mm
200
Page | 151
FINAL YEAR PROJECT 2020
Hence, ∆ max =9.63 mm<20 mm … … … … . Ok !∆ max =22.472mm< σ all =30.75 mm OK !
Where, k 1 =1+50 ρ
0.5 0.5
Where ρmin = = =0.0017
f yk 300
d = 139mm
k 2=1.6−d=1.6−0.119=1.481bw=0.773m
Vc= 0.25*1032*1.085*1.461*0.773*0.139 =43.95KN
Vc=43.95KN>Vsd,max=21.25KN. . . . . . . . . . . . . . . . . . OK!
Mcap ≥ Mi
Mi=maximum moment
dreq≥
√ Mi
0.8∗f cd∗B∗ρmax∗m(1−0.4 ρmax∗m)
Where
Mi = 22.55KNm
fcd =11.33mpa
Page | 152
FINAL YEAR PROJECT 2020
B=1000mm
fyd 260.87
M= = =28.78
0.8∗fcd 0.8∗11.33
[ ( ) ]
εcu
∗1
fyd 260.87 mpa
=0.75 εcu+ = =1.304*10-3
εs fyd 200 Gpa
εs=
m Es
[
=0.75 0.0035+ 0.001304 )
(
]
0.0035
∗1
28.78
ρmax =0.0189
0.5
ρmin = = 0.5/300 = 0.00167
fyk
√
6
22.5 Nmm∗10
Hence, dreq=
0.8∗11.33∗1000∗0.0189∗28.78(1−0.4∗0.0189∗28.78)
=76.37mm
Ø
D provided =D- - cover, use Ø=12 mm ¯¿
2
12
=160− −25
2
=139mm
Therefore Mcap¿MExt
Provide reinforcement
Positive(bottom) reinforcement
Page | 153
FINAL YEAR PROJECT 2020
As = ρ *b*d
−Ø
d=D −¿Cover
2
12
=160- - 25
2
=129mm
ρ=
1
2[ √ 2
C 1− C 1 −
4 Mext
C 2∗b∗d
2 ]
m =fcd/0.8fyd
2.5 2.5
C1= = =0.087
m 28.78
C2=0.32*fcd*m2
=0.32*11.33*28.782=3003.04
Mext = Mi = 22.55*106Nmm
ρ=
1
2 [ √
0.087− 0.0872−
4∗22.55∗10 6
3003.04∗1000∗129
2 ]
ρ = 0.00553
ρmin ≤ ρ ≤ ρmax
=0.00553*1000*129
=713.37mm2
Spacing
2 2
as∗B π Ø 3.14∗12
S= , as= = =113.04mm2
As 4 4
Page | 154
FINAL YEAR PROJECT 2020
113.04∗1000
= =158.46 ≈ 150mm
713.37
Smax=min 2*D=2*150=300,Smax=300mm
350
Smin=20mm
Therefore, Smin≤S≤Smax
20mm¿S¿300mm………………………..ok
Provide Ø12mm bar @150mm c/c placed at bottom in the direction of flight.
At discontinuous support Nominal top reinforcement /steel/ about half of the positive reinforce-
ment /steel/
Provide Ø12mm bar @300mm c/c placed at top in the direction of flight
{
( 0.2∗713.37 )
0.2∗A S ( main ) /w= =184.57 mm2
0.773
AS 0.5∗( b∗d ) 0.5∗( 1000∗139 )
A S (min❑ )= = =231.67 mm2
fyk 300
¿
Space of bar
as∗B
S= , as for Ø10mm = 78.5mm2
As
78.5∗1000
= = 338.84 mm ≈ (use 300mm)
231.67 mm 2
Page | 155
FINAL YEAR PROJECT 2020
Provide 10mm bar @300mmc/c placed at bottom in the direction of steps
Page | 156
FINAL YEAR PROJECT 2020
Design Loads
Design moment
Design shear
Support A = 25.5 KN
Support B = 13.62 KN
Page | 157
FINAL YEAR PROJECT 2020
Since the Section C-C is symmetric with the section A-A it satisfy the deflection, shear and flex-
ure requirement
Provide reinforcement
Positive(bottom) reinforcement
As = ρ *b*d
−Ø
d=D −¿Cover
2
12
=150- - 25
2
=119mm
1
[ √ 2
ρ = 2 C 1− C 1 −
4 Mext
C 2∗b∗d
2 ]
m =fcd/0.8fyd
2.5 2.5
C1= = =0.087
m 28.78
C2=0.32*fcd*m2
=0.32*11.33*28.782=3003.04
Mext = Mi = 8.69*106Nmm
ρ=
1
2[ √ 2
0.087− 0.087 −
4∗8.69∗10 6
3003.04∗1000∗119
2 ]
ρ = 0.002415
ρmin ≤ ρ ≤ ρmax
=0.002415*1000*119
Page | 158
FINAL YEAR PROJECT 2020
=287.5mm2
Spacing
as∗B π Ø 2 3.14∗122
S= As , as= = =113.04mm2
4 4
113.04∗1000
= 287.5
=393.18
Smax=min 2*D=2*150=300,Smax=300mm
350
Smin=20mm
Provide Ø12mm bar @300mm c/c placed at bottom in the direction of flight.
Mext = Mi = 15.03Nmm
ρ=
1
2[ √
0.087− 0.0872−
4∗15.03∗10 6
3003.04∗1000∗1192 ]
ρ = 0.00427
ρmin ≤ ρ ≤ ρmax
=0.00427*1000*119
=508.13mm2
Spacing
Page | 159
FINAL YEAR PROJECT 2020
2 2
as∗B π Ø 3.14∗12
S= , as= = =113.04mm2
As 4 4
113.04∗1000
= = 222.46 ≈ 220mm
508.13
Provide Ø12mm bar @220mm c/c placed at top in the direction of flight
{
( 0.2∗287.5 )
0.2∗A S ( main ) /w= =52.27 mm2
1.1
AS 0.5∗( b∗d ) 0.5∗( 1000∗129 )
A S (min❑ )= = =215mm 2
fyk 300
¿
Space of bar
as∗B
S= , as for Ø10mm = 78.5mm2
As
78.5∗1000
= = 365.11 mm ≈(use 300mm)
215 mm2
NOTE: For the rest of floors section A-A become similar with section C-C and other section is
the same as a ground floor
Page | 160
FINAL YEAR PROJECT 2020
From ground floor 1st floor For the rest of floors
to
Sec A-A RA=21.23 Sec A-A RA=25.5
RB=17.9 RB=13.62
Sec B-B RA=21.53 Sec B-B RA=21.53
RB=21.53 RB=21.53
Sec C-C RA=25.5 Sec C-C RA=25.5
RB=13.62 RB=13.62
Page | 161
FINAL YEAR PROJECT 2020
Page | 162
FINAL YEAR PROJECT 2020
CHAPTER FOUR
FRAME ANALYSIS
Page | 163
FINAL YEAR PROJECT 2020
4. FRAME ANALYSIS
4.1 Introduction
Earthquake is movements with in the Earth’s crust cause stress to build up at points of weakness
when the stress finally exceeds the strength of the rock, the rock fractures along a fault at a zone
of existing weakness within the rock. The stored energy is suddenly released as an earthquake.
Energy released radiates in all directions from its source, the focus. Energy is in the form of
waves.
Causes of earthquake:
Volcanic eruption
Tectonic movements of the earth’s crust.
Explosion of nuclear and chemical devices
Collapse of underground cavities
Generally, there are two method of Earth quake Analysis. These are
Page | 164
FINAL YEAR PROJECT 2020
Response spectrum Analysis
Since the requirements for static method is more satisfied than dynamic, we used static method
for the analysis of earthquake. The nature of supporting ground has influence on the seismic ac-
tion. This shall generally be accounted for by considering subsoil classes.
According to EBCS_1-1995, for the ground condition in the absence of more accurate informa-
tion on soil condition, the seismic action may be determined assuming ground conditions subsoil
class B.
∑wi∗xi ∑ wi∗yi
Xm ¿ ∑ wi Ym = ∑ wi
Page | 165
FINAL YEAR PROJECT 2020
4.2.1 Weight of ground floor
4.2.1.1 Weight of slab for ground floor
Page | 166
FINAL YEAR PROJECT 2020
Page | 167
FINAL YEAR PROJECT 2020
Page | 168
FINAL YEAR PROJECT 2020
Page | 169
FINAL YEAR PROJECT 2020
4.2.1.4 Weight of beam on ground floor
Page | 170
FINAL YEAR PROJECT 2020
Page | 171
FINAL YEAR PROJECT 2020
P-16 Beam B-C', @5' 25 4.5 0.3 0.5 16.875 13.5 2.45 227.8 41.34
Beam 4-5' @B 25 4.5 0.3 0.5 16.875 11.45 0.2 193.2 3.375
P-17 Beam E-C' @7 25 4.5 0.3 0.5 16.875 18 6.95 303.8 117.3
P-18 Beam 1-3 @A 25 5.8 0.3 0.5 21.75 2.9 -0.9 63.08 -19.6
Beam A-B @1 25 0.8 0.3 0.5 3 -0.1 -0.7 -0.3 -2.1
Beam A-B @3 25 0.8 0.3 0.5 3 6 -0.7 18 -2.1
P-19 Beam 3-4 @A 25 3 0.3 0.5 11.25 7.5 -0.7 84.38 -7.88
Beam A-B @4 25 0.8 0.3 0.5 3 9 -0.7 27 -2.1
Total 672.38 6237 6127
Page | 172
FINAL YEAR PROJECT 2020
