Daily Report For The Month-Of MAR - 2023
Daily Report For The Month-Of MAR - 2023
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 540.263 542.782 1000
LT Room Feeder DG 7525.340 7895.965 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8374.071 8377.076 1000
AC Panel 3219.058 3220.359 1000
Power Panel 25.178 25.185 1000
Lighting Panel 139.692 139.748 1000
W/S UPS Panel- 20 KVA UPS 95.135 95.174 1000
Lab & Server Panel - 200 KVA UPS 4686.227 4687.909 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
3005
1301
7
56
39
1682
3085
Completed date
Completed date
REPORT DATE:02-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 542.782 545.699 1000
LT Room Feeder DG 7895.965 7895.965 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8377.076 8379.987 1000
AC Panel 3220.359 3221.574 1000
Power Panel 25.185 25.192 1000
Lighting Panel 139.748 139.813 1000
W/S UPS Panel- 20 KVA UPS 95.174 95.213 1000
Lab & Server Panel - 200 KVA UPS 4687.909 4689.551 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2911
1215
7
65
39
1642
2968
Completed date
Completed date
REPORT DATE:03-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 545.699 548.385 1000
LT Room Feeder DG 7895.965 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8379.987 8382.744 1000
AC Panel 3221.574 3222.731 1000
Power Panel 25.192 25.199 1000
Lighting Panel 139.813 139.873 1000
W/S UPS Panel- 20 KVA UPS 95.213 95.250 1000
Lab & Server Panel - 200 KVA UPS 4689.551 4691.098 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2757
1157
7
60
37
1547
2808
Completed date
Completed date
REPORT DATE:04-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 548.385 551.319 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8382.744 8385.653 1000
AC Panel 3222.731 3224.028 1000
Power Panel 25.199 25.202 1000
Lighting Panel 139.873 139.925 1000
W/S UPS Panel- 20 KVA UPS 95.250 95.275 1000
Lab & Server Panel - 200 KVA UPS 4691.098 4692.732 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2909
1297
3
52
25
1634
3011
Completed date
Completed date
REPORT DATE:05-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 551.319 554.204 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8385.653 8388.572 1000
AC Panel 3224.028 3225.364 1000
Power Panel 25.202 25.204 1000
Lighting Panel 139.925 139.926 1000
W/S UPS Panel- 20 KVA UPS 95.275 95.295 1000
Lab & Server Panel - 200 KVA UPS 4692.732 4694.380 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2919
1336
2
1
20
1648
3007
Completed date
Completed date
REPORT DATE:06-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 554.204 557.133 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8388.572 8391.414 1000
AC Panel 3225.364 3226.586 1000
Power Panel 25.204 25.211 1000
Lighting Panel 139.926 139.973 1000
W/S UPS Panel- 20 KVA UPS 95.295 95.332 1000
Lab & Server Panel - 200 KVA UPS 4694.380 4695.970 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2842
1222
7
47
37
1590
2903
Completed date
Completed date
REPORT DATE:07-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 557.133 560.069 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8391.414 8394.339 1000
AC Panel 3226.586 3227.893 1000
Power Panel 25.211 25.218 1000
Lighting Panel 139.973 140.017 1000
W/S UPS Panel- 20 KVA UPS 95.332 95.370 1000
Lab & Server Panel - 200 KVA UPS 4695.970 4697.590 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2925
1307
7
44
38
1620
3016
Completed date
Completed date
REPORT DATE:08-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 560.069 563.040 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8394.339 8397.252 1000
AC Panel 3227.893 3229.189 1000
Power Panel 25.218 25.225 1000
Lighting Panel 140.017 140.063 1000
W/S UPS Panel- 20 KVA UPS 95.370 95.408 1000
Lab & Server Panel - 200 KVA UPS 4697.590 4699.202 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2913
1296
7
46
38
1612
2999
Completed date
Completed date
REPORT DATE:09-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 563.040 565.921 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8397.252 8400.140 1000
AC Panel 3229.189 3230.445 1000
Power Panel 25.225 25.232 1000
Lighting Panel 140.063 140.119 1000
W/S UPS Panel- 20 KVA UPS 95.408 95.446 1000
