Dynamic Checks (SENR6430-02) PDF
Dynamic Checks (SENR6430-02) PDF
SMCS - SENR64300005
2. Close the rated speed switch (or put jumper across T9 and T10).
4. Magnetic Pickup 1
SEN 5:21+ 3
© 2 R643 03:00
a. Activate manual shutoff (or disconnect wires to actuator from terminals T3 and T4).
023 0
b. Crank the engine and measure output voltage of magnetic pickup across terminals T5 and T6 [should
be greater than 1 VDC (measured at RMS voltage)].
Cat
c. Release manual shutoff (or reconnect wires to actuator from terminals T3 and T4).
erp
illa
r In
c.
The engine can overspeed (run out of control) due to improper
governor assembly or adjustment, which could result in
personal injury, loss of life, and/or property damage.
5. Start the engine. It may be necessary to turn the rated speed potentiometer one or two turns
clockwise before the engine will start.
NOTICE
a. Set engine rated speed by turning this potentiometer clockwise to increase speed setting.
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Dynamic%2520Checks%2520(SENR6430-02)%2522%252C%2522… 1/2
23/04/2023 13:15 SIS 2.0
b. Measure magnetic pickup output voltage at terminals T5 and T6. Voltage should be less than 50
VAC, but greater than 1.5 VAC (measured as RMS voltage). If voltage is greater or less than indicated
VAC, check clearance between magnetic pickup and flywheel ring gear tooth. Make adjustments as
necessary. (See Service Procedure C.)
7. Connect a DC voltmeter to terminals T3 (+) and T4 (-) to get an indication of actuator voltage stability.
PSP-0004AE6C
2023/04/23
10:15:15+03:00
SENR64300005
© 2023 Caterpillar Inc.
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Dynamic%2520Checks%2520(SENR6430-02)%2522%252C%2522… 2/2