Page | 173
FINAL YEAR PROJECT 2020
Page | 174
FINAL YEAR PROJECT 2020
4.2.1.6 Weight of shear wall on ground floor
Page | 175
FINAL YEAR PROJECT 2020
4.2.1.8 Center of mass for ground floor
Page | 176
FINAL YEAR PROJECT 2020
4.2.2 Weight of first floor
4.2.2.1 Weight of slab for first floor
Page | 177
FINAL YEAR PROJECT 2020
4.2.2.2 Weight of column for first floor
description
γ (KN/m3)L (m) W (m) D (m) Weight (KN)
X (m) Y (m) W*X W*Y
C B1 25 0.4 0.4 3 12 0 0 0 0
C C1 25 0.4 0.4 3 12 0 3 0 36
C D1 25 0.4 0.4 3 12 0 6 0 72
C E1 25 0.4 0.4 3 12 0 9 0 108
C F1 25 0.4 0.4 3 12 0 12 0 144
C G1 25 0.4 0.4 3 12 0 15 0 180
C H1 25 0.4 0.4 3 12 0 18 0 216
C H2 25 0.4 0.4 3 12 3 18 36 216
C H3 25 0.4 0.4 3 12 6 18 72 216
C F3 25 0.4 0.4 3 12 6 12 72 144
C E3 25 0.4 0.4 3 12 6 9 72 108
C D3 25 0.4 0.4 3 12 6 6 72 72
C C3 25 0.4 0.4 3 12 6 3 72 36
C B3 25 0.4 0.4 3 12 6 0 72 0
C H4 25 0.4 0.4 3 12 9 18 108 216
C F4 25 0.4 0.4 3 12 9 12 108 144
C E4 25 0.4 0.4 3 12 9 9 108 108
C C'4 25 0.4 0.4 3 12 9 4.5 108 54
C B4 25 0.4 0.4 3 12 9 0 108 0
C H5' 25 0.4 0.4 3 12 13.5 18 162 216
C F5' 25 0.4 0.4 3 12 13.5 12 162 144
Page | 178
FINAL YEAR PROJECT 2020
description Length Thickness Height γ (KN/m3) Weight X(m) Y(m) W*X W*Y
PW1 7 0.15 3 14 44.1 3.7 15.075 163.17 664.81
PW2 2.71 0.1 3 14 11.382 1.355 12.7 15.42261 144.55
PW3 0.43 0.15 3 14 2.709 0.215 11.3 0.582435 30.612
PW4 1.69 0.15 3 14 10.647 1.745 11.63 18.57902 123.82
PW5 2.63 0.15 3 14 16.569 3.075 0.18 50.94968 2.9824
PW6 2.02 0.15 3 14 12.726 7.275 17.19 92.58165 218.76
Page | 179
FINAL YEAR PROJECT 2020
Page | 180
FINAL YEAR PROJECT 2020
4.2.2.4 Weight of beam on first floor
Page | 181
FINAL YEAR PROJECT 2020
Page | 182
FINAL YEAR PROJECT 2020
P-16 Beam B-C', @5' 25 4.5 0.25 0.4 11.25 13.5 2.45 151.88 27.56
Beam 4-5' @B 25 4.5 0.25 0.4 11.25 11.45 0.2 128.81 2.25
P-17 Beam E-C' @7 25 4.5 0.25 0.4 11.25 18 6.95 202.5 78.19
P-18 Beam 1-3 @A 25 3 0.25 0.4 7.5 1.5 -0.9 11.25 -6.75
Beam A-B @1 25 0.8 0.25 0.4 2 -0.1 -0.7 -0.2 -1.4
Beam A-B @2 25 0.8 0.25 0.4 2 3.075 -0.7 6.15 -1.4
P-19 Beam 3-4 @A 25 2.85 0.25 0.4 7.125 4.575 -0.7 32.597 -4.99
Beam A-B @3 25 1.76 0.25 0.4 4.4 6 -0.98 26.4 -4.31
p-20 Beam A-B @4 25 1.76 0.25 0.4 4.4 9 -0.98 39.6 -4.31
Beam 3-4 @A 25 3 0.25 0.4 7.5 7.5 -0.98 56.25 -7.35
Total 455.175 4202 4076
4.2.2.5 Wall on beam on first floor
Page | 183
FINAL YEAR PROJECT 2020
Page | 184
FINAL YEAR PROJECT 2020
4.2.2.6 Weight of shear wall on first floor
description
Length Thickness Height γ (KN/m3)Weight X(m) Y(m) W*X W*Y
1 1.7 0.2 3 25 25.5 10.55 9.85 269.025 251.18
2 1.7 0.2 3 25 25.5 12.05 9.85 307.275 251.18
3 1.5 0.2 3 25 22.5 10.55 9.1 237.375 204.75
4 1.5 0.2 3 25 22.5 10.55 10.4 237.375 234
total 96 1051.05 941.1
description
Length Thickness width γ (KN/m3)Weight X(m) Y(m) W * X W * Y
flight 3 1.8 0.17 1.1 25 8.415 11.195 11.31 94.20593 95.174
flight 2 1.17 0.17 1.89 25 9.39803 9.66 9.945 90.78492 93.463
fight 1 1.17 0.17 1.89 25 9.39803 12.695 9.945 119.3079 93.463
landing 1 1.15 0.17 1.1 25 5.37625 10.295 11.31 55.34849 60.805
landing 2 1.15 0.17 1.1 25 5.37625 12.67 11.31 68.11709 60.805
total 27.2111 304.2988 282.1
Page | 185
FINAL YEAR PROJECT 2020
4.2.2.8 Center of mass for first floor
Page | 186
FINAL YEAR PROJECT 2020
4.3.3 Weight second floor
4.3.3.1 Weight of slab for second floor
Page | 187
FINAL YEAR PROJECT 2020
4.3.3.2 Weight of column for second floor
Page | 188
FINAL YEAR PROJECT 2020
Page | 189
FINAL YEAR PROJECT 2020
Page | 190
FINAL YEAR PROJECT 2020
4.3.3.4 Weight of beam on second floor
description γ (KN/m3)
L (m) W (m) D (m) Weight (KN)
X (m) Y (m) W * X W * Y
P-1 Beam on G-H @ 1 25 2.6 0.25 0.4 6.5 -0.1 16.5 -0.65 107.3
Beam on F-G @ 1 25 2.6 0.25 0.4 6.5 -0.1 13.5 -0.65 87.75
Beam on 1 to 2 @ H 25 2.6 0.25 0.4 6.5 1.5 18.1 9.75 117.7
Beam on H-F @ 3 25 5.6 0.25 0.4 14 6 15 84 210
Beam on 2 to 3 @ H 25 2.6 0.25 0.4 6.5 4.5 18.1 29.25 117.7
Beam on 1 to 3 @ F 25 5.6 0.25 0.4 14 3 12 42 168
P-2 Beam on 3 to 4 @ H 25 2.6 0.25 0.4 6.5 7.5 18.1 48.75 117.7
Beam on 3 to 4 @ F 25 2.6 0.25 0.4 6.5 7.5 12 48.75 78
Beam on H-F @ 4 25 5.6 0.25 0.4 14 9 15 126 210
P-3 Beam on 4 to 5' @H 25 4.1 0.25 0.4 10.25 11.25 18.1 115.3 185.5
Beam on 4 to 5' @F 25 4.1 0.25 0.4 10.25 11.25 12 115.3 123
Beam on H-F @ 5' 25 5.6 0.25 0.4 14 13.5 15 189 210
P-4 Beam on 5' to 7 @ H 25 4.1 0.25 0.4 10.25 15.75 18.1 161.4 185.5
Beam on 5' to 7 @ F 25 4.1 0.25 0.4 10.25 15.75 12 161.4 123
Beam on H-F @ 7 25 5.6 0.25 0.4 14 18 15 252 210
P-5 Beam on G-F @ 8 25 2.6 0.25 0.4 6.5 21 13.5 136.5 87.75
Beam on H-G @ 8 25 2.6 0.25 0.4 6.5 21 16.5 136.5 107.3
Beam on 7 to 8 @H 25 2.6 0.25 0.4 6.5 19.5 18.1 126.8 117.7
Beam on 7 to 8 @F 25 2.6 0.25 0.4 6.5 18 12 117 78
P-6 Beam on E-F @ 1 25 2.6 0.25 0.4 6.5 -0.1 10.5 -0.65 68.25
Beam on E-F @ 3 25 2.6 0.25 0.4 6.5 6 10.5 39 68.25
Beam on 1 to 3 @ E 25 5.6 0.25 0.4 14 3 9 42 126
Page | 191
FINAL YEAR PROJECT 2020
Page | 192
FINAL YEAR PROJECT 2020
P-17 Beam E-C' @7 25 4.5 0.25 0.4 11.25 18 6.95 202.5 78.19
P-18 Beam 1-3 @A 25 3 0.25 0.4 7.5 1.5 -0.9 11.25 -6.75
Beam A-B @1 25 0.8 0.25 0.4 2 -0.1 -0.7 -0.2 -1.4
Beam A-B @2 25 0.8 0.25 0.4 2 3.075 -0.7 6.15 -1.4
P-19 Beam 3-4 @A 25 2.85 0.25 0.4 7.125 4.575 -0.7 32.6 -4.988
Beam A-B @3 25 1.76 0.25 0.4 4.4 6 -0.98 26.4 -4.312
p-20 Beam A-B @4 25 1.76 0.25 0.4 4.4 9 -0.98 39.6 -4.312
Beam 3-4 @A 25 3 0.25 0.4 7.5 7.5 -0.98 56.25 -7.35
Total 455.175 4202 4076
4.3.3.5 Weight of wall on beam of second floor
Page | 193
FINAL YEAR PROJECT 2020
Page | 194
FINAL YEAR PROJECT 2020
Page | 195
FINAL YEAR PROJECT 2020
4.3.3.7 Weight of stair on second floor
Page | 196
FINAL YEAR PROJECT 2020
4.3.4 Weight of 3rd floor
Page | 197
FINAL YEAR PROJECT 2020
4.3.4.2 Weight of column for third floor
Page | 198
FINAL YEAR PROJECT 2020
Page | 199
FINAL YEAR PROJECT 2020
Page | 200
FINAL YEAR PROJECT 2020
4.3.4.4 Weight of wall on beam of third floor
Page | 201
FINAL YEAR PROJECT 2020
4.3.4.5 Weight of beam on third floor
Page | 202
FINAL YEAR PROJECT 2020
Page | 204
FINAL YEAR PROJECT 2020
4.3.4.8 Center of mass for third floor
Page | 205
FINAL YEAR PROJECT 2020