Lab & Server Panel - 200 KVA UPS 4699.202 4700.809 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2888
1256
7
56
38
1607
2964
Completed date
Completed date
REPORT DATE:10-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 565.921 568.860 1000
LT Room Feeder DG 8146.482 8146.482 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8400.140 8403.059 1000
AC Panel 3230.445 3231.694 1000
Power Panel 25.232 25.239 1000
Lighting Panel 140.119 140.170 1000
W/S UPS Panel- 20 KVA UPS 95.446 95.484 1000
Lab & Server Panel - 200 KVA UPS 4700.809 4702.463 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2919
1249
7
51
38
1654
2999
Completed date
Completed date
REPORT DATE:11-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 568.860 571.626 1000
LT Room Feeder DG 8146.482 8179.128 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8403.059 8405.830 1000
AC Panel 3231.694 3232.897 1000
Power Panel 25.239 25.242 1000
Lighting Panel 140.170 140.197 1000
W/S UPS Panel- 20 KVA UPS 95.484 95.513 1000
Lab & Server Panel - 200 KVA UPS 4702.463 4704.046 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2771
1203
3
27
29
1583
2845
Completed date
Completed date
REPORT DATE:12-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 571.626 574.571 1000
LT Room Feeder DG 8146.482 8179.128 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8405.830 8408.738 1000
AC Panel 3232.897 3234.297 1000
Power Panel 25.242 25.243 1000
Lighting Panel 140.197 140.208 1000
W/S UPS Panel- 20 KVA UPS 95.513 95.537 1000
Lab & Server Panel - 200 KVA UPS 4704.046 4705.663 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2908
1400
1
11
24
1617
3053
Completed date
Completed date
REPORT DATE:13-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 574.571 577.544 1000
LT Room Feeder DG 8146.482 8179.128 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8408.738 8411.721 1000
AC Panel 3234.297 3235.614 1000
Power Panel 25.243 25.250 1000
Lighting Panel 140.208 140.261 1000
W/S UPS Panel- 20 KVA UPS 95.537 95.574 1000
Lab & Server Panel - 200 KVA UPS 4705.663 4707.304 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2983
1317
7
53
37
1641
3055
Completed date
Completed date
REPORT DATE:14-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 577.544 580.531 1000
LT Room Feeder DG 8179.128 8179.128 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8411.721 8414.575 1000
AC Panel 3235.614 3236.945 1000
Power Panel 25.250 25.256 1000
Lighting Panel 140.261 140.313 1000
W/S UPS Panel- 20 KVA UPS 95.574 95.612 1000
Lab & Server Panel - 200 KVA UPS 4707.304 4708.909 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2854
1331
6
52
38
1605
3032
Completed date
Completed date
REPORT DATE:15-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 580.531 583.487 1000
LT Room Feeder DG 8179.128 8179.128 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8414.575 8417.609 1000
AC Panel 3236.945 3238.240 1000
Power Panel 25.256 25.263 1000
Lighting Panel 140.313 140.367 1000
W/S UPS Panel- 20 KVA UPS 95.612 95.652 1000
Lab & Server Panel - 200 KVA UPS 4708.909 4710.525 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
3034
1295
7
54
40
1616
3012
Completed date
Completed date
REPORT DATE:16-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 583.487 586.407 1000
LT Room Feeder DG 8179.128 8191.359 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8417.609 8420.520 1000
AC Panel 3238.240 3239.504 1000
Power Panel 25.263 25.270 1000
Lighting Panel 140.367 140.417 1000
W/S UPS Panel- 20 KVA UPS 95.652 95.690 1000
Lab & Server Panel - 200 KVA UPS 4710.525 4712.144 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2911
1264
7
50
38
1619
2978
Completed date
Completed date
REPORT DATE:17-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 586.407 589.405 1000
LT Room Feeder DG 8191.359 8235.923 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8420.520 8423.544 1000
AC Panel 3239.504 3240.868 1000
Power Panel 25.270 25.277 1000
Lighting Panel 140.417 140.472 1000
W/S UPS Panel- 20 KVA UPS 95.690 95.729 1000
Lab & Server Panel - 200 KVA UPS 4712.144 4713.788 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
3024
1364
7
55
39
1644
3109
Completed date
