Professional Documents
Culture Documents
Reporton Generating Substation 220 KV GSS
Reporton Generating Substation 220 KV GSS
Reporton Generating Substation 220 KV GSS
net/publication/358088750
CITATIONS READS
0 2,935
1 author:
Tanishk Jharwal
Swami Keshvanand Institute of Technology Management and Gramothan (SKIT)
3 PUBLICATIONS 0 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Tanishk Jharwal on 25 January 2022.
Submitted for partial fulfilment of the requirements for the award of the degree of
Bachelor of Technology
in
Electrical Engineering
Session: 2021-22
Conclusion………………………………………………………………………………51
References………………………………………………………………………………52
TABLE 9 BATTERY 50
CHARGER(RATING &
MANUFACTURER)
and distribution system. Substations transform voltage from high to low, or the
reverse, or perform any of several other important functions. Between the generating
station and consumer, electric power may flow through several substations at different
The word substation comes from the days before the distribution system became
a grid. As central generation stations became larger, smaller generating plants were
converted to distribution stations, receiving their energy supply from a larger plant
instead of using their own generators. The first substations were connected to only
one power station, where the generators were housed, and were subsidiaries of that
powerstation
1.1) INTRODUCTION
I. Training details
• Name of Training – Industrial Training
• offering institute – 220 KV GSS, RRVPN, I.G Nagar, Jaipur
• Duration of course- 30 Days
C) Distribution substations
are located near to the end-users. Distribution substation transformers change the
transmission or subtransmission voltage to lower levels for use by end-users. Typical
distribution voltages vary from 34,500Y/19,920 volts to 4,160Y/2400 volts.
34,500Y/19,920 volts is interpreted as a three-phase circuit with a grounded neutral
source. This would have three high-voltage conductors or wires and one grounded
neutral conductor, a total of four wires. The voltage between the three phase
conductors or wires would be 34,500 volts and the voltage between one phase
conductor and the neutral ground would be 19,920 volts.
From here the power is distributed to industrial, commercial, and residential
customers.
▪ Conduits
▪ Duct Runs
▪ Manholes
▪ High-Voltage Underground Cables
▪ Transformer Vault
▪ Riser
▪ Transformers
From here the power is distributed to industrial, commercial, and residential
customers.
E) Substation Functions
Substations are designed to accomplish the following functions, although not all
substations have all these functions:
▪ Change voltage from one level to another
▪ Regulate voltage to compensate for system voltage changes
▪ Switch transmission and distribution circuits into and out of the grid system
▪ Measure electric power qualities flowing in the circuits
▪ Connect communication signals to the circuits
▪ Eliminate lightning and other electrical surges from the system
Department of Electrical Engineering, SKIT M&G, Jaipur Page 13
▪ Connect electric generation plants to the system
▪ Make interconnections between the electric systems of more than one utility
▪ Control reactive kilovolt-amperes supplied to and the flow of reactive kilovolt-
amperes in the circuits
F) Substation Components
The major components of a typical substation are:
▪ Air Circuit Breaker
▪ Batteries
▪ Bus Support Insulators
▪ Capacitor Bank
▪ Circuit Switchers
▪ Concrete Foundation
▪ Conduits
▪ Control House
▪ Control Panels
▪ Control Wires
▪ Converter Stations
▪ Coupling Capacitors
▪ Current Transformers
▪ Disconnect Switches
▪ Distribution Bus
▪ Duct Runs
▪ Frequency Changers
▪ Grounding Resistors
▪ Grounding Transformers
▪ High-Voltage Underground Cables
▪ High-Voltage Fuses
▪ Lightning Arresters
▪ Manholes
▪ Metal-clad Switchgear
SUBSTATION COMPONENTS
A) Types of Arrestors:-
i) Rod/sphere gap:- It is a very simple protective device i.e. gap is provided across the
stack of Insulators to permit flash-over when undesirable voltages are
impressed of the system.
ii)Expulsion type LA:- It have two electrodes at each end and consists of a fiber tube
capable of producing a gas when is produced. The gas so evolved blows the arc
through the bottom electrode.
iii) Valve type LA:- It consists of a divided spark-gap in series will a non linear
resistor. The divided spark gap consists of a no. of similar elements, each of it two
electrode across which are connected high resistor.
2.2) BUS BARS
Bus Bars are the common electrical component through which a large no of feeders
operating at same voltage have to be connected. If the bus bars are of rigid type
(Aluminum types) the structure height are low and minimum clearance is required.