4.3.5 Weight of slab for fourth floor
Page | 206
FINAL YEAR PROJECT 2020
4.3.5.2 Weight of column on fourth floor
Page | 207
FINAL YEAR PROJECT 2020
Page | 208
FINAL YEAR PROJECT 2020
Page | 210
FINAL YEAR PROJECT 2020
Page | 211
FINAL YEAR PROJECT 2020
description γ (KN/m3)
L (m) W (m) D (m) Weight (KN) X (m) Y (m) W * X W * Y
P-1 Beam on G-H @ 1 25 2.6 0.25 0.4 6.5 -0.1 16.5 -0.65 107.25
Beam on F-G @ 1 25 2.6 0.25 0.4 6.5 -0.1 13.5 -0.65 87.75
Beam on 1 to 2 @ H 25 2.6 0.25 0.4 6.5 1.5 18.1 9.75 117.65
Beam on H-F @ 3 25 5.6 0.25 0.4 14 6 15 84 210
Beam on 2 to 3 @ H 25 2.6 0.25 0.4 6.5 4.5 18.1 29.25 117.65
Beam on 1 to 3 @ F 25 5.6 0.25 0.4 14 3 12 42 168
P-2 Beam on 3 to 4 @ H 25 2.6 0.25 0.4 6.5 7.5 18.1 48.75 117.65
Beam on 3 to 4 @ F 25 2.6 0.25 0.4 6.5 7.5 12 48.75 78
Beam on H-F @ 4 25 5.6 0.25 0.4 14 9 15 126 210
P-3 Beam on 4 to 5' @H 25 4.1 0.25 0.4 10.25 11.25 18.1 115.313 185.525
Beam on 4 to 5' @F 25 4.1 0.25 0.4 10.25 11.25 12 115.313 123
Beam on H-F @ 5' 25 5.6 0.25 0.4 14 13.5 15 189 210
P-4 Beam on 5' to 7 @ H 25 4.1 0.25 0.4 10.25 15.75 18.1 161.438 185.525
Beam on 5' to 7 @ F 25 4.1 0.25 0.4 10.25 15.75 12 161.438 123
Beam on H-F @ 7 25 5.6 0.25 0.4 14 18 15 252 210
Page | 212
FINAL YEAR PROJECT 2020
P-5 Beam on G-F @ 8 25 2.6 0.25 0.4 6.5 21 13.5 136.5 87.75
Beam on H-G @ 8 25 2.6 0.25 0.4 6.5 21 16.5 136.5 107.25
Beam on 7 to 8 @H 25 2.6 0.25 0.4 6.5 19.5 18.1 126.75 117.65
Beam on 7 to 8 @F 25 2.6 0.25 0.4 6.5 18 12 117 78
P-6 Beam on E-F @ 1 25 2.6 0.25 0.4 6.5 -0.1 10.5 -0.65 68.25
Beam on E-F @ 3 25 2.6 0.25 0.4 6.5 6 10.5 39 68.25
Beam on 1 to 3 @ E 25 5.6 0.25 0.4 14 3 9 42 126
P-7 Beam on 3 to 4 @E 25 2.6 0.25 0.4 6.5 4.5 9 29.25 58.5
Beam on E-F @ 4 25 2.6 0.25 0.4 6.5 9 10.5 58.5 68.25
P-9 Beam on E-F @5' 25 2.6 0.25 0.4 6.5 13.5 10.5 87.75 68.25
Beam on E-F @7 25 2.6 0.25 0.4 6.5 18 10.5 117 68.25
Beam on 5' to 7 @ E 25 4.1 0.25 0.4 10.25 15.75 9 161.438 92.25
P-10 Beam on 7 to 8, @E 25 2.6 0.25 0.4 6.5 19.5 9 126.75 58.5
Beam on E-F @8 25 2.6 0.25 0.4 6.5 21 10.5 136.5 68.25
P-11 Beam on E-D @ 1 25 2.6 0.25 0.4 6.5 -0.1 7.5 -0.65 48.75
Beam on 1 to 3 @ D 25 5.6 0.25 0.4 14 3 6 42 84
Beam on E-D @ 3 25 2.6 0.25 0.4 6.5 6 7.5 39 48.75
P-12 Beam on 3 to 4 @ C 25 5.6 0.25 0.4 14 7.5 3 105 42
Beam on D-C @ 1 25 2.6 0.25 0.4 6.5 -0.1 4.5 -0.65 29.25
Beam on D-C @ 3 25 2.6 0.25 0.4 6.5 6 4.5 39 29.25
P-13 Beam 1 to 3 @B 25 5.6 0.25 0.4 14 3 0 42 0
Beam B-C @ 1 25 2.6 0.25 0.4 6.5 -0.1 1.5 -0.65 9.75
Beam B-C @3 25 2.6 0.25 0.4 6.5 6 1.5 39 9.75
P-14 Beam E-C' @4 25 4.1 0.25 0.4 10.25 9 6.75 92.25 69.1875
Beam C'-B @4 25 4.1 0.25 0.4 10.25 9 2.25 92.25 23.0625
P-15 Beam 4 to 5' @E 25 4.1 0.25 0.4 10.25 11.25 9 115.313 92.25
Beam 4 to 5' @C' 25 4.5 0.25 0.4 11.25 8.45 4.5 95.0625 50.625
Beam E-C' @5' 25 4.5 0.25 0.4 11.25 13.5 6.75 151.875 75.9375
Page | 213
FINAL YEAR PROJECT 2020
P-16 Beam B-C', @5' 25 4.5 0.25 0.4 11.25 13.5 2.45 151.875 27.5625
Beam 4-5' @B 25 4.5 0.25 0.4 11.25 11.45 0.2 128.813 2.25
P-17 Beam E-C' @7 25 4.5 0.25 0.4 11.25 18 6.95 202.5 78.1875
P-18 Beam 1-3 @A 25 3 0.25 0.4 7.5 1.5 -0.9 11.25 -6.75
Beam A-B @1 25 0.8 0.25 0.4 2 -0.1 -0.7 -0.2 -1.4
Beam A-B @2 25 0.8 0.25 0.4 2 3.075 -0.7 6.15 -1.4
P-19 Beam 3-4 @A 25 2.85 0.25 0.4 7.125 4.575 -0.7 32.5969 -4.9875
Beam A-B @3 25 1.76 0.25 0.4 4.4 6 -0.98 26.4 -4.312
p-20 Beam A-B @4 25 1.76 0.25 0.4 4.4 9 -0.98 39.6 -4.312
Beam 3-4 @A 25 3 0.25 0.4 7.5 7.5 -0.98 56.25 -7.35
Total 455.175 4202.02 4076.45
Page | 214
FINAL YEAR PROJECT 2020
4.3.5.7 Weight of stair on fourth floor
Page | 215
FINAL YEAR PROJECT 2020
4.3.6 Weight of roof
Slab type
γ
descrip- L W D W W of W To- X Y
(KN/ W*X W*Y
tion (m) (m) (m) (KN) CC tal (m) (m)
m3)
0.1
s15 25 4 4 68 11.04 79.04 11 6.5 869.44 513.76
7
0.1 86.062 13.972 100.03 11.2 2.2 1125.39 225.078
s16 25 4.5 4.5
7 5 5 5 5 5 4 8
0.1 86.062 13.972 100.03 15.7 6.7 1575.55 675.236
s17 25 4.5 4.5
7 5 5 5 5 5 1 3
-
0.1 297.525 -
s18 25 5.8 1.76 43.384 7.044 50.428 5.9 0.8
7 2 44.3766
8
0.1 121.72 18.8 2297.50
s19 25 1.76 14 104.72 17.002 7 852.054
7 2 8 3
0.1
s20 25 3.4 1 14.45 2.346 16.796 1.5 -0.5 25.194 -8.398
7
402.67 468.05 6190.60 2213.35
slab type 65.377
9 6 7 4
Truss type
Page | 216
FINAL YEAR PROJECT 2020
Page | 217
FINAL YEAR PROJECT 2020
Page | 218
FINAL YEAR PROJECT 2020
β, design response factor
αo=0.05)
T = CH3/4 H=17.5m
Page | 219
FINAL YEAR PROJECT 2020
= 1.00 for regular structures
γ = 0.2 x 1.5 x 1 x1
Sd (T) = αβγ
= 0.04
description Weight
On ground 4190.689
On first 3952.38
On second 3985.56
On third 4117.034
On fourth 4088.22
On roof 759.06
Total 21092.943
Fb = Sd(T1)WT
Page | 220
FINAL YEAR PROJECT 2020
= 0.04 * 21092.943
= 843.72 KN
= 37.92KN
Portion of the base shear distributed over the height of the structure
(843.72 – 37.92)W i h i
Fi =
ΣW jh j
805.8W i h i
=
Σ W jh j
Lateral forces from earth quake loads at each floor are tabulated as shown below.
Page | 221
FINAL YEAR PROJECT 2020
Accidental eccentricity
Where: eu = accidental eccentricity of story mass I from its normal location applied in the same
Lx = 19.96
Ly = 21.4
ex = ± 0.05 Lx
ey = ± 0.05 Ly
Page | 222
FINAL YEAR PROJECT 2020
CHAPTER FIVE
BEAM AND COLUMN DESIGN
Page | 223
FINAL YEAR PROJECT 2020
Depth determination
D = 400 mm
B = 250 mm
fcd=11.33MPa
-Stirrup - Ø 8mm
( f l
)
d≥ 0 . 4+ 0 .6 yk e , f yk =300 MPa
400 β a
300 l e l
(
d≥ 0 . 4+ 0 .6
400 β a)=0 . 85 e
βa
Exterior span
le = 2.8m ßa = 24
d ≥ (0.85)* 2800/24 = 99.2mm
Interior span
le =2.8m ßa = 28
d ≥ (0.85) *2800/28 = 85mm
Overall depth, D = d + cover + Ø/2 + Østtirup
D = 99.2 +25+7+8
= 139.2mm < Dused = 400mm……………………ok!
Page | 224
FINAL YEAR PROJECT 2020
.
Page | 225
FINAL YEAR PROJECT 2020
To check whether the Floor beams are singly reinforced or doubly reinforced we checked for the
maximum support moment as shown below.
→ If μ> μmax = 0.294(for 0% , redistribution of elastic moment, double reinforcement)
Mu 10.67∗106
μ = fcd . b . d
2 = 11.33∗250∗3602
= 0.029
μ=0.029< μmax = (0.294) (design as single reinforced beam)
Singly reinforcement is enough, i.e. no compression reinforcement is needed.