Completed date
REPORT DATE:18-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 589.405 592.253 1000
LT Room Feeder DG 8235.923 8235.923 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8423.544 8426.372 1000
AC Panel 3240.868 3242.141 1000
Power Panel 25.277 25.279 1000
Lighting Panel 140.472 140.491 1000
W/S UPS Panel- 20 KVA UPS 95.729 95.750 1000
Lab & Server Panel - 200 KVA UPS 4713.788 4715.378 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2828
1273
2
19
21
1590
2905
Completed date
Completed date
REPORT DATE:19-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 592.253 595.180 1000
LT Room Feeder DG 8235.923 8235.923 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8426.372 8429.354 1000
AC Panel 3242.141 3243.512 1000
Power Panel 25.279 25.281 1000
Lighting Panel 140.491 140.504 1000
W/S UPS Panel- 20 KVA UPS 95.750 95.772 1000
Lab & Server Panel - 200 KVA UPS 4715.378 4717.060 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2982
1371
2
13
22
1682
3090
Completed date
Completed date
REPORT DATE:20-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 595.180 598.127 1000
LT Room Feeder DG 8235.923 8235.923 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8429.354 8432.197 1000
AC Panel 3243.512 3244.760 1000
Power Panel 25.281 25.288 1000
Lighting Panel 140.504 140.558 1000
W/S UPS Panel- 20 KVA UPS 95.772 95.809 1000
Lab & Server Panel - 200 KVA UPS 4717.060 4718.615 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2843
1248
7
54
37
1555
2901
Completed date
Completed date
REPORT DATE:21-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 598.127 601.022 1000
LT Room Feeder DG 8235.923 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8432.197 8435.118 1000
AC Panel 3244.760 3246.036 1000
Power Panel 25.288 25.295 1000
Lighting Panel 140.558 140.606 1000
W/S UPS Panel- 20 KVA UPS 95.809 95.846 1000
Lab & Server Panel - 200 KVA UPS 4718.615 4720.224 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2921
1276
7
48
37
1609
2977
Completed date
Completed date
REPORT DATE:22-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 601.022 603.985 1000
LT Room Feeder DG 8283.016 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8435.118 8438.062 1000
AC Panel 3246.036 3247.403 1000
Power Panel 25.295 25.297 1000
Lighting Panel 140.606 140.620 1000
W/S UPS Panel- 20 KVA UPS 95.846 95.871 1000
Lab & Server Panel - 200 KVA UPS 4720.224 4721.851 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2944
1367
2
14
25
1627
3035
Completed date
Completed date
REPORT DATE:23-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 603.985 607.070 1000
LT Room Feeder DG 8283.016 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8438.062 8441.110 1000
AC Panel 3247.403 3248.828 1000
Power Panel 25.297 25.304 1000
Lighting Panel 140.620 140.668 1000
W/S UPS Panel- 20 KVA UPS 95.871 95.909 1000
Lab & Server Panel - 200 KVA UPS 4721.851 4723.476 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
3048
1425
7
48
38
1625
3143
Completed date
Completed date
REPORT DATE:24-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 607.070 609.946 1000
LT Room Feeder DG 8283.016 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8441.110 8443.978 1000
AC Panel 3248.828 3250.068 1000
Power Panel 25.304 25.313 1000
Lighting Panel 140.668 140.712 1000
W/S UPS Panel- 20 KVA UPS 95.909 95.942 1000
Lab & Server Panel - 200 KVA UPS 4723.476 4725.061 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2868
1240
9
44
33
1585
2911
Completed date
Completed date
REPORT DATE:25-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 609.946 613.045 1000
LT Room Feeder DG 8283.016 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8443.978 8447.056 1000
AC Panel 3250.068 3251.512 1000
Power Panel 25.313 25.316 1000
Lighting Panel 140.712 140.732 1000
W/S UPS Panel- 20 KVA UPS 95.942 95.960 1000
Lab & Server Panel - 200 KVA UPS 4725.061 4726.732 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
3078
1444
3
20
18
1671
3156
Completed date
Completed date
REPORT DATE:26-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 613.045 616.012 1000
LT Room Feeder DG 8283.016 8283.016 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8447.056 8449.996 1000
