THREE PHASE AUTOMATIC CHANGEOVER WITH CURRENT LIMITER
• Settable overload current limit at DG side
• Separate power consumption monitoring for mains & genset
• Settable TPN / SPN mode for three phase and single phase DG supply
Standards :
IEC 60947-5-1
IEC 61000-4
IEC 60068-2
1
TECHNICAL SPECIFICATIONS
Electrical Characteristics :
Supply Voltage 180V - 265V AC
Supply Frequency 50Hz (±3%)
Power Consumption <=7 VA <=12 VA <=24 VA <=24 VA
Each Phase: Current, Voltage, Active Power, Power Factor, Line to Line Voltage
Run Parameters displayed for
Average: Phase Current, Phase Voltage, Line Voltage, Power Factor. Total active
Active Source (EB or DG)
Power, Units (KWH), Load Hours and Supply frequency.
Fault Tripping :
Fault protection for both EB and DG Over Current, Under Voltage, Over Voltage, Phase loss, Voltage error.
4 Sec for UV/OV fault and Immediate trip for phase fail, extreme UV
Trip Time
(less than 115V) and extreme OV (above 320V)
Environmental Characteristics :
Operating Temperature -5° to +55°C
Storage Temperature -10° to +60°C
Humidity 95% RH (Non - condensing)
Pollution Degree 2
Mechanical characteristics
Tightening Torque 1.2 Nm 1.2 Nm 2.0 Nm 3.0 Nm
Main pole Terminal M4 M4 M5 M6
No of cable x (Min. range - Max. range) 1 x 1-10 mm sq 1 x 4-16 mm sq 1 x 4-25 mm sq 1 x 10-70 mm sq
Dimensions (H x W x D) 178 x 164.6 x 125 234.7 x 260 x 125 298 x 246 x 125 451 x 380 x 179.4
Weight (Kg) 1.8 4.3 5.2 11.7
2
OPERATION
* Refer page no 6 - Edit Menu Structure to set specific parameter with the help of programming
3
FEATURES FEATURES
CONFIGURABLE DG
HIGHLY SECURED
CURRENT SETTING The devices is protected with fixed
DG overload current limit can be set master password & changeable slave
through programming right from 1A password. Master password permits
to max rating of device. Different the DG overload current setting &
units are not required for different slave password permits to other
current ratings. {1.B}* editable parameters. {5.B}*
* Refer page no 6 - Edit Menu Structure to set specific parameter with the help of programming
4 5
PROGRAMMING
Edit Menu Structure
· Press ESC to enter programming (Edit) mode, when run parameters are displayed.
Edit Mode
A) Enter correct A) Enable / A) Enable / A) Set no. of A) Enable/ A) Set OL trip A) Enter correct
Password Disable UV Disable UV OL warning Disable method Password
cycles (Cy) password
F) Set DG Supply
TPN or SPN
G) Save
UV 180 UV 180
OV DIS/EN OV DIS/EN
OV 280 OV 280
DG AMP
DG ON time
DG Supply
TPN or SPN 6
DISPLAY OF PARAMETERS
BR phase voltage
Phase current
R phase current
7
RECOMMENDED CONNECTION
MCB MCB
R Y B N R Y B N
LOAD LOAD
MAINS GENSET
R Y B N R Y B N
MAINS GENSET
R Y B N R Y B N
R Y B N R Y B N
R Y B N R N
8
DIMENSIONS
R Y B N
LOAD
178
166
234,7
219,7
MAINS GENSET
R Y B N R Y B N
125 125
10
115
33,8
10
80/80 A 125/125 A
380
246
212
451
430
298
280
320
125
179,4
33,8 33,8 10,3
10
185
260
344
1,5
9
SP 51030