Design for Support Moment
For support at -left
→ Msupport = 6.47
→ Mu = 0.9 *6.47 = 5.823KN
Mu
μ=
fcd . b . d 2
, d = 400-25-8-14/2 =360
b = 250mm
5.823∗10 6
μ= 2
z = 0.022
11.33∗250∗360
Page | 226
FINAL YEAR PROJECT 2020
Provide reinforcement : for single reinforced beam
Mu
As =
fyd∗Z
d
Z= (1+√ 1−2 μ ¿ ¿ , d= 360 , μ = 0.022
2
360
Z= (1+√ 1−2∗0.022¿ ¿ = 356mm
2
MU 5.823∗106
As =
fyd . z
= = 62.7 mm2<Asmin=180 mm2
356∗260.87
Number of bar(N) (using ∅ =14)
180
N=As/as = π 2 = 1.17
14
4
∴Provide 2∅ 14mm bars
For support at- right
Msupport = 11.857(at the center of column)
Mu = 0.9*11.857=10.67KN.m
6
Mu 10.67∗10
μ = fcd . b . d 2 = 11.33∗250∗360
2 = 0.029
μ=0.029< μmax =(0.294) ( design as single reinforced beam)
MU
As = fyd . z
d 360
Z= 2 (1+√
1−2 μ = 2 (1+√
1−2∗0.029 = 355mm
10.67∗106
As = 260.87∗355
= 115.22mm2<Asmin=180 mm2
Page | 227
FINAL YEAR PROJECT 2020
Number of bar(N) = (use ∅ = 14)
180
As
N= = π 142 = 1.17
as
4
Mu 5.93∗10 6
μ = fcd . b . d
2 = 11.33∗250∗. 3602
= 0.016< μmax =0.294
Provide reinforcement
MU
As = fyd . z
d 360
Z= 2 (1+√
1−2 μ )= 2 (1+√
1−2∗0.016 ) = 177.09mm
5.93∗106
As = 260.87∗177.09
= 128.36mm2 <Asmin=180 mm2
Number of bar (use ∅ = 14mm)
180
N = As/as = π∗142 = 1.169 use 2
4
For other are calculated in the same way & tabulated as follows
Page | 228
FINAL YEAR PROJECT 2020
Page | 229
FINAL YEAR PROJECT 2020
Axis-1 Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis B 1.209 0.003 359.4592 12.892562 180 180 2ɸ 14
Axis-B b/n C 0.605 0.002 359.6396 6.4483769 180 180 2ɸ 14
At Axis C 0.13 0 360 1.3842145 180 180 2ɸ 14
At Axis C 2.106 0.006 358.9167 22.491957 180 180 2ɸ 14
Axis-C b/n-D 1.053 0.003 359.4592 11.229006 180 180 2ɸ 14
At Axis -D 1.756 0.005 359.0977 18.744525 180 180 2ɸ 14
At Axis -D 1.632 0.004 354.5165 17.645999 180 180 2ɸ 14
Axis-D b/ E 0.816 0.002 356.1795 8.7818049 180 180 2ɸ 14
At Axis E 0.917 0.002 352.2742 9.9781733 180 180 2ɸ 14
At Axis E 4.567 0.012 333.7921 52.44662 180 180 2ɸ 14
At Axis E b/n-F 2.428 0.007 338.9717 27.456665 180 180 2ɸ 14
Axis-F 4.855 0.013 314.4589 59.181761 180 180 2ɸ 14
Axis-F 2.683 0.007 358.7356 28.668749 180 180 2ɸ 14
At Axis F b/n-G 1.342 0.004 359.2786 14.318045 180 180 2ɸ 14
Axis-G 2.82 0.037 353.212 30.60386 180 180 2ɸ 14
Axis-G 2.518 0.018 356.7303 27.056915 180 180 2ɸ 14
At Axis-G b/n-H 1.259 0.022 355.9955 13.556381 180 180 2ɸ 14
Axis-H 1.152 0.003 359.4592 12.284724 180 180 2ɸ 14
Page | 230
FINAL YEAR PROJECT 2020
Axis-3 Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis B 6.387 0.017 356.9135 68.59564 180 180 2ɸ 14
Axis-B b/n C 3.808 0.01 358.1909 40.75163 180 180 2ɸ 14
At Axis C 7.615 0.021 356.1795 81.95275 180 180 2ɸ 14
At Axis C 3.79 0.01 358.1909 40.559 180 180 2ɸ 14
Axis-C b/n-D 3.93 0.011 358.009 42.07859 180 180 2ɸ 14
At Axis -D 7.858 0.021 356.1795 84.56792 180 180 2ɸ 14
At Axis -D 4.228 0.012 357.8269 45.29232 180 180 2ɸ 14
Axis-D b/ E 4.66 0.013 357.6446 49.94555 180 180 2ɸ 14
At Axis E 9.32 0.025 355.4423 100.51 180 180 2ɸ 14
At Axis E 6.993 0.019 356.5469 75.18123 180 180 2ɸ 14
At Axis E b/n-F 4.65 0.013 357.6446 49.83837 180 180 2ɸ 14
Axis-F 9.3 0.025 355.4423 100.2943 180 180 2ɸ 14
Axis-F 69.068 0.188 322.1886 821.7302 180 821.73021 5ɸ 14
At Axis F b/n-H 34.534 0.094 342.1999 386.8384 180 386.83837 3ɸ 14
Axis-H 67.509 0.037 353.212 732.6369 180 180 2ɸ 14
Page | 231
FINAL YEAR PROJECT 2020
Axis-3 Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis B 1.433 0.004 359.2786 15.28894 180 180 2ɸ 14
Axis-B b/n C 0.821 0.002 359.6396 8.750607 180 180 2ɸ 14
At Axis C 1.642 0.021 356.1795 17.67123 180 180 2ɸ 14
At Axis C 4.434 0.01 358.1909 47.45082 180 180 2ɸ 14
Axis-C b/n-D 2.217 0.011 358.009 23.73746 180 180 2ɸ 14
At Axis -D 0.814 0.021 356.1795 8.760281 180 180 2ɸ 14
At Axis -D 6.418 0.012 357.8269 68.75262 180 180 2ɸ 14
Axis-D b/ E 3.209 0.013 357.6446 34.39383 180 180 2ɸ 14
At Axis E 0.316 0.025 355.4423 3.40785 180 180 2ɸ 14
At Axis E 6.443 0.019 356.5469 69.26822 180 180 2ɸ 14
At Axis E b/n-F 3.222 0.013 357.6446 34.53317 180 180 2ɸ 14
Axis-F 4.329 0.025 355.4423 46.68539 180 180 2ɸ 14
Axis-F 78.701 0.214 322.1886 936.3379 180 936.3379475 5ɸ 14
At Axis F b/n-H 39.35 0.107 339.582 444.1837 180 444.1837012 4ɸ 14
Axis-H 78.696 0.214 316.1352 954.2064 180 954.2064483 5ɸ 14
Page | 232
FINAL YEAR PROJECT 2020
Axis-3 Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis B 1.618 0.004 359.2786 17.26273927 180 180 2ɸ 14
Axis-B b/n C 1.654 0.005 359.0977 17.6557197 180 180 2ɸ 14
At Axis C 3.307 0.009 358.3726 35.37218934 180 180 2ɸ 14
At Axis C 1.735 0.005 359.0977 18.52035893 180 180 2ɸ 14
Axis-C b/n-D 2.176 0.006 358.9167 23.23955291 180 180 2ɸ 14
At Axis -D 4.351 0.012 357.8269 46.60995042 180 180 2ɸ 14
At Axis -D 0.314 0.001 359.8199 3.345083886 180 180 2ɸ 14
Axis-D b/ E 3.394 0.009 358.3726 36.30275495 180 180 2ɸ 14
At Axis E 6.788 0.018 356.7303 72.93976811 180 180 2ɸ 14
At Axis E 3.208 0.009 358.3726 34.31326985 180 180 2ɸ 14
At Axis E b/n-F 5.23 0.014 357.4621 56.08338653 180 180 2ɸ 14
Axis-F 10.452 0.028 354.8874 112.8941309 180 180 2ɸ 14
Axis-F 79.245 0.216 315.6584 962.3145728 180 962.314573 5ɸ 14
At Axis F b/n-H 39.623 0.108 339.3788 447.5331275 180 447.533128 3ɸ 14
Axis-H 78.452 0.214 316.1352 951.2478942 180 951.247894 5ɸ 14
Page | 233
FINAL YEAR PROJECT 2020
Table 5. 51st Floor beam Reinforcement design
For First Floor Beam
1st Floor Beam Reinforcement Design
Axis-F Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis 1 69.915 0.019 321.7321 832.9876 180 832.9876 4ɸ 14
Axis-1 b/n 3 35.9985 0.098 341.3989 404.1893 180 404.1893 3ɸ 14
At Axis 3 71.997 0.01 457.6884 602.9857 180 602.9857 3ɸ 14
At Axis 3 6.469 0.018 356.7303 69.51199 180 180 2ɸ 14
Axis-3 b/n-4 5.9285 0.016 357.0966 63.63875 180 180 2ɸ 14
At Axis -4 11.857 0.032 354.1448 128.3384 180 180 2ɸ 14
At Axis -4 11.121 0.03 354.5165 120.2458 180 180 2ɸ 14
Axis-4 b/n-5' 7.68 0.021 356.1795 82.65228 180 180 2ɸ 14
'
At Axis 5 15.361 0.042 352.2742 167.148 180 180 2ɸ 14
At Axis 5' 49.46 0.135 333.7921 567.9899 180 567.9899 3ɸ 14
At Axis 5' b/n-7 40.485 0.011 338.9717 457.8184 180 457.8184 3ɸ 14
Axis-7 80.97 0.221 314.4589 987.0128 180 987.0128 5ɸ 14
Axis-7 13.419 0.037 353.212 145.6288 180 180 2ɸ 14
At Axis-7 b/n-8 6.709 0.018 356.7303 72.09088 180 180 2ɸ 14
Axis-8 8.088 0.022 355.9955 87.08817 180 180 2ɸ 14
Page | 234
FINAL YEAR PROJECT 2020
Table 5. 6Grade beam Reinforcement design
For Ground Floor Beam
Grade Beam Reinforcement Design
Axis-F Mu(KN.m) µ Z As(cal) As(min) As(prov) No of bar
At Axis 1 6.87 0.01 457.6884 57.53729 276 276 2ɸ 16
Axis-1 b/n 3 3.759 0.005 458.8471 31.40269 276 276 2ɸ 16
At Axis 3 7.518 0.01 457.6884 62.96438 276 276 2ɸ 16
At Axis 3 21.629 0.03 452.9933 183.0236 276 276 2ɸ 16
Axis-3 b/n-4 10.8145 0.015 456.5237 90.80414 276 276 2ɸ 16
At Axis -4 21.561 0.03 452.9933 182.4482 276 276 2ɸ 16
At Axis -4 6.38 0.009 457.9206 53.40637 276 276 2ɸ 16
Axis-4 b/n-5' 3.2775 0.005 458.8471 27.38024 276 276 2ɸ 16
'
At Axis 5 6.555 0.009 457.9206 54.87128 276 276 2ɸ 16
At Axis 5' 15.975 0.022 454.8831 134.6181 276 276 2ɸ 16
At Axis 5' b/n-7 7.9875 0.011 457.4559 66.93052 276 276 2ɸ 16
Axis-7 11.919 0.017 456.0562 100.1807 276 276 2ɸ 16
Axis-7 26.147 0.036 451.5653 221.9544 276 276 2ɸ 16
At Axis-7 b/n-8 13.0735 0.018 455.8221 109.9408 276 276 2ɸ 16
Axis-8 19.92 0.028 453.4672 168.386 276 276 2ɸ 16
Page | 235
FINAL YEAR PROJECT 2020
Design for shear
The minimum web reinforcement,
0.4 0. 4
ρmin = = =0.00133
f yk 300 [EBCS 2/95 part 2, sec.7.2.1.1]
The maximum spacing between stirrups
2
S max =0. 5 d <300 mm , if V sd < V rd
3
2
S max =0. 3 d <200 mm , if V sd < V rd
3 [EBCS 2/95 part 2, sec.3.5.4.1b]
Page | 236
FINAL YEAR PROJECT 2020
Span – 10
36.0
4.65-X
52.0
By Triangle similarity
52.0(4.65-X)=36.0X
241.8-52X=36X
X=2.747m
36
2.75
1.90
52.0
Page | 237
FINAL YEAR PROJECT 2020
d=400-25-8-20/2=357mm=0.357
0.4
2.75−(0.357 + )
vcr1L= 2 *52.0=44.84
2.75
0.4
1.9−(0.357+ )
vcr1R= 2 *36=25.45
1.9
Vrd=0.25fcd*bw*d
Vrd=0.25*11.33*250*357*10^-3=252.8KN
Vc = 0.25fctd*k1*k2*bw*d
(ɪ)For left
K1=1+50p=1+50(4*153.86)/ (250*410)
K2=1.6-d=1.6-0.410=1.19
(ɪɪ)for right
K1=1+50p=1+50(5*153.86)/(250*410)
K2=1.6-d=1.6-0.410=1.19
Vc L= 0.25fctd*k1*k2*bw*d
VcL = 0.25*1*1.3*1.19*250*410*10^-3
Page | 238
FINAL YEAR PROJECT 2020
VcL = 39.64KN
Vc R= 0.25fctd*k1*k2*bw*d
VcR = 0.25*1*1.375*1.19*250*410*10^-3
VcR = 66.94KN
Avdfyd
Smax=
0. 4 bw
Use Φ=8mm
2
π (8)
∗250
Smax= 4 =125.6mm
0.4∗250
Hence, Vsd < Vc, the section is adequate and 8mm c/c @ 120mm shall be provided for nom-
inal web reinforcement for the whole span.
Page | 239
FINAL YEAR PROJECT 2020
For buildings, a design method may be used which assumes the compression members to be iso-
lated. The additional eccentricity induced in the column by its deflection is then calculated as a
function of slenderness ratio and curvature at the critical section.
N sd
≤ 0.1
N cr
In beam-and-column type plane frames in building structures with beams connecting each col-
umn at each story level may be classified as non-sway for a given load case, when first-order the-
ory is used, the horizontal displacements in each story due to the design loads (both horizontal
and vertical), plus the initial sway imperfection satisfy the following criteria:
Nδ
≤ 0.1
HL
Where: δ is the horizontal displacement at the top of the story, relative to the bottom of the story.