AC Panel 3251.512 3252.910 1000
Power Panel 25.316 25.318 1000
Lighting Panel 140.732 140.744 1000
W/S UPS Panel- 20 KVA UPS 95.960 95.987 1000
Lab & Server Panel - 200 KVA UPS 4726.732 4728.330 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Normal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2940
1398
2
12
27
1598
3037
Completed date
Completed date
REPORT DATE:27-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 616.012 618.669 1000
LT Room Feeder DG 8283.016 8694.225 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8449.996 8452.983 1000
AC Panel 3252.910 3254.248 1000
Power Panel 25.318 25.325 1000
Lighting Panel 140.744 140.792 1000
W/S UPS Panel- 20 KVA UPS 95.987 96.025 1000
Lab & Server Panel - 200 KVA UPS 4728.330 4729.960 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Abnormal
Electrical Panels Normal 200 KVA UPS o/p energy meter 16% error
ALCATEL FEEDERS
KWH Units Remarks
2987
1338
7
48
38
1630
3061
Completed date
Completed date
REPORT DATE:28-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 618.669 621.650 1000
LT Room Feeder DG 8694.225 8694.225 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8452.983 8455.992 1000
AC Panel 3254.248 3255.628 1000
Power Panel 25.325 25.332 1000
Lighting Panel 140.792 140.842 1000
W/S UPS Panel- 20 KVA UPS 96.025 96.064 1000
Lab & Server Panel - 200 KVA UPS 4729.960 4731.570 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Normal
Electrical Panels Normal
HVAC BMS System Normal
Pre-Action System Normal
Fire Panel Normal
Whether
Equipment Name-Carpentry Normal / Reason if Abnormal
Abnormal
Door Closures Normal
Doors (Handles & door alignment) Normal
Floor spring Normal
Whether
Equipment Name (Plumbing) Normal / Reason if Abnormal
Abnormal
Urinal Normal
Wash basin Normal
Dish Wash basin Normal
Solenoid valve`s Abnormal
W/C Flush Normal
Health faucet Normal
Seat covers Normal
wash basin taps Normal
Wash basin tap spindle Normal
Drain block if any Normal
Whether
Cafeteria Equipment's Normal / Reason if Abnormal
Abnormal
Micro oven. Total =2Nos Normal
Refrigerator-1Nos Normal
REGULAR WORK ACTIVITI
Checked & Updated AHU, UPS, PAC & Electrical panel daily check list.
Checked LDB's, UPS DB's,Lighting DB's and ELDB's found normal.
Switched ON workstation lights as per requirements
Hourly UPS reading recorded & all its parameters.
Checked & Updated daily PAC, AHU, & Hub room temp check list .
Every two hours temperature reading recorded for the PAC units, Lab & Hub Room.
Taking the Access report(First IN & Last Out Entry report)
A' Check carried of the basement 380KVA DG.
Switching OFF Workstation Unwanted Lightings
Recording KWH reading of all the feeders & BTU Meter reading @ 00:00Hrs.
Water dispenser & Coffee vending machine switched OFF
VENDOR & IN HOUSE WORK AC
EPORT MONTH OF MARCH - 2023 SUBMISSION DATE: 29-03-2023
RIGADE MAGNUM FEEDERS
KWH Units Remarks
2981
0
2981
ALCATEL FEEDERS
KWH Units Remarks
3009
1380
7
50
39
1610
3086
Completed date
Completed date
REPORT DATE:29-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 621.650 624.794 1000
LT Room Feeder DG 8694.225 8694.225 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8455.992 8459.119 1000
AC Panel 3255.628 3257.139 1000
Power Panel 25.332 25.340 1000
Lighting Panel 140.842 140.900 1000
W/S UPS Panel- 20 KVA UPS 96.064 96.102 1000
Lab & Server Panel - 200 KVA UPS 4731.570 4733.218 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Normal
Electrical Panels Normal
HVAC BMS System Normal
Pre-Action System Normal
Fire Panel Normal
Whether
Equipment Name-Carpentry Normal / Reason if Abnormal
Abnormal
Door Closures Normal
Doors (Handles & door alignment) Normal
Floor spring Normal
Whether
Equipment Name (Plumbing) Normal / Reason if Abnormal
Abnormal
Urinal Normal
Wash basin Normal
Dish Wash basin Normal
Solenoid valve`s Abnormal
W/C Flush Normal
Health faucet Normal
Seat covers Normal
wash basin taps Normal
Wash basin tap spindle Normal
Drain block if any Normal
Whether
Cafeteria Equipment's Normal / Reason if Abnormal
Abnormal
Micro oven. Total =2Nos Normal
Refrigerator-1Nos Normal
REGULAR WORK ACTIVITI
Checked & Updated AHU, UPS, PAC & Electrical panel daily check list.