While in case of strain type of bus bars suitable ACSR conductor are strung/tensioned
by tension insulators discs according to system voltages. In the widely used strain type
bus bars stringing tension is about 500-900 Kg depending upon the size of conductor
used.
Here proper clearance would be achieved only if require tension is achieved. Loose
bus bars would effect the clearances when it swings while over tensioning may
damage insulators. Clamps or even effect the supporting structures in low temperature
conditions.
The clamping should be proper, as loose clamp would spark under in full load
condition damaging the bus bars itself.
A) TYPE OF INSULATORS:
1. Pin type
2. Suspension type
3. Strain insulator
Insulators, generally used in GSS, is suspension type insulator.
SUSPENSION TYPE: Suspension type insulators consist of a number of porcelain
disc connected in series by metal links in the form of a string. Its working voltage is
66KV. Each disc is designed for low voltage for 11KV.
(a) (b)
Fig.2.3 (a)pin type insulator (b) Strain type insulator
2.4) ISOLATORS
“Isolator" is one, which can break and make an electric circuit in no load condition.
These are normally used in various circuits for the purposes of Isolation of a certain
Fig.2.4- Isolators
Its main application is in connection with transformer feeder as this unit makes it
possible to switch out one transformer, while the other is still on load. The most
common type of isolators is the rotating centre pots type in which each phase has three
insulator post, with the outer posts carrying fixed contacts and connections while the
centre post having contact arm which is arranged to move through 90` on its axis.
The following interlocks are provided with isolator:
a) Bus 1 and2 isolators cannot be closed simultaneously.
b) Isolator cannot operate unless the breaker is open.
c) Only one bay can be taken on bypass bus.
d) No isolator can operate when corresponding earth switch is on breaker.
*Circuit Breakers, generally used in GSS, are SF6 and Air blast circuit
breaker.
i) SF6 CIRCUIT BREAKER:-
Sulphur hexafluoride has proved its-self as an excellent insulating and arc quenching
medium. It has been extensively used during the last 30 years in circuit breakers, gas-
insulated switchgear (GIS), high voltage capacitors, bushings, and gas insulated
transmission lines. In SF6 breakers the contacts are surrounded by low pressure SF6
gas. At the moment the contacts are opened, a small amount of gas is compressed and
forced through the arc to extinguish it.
Disadvantages:
Air has relatively inferior arc extinguishing properties.
• Air blast circuit breakers are very sensitive to the variations in the rate of restriking
voltage.
• Considerable maintenance is required for the compressor plant which supplies the
air blast
• Air blast circuit breakers are finding wide applications in high voltage installations.
Majority of circuit breakers for voltages beyond 110 kV are of this type.
(c)
Fig.2.7 (a)oil circuit breaker (b)bulk oil circuit breaker (c)minimum oil circuit breaker
Fig.2.8 -Relays
A) Distance Relays:
Distance relays respond to the voltage and current, i.e., the impedance, at the relay
location. The impedance per mile is fairly constant so these relays respond to the
distance between the relay location and the fault location. As the power systems
become more complex and the fault current varies with changes in generation and
system configuration, directional over current relays become difficult to apply and to
set for all contingencies, whereas the distance relay setting is constant for a wide
variety of changes external to the protected line.
i) Types of Distance relay:-
a) Impedance Relay:
The impedance relay has a circular characteristic centred. It is non directional and is
used primarily as a fault detector.
b) Admittance Relay:
The admittance relay is the most commonly used distance relay. It is the tripping relay
in pilot schemes and as the backup relay in step distance schemes. In the
electromechanical design it is circular, and in the solid state design, it can be shaped to
correspond to the transmission line impedance.
D)Transformer Accessories:
i) Buchholz Relay:
This has two Floats, one of them with surge catching baffle and gas collecting space at
Fig.2.11-Buchholz Relay
ii) Temperature Indicators:
Most of the transformer (small transformers have only OTI) are provided with
indicators that displace oil temperature and winding temperature. There are
thermometers pockets provided in the tank top cover which hold the sensing bulls in
them. Oil temperature measured is that of the top oil, where as the winding
temperature measurement is indirect. This is done by adding the temperature rise due
to the heat produced in a heater coil (known as image coil) when a current proportional
to that flowing in windings is passed in it to that or top oil. For proper functioning or
OTI & WTI it is essential to keep the thermometers pocket clean and filled with oil.