Page | 240
FINAL YEAR PROJECT 2020
H is the total horizontal reaction at the bottom of the story
Since the columns are in non-sway mode, it is better to assume that the whole frame is a non-
sway type frame. In addition, by considering the frame as sway, the design of the columns will
be a safe design.
Page | 241
FINAL YEAR PROJECT 2020
Unbalanced moments from beams
The bending moments can be converted in to un-equivalent axial load applied at eccentricity.
Therefore columns should be designed for the design moment obtained from the total eccentric-
ity.
According to EBCS 2 for column with constant section isolated or belonging to a frame the slen-
derness is defined by
√ √ √ √
3 2 2
I b∗h /12 = h = 0.4 =0.1155
= =
Ag b∗h 12 12
αm+0.4
Le =L* αm+0.8 ≥ 0.7L [EBCS 2 1995]
Kc 1+ Kc 2 Kc 1+ Kc 3 α 1+α 2
α1 = Kb1+ Kb 2 α2 = Kb3+ Kb 4 αm = 2
In this project column at the intersection of Axis-F and Axis-3 for 1st floor is selected for design.
Page | 242
FINAL YEAR PROJECT 2020
Mo-
ment of inertia of beams and columns in X-X direction
= 0.00213/3
= 0.000711m2
Page | 243
FINAL YEAR PROJECT 2020
Kc3 = 0.00213/L
= 0.00213/1.8
2
= 0.00118m
= 0.00189/6 = 0.00063m3
=0.000315m3
= 0.00521/6 = 0.00173m3
=0.000868m3
Moment of inertia of beams and columns in Y-Y direction
= 0.00213/3
= 0.000711m2
Kc3 = 0.00213/L
= 0.00213/1.8
= 0.00118m2
Page | 244
FINAL YEAR PROJECT 2020
Kb1= 0.00133/L Kb2=0.00133/3
= 0.00189/6 = 0.00063m3
=0.000315m3
Kb3 =0.00312/L Kb4 =0.00312/3
= 0.00521/6 = 0.00173m3
=0.000868m3
0.000711+0.00118
α1 = 0.00063+0.000868 α2 = 0.000711+ 0.000711
0.000315+ 0.00173
= 1.262 = 0.695
1.262+ 0.695
αm =
2
αm =0.978
0.978+0.4
Le = 3* =2.32m, λ(x)=Le/i=(2.32/0.1155)=20.08
0.978+0.8
= 1.262 = 0.695
1.262+ 0.695
αm = 2
αm =0.978
Page | 245
FINAL YEAR PROJECT 2020
0.978+0.4
Le = 3* =2.32m, λ(x)=Le/i=(2.32/0.1155)=20.08
0.978+0.8
In x-direction
In y-direction
Design actions
Pd =1183.47KN
Page | 246
FINAL YEAR PROJECT 2020
(0.02423, 0.01816)
ee = 0.02423
(0.02423, 0.01816)
ee = 0.02423
Nsd = 1183.47KN
Reinforcement calculations
Page | 247
FINAL YEAR PROJECT 2020
Nsd 1183.47∗0.001
νsd = fcd∗Ac = 11.33∗0.4∗0.4 = 0.65
Msdx−x 52.345∗0.001
μsd x-x = fcd∗Ac∗h = 11.33∗0.4∗0.4∗0.4 = 0.0721
Msdy− y 52.345∗0.001
μsd y-y = fcd∗Ac∗b = 11.33∗0.4∗0.4∗0.4 = 0.0721
All the above values of ω for each values of ν are interpolated on the respective μ values from
the chart chosen.
0.789∗Ac∗f cd 0.789∗0.4∗0.4∗11.33
As,tot = = = 0.005482m2 = 5482.80mm2
f yd 260.87
On the choosen frame, column cross section on1st floor to 2ndfloor is 400*400mm
Page | 248
FINAL YEAR PROJECT 2020
= 0.00213/3
= 0.000711m2
= 0.00133/6 = 0.000443m3
=0.000221m3
Moment of inertia of beams and columns in Y-Y direction
= 0.00213/3
= 0.000711m2
= 0.00133/6 = 0.000443m3
=0.000221m3
0.000711+0.000711
α1 = 0.000443+0.000221 α2 = 0.000711+0.000711
0.000221+ 0.000443
= 2.145 = 2.145
2.145+2.145
αm = 2
αm =2.145
2.145+0.4
Le = 3* =2.59m, λ(x)=Le/i=(2.59/0.1155)=22.44
2.145+0.8
0.000711+0.000711
α1 = 0.000443+0.000221 α2 = 0.000711+0.000711
0.000221+ 0.000443
= 2.145 = 2.145
2.145+2.145
αm = 2
αm =2.145
Page | 250
FINAL YEAR PROJECT 2020
2.145+0.4
Le = 3* =2.59m, λ(x)=Le/i=(2.59/0.1155)=22.44
2.145+0.8
To check the slenderness of the column
In x-direction
In y-direction
Design actions
Pd = 901.37KN
Page | 251
FINAL YEAR PROJECT 2020
(0.0455, 0.0107)
ee = 0.0455
(0.0455, 0.0107)
ee = 0.0455
Nsd = 901.37KN
Reinforcement calculations
Page | 252
FINAL YEAR PROJECT 2020
Nsd 901.37∗0.001
νsd = = = 0.497
fcd∗Ac 11.33∗0.4∗0.4
Msdx−x 59.04∗0.001
μsd x-x = = = 0.081
fcd∗Ac∗h 11.33∗0.4∗0.4∗0.4
Msdy − y 59.04∗0.001
μsd y-y = = = 0.081
fcd∗Ac∗b 11.33∗0.4∗0.4∗0.4
All the above values of ω for each values of ν are interpolated on the respective μ values from
the chart chosen.
0.535∗Ac∗f cd 0.535∗0.4∗0.4∗11.33
As,tot = = = 0.0037177m2 = 3717.744mm2
f yd 260.87
On the choosen frame, column cross section on 2nd floor to 3rd floor is 400*400mm
Page | 253
FINAL YEAR PROJECT 2020
Le=2.59m, λ(x)=Le/i=(2.59/0.1155)=22.44
In x-direction
In y-direction
Design actions
Pd = 594.87KN
Page | 254
FINAL YEAR PROJECT 2020
M1 = 15.14KNm (Y-Y direction)
(0.0851, 0.05)
ee = 0.0851
(0.0851, 0.05)
ee = 0.0851
Page | 255
FINAL YEAR PROJECT 2020
etot= 0.0851 + 0.02 +0.00 = 0.1051( Y-Y direction)
Nsd = 594.87KN
Reinforcement calculations
Nsd 594.87∗0.001
νsd = = = 0.328
fcd∗Ac 11.33∗0.4∗0.4
Msdx−x 62.52∗0.001
μsd x-x = = = 0.086
fcd∗Ac∗h 11.33∗0.4∗0.4∗0.4
Msdy − y 62.52∗0.001
μsd y-y = = = 0.086
fcd∗Ac∗b 11.33∗0.4∗0.4∗0.4
All the above values of ω for each values of ν are interpolated on the respective μ values from
the chart chosen.
0.802∗Ac∗f cd 0.802∗0.4∗0.4∗11.33
As,tot = = = 0.005573m2 = 5573.14mm2
f yd 260.87
Page | 256
FINAL YEAR PROJECT 2020
Provide 12no of 24mmØ rods
On the choosen frame, column cross section on 3rd floor to 4th floor is 400*400mm
Le=2.59m, λ(x)=Le/i=(2.59/0.1155)=22.44
Design actions
Pd = 301.98KN
Page | 257
FINAL YEAR PROJECT 2020
M1 = 10.95KNm (Y-Y direction)
(0.1314, 0.078)
ee = 0.1314
Nsd = 301.98KN
Reinforcement calculations
Page | 258
FINAL YEAR PROJECT 2020
Nsd 301.98∗0.001
νsd = = = 0.166
fcd∗Ac 11.33∗0.4∗0.4
Msdx−x 45.71∗0.001
μsd x-x = = = 0.063
fcd∗Ac∗h 11.33∗0.4∗0.4∗0.4
Msdy − y 45.71∗0.001
μsd y-y = = = 0.063
fcd∗Ac∗b 11.33∗0.4∗0.4∗0.4
All the above values of ω for each values of ν are interpolated on the respective μ values from
the chart chosen.
0.606∗Ac∗f cd 0.606∗0.4∗0.4∗11.33
As,tot = = = 0.004211m2 = 4211.13mm2
f yd 260.87
On the choosen frame, column cross section on 4th floor to roof is 400*400mm
Page | 259
FINAL YEAR PROJECT 2020
Le=2.59m, λ(x)=Le/i=(2.59/0.1155)=22.44
To check the slenderness of the column
Design actions
Pd = 9.39KN
Page | 260
FINAL YEAR PROJECT 2020
Calculation of eccentricities in X-X and Y-Y direction
(4.6, 2.35)
ee = 4.6
Nsd = 9.39KN
Reinforcement calculations
Nsd 9.39∗0.001
νsd = = = 0.00517
fcd∗Ac 11.33∗0.4∗0.4
Msdx−x 43.38∗0.001
μsd x-x = = = 0.059
fcd∗Ac∗h 11.33∗0.4∗0.4∗0.4
Page | 261
FINAL YEAR PROJECT 2020
Msdy − y 43.38∗0.001
μsd y-y = = = 0.059
fcd∗Ac∗b 11.33∗0.4∗0.4∗0.4
All the above values of ω for each values of ν are interpolated on the respective μ values from
the chart chosen.
0.245∗Ac∗f cd 0.2450.4∗0.4∗11.33
As,tot = = = 0.0017025m2 = 1702.518mm2
f yd 260.87
Lateral ties
= 6mm
= 280mm
Max shear force =47.27KN, it occurs at the 4th floor with Nsd=471.06KN
Page | 262
FINAL YEAR PROJECT 2020
Limiting value of ultimate shear force:
v RD =0.25 f cd b w d
= 0.25*11.33*400*400*0.001
Vc = 0.25*fctd*k1*k2*bw*d
k1 = (1+50*0.0226) = 2.131>2
=2
= 1.243
Vc = 0.25*1.0*2*1.243*400*400
=99.44 KN
0 . 1×b w ×d
V cn = N sd
Ac
0 . 1×357×357×471 .06
V cn =
400×400
= 37.52KN
Page | 263
FINAL YEAR PROJECT 2020
Lap Length
The length of lap, lo, shall be at least equal to [EBCS-2, 1995 section 7.1.6.5]
Required anchorage length lb, net depends on the type of anchorage and on the stress in the rein-
forcement and calculated as
As
l b , net=al b ≥l b ,min
A s , eff
l b ,min=0 . 6 lb ≥10 φ
or≥200 mm
Where Ascal = the theoretical area of reinforcement required by the design
Page | 264
FINAL YEAR PROJECT 2020
The basic anchorage length is the embedment length required to develop the full design
strength of a straight reinforcing bars
φ f yd
lb=
4 f bd
For good bond condition the design bond strength of deformed bars may be taken as twice the
value for plain bars:
The percentage of lapped bars in compression in any one section may be 100% of the total steel
cross section
φ 260 . 87
lb= ∗
4 2∗1 .03
lb=(260.87*24)/(4*2*1.03)=759.82mm
l b ,min=0 . 6 lb ≥10 φ
or≥200 mm
lb,min=0.6*759.82=455.89 ≥ 240 (10Ø)
lo ,min=0.3aa1 lb ≥15φ
or≥200 mm
α1 = 1.4
Page | 265
FINAL YEAR PROJECT 2020
α= 1.0
lo,min =360mm
As
l b , net=al b ≥l b ,min
A s , eff
3503. 35
l b , net =1∗759. 82 ≥l ,min
3619. 11 b
Lb ,net=735.52mm
lo=1030mm
Page | 266
FINAL YEAR PROJECT 2020
Page | 267
FINAL YEAR PROJECT 2020
CHAPTER SIX
FOUNDATION DESIGN
Page | 268
FINAL YEAR PROJECT 2020
6.1 Introduction
Foundation is that part of a structure which transfers the load of the structure to soil on which it
rests. The main objectives of a foundation are the following
To distribute the weight of the structure over larger area so as to avoid over loading of the
soil beneath.