Checked LDB's, UPS DB's,Lighting DB's and ELDB's found normal.
Switched ON workstation lights as per requirements
Hourly UPS reading recorded & all its parameters.
Checked & Updated daily PAC, AHU, & Hub room temp check list .
Every two hours temperature reading recorded for the PAC units, Lab & Hub Room.
Taking the Access report(First IN & Last Out Entry report)
A' Check carried of the basement 380KVA DG.
Switching OFF Workstation Unwanted Lightings
Recording KWH reading of all the feeders & BTU Meter reading @ 00:00Hrs.
Water dispenser & Coffee vending machine switched OFF
VENDOR & IN HOUSE WORK AC
EPORT MONTH OF MARCH - 2023 SUBMISSION DATE: 30-03-2023
RIGADE MAGNUM FEEDERS
KWH Units Remarks
3144
0
3144
ALCATEL FEEDERS
KWH Units Remarks
3127
1511
8
58
38
1648
3263
Completed date
Completed date
REPORT DATE:30-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 624.794 627.856 1000
LT Room Feeder DG 8694.225 8694.225 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8459.119 8462.180 1000
AC Panel 3257.139 3258.554 1000
Power Panel 25.340 25.348 1000
Lighting Panel 140.900 140.947 1000
W/S UPS Panel- 20 KVA UPS 96.102 96.136 1000
Lab & Server Panel - 200 KVA UPS 4733.218 4734.901 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Normal
Electrical Panels Normal
HVAC BMS System Normal
Pre-Action System Normal
Fire Panel Normal
Whether
Equipment Name-Carpentry Normal / Reason if Abnormal
Abnormal
Door Closures Normal
Doors (Handles & door alignment) Normal
Floor spring Normal
Whether
Equipment Name (Plumbing) Normal / Reason if Abnormal
Abnormal
Urinal Normal
Wash basin Normal
Dish Wash basin Normal
Solenoid valve`s Abnormal
W/C Flush Normal
Health faucet Normal
Seat covers Normal
wash basin taps Normal
Wash basin tap spindle Normal
Drain block if any Normal
Whether
Cafeteria Equipment's Normal / Reason if Abnormal
Abnormal
Micro oven. Total =2Nos Normal
Refrigerator-1Nos Normal
REGULAR WORK ACTIVITI
Checked & Updated AHU, UPS, PAC & Electrical panel daily check list.
Checked LDB's, UPS DB's,Lighting DB's and ELDB's found normal.
Switched ON workstation lights as per requirements
Hourly UPS reading recorded & all its parameters.
Checked & Updated daily PAC, AHU, & Hub room temp check list .
Every two hours temperature reading recorded for the PAC units, Lab & Hub Room.
Taking the Access report(First IN & Last Out Entry report)
A' Check carried of the basement 380KVA DG.
Switching OFF Workstation Unwanted Lightings
Recording KWH reading of all the feeders & BTU Meter reading @ 00:00Hrs.
Water dispenser & Coffee vending machine switched OFF
VENDOR & IN HOUSE WORK AC
EPORT MONTH OF MARCH - 2023 SUBMISSION DATE: 31-03-2023
RIGADE MAGNUM FEEDERS
KWH Units Remarks
3062
0
3062
ALCATEL FEEDERS
KWH Units Remarks
3061
1415
8
47
34
1683
3187
Completed date
Completed date
REPORT DATE:31-03-2023 DAILY REPORT MONTH O
BRIGADE MAGNUM FE
Feeder Name Opening Closing Multiplication Factor
LT Room Feeder EB 627.856 630.899 1000
LT Room Feeder DG 8694.225 8694.225 1
ALCATEL FEEDE
Feeder Name Opening Closing Multiplication Factor
Main Common Panel 8462.180 8465.393 1000
AC Panel 3258.554 3260.032 1000
Power Panel 25.348 25.357 1000
Lighting Panel 140.947 141.048 1000
W/S UPS Panel- 20 KVA UPS 96.136 96.174 1000
Lab & Server Panel - 200 KVA UPS 4734.901 4736.680 1000
DG SET'S RUNNING D
From Time From Time To Time Duration
Power failure-1 0:00 0:00 0:00
Power failure-2 0:00 0:00 0:00
Power failure-3 0:00 0:00 0:00
Total DG set's running Hours
EQUIPMENT HEALTHINES
Whether
Equipment Name Normal / Reason if Abnormal
Abnormal
UPS Normal
DG-380KVA Normal
Security systems Normal
Precision A/c Normal
CSU's Normal
DX Unit Normal
Split Ac Normal
AHU's Normal
VFD's Normal
Battery monitoring system Abnormal
CCTV Normal
Electrical Panels Normal
HVAC BMS System Normal
Pre-Action System Normal
Fire Panel Normal
Whether
Equipment Name-Carpentry Normal / Reason if Abnormal
Abnormal
Door Closures Normal
Doors (Handles & door alignment) Normal
Floor spring Normal
Whether
Equipment Name (Plumbing) Normal / Reason if Abnormal
Abnormal
Urinal Normal
Wash basin Normal
Dish Wash basin Normal
Solenoid valve`s Abnormal
W/C Flush Normal
Health faucet Normal
Seat covers Normal
wash basin taps Normal
Wash basin tap spindle Normal
Drain block if any Normal
Whether
Cafeteria Equipment's Normal / Reason if Abnormal
Abnormal
Micro oven. Total =2Nos Normal
Refrigerator-1Nos Normal
REGULAR WORK ACTIVITI
Checked & Updated AHU, UPS, PAC & Electrical panel daily check list.