Fig.2.15-Current Transformers
It can be used to supply information for measuring power flows and the electrical
inputs for the operation of protective relays associated with the transmission and
distribution circuit or for power transformer. These current transformers have the
primary winding connected in series with the conductor carrying the current to be
measured or controlled. The secondary winding is thus insulated from the high voltage
and can then be connected to low voltage metering circuits.
2.9) POTENTIAL TRANSFORMER
A potential transformer (PT) is used to transform the high voltage of a power line to a
lower value, which is in the range of an ac voltmeter or the potential coil of an ac
voltmeter.
secondary terminals.
The porcelain in multi unit stack, all the potentials points are electrically tied and
suitably shielded to overcome the effect of corona RIV etc. Capacitive voltage
transformers are available for system voltage.
2.11) CAPACITOR BANK
The capacitor bank provides reactive power at grid substation. The voltage regulation
problem frequently reduces so of circulation of reactive power.
Unlike the active power, reactive power can be produced, transmitted and absorbed of
course with in the certain limit, which have always to be workout. At any point in the
system shunt capacitor are commonly used in all voltage and in all size.
Benefits of using the capacitor bank are many and the reason is that capacitor reduces
the reactive current flowing in the whole system from generator to the point of
installation.
1 .Increased voltage level at the load
2. Reduced system losses
3. Increase power factor of loading current
2.12) EARTHING OF THE SYSTEM
The provision of an earthing system for an electric system is necessary by the
following reason.
• In the event of over voltage on the system due to lightening discharge or other
system fault. These parts of equipment, which are normally dead, as for as voltage,
are concerned do not attain dangerously high potential.
• In a three phase, circuit the neutral of the system is earthed in order to stabilize the
potential of circuit with respect to earth.
A. ANNOUNCING SECTION
This section is always checked by shift incharge. If any faults or any relays moves
from L.T. alarms swings and type of fault is indicated on the announcing box. The
most important section is indicated by announcing box. The most important section is
transformer controller section, winding temperature indicator, tap position selector is
situated on control panel. A control engineer controls loading of various lines,
outgoing feeders, synchronizing the indicating lines with bus bar.
C. EVENT LOGGER
To work in control room contain work are automated with computer based control
system .By facilitate the operator locating identification and reporting fault
information is required.
F) CRT DISPLAY
The operation in the control room needs information regarding parameters and
configuration according to the feeders. It Is divided into many parts.
1. Indication system
2. Control switches
3. Relay section
4. Meter section
5. Announcing section
6. DC supply system
7. Transformer control unit
J) METER SECTION
This includes a different type of meter .One network CRT display provides operator
with following information whenever he works. Two type of display includes
∙ Tabulated values of parameter
∙ Measured values and computed characteristic symbolic representation of equipment
states usually in the forms of diagram of substation.
➢ iii) FREQUENCY METER: To measure the frequency at each feeder there is the
provision of analog or digital frequency meter.
➢ iv) VOLTMETER: It is provided to measure the phase to phase voltage .It is also
available in both the analog and digital frequency meter.
➢ vi) MAXIMUM DEMAND INDICATOR: There are also mounted the control
panel to record the average power over successive predetermined period.
Fig.3.2.-Wave Trap
The Line trap OFFERS HIGH IMPEDANCE TO THE HIGH FREQUENCY COMMUNICATION
SIGNALS thus obstructs the flow of these signals in to the substation bus bars. If there
were not to be there, then signal loss is more and communication will be
ineffective/probably impossible.
The increasing demand of electrical power in cities and industrial centers necessitates
the installation of a compact and efficient distribution and transmission network. High
voltage gas insulated switchgear (GIS) is ideal for such applications.
The range of application of SF₆ Gas Insulated Switchgear extends from voltage ratings
of 72.5 kV up to 800 kV with breaking currents of up to 63 kA, and in special cases up
to 80 kA. Both small transformer substations and large load-center substations can be
designed with GIS technology. The distinctive advantages of SF₆ Gas Insulated
Switchgear are: compact, low weight, high reliability, safety against touch contact, low
maintenance and long life. Extensive in-plant preassembly and testing of large units
and complete bays reduces assembly and commissioning time on the construction site.
GIS equipment is usually of modular construction. All components such as bus-bars,
disconnectors, circuit-breakers, instrument transformers, cable terminations and joints
are contained in earthed enclosures filled with sulphur hexafluoride gas (SF₆).
