R1
having reinf. of dia. 12mm.
(to links of column)
V Slabs 20 30 45
VI Beams 20 30 45
(to stirrups of beam)
VII Lift wall 40 40 45
DETAILS OF STAIRCASE (ST2) For main reinf. up to 12mm dia. bar for mild exposure the nominal cover
may be reduced by 5mm for slabs & beams only.
SECTION THROUGH SECOND FLIGHT 4. Beams having depth more than 750mm, provide side-face reinforcement.
5. Substratum shall be approved from our office before laying P.C.C.
6. Minimum clear spacing between any two longitudinal bars in beam= 50mm.
7. All laps (Ld) shall be staggered & not more than 50% bars to be lapped
at any given section.
GRADE OF REINF. M20 M25 M30 M35 M40 & ABOVE
Fe415 55 X D 47 X D 44 X D 39 x D 35 x D
Fe500 (TMT) 66 X D 56 X D 53 X D 46 x D 42 x D
8. All buildings shall have tie beams/plinth beams at ground/plinth level.
9. If footings overlap each other, necessary revision shall be obtained from our office.
10. Design is valid for number of floors as indicated in the drawing.
11. At any level where column size gets reduced in either dimension
tie beams/plinth beams are essential.
12. For cantilevers, top bars to be anchored behind from external face of support for - Ld or
span of cantilever - whichever is greater.
13. Fire rating considered:- 1 Hour Max.
Use of this drawing for construction shall explicitly confirm acceptance of following conditions
by Owner / Builder / Contractor
1. Our responsibility shall remain limited to safe and sound structural design as transmitted
by this drawing and we shall not remain responsible for
a) Safety of old structure during demolition.
DETAILS OF STAIRCASE (ST1) b) Safety of any adjoining building /persons staying in adjoining building/persons
and properties on adjoining roads.
SECTION THROUGH FIRST FLIGHT c) Safety of construction worker/any personnel at work site during construction
d) Correctness/safety of any temporary structure, scaffolding, shuttering, centering erected at site and
any injury to any personnel arising out of any accidents.
e) Accidents occurring due to premature deshuttering, faulty / substandard construction material or
workmanship / faulty construction procedure.
f) Any accident occurring due to construction of elements of buildings not designed by us.
2. Supervision if specifically asked for will be provided to the extent of verification of reinforcement on site
but responsibility regarding correct & sound construction shall solely rest with contractor/ builder / owner.
3. All structural concrete should be weigh batched, machine mixed & mechanically vibrated.
4. Any discrepancy between our drawing & Architects' drawing shall be brought to our notice before construction.
5. This drawing is property of INFINITY STRUCTURAL SOLUTION and shall not be reproduced or used
MARK GRID TO F.F.L. 0.00M
without explicit permission of this office.
G.L. -0.50M NO. REV. DATE DESCRIPTION NO. REV. DATE DESCRIPTION
R0 23-02-2023 APRROVAL R5
03-03-2023 AS PER DUCTILE
R1 DETAILING R6
TYPICAL SECTION R2 R7
R3 R8
R4 R9
TYPE THICKNESS STEEL @SHORTER SPAN STEEL @LONGER SPAN REMARKS
STAIRCASE SLAB PROVIDE SCISSOR JOINT
S.B.C. :- 14 T/SQM.@3000MM. BELOW GL.
ST1,ST2 200 T8@200C/C 12 @100C/C AT RESPECTIVE UPPER LANDING (SUPPORT ST3)
SEISMIC ZONE = III
USE PB INSTEAD
OF B PLINTH LEVEL PLAN @ -0.20M ST3 200 T8@200C/C 12 @100C/C
STAIRCASE SLAB PROVIDE SCISSOR JOINT
AT RESPECTIVE UPPER LANDING (REST ON ST1&ST2)
WIND VELOCITY = 39M/S
(A) BEAM SCHEDULE AT -0.20M LEVEL. LIVE LOAD. = 250KG/SQM
(UNLESS SPECIFIED) EQUIP LOAD BY PLANT SUPPLIER
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT 100(TYP) IN PLACE
BEAM SHEAR STIRRUPS SFR REMARKS
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA OF 75C/C
3-T20 ALL TOP LEFT RIGHT LEFT ALL
SUPP BOTTOM
RIGHT SUPP
3-16 CLADDING IS CONSIDER FOR DESIGN
UPLIFT-(WATER)PRESSURE IS NOT CONSIDER FOR DESIGN
B1,B2 230 530 3-T12 - - - 3-T12 - - 56-2L-T8@75,200,75 C/C 1-T10EF -
B18,B22 230 530 3-T12 - - - 3-T12 - - 45-2L-T8@75,200,75 C/C 1-T10EF - PRAMOD MANASI 1036-22-DRYER-PB-211-1 DRYER 1036-22
PLANT SUPPLIER - JOB NO.
B19,B23 230 530 3-T12 - - - 3-T12 - - 64-2L-T8@75,200,75 C/C 1-T10EF -
MSD-651
B20,B24,B30,B34 230 450 3-T12 - - - 3-T12 - - 31-2L-T8@75,150,75 C/C - -
MOJJ ENGINEERING SYSTEMS LTD.
SHEET-A1
B25,B31 230 450 3-T12 - - - 3-T12 - - 26-2L-T8@75,150,75 C/C - -
B26 230 530 3-T12 - - - 3-T12 - - 48-2L-T8@75,200,75 C/C 1-T10EF - CLIENT - ADITYA BIRLA GRASIM.
2-T10 PLANT - SPRAY DRYER PLANT AT JHARKHAND
B27 230 530 2-T16 - - - 3-T12 - - 72-2L-T8@75,200,75C/C 1-T10EF - TITLE - PLAN & SCHEDULE OF RCC PLINTH BEAM AT-0.20M LEVEL.
2-T10 2-T10
HEAD OFFICE - Pride Ashiyana,C-303,3rd floor
B28 230 530 3-T12 - - - 3-T12 - - 56-2L-T8@75,200,75 C/C 1-T10EF - Lohegaon Pune - 411047. INDIA.
2-T10 DHULE BRANCH - Jawahar Nagar Sakri Road,
B29 230 450 3-T12 - - - 3-T12 - - 8-2L-T8@150 C/C - -
Plot.no.-37,Dhule- 424001
Mobile.No.. - +91 8975476691
B32 230 530 3-T12 - - - 3-T12 - - 45-2L-T8@75,200,75 C/C 1-T10EF - Email - infinitystructuralssolutions@gmail.com
2-T12
website:-www.infinitystructural.co.in
B33 230 530 3-T12 - - - 3-T12 - - 64-2L-T8@75,200,75 C/C 1-T10EF -
2-T12