Professional Documents
Culture Documents
Normas Instalaciones Electricas
Normas Instalaciones Electricas
Normas Instalaciones Electricas
on Rotating Machines
Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, A. Romashkov
Cutler Hammer Predictive Diagnostics Division
Abstract: This paper presents the authors’ practical experience Why do We Need RTD as PD Detector?
in the on-line measurement of partial discharges in medium The traditional approach for PD detection in rotating machines uses
voltage motor and generator stator windings using the RTD as a sensors installed near machine line terminals. What is the value of
partial discharge detector. Results of off-line calibration on data obtained from such sensors and what additional information is
several machines are also presented. required to reliably assess winding insulation condition? Based on
our experience, PD sensors located near machine line terminals
Introduction provide valuable information for line terminals and, possibly, for a
On-line measurement of partial discharges (PD) has proved to be an ring bus, but not for the winding.
effective tool in evaluating the condition of stator insulation in high
and medium voltage electric motors and generators [l]. This method The example below with data obtained on-line from a 37,00OkVA,
is widely used in addition to the traditional off-line insulation tests 13.8kV generator confirms this statement. The generator has an
performed during scheduled outages. 80pF coupling capacitor installed on each line terminal and also 12
RTDs evenly distributed around the circumference of the stator core.
Most of PD technologies available now on the market for on-line Six RTDs are placed on the exciter and six on the turbine ends of
measurements function within the radio-frequency band of PD the machine. Figure 1 presents three sets of oscillograms taken from
signals. Such technologies have the common problem resulting from 80 pF coupling capacitor (Plot # I ) and from RTD#I (Plot #2) and
very rapid attenuation of the high frequency signal as it travels RTD#7 (Plot #3). All of them are on the same phase A. RTDs are
through the winding. Therefore, sensors commonly installed at also located in the same slot on the exciter and turbine ends
winding terminals have a limited zone of sensitivity and provide respectively. The oscilloscope was triggered from the PD pulse
valuable information for that zone only [4]. The evident solution to originating near the line terminals on phase A and also from the
this problem is the use of PD sensors imbedded into the winding to pulse originating near each of the two RTDs. One can see that the
get information on the winding itself. Some of the PD technology coupling capacitor provides no response to the PD originating in the
vendors suggest installing specially designed sensors into a winding. winding on either side of the generator. The opposite is true as well.
But this approach is relatively expensive and requires an extensive The attenuation of PD signal along the slot is also very high and
machine outage and invasion into the winding assembly. exceeds 10 times. Therefore, it is necessary to install additional
sensors into a winding or to use RTDs to get information about the
Alternatively, most of the HV machines already have RTD detectors winding condition.
embedded into the winding by the manufacturer and these detectors
can be used for partial discharge measurements [2,4]. Cutler- .. .. .. .. .. .. .. ..
Hammer has over two years of experience using RTDs as PD
.. .. .. ..
detectors. The special PD transducer (RFVS) was designed for
connection to the RTD wire at the RTD terminal block located on
the frame of the motor or generator. The transducer does not disturb
temperature measurements and only passes high frequency PD
signals to the PD instrument. Over 300 machines, primarily HV
r v
motors, were tested during the past two years with good results.
RTDs were used for both the initial survey/evaluation and for on-
Triggeringfrom line terminal PD.
going periodic measurements and data trending.
205
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.
Why do We Need Calibration? applies primarily for partial discharges originating close to a sensor.
The real need to calibrate or normalize a PD measuring circuit on a Signal attenuation is not taken into consideration in this factor. On
rotating machine exists today. As the science of Partial Discharge the other hand, attenuation is a very important factor for PD signals
measurement was making its first steps, it was agreed that distant to a sensor. Therefore, if sensitivity defined as it is described
calibration on rotating machine is a very difficult procedure. above is used, data obtained on-line from a sensor in terms of nano-
Therefore, it was decided to utilize the Partial Discharge Magnitude Coulombs presents the lower limit estimation of an apparent charge
parameter measured in millivolts or Volts [I]. Based on that, the for discharges originating close to a sensor. In other words, a
only valid procedure of using PD data is through relative ,discharge value can be greater for PD near the sensor, but it can not
comparison of PD data collected using the same vendor’s be less. In spite of the approximate character of this approach, it is
technology over time on the same machine or between similar still more accurate than millivolts alone. It creates the opportunity to
machines. This situation was bearable while the number of PD compare data taken from different sensors, taken from different
technology users was relatively small and most of sensors’ machines and even for machines of different rated voltages. All of
installation, data collection and interpretation were provided by a the above is true, to the same extent of approximation, for all
qualified expert. quantities which can be derived from “raw” PD data. These
quantities could be PD power or PD current and so on.
