Design material properties (as per equation 7.1 & 7.2 of Cl.7.2 of ACI 440)
Though recommended by ACI 440, the CE value should be considered as 0.7 or 0.8
for GFRP, considering the temporary nature of work and as practiced in industry the
value of CE shall be considered as 1.0 . That is to say that no reduction of strength is
considered of GFRP for environmental exposure
Strength Capacity of Member (as per equation 8-1 of Cl.8.2 of ACI 440 & as
per Cl.9.3.2.3 of ACI 318)
Provide - 48 Dia + 0
56 - 32 Dia Af = 14074.335 mm2/m
(45+11)
Concrete crushing failure (section controled byCompression, ρf>ρfb)
Ld =((ffu/(0.083*fc'^0.5))-340)/(13.6+C/db)* db = 47 db
Development length of T 40 Bar = 1874 mm
Development length of T 48 Bar = 2249 mm
For horizontal bars Ld = 48 db
Development length of T 22 Bar = 1056 mm
Soil Side
Excavation Side
T48 11700 Lg. X 29 No. = 339.30 m - BAR MKD.-(1)
T48 10950 Lg. X 13 No. = 142.35 m - BAR MKD.-(2)
T48 9365 Lg. X 14 No. = 131.11 m - BAR MKD.-(3)
T48 9125 Lg. X 21 No. = 191.63 m - BAR MKD.-(4)
T48 8575 Lg. X 17 No. = 145.78 m - BAR MKD.-(5)
T48 7785 Lg. X 20 No. = 155.70 m - BAR MKD.-(6)