To load the sub structure evenly so as to avoid unequal settlement.
To provide a level surface for building operations
To take the sub structure deep into the ground and thus increase its stability and avoid over
turning
Once the size of the footing is determined, the footing must be designed structurally for
The critical section for punching is at a distance “1.5d” from the face of the column (Ac-
cording to EBCS – 2, 1995)
The critical section for punching shear is at a distance of “0.5” from the face of the col-
umn. (According to EBCS-2, 1985)
We can use one of the above two methods in footing depth determination.
Page | 269
FINAL YEAR PROJECT 2020
The critical section for wide beam shear is at a distance of “d” from the face of the col-
umn and it is a one way shear consideration in both axis. (According to both EBCS-2,
1985, &1995).
Thus, let categorize into three groups and take the largest factored load and moment.
There are 8 factored loads and its moments, from these the largest load is 567.23KN,
There are 7 factored loads and its moments, from these the largest load is 882.5,
There are 6 factored loads and its moments, from these the largest load is 1071.52KN,
There are 6 factored loads and its moments, from these the largest load is 1480.1KN,
There are 6 factored loads and its moments, from these the largest load is 1959.32KN,
Page | 270
FINAL YEAR PROJECT 2020
Due to moment (eccentric load) the base area should be modified or the axial force shifts from
the geometric centre of the footing.
Assumptions
Since the load from the superstructure is factored. Therefore, the allowable bearing capacity of
1.3+1.4
the soil must be factored by an average i.e. =1.45
2
Page | 271
FINAL YEAR PROJECT 2020
σall = 1.45*280KN/m3
= 406KN/m3
Soil weight and Own weight of footing
= 144.87KN
= 712.1KN
p 6 ea 6 eb
σ= ( 1± ± )
A a b
a = length of footing
b = width of footing
Mx 29.816 KNm
ea = P = 712.1 KN =0.042
My 33.686 KNm
eb = P = 712.1 KN =0.047
pmax 6 ea 6 eb
σ all= (1 ± ± )
A a b
Page | 272
FINAL YEAR PROJECT 2020
pmax 6 ea 6 eb
Critical case, σ all= (1+ + )
A a b
Therefore, a = b = 1.6m
σ 1+ σ 2+σ 3+σ 4
σ=
4
371.06+273.15+283.17+185.25
σ= = 278.16 KN/m2
4
Determination of depth, D
In the structural design of footings adequacy of the thickness of the footing and provide the nec-
essary reinforcement to withstand punching shear and shear diagonal tension (wide beam shear)
moment and bond stress should be checked.
Page | 273
FINAL YEAR PROJECT 2020
Net punching shear force, Pp is given by
Pp = Pt – σ avgAc
For the structural design, a simplifying assumption is made in which the contact pressure
distribution is assumed uniform and it magnitude is taken as the average of the each side contact
pressure.
d = effective depth
Page | 274
FINAL YEAR PROJECT 2020
0.21 fck 2 /3
f ctd= fck = 0.8fcu
ϒc
As
K1 = 1+50ρ ≤ 2.0 ρ steel ratio =
bd
0.6
K2 = 1.6-d ≥ 1.0 ρ = ρmin = f
yk
0.6
ρ = ρmin = = 0.002
300
2/ 3
0.21(0.8∗25)
f ctd= =1.03 Mpa
1.5
Ac = (0.4 + 3d) 2
Ʋ= 4(0.4 + 3d)
Vrd = 0.25*1.03Mpa*1.1*1*4(0.4+3d)*d
d2+0.266d – 0.269 = 0
Page | 275
FINAL YEAR PROJECT 2020
Check d for wide beam shear
The check will do for critical section at d distance from the face of column.
Vrd = 0.25fctdk1k2µd
Section a-a
Ʋw = σ avgA < ƲC
= 278.16KN/m2* 0.2m * 1m
Page | 276
FINAL YEAR PROJECT 2020
Figure 6. 2 design for flexure
M1-1 = 278.16KN/m * (0.4m)2/2= 22.25KN.m
Reinforcement
0.6
ρ min = fyk =0.002
= 800mm2
Fcd = 0.68fcu/1.5
= 0.68(25)/1.5
= 11.3Mpa
ρ= √
1− 1−
2M
bd∗d∗fcd
fyd / fcd
ρ= √
1− 1−
2∗22.25∗106
2
1000∗400 ∗11.3
260.87 /11.3
= 800mm2
Use Φ16 mm
as = π d2 /4 = 125.66
Spacing
S = (asb)/As
Page | 277
FINAL YEAR PROJECT 2020
= (125.66*1000)/800
= 157.08mm
Moment along section 2-2 Reinforcement for section 1-1 same as Moment along section
2-2
Development length
∅ b fyd
Lb = * fbd = 1.033Mpa
4 fbd
16 260.87
Lb = 4 * 1.033 = 1010.14mm >850mm-50mm > 800mm
Page | 278
FINAL YEAR PROJECT 2020
Since the load from the superstructure is factored. Therefore, the allowable bearing capacity of
1.3+1.4
the soil must be factored by an average i.e. =1.45
2
σall = 1.45*280KN/m3 = 406KN/m3
= 144.87KN
= 2104.19KN
d = 0.4
p 6 ea 6 eb
σ= (1± ± )
A a b
Where;
a = length of footing
b = width of footing
Mx 44.094 KNm
ea = P = 2104.19 KN =0.02
My 53.897 KNm
eb = P = 2104.19 KN =0.026
Page | 279
FINAL YEAR PROJECT 2020
pmax 6 ea 6 eb
σ all= (1 ± ± )
A a b
pmax 6 ea 6 eb
Critical case,σ all= (1+ + )
A a b
Therefore, a = b = 2.4m
σ 1+ σ 2+σ 3+σ 4
σ=
4
Determination of Depth, D
Page | 280
FINAL YEAR PROJECT 2020
In the structural design of footings adequacy of the thickness of the footing and provide the nec-
essary reinforcement to withstand punching shear and shear diagonal tension (wide beam shear)
moment and bond stress should be checked.
Pp = PT – σavgAc
For the structural design, a simplifying assumption is made in which the contact pressure
distribution is assumed uniform and it magnitude is taken as the average of the each side contact
pressure.
Page | 281
FINAL YEAR PROJECT 2020
0.21 fck 2 /3
Where; f ctd= fck = 0.8fcu
ϒc
As
K1 = 1+50ρ ≤ 2.0 ρ steel ratio = bd
K2 = 1.6-d ≥ 1.0
0.6
ρ = ρmin = f
yk
d = effective depth
0.6
ρ = ρmin = 300 = 0.002
2/ 3
0.21(0.8∗25)
f ctd= =1.03 Mpa
1.5
Ac = (0.4 + 3d) 2
Ʋ= 4(0.4 + 3d)
vrd = 0.25*1.03Mpa*1.1*1*4(0.4+3d)*d
vrd = 3.399d2+0.45d--------------------------------------(**)
d2+0.266d – 0.622 = 0
The check will do for critical section at d distance from the face of column
vrd = 0.25fctdk1k2µd
Section a-a
Ʋw = σavg * A < ƲC
Page | 283
FINAL YEAR PROJECT 2020
6.2.3 REINFORCEMENT
0.6
ρ min = fyk =0.002
ρ= √
1− 1−
2M
bd∗d∗fcd
fyd/ fcd
√
6
2∗29.22∗10
1− 1−
ρ= 1000∗7002∗11.3 = 0.00023 <ρ min = 0.002
260.87/ 11.3
As = ρbwd = 0.002 * 1000mm * 700mm = 1400mm2
Use Φ16 mm
Page | 284
FINAL YEAR PROJECT 2020
as = π d2 /4 = 384.85
Moment along section 2-2 Reinforcement for section 1-1 same as Moment along section
2-2
Development length
∅ b fyd
Lb = * fbd = 1.033Mpa
4 fbd
16 260.87
Lb = 4 * 1.033 = 1010.14mm >850mm-50mm > 800mm
Page | 285
FINAL YEAR PROJECT 2020
Conclusion
Every structural design must aim at creating a structure that is structural safe and economically
feasible. As a result all the design procedures must be in accordance with these two important
Page | 286
FINAL YEAR PROJECT 2020
principles. Sometimes due to sophistication of architectural drawings it is hard to adhere to both
this principles simultaneously. The purpose of the building makes it inherently expensive since it
is intended to be a G+4 hospital building. It is also relatively high rising building.
For designing and analysis of this G+4 building EBCS code of 1995 was the main and funda-
mental reference for any relevant assumptions carried out in this project papers. On analysis of
this project many tedious calculation works were compiled with ETABS and the result was taken
for designing purpose, as the adequacy of each building elements was understandable by the pro-
gram and can generate the output results with acceptable sign convention.
From this what we conclude is that if this program is not available it was such difficult to com-
plete this project with in this time constraint. In accordance with the design and analysis, the
structure is economical and safe against lateral and different load application, but for actual im-
plementation as the soil bearing capacity for the foundation was taken from relevant assumption,
it needs further soil exploration and modification of foundations accordingly.
In general, we have tried to make the structure as economically as possible by systematically ad-
justing the design as well as the detail drawings.
Page | 287
FINAL YEAR PROJECT 2020
Recommendation
It has been quite challenging to prepare a precise reinforcement detail; however, as it is essential
to achieve a quality performance of a structure under the situation it has been designed.Also we
recommend that structural as well as high way software like SAP,ETABS should be given in ap-
propriate and scheduled way.
In this projectthere is time constraint starting from late data provisionfor the groups till compil-
ing and submission of the documents thereby coincides
with exam schedule. Thus we recommend that the data have to be given on time
at the beginning of second semester likewise submission and presentation date
should be at least some days after examination.
REFERENCE
1. EBCS-1, 1995
Page | 288
FINAL YEAR PROJECT 2020
2. EBCS-2, 1995
3. EBCS-3, 1995
4. EBCS-7, 1995
5. EBCE-8, 1995
6. Manual of cold formed galvanized steel sheet for roofing cladding window and door profiles
fittings Kality Steel Industry – 1985.