Checked LDB's, UPS DB's,Lighting DB's and ELDB's found normal.
Switched ON workstation lights as per requirements
Hourly UPS reading recorded & all its parameters.
Checked & Updated daily PAC, AHU, & Hub room temp check list .
Every two hours temperature reading recorded for the PAC units, Lab & Hub Room.
Taking the Access report(First IN & Last Out Entry report)
A' Check carried of the basement 380KVA DG.
Switching OFF Workstation Unwanted Lightings
Recording KWH reading of all the feeders & BTU Meter reading @ 00:00Hrs.
Water dispenser & Coffee vending machine switched OFF
VENDOR & IN HOUSE WORK AC
EPORT MONTH OF MARCH - 2023 SUBMISSION DATE: 1-04-2023
RIGADE MAGNUM FEEDERS
KWH Units Remarks
3043
0
3043
ALCATEL FEEDERS
KWH Units Remarks
3213
1478
9
101
38
1779
3405
Completed date
Completed date
LT ROOM EB / Brigade LT ROOM
DATE
Opening Closing Consum. Cumulative Opening
1-Mar-2023 540263 542782 2519 2519 7525.340
2-Mar-2023 542782 545699 2917 5436 7895.965
3-Mar-2023 545699 548385 2686 8122 7895.965
4-Mar-2023 548385 551319 2934 11056 8146.482
5-Mar-2023 551319 554204 2885 13941 8146.482
6-Mar-2023 554204 557133 2929 16870 8146.482
7-Mar-2023 557133 560069 2936 19806 8146.482
8-Mar-2023 560069 563040 2971 22777 8146.482
9-Mar-2023 563040 565921 2881 25658 8146.482
10-Mar-2023 565921 568860 2939 28597 8146.482
11-Mar-2023 568860 571626 2766 31363 8146.482
12-Mar-2023 571626 574571 2945 34308 8179.128
13-Mar-2023 574571 577544 2973 37281 8179.128
14-Mar-2023 577544 580531 2987 40268 8179.128
15-Mar-2023 580531 583487 2956 43224 8179.128
16-Mar-2023 583487 586407 2920 46144 8179.128
17-Mar-2023 586407 589405 2998 49142 8191.359
18-Mar-2023 589405 592253 2848 51990 8235.923
19-Mar-2023 592253 595180 2927 54917 8235.923
20-Mar-2023 595180 598127 2947 57864 8235.923
21-Mar-2023 598127 601022 2895 60759 8235.923
22-Mar-2023 601022 603985 2963 63722 8283.016
23-Mar-2023 603985 607070 3085 66807 8283.016
24-Mar-2023 607070 609946 2876 69683 8283.016
25-Mar-2023 609946 613045 3099 72782 8283.016
26-Mar-2023 613045 616012 2967 75749 8283.016
27-Mar-2023 616012 618669 2657 78406 8283.016
28-Mar-2023 618669 621650 2981 81387 8684.225
29-Mar-2023 621650 624794 3144 84531 8684.225
30-Mar-2023 624794 627856 3062 87593 8684.225
31-Mar-2023 627856 630899 3043 90636 8694.225
Total (EB+DG) Units /
LT ROOM DG / Brigade
Brigade Feeder
Closing Consum. Cumulative KWH Units
7895.965 371 370.625 2890
7895.965 0 371 2917
8146.482 251 621 2937
8146.482 0 621 2934
8146.482 0 621 2885
8146.482 0 621 2929
8146.482 0 621 2936
8146.482 0 621 2971
8146.482 0 621 2881
8146.482 0 621 2939
8179.128 33 654 2799
8179.128 0 654 2945