Now the situation is different. As PD technology is maturing, real-
life cases reveal the need for a standardized PD measuring circuit The question left without an answer is the applicability of such
calibration procedure. For instance, paper [3] reported a 19,000HP approximation or, in other words where is the limit, beyond which a
motor failure just because the 80pF couplers were installed about comparison looses any practical sense? The answer to this question
4m away from the motor line terminals. That caused signal is in the term described below and called the “Zone of Sensor
attenuation by a factor of 5 and resulted in misinterpretation of the Sensitivity”.
PD data. As a result the authors of [3] have now normalized all their
PD sensors with pulse generator and oscilloscope and are now using Zone of Sensor Sensitivity - this term is more qualitative than
normalized data for relative comparison between monitored motors. quantitative. It limits the boundaries of a spatial zone that can be
assessed using a particular sensor. We use 20dB attenuation of a
The necessity of calibration is also important when different sensors signal as the criterion to determine the border of the Zone of Sensor
are used for partial discharge measurements on the same machine. Sensitivily. One can not evaluate PD data reliably beyond that zone
These sensors are of different design and must be normalized to the of a particular sensor. From the example given above, we can
same scale. Furthermore, RTDs were not especially designed for evaluate the line terminal insulation condition based on the 80 pF
high frequency application. Therefore, one can find a quite different capacitor readings, but we can not seriously discuss the winding
response of a RTD to the same discharge on machines of different condition due to the inability of the line terminal PD sensors to
designs. Another issue that further promotes the need for sensor detect winding related PD signals. Any conclusions beyond the
normalization, or calibration, is the increasing flow of practical data Zone of Sensor Sensitivity would be just a guess based on previous
collected by different vendors. For instance, the author of [ 5 ] experience on similar machines with similar operating conditions,
reported the analysis of over 13,000 test samples. This data is not but not on the real data. The knowledge obtained based on the Zone
very useful for other users since normalization to conventional of Sensor Sensitivity, for various PD sensor technologies, allows for
measurement units was not done. The above clearly indicates the better planning concerning the number and location of sensors for a
need to establish a field calibration procedure to allow for the future particular application and provides a check on the reliability of the
advancement of the benefits of the varying PD technologies information obtained. The Zone of Sensor Sensitiviw can be
available today. determined during off-line calibration.
206
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.
pulse magnitude and dosing capacitance. A small RFCT is
additionally inserted into the charge injecting circuit and measures
injected current. This is an additional method to obtain an injected
charge. An injected charge is calculated as the area under the
oscillogram of the injected current. The first peak of the oscillogram
is used for injected charge calculation. In all cases, we have had
within 20% agreement between injected charges measured in both
ways. This proves that either of the two methods can be used.
SwdInteriace
Pulse Generator
I Some Calibration Results
The results of calibration on small generator and two HV motors are
presented below.
207
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.
The effect of signal attenuation from the RTD to the RTD terminals
0.12 is most significant for RTD wires protected by a spiral steel shield.
0.1
Sensitivity for such RTDs is commonly in the range from 0.015 to
0.02 Volt per nano-Coulomb.
0.08
0.08 The above results of RTD calibration confirm that RTDs can be
0.04
psed as PD detectors in PD technologies based on high frequency
pulse recording.
0.m
25 -
Coupling CapacitorResponseto Injected Charge
1 a very valuable tool in PD technology.
directions. This motor has a large diameter and relatively short core
of about 1.5 m. In spite of the short core and approximately centrally
located RTD, they show 6 - 7 times better response to pulses
injected from the side of the RTD wires. Significant influence of
RTD wires placed in a slot can be assumed. A wire works as a RF
antenna as well and therefore the effective length of antenna is &
greater for a pulse injected from a RTD wire side of the core. The mv
motor also showed moderate scatter in RTD sensitivity for different Figure 6. Phase B PD data.
RTDs. It varies from 0.2 to 0.28 Volt per nano-Coulomb, which is
about +_I5 - 20%. RTDs located closer to the RTD terminals at the
motor showed higher sensitivity. Higher signal attenuation as a
result of longer wires is the most probable reason for the observed
scatter.
208
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.
Figure 9. Maximum Apparent Charge.
Conclusions
1. Attenuation of high frequency signals in rotating machine
winding is the main factor complicating PD measurements on
such equipment. Sensors commonly placed near machine line
Figure 7. Charts show PD Intensity, Maximum Apparent
terminals are insensitive, as a rule, to distant PD originated in
Charge and Pulse Repetition Rate Respectively. machine winding. Additional sensors placed in winding are
(All Calculated from PD data above 0.1 nC.) required to reliably detect partial discharges. Resistive
Temperature Detectors (RTDs) