Load Calculation on Column C1 :-

Loading :-
Where Maximum height of column = 5m

i) Self Wt. of Column = 25 x 0.3 x 0.3 x5 = 11.25 KN


ii) Load from beam B4 = 65.81 x2 = 131.625 KN
w= 142.875 KN

As the Seismic zone is - II with importance factor 1.5, the B.M due to seismic is more
critical than wind load hence there is no need of design for Wind loads.

Bending Moment due to Seismic Load :- For Seismic Zone -II


Zone Factor Z = 0.1
Importance Factor I = 1.5
Response Reduction Factor R = 5
Sa / g = 2.5

Z I
Seismic Coeff. (Ah) = x x Sa / g = 0.04
2 R

Horizontal Seismic Force VB = 0.04 x 142.88 = 5.36

5.36 x 5
Moment due to Seismic Force = = 13.39 KN-m
2

Minimum Ecc. e = 20 mm
Moment about Minor Axis = 2.86 KN-m

Maximum B.M. Due to Seismic Force = 13.39 KN-m

Total Design Load = 1.5 x 142.88 = 214.31 KN


Moment about Minor Axis emin = 1.5 x 2.86 = 4.29 KN-m
Moment about Major Axis (S.F.) = 1.5 x 13.39 = 20.09 KN-m