8179.128 0 654 2973
8179.128 0 654 2987
8179.128 0 654 2956
8191.359 12 666 2932
8235.923 45 711 3043
8235.923 0 711 2848
8235.923 0 711 2927
8235.923 0 711 2947
8283.016 47 758 2942
8283.016 0 758 2963
8283.016 0 758 3085
8283.016 0 758 2876
8283.016 0 758 3099
8283.016 0 758 2967
8684.225 401 1159 3058
8684.225 0 1159 2981
8684.225 0 1159 3144
8694.225 10 1169 3072
8694.225 0 1169 3043
Diff. b/w Brigade &
Alcatel Main Incomer
Alcatel Feeder
KWH Units Opening Closing Consum. Cumulative
-115 8374.071 8377.076 3005 3005
6 8377.076 8379.987 2911 5916
180 8379.987 8382.744 2757 8673
25 8382.744 8385.653 2909 11582
-34 8385.653 8388.572 2919 14501
87 8388.572 8391.414 2842 17343
11 8391.414 8394.339 2925 20268
58 8394.339 8397.252 2913 23181
-7 8397.252 8400.140 2888 26069
20 8400.140 8403.059 2919 28988
28 8403.059 8405.830 2771 31759
37 8405.830 8408.738 2908 34667
-10 8408.738 8411.721 2983 37650
133 8411.721 8414.575 2854 40504
-78 8414.575 8417.609 3034 43538
21 8417.609 8420.520 2911 46449
19 8420.520 8423.544 3024 49473
20 8423.544 8426.372 2828 52301
-55 8426.372 8429.354 2982 55283
104 8429.354 8432.197 2843 58126
21 8432.197 8435.118 2921 61047
19 8435.118 8438.062 2944 63991
37 8438.062 8441.110 3048 67039
8 8441.110 8443.978 2868 69907
21 8443.978 8447.056 3078 72985
27 8447.056 8449.996 2940 75925
71 8449.996 8452.983 2987 78912
-28 8452.983 8455.992 3009 81921
17 8455.992 8459.119 3127 85048
11 8459.119 8462.180 3061 88109
-170 8462.180 8465.393 3213 91322
All UPS Transformer
HVAC PANEL
losses
CONSUMPTION Opening Closing Consum. Cumulative
-80 3219.058 3220.359 1301 1301
-57 3220.359 3221.574 1215 2516
-51 3221.574 3222.731 1157 3673
-102 3222.731 3224.028 1297 4970
-88 3224.028 3225.364 1336 6306
-61 3225.364 3226.586 1222 7528
-91 3226.586 3227.893 1307 8835
-86 3227.893 3229.189 1296 10131
-76 3229.189 3230.445 1256 11387
-80 3230.445 3231.694 1249 12636
-74 3231.694 3232.897 1203 13839
-145 3232.897 3234.297 1400 15239
-72 3234.297 3235.614 1317 16556
-178 3235.614 3236.945 1331 17887
23 3236.945 3238.240 1295 19182
-68 3238.240 3239.504 1264 20446
-85 3239.504 3240.868 1364 21810
-77 3240.868 3242.141 1273 23083
-108 3242.141 3243.512 1371 24454
-58 3243.512 3244.760 1248 25702
-56 3244.760 3246.036 1276 26978
-91 3246.036 3247.403 1367 28345
-95 3247.403 3248.828 1425 29770
-43 3248.828 3250.068 1240 31010
-78 3250.068 3251.512 1444 32454
-97 3251.512 3252.910 1398 33852
-74 3252.910 3254.248 1338 35190
-77 3254.248 3255.628 1380 36570
-136 3255.628 3257.139 1511 38081
-126 3257.139 3258.554 1415 39496
808 3258.554 3260.032 1478 40974
RAW POWER PANEL LIGHTING PANEL