ADVANTAGES:
Gas Insulated Switchgear (GIS) that uses compresses sulfur hexafluoride (SF6) gas
overcomes many of the limitations of the conventional open type AIS, as it offers the
following advantages:
(1)The space occupied by the switchgear is greatly reduced
(2) It is totally unaffected by atmospherically conditions such as polluted or saline air
in industrial and coastal areas, or desert climates.
(3) It possesses a high degree of operational reliability and safety to personal.
(4) It is easier to install in difficult site conditions ( e.g. on unstable ground or in
Department of Electrical Engineering, SKIT M&G, Jaipur Page 41
seismically active areas)
(5) In addition to having a dielectric strength much greater than that of air, SF6 has the
advantages of being nontoxic and non flammable.
4.2) GIS COMPONENTS:
In GIS all live parts are enclosed in compressed gas system which is divided into a
number of compartments. This division enables the isolation of one compartment for
maintenance or repair purpose while the other compartments remain pressurized. In
figure below the single-line diagram of a double bus-bar arrangement is shown.
Fig.4.4 PASS
4.3) ADVANTAGES
PASS combines all the typical functions of a complete AIS bay for electrical
substations with voltage ratings of up to 245 kV in a unit whose volume is comparable
to that of a conventional circuit-breaker of equal class. It takes advantage and widens
the scope of the operating philosophy of the PASS series whose dominating factors,
those that have dictated the product‟s success with more than 2000 systems sold
throughout the world, is briefly outlined below:
1. Relatively inexpensive AIS bus bar.
∙ Yet traditionally highly reliable.
Fig.4.5 PASS(2)
RATINGS OF EQUIPMENTS
17.1) TRANSFORMER:
Total No. of transformers = 4 No. of
transformers
IV 132
LV K 11
V
A
TABLE 2.TRANSFORMERS SPECIFICATIONS (TYPE OF COOLING)
No. of phases 3
Max. Temp. ‘C 40
Ambient of 50’C Top oil avg. wdg 55
TABLE 4.TRANSFORMERS SPECIFICATIONS (TEMPARATURE)
TAP Connect Line Line current (A) Line Line Current (A)
Positio 3T 15T voltage(K ONA ONA ODAF Volta ONA ONA ODAF
n O O V) N F 100M ge N F 100M
50MV 70MV VA (KV) 50MV 70MV VA
A A A A
1Max 4 14 242.00 119.4 167.2 238.86
3 0
2 13 239.25
3 12 236.50
4 11 233.75
5 10 231.00
6 9 228.25
7 8 225.50
Ratio
Acc. Burden Knee Exciting Max. Sec. Purpose
Class (VA) Point Current Resistance
Voltage ATVK(mA) 75’C(ohms)
1VCT - 5 R.E.F.
CORE1 600/1 PS 1000 60 Protection
1VCT1
- 5 Differential
CORE2 600/1 PS 1000 60 Protection
1WCT
1VCT2 309/2 3 30 - - - WTI
2VCT - 5 R.E.F.
CORE1 600/1 PS 1000 60 Protection
2VCT1
- 5 Differential
CORE2 600/1 PS 1000 60 Protection
2WCT
2VCT2 438/2 3 30 - - - WTI
NVCT - 5 R.E.F.
CORE1 600/1 PS 1000 60 Protection
NVCT1
POTENTIAL TRANSFORMER
Secondary V/R(KV) VA Class Primary Secondary Purpose
Winding Terminals Terminals
I 11/0.110 50 0.5/3P A2B2C2N a2b2c2 Measurement
II 11/0.110 50 3P - da2-dn Protection
TABLE 8. POTENTIAL TRANSFORMER RATING
BATTERY CHARGER
Training at 220KV GSS IG Nagar, Jaipur gives the insight of the real instruments
used. There are many instruments like transformer, CT, PT, CVT, LA, relay, PLCC,
bus bars, capacitor bank, insulator, isolators, control room, Battery room etc.
What is the various problem seen in substation while handling this instruments.
There are various occasion when relay operate and circuit breaker open, load shedding,
shut down, which has been heard previously. To get insight of the substation, how
things operate, how things manage all is learned there. Practical training as a whole
proved to be extremely informative and experience building and the things learnt at it
would definitely help a lot in snapping the future ahead a better way.
P516,
➢ http://upload.wikimedia.org/wikipedia/en/6/63/cvt.png
➢ http://images.google.co.in/(Equipment’s name)
➢ www.browzen.com/relay
➢ www.electrical-engineering-portal.com