Appendix
1. Output for foundation design
Page | 289
FINAL YEAR PROJECT 2020
COMBO point Fz Mx My
COMBO 1 157 82.33 25.77 26.798
COMBO 1 158 82.33 26.395 26.831
COMBO 1 21 417.63 26.841 28.649
COMBO 1 7 421.02 28.005 31.92
COMBO 1 9 424.77 28.352 32.393
COMBO 1 1 506.29 28.589 32.892
COMBO 1 2 566.63 28.73 33.296
COMBO 1 8 567.23 29.816 33.686
COMBO 1 15 636.13 29.835 33.758
COMBO 1 24 696.68 30.21 33.836
COMBO 1 23 698.02 31.547 34.36
COMBO 1 22 744.04 31.559 34.517
COMBO 1 16 750.38 31.966 35.089
COMBO 1 6 844.82 32.195 35.126
COMBO 1 4 882.5 32.534 36.01
COMBO 1 25 967.31 32.808 36.083
COMBO 1 3 994.49 34.633 36.117
COMBO 1 5 1016.78 34.851 36.15
COMBO 1 10 1021.8 35.59 38.436
COMBO 1 26 1033.28 35.825 38.565
COMBO 1 27 1071.52 35.897 38.787
COMBO 1 17 1121.1 35.992 38.862
COMBO 1 18 1167.78 36.092 41.749
COMBO 1 62 1200.83 36.209 41.866
COMBO 1 14 1308.81 36.453 42.053
COMBO 1 20 1315.68 36.551 42.275
COMBO 1 29 1480.1 36.841 42.602
COMBO 1 95 1508.45 37.816 42.802
COMBO 1 19 1653.71 37.82 44.4
COMBO 1 18 1661.72 39.23 46.101
COMBO 1 19 1730.35 39.354 47.015
COMBO 1 20 1825.99 43.269 53.864
COMBO 1 21 1959.32 44.094 53.897
Page | 290
FINAL YEAR PROJECT 2020
ROOF C1 ENVET MAX 1.375 -18.29 -3.23 4.03 0.724 6.134 0.719
ROOF C1 ENVET MAX 2.75 -13.24 -3.23 4.03 0.724 1.068 5.279
ROOF C1 ENVET MIN 0 -34.47 -4.58 2.26 -0.415 2.43 -10.71
ROOF C1 ENVET MIN 1.375 -27.73 -4.58 2.26 -0.415 -0.821 -5.825
ROOF C1 ENVET MIN 2.75 -21 -4.58 2.26 -0.415 -4.072 -0.939
FOURTH C1 ENVET MAX 0 -92.88 -1.08 7.57 1.357 8.294 -6.04
FOURTH C1 ENVET MAX 1.375 -87.83 -1.08 7.57 1.357 6.541 4.886
FOURTH C1 ENVET MAX 2.75 -82.78 -1.08 7.57 1.357 5.712 15.812
FOURTH C1 ENVET MIN 0 -136.06 -7.95 0.6 -0.969 4.891 -9.19
FOURTH C1 ENVET MIN 1.375 -129.32 -7.95 0.6 -0.969 -5.341 -6.261
FOURTH C1 ENVET MIN 2.75 -122.58 -7.95 0.6 -0.969 -15.753 -4.779
THIRD C1 ENVET MAX 0 -155.12 2.96 11.88 1.981 12.324 -1.013
THIRD C1 ENVET MAX 1.375 -150.07 2.96 11.88 1.981 5.145 3.983
THIRD C1 ENVET MAX 2.75 -145.01 2.96 11.88 1.981 9.815 20.269
THIRD C1 ENVET MIN 0 -237.02 -11.85 -3.4 -1.581 0.474 -12.304
THIRD C1 ENVET MIN 1.375 -230.28 -11.85 -3.4 -1.581 -4.008 -5.077
THIRD C1 ENVET MIN 2.75 -223.55 -11.85 -3.4 -1.581 -20.34 -9.141
SECOND C1 ENVET MAX 0 -217.37 5.97 16.08 2.302 23.196 8.877
SECOND C1 ENVET MAX 1.375 -212.31 5.97 16.08 2.302 1.09 0.662
SECOND C1 ENVET MAX 2.75 -207.26 5.97 16.08 2.302 8.224 21.728
SECOND C1 ENVET MIN 0 -346.18 -16.42 -6.73 -1.993 -10.277 -23.417
SECOND C1 ENVET MIN 1.375 -339.44 -16.42 -6.73 -1.993 -1.027 -0.845
SECOND C1 ENVET MIN 2.75 -332.7 -16.42 -6.73 -1.993 -21.015 -7.553
FIRST C1 ENVET MAX 0 -277.61 7.68 14.14 1.777 27.305 22.809
FIRST C1 ENVET MAX 1.375 -272.56 7.68 14.14 1.777 7.86 12.251
FIRST C1 ENVET MAX 2.75 -267.5 7.68 14.14 1.777 -2.103 12.21
FIRST C1 ENVET MIN 0 -453.98 -15.27 -7.51 -1.617 -22.757 -29.791
FIRST C1 ENVET MIN 1.375 -447.24 -15.27 -7.51 -1.617 -12.43 -8.79
FIRST C1 ENVET MIN 2.75 -440.5 -15.27 -7.51 -1.617 -11.584 1.692
GROUN
D C1 ENVET MAX 0 -295.31 14.31 20.52 0.642 32.534 30.146
GROUN
D C1 ENVET MAX 0.75 -292.56 14.31 20.52 0.642 17.146 19.411
GROUN
D C1 ENVET MAX 1.5 -289.8 14.31 20.52 0.642 1.759 8.677
GROUN
D C1 ENVET MIN 0 -506.29 -19.12 -15.4 -0.605 -31.207 -31.92
GROUN
D C1 ENVET MIN 0.75 -502.62 -19.12 -15.4 -0.605 -19.658 -17.576
GROUN
D C1 ENVET MIN 1.5 -498.94 -19.12 -15.4 -0.605 -8.108 -3.232
ROOF C2 ENVET MAX 0 -31.03 0.65 2.85 0.724 9.315 -2.096
ROOF C2 ENVET MAX 1.375 -25.98 0.65 2.85 0.724 5.398 2.729
ROOF C2 ENVET MAX 2.75 -20.93 0.65 2.85 0.724 1.481 8.172
ROOF C2 ENVET MIN 0 -42.13 -3.96 -1.64 -0.415 -4.472 -3.424
Page | 291
FINAL YEAR PROJECT 2020
ROOF C2 ENVET MIN 1.375 -35.39 -3.96 -1.64 -0.415 -2.224 -3.316
ROOF C2 ENVET MIN 2.75 -28.65 -3.96 -1.64 -0.415 0.025 -4.209
FOURTH C2 ENVET MAX 0 -115.93 7.75 0.8 1.357 8.24 5.936
FOURTH C2 ENVET MAX 1.375 -110.87 7.75 0.8 1.357 7.383 3.857
FOURTH C2 ENVET MAX 2.75 -105.82 7.75 0.8 1.357 6.527 13.256
FOURTH C2 ENVET MIN 0 -156.16 -6.84 0.45 -0.969 -6.063 -5.543
FOURTH C2 ENVET MIN 1.375 -149.42 -6.84 0.45 -0.969 -6.867 -4.714
FOURTH C2 ENVET MIN 2.75 -142.69 -6.84 0.45 -0.969 -7.67 -15.363
THIRD C2 ENVET MAX 0 -200.56 14.47 1.76 1.981 5.706 17.234
THIRD C2 ENVET MAX 1.375 -195.5 14.47 1.76 1.981 6.059 3.341
THIRD C2 ENVET MAX 2.75 -190.45 14.47 1.76 1.981 6.411 22.219
THIRD C2 ENVET MIN 0 -269.81 -13.73 -0.26 -1.581 -3.598 -15.538
THIRD C2 ENVET MIN 1.375 -263.07 -13.73 -0.26 -1.581 -6.019 -2.666
THIRD C2 ENVET MIN 2.75 -256.33 -13.73 -0.26 -1.581 -8.44 -22.566
SECOND C2 ENVET MAX 0 -291.01 19.69 4.12 2.302 5.344 29.642
SECOND C2 ENVET MAX 1.375 -285.95 19.69 4.12 2.302 -0.324 2.564
SECOND C2 ENVET MAX 2.75 -280.9 19.69 4.12 2.302 3.186 24.775
SECOND C2 ENVET MIN 0 -391.13 -18.69 -2.83 -1.993 -4.591 -26.633
SECOND C2 ENVET MIN 1.375 -384.39 -18.69 -2.83 -1.993 -0.703 -0.929
SECOND C2 ENVET MIN 2.75 -377.66 -18.69 -2.83 -1.993 -5.992 -24.515
FIRST C2 ENVET MAX 0 -378.86 19.14 3.39 1.777 11.95 38.621
FIRST C2 ENVET MAX 1.375 -373.8 19.14 3.39 1.777 7.288 12.308
FIRST C2 ENVET MAX 2.75 -368.75 19.14 3.39 1.777 2.627 16.044
FIRST C2 ENVET MIN 0 -508.81 -19.19 -2.68 -1.617 -14.662 -36.728
FIRST C2 ENVET MIN 1.375 -502.07 -19.19 -2.68 -1.617 -10.972 -10.342
FIRST C2 ENVET MIN 2.75 -495.33 -19.19 -2.68 -1.617 -7.282 -14.005
GROUN
D C2 ENVET MAX 0 -421.86 25.61 8.56 0.642 25.77 36.445
GROUN
D C2 ENVET MAX 0.75 -419.1 25.61 8.56 0.642 19.349 17.234
GROUN
D C2 ENVET MAX 1.5 -416.34 25.61 8.56 0.642 12.928 3.922
GROUN
D C2 ENVET MIN 0 -566.63 -26.71 -7.65 -0.605 -26.615 -36.15
GROUN
D C2 ENVET MIN 0.75 -562.95 -26.71 -7.65 -0.605 -20.874 -16.114
GROUN
D C2 ENVET MIN 1.5 -559.28 -26.71 -7.65 -0.605 -15.133 -1.977
ROOF C3 ENVET MAX 0 -24.68 4.07 23.52 0.724 56.352 3.766
ROOF C3 ENVET MAX 1.375 -19.63 4.07 23.52 0.724 24.01 3.607
ROOF C3 ENVET MAX 2.75 -14.57 4.07 23.52 0.724 -3.982 4.707
ROOF C3 ENVET MIN 0 -33.61 -0.8 16.58 -0.415 37.207 1.91
ROOF C3 ENVET MIN 1.375 -26.87 -0.8 16.58 -0.415 14.346 -2.457
ROOF C3 ENVET MIN 2.75 -20.13 -0.8 16.58 -0.415 -8.516 -8.055
FOURTH C3 ENVET MAX 0 -188.77 11.62 51.59 1.357 73.174 11.561
Page | 292
FINAL YEAR PROJECT 2020
FOURTH C3 ENVET MAX 1.375 -183.72 11.62 51.59 1.357 7.985 4.208
FOURTH C3 ENVET MAX 2.75 -178.66 11.62 51.59 1.357 -42.423 8.334
FOURTH C3 ENVET MIN 0 -254.24 -3 36.66 -0.969 51.369 0.082
FOURTH C3 ENVET MIN 1.375 -247.5 -3 36.66 -0.969 -4.623 -4.421
FOURTH C3 ENVET MIN 2.75 -240.76 -3 36.66 -0.969 -68.692 -20.402
THIRD C3 ENVET MAX 0 -352.79 18.18 46.42 1.981 71.145 22.904
THIRD C3 ENVET MAX 1.375 -347.74 18.18 46.42 1.981 10.588 4.011
THIRD C3 ENVET MAX 2.75 -342.69 18.18 46.42 1.981 -31.003 17.483
THIRD C3 ENVET MIN 0 -476.77 -9.8 30.25 -1.581 52.179 -9.461
THIRD C3 ENVET MIN 1.375 -470.03 -9.8 30.25 -1.581 0.384 -2.098
THIRD C3 ENVET MIN 2.75 -463.29 -9.8 30.25 -1.581 -56.516 -27.101
SECOND C3 ENVET MAX 0 -524.43 23.76 50.68 2.302 76.097 35.817
SECOND C3 ENVET MAX 1.375 -519.38 23.76 50.68 2.302 6.414 3.152
SECOND C3 ENVET MAX 2.75 -514.32 23.76 50.68 2.302 -37.666 19.338
SECOND C3 ENVET MIN 0 -711.18 -14.29 30.39 -1.993 45.9 -19.956
SECOND C3 ENVET MIN 1.375 -704.45 -14.29 30.39 -1.993 4.117 -0.309
SECOND C3 ENVET MIN 2.75 -697.71 -14.29 30.39 -1.993 -63.268 -29.513
FIRST C3 ENVET MAX 0 -683.32 20.94 25.4 1.777 34.301 40.056
FIRST C3 ENVET MAX 1.375 -678.27 20.94 25.4 1.777 -0.628 11.264
FIRST C3 ENVET MAX 2.75 -673.22 20.94 25.4 1.777 -35.188 11.945
FIRST C3 ENVET MIN 0 -928.73 -16.82 11.28 -1.617 -4.305 -34.319
FIRST C3 ENVET MIN 1.375 -921.99 -16.82 11.28 -1.617 -19.811 -11.187
FIRST C3 ENVET MIN 2.75 -915.25 -16.82 11.28 -1.617 -47.25 -17.527
GROUN
D C3 ENVET MAX 0 -727.92 24.83 10.66 0.642 26.841 36.009
GROUN
D C3 ENVET MAX 0.75 -725.17 24.83 10.66 0.642 18.843 17.384
GROUN
D C3 ENVET MAX 1.5 -722.41 24.83 10.66 0.642 10.844 3.685
GROUN
D C3 ENVET MIN 0 -994.49 -26.46 -16.05 -0.605 -31.019 -36.01
GROUN
D C3 ENVET MIN 0.75 -990.81 -26.46 -16.05 -0.605 -18.979 -16.162
GROUN
D C3 ENVET MIN 1.5 -987.14 -26.46 -16.05 -0.605 -6.94 -1.24
ROOF C4 ENVET MAX 0 -36.7 -0.31 18.75 0.724 43.658 -2.99
ROOF C4 ENVET MAX 1.375 -31.64 -0.31 18.75 0.724 17.879 2.433
ROOF C4 ENVET MAX 2.75 -26.59 -0.31 18.75 0.724 -3.366 7.963
ROOF C4 ENVET MIN 0 -50.07 -4.02 13.08 -0.415 27.86 -4.922
ROOF C4 ENVET MIN 1.375 -43.33 -4.02 13.08 -0.415 9.731 -3.862
ROOF C4 ENVET MIN 2.75 -36.59 -4.02 13.08 -0.415 -8.485 -3.438
FOURTH C4 ENVET MAX 0 -165.28 5.56 38.02 1.357 53.58 2.431
FOURTH C4 ENVET MAX 1.375 -160.22 5.56 38.02 1.357 7.127 4.121
FOURTH C4 ENVET MAX 2.75 -155.17 5.56 38.02 1.357 -29.092 13.64
FOURTH C4 ENVET MIN 0 -224.93 -6.92 26.34 -0.969 36.788 -5.399
Page | 293
FINAL YEAR PROJECT 2020
FOURTH C4 ENVET MIN 1.375 -218.19 -6.92 26.34 -0.969 -5.169 -5.208
Page | 294
FINAL YEAR PROJECT 2020
THIRD B1 ENVET MAX 0.2 -21.57 2.674 0.615
THIRD B1 ENVET MAX 0.633 -11.47 2.674 7.775
THIRD B1 ENVET MAX 1.067 -1.37 2.674 10.558
THIRD B1 ENVET MAX 1.5 8.73 2.674 11.957
THIRD B1 ENVET MAX 1.933 18.83 2.674 12.274
THIRD B1 ENVET MAX 2.367 28.92 2.674 11.202
THIRD B1 ENVET MAX 2.8 39.02 2.674 5.753
THIRD B1 ENVET MIN 0.2 -43.03 1.441 -27.2
THIRD B1 ENVET MIN 0.633 -32.87 1.441 -10.767
THIRD B1 ENVET MIN 1.067 -22.77 1.441 1.29
THIRD B1 ENVET MIN 1.5 -12.67 1.441 8.952
THIRD B1 ENVET MIN 1.933 -2.57 1.441 2.996
THIRD B1 ENVET MIN 2.367 7.52 1.441 -7.35
THIRD B1 ENVET MIN 2.8 17.62 1.441 -22.072
SECOND B1 ENVET MAX 0.2 -19.32 3.08 6.052
SECOND B1 ENVET MAX 0.633 -8.34 3.08 12.045
SECOND B1 ENVET MAX 1.067 2.64 3.08 13.279
SECOND B1 ENVET MAX 1.5 13.63 3.08 13.022
SECOND B1 ENVET MAX 1.933 24.61 3.08 14.741
SECOND B1 ENVET MAX 2.367 35.59 3.08 14.945
SECOND B1 ENVET MAX 2.8 46.57 3.08 10.39
SECOND B1 ENVET MIN 0.2 -49.89 1.532 -33.665
SECOND B1 ENVET MIN 0.633 -38.91 1.532 -14.425
SECOND B1 ENVET MIN 1.067 -27.93 1.532 0.056
SECOND B1 ENVET MIN 1.5 -16.94 1.532 9.753
SECOND B1 ENVET MIN 1.933 -5.96 1.532 1.471
SECOND B1 ENVET MIN 2.367 5.02 1.532 -11.572
SECOND B1 ENVET MIN 2.8 16 1.532 -29.373
FIRST B1 ENVET MAX 0.2 -17.58 3.292 7.533
FIRST B1 ENVET MAX 0.633 -6.88 3.292 12.832
FIRST B1 ENVET MAX 1.067 3.81 3.292 13.496
FIRST B1 ENVET MAX 1.5 14.51 3.292 12.715
FIRST B1 ENVET MAX 1.933 25.21 3.292 14.727
FIRST B1 ENVET MAX 2.367 35.9 3.292 15.274
FIRST B1 ENVET MAX 2.8 46.6 3.292 11.185
FIRST B1 ENVET MIN 0.2 -49.39 1.685 -33.803
FIRST B1 ENVET MIN 0.633 -38.69 1.685 -14.719
FIRST B1 ENVET MIN 1.067 -28 1.685 -0.269
FIRST B1 ENVET MIN 1.5 -17.3 1.685 9.523
FIRST B1 ENVET MIN 1.933 -6.61 1.685 0.921
FIRST B1 ENVET MIN 2.367 4.09 1.685 -12.318
FIRST B1 ENVET MIN 2.8 14.78 1.685 -30.192
Page | 295
FINAL YEAR PROJECT 2020
GROUN
D B1 ENVET MAX 0.2 -0.22 0.602 13.821
GROUN
D B1 ENVET MAX 0.633 4.82 0.602 12.825
GROUN
D B1 ENVET MAX 1.067 9.86 0.602 9.644
GROUN
D B1 ENVET MAX 1.5 14.9 0.602 5.78
GROUN
D B1 ENVET MAX 1.933 19.95 0.602 10.543
GROUN
D B1 ENVET MAX 2.367 24.99 0.602 14.511
GROUN
D B1 ENVET MAX 2.8 30.03 0.602 16.294
GROUN
D B1 ENVET MIN 0.2 -31.85 -1.372 -27.177
GROUN
D B1 ENVET MIN 0.633 -26.8 -1.372 -14.47
GROUN
D B1 ENVET MIN 1.067 -21.76 -1.372 -3.947
GROUN
D B1 ENVET MIN 1.5 -16.72 -1.372 4.279
GROUN
D B1 ENVET MIN 1.933 -11.68 -1.372 -3.272
GROUN
D B1 ENVET MIN 2.367 -6.64 -1.372 -13.007
GROUN
D B1 ENVET MIN 2.8 -1.59 -1.372 -24.928
ROOF B2 ENVET MAX 0.2 -4.41 0.001 1.215
ROOF B2 ENVET MAX 0.633 -1.95 0.001 2.594
ROOF B2 ENVET MAX 1.067 0.51 0.001 2.908
ROOF B2 ENVET MAX 1.5 2.97 0.001 2.659
ROOF B2 ENVET MAX 1.933 5.42 0.001 1.825
ROOF B2 ENVET MAX 2.367 7.88 0.001 0.753
ROOF B2 ENVET MAX 2.8 11.01 0.001 -1.386
ROOF B2 ENVET MIN 0.2 -8.67 -0.236 -4.542
ROOF B2 ENVET MIN 0.633 -6.13 -0.236 -1.352
ROOF B2 ENVET MIN 1.067 -3.67 -0.236 0.773
ROOF B2 ENVET MIN 1.5 -1.21 -0.236 1.832
ROOF B2 ENVET MIN 1.933 1.25 -0.236 0.338
ROOF B2 ENVET MIN 2.367 3.7 -0.236 -2.546
ROOF B2 ENVET MIN 2.8 6.16 -0.236 -6.495
FOURTH B2 ENVET MAX 0.2 -23.01 -0.09 -1.05
FOURTH B2 ENVET MAX 0.633 -12.94 -0.09 6.739
FOURTH B2 ENVET MAX 1.067 -2.87 -0.09 10.325
Page | 296
FINAL YEAR PROJECT 2020
FOURTH B2 ENVET MAX 1.5 7.2 -0.09 12.103
FOURTH B2 ENVET MAX 1.933 17.27 -0.09 8.169
FOURTH B2 ENVET MAX 2.367 29.46 -0.09 3.047
FOURTH B2 ENVET MAX 2.8 42.89 -0.09 -6.439
FOURTH B2 ENVET MIN 0.2 -37.67 -0.526 -14.977
FOURTH B2 ENVET MIN 0.633 -24.24 -0.526 -2.645
FOURTH B2 ENVET MIN 1.067 -13.35 -0.526 5.323
FOURTH B2 ENVET MIN 1.5 -3.28 -0.526 8.928
FOURTH B2 ENVET MIN 1.933 6.79 -0.526 3.924
FOURTH B2 ENVET MIN 2.367 16.86 -0.526 -5.741
FOURTH B2 ENVET MIN 2.8 26.93 -0.526 -19.771
THIRD B2 ENVET MAX 0.2 -17.35 0.169 6.503
THIRD B2 ENVET MAX 0.633 -7.25 0.169 11.832
THIRD B2 ENVET MAX 1.067 2.85 0.169 12.784
THIRD B2 ENVET MAX 1.5 12.95 0.169 12.019
THIRD B2 ENVET MAX 1.933 23.05 0.169 10.087
THIRD B2 ENVET MAX 2.367 33.15 0.169 7.129
Page | 297
FINAL YEAR PROJECT 2020
Page | 298
FINAL YEAR PROJECT 2020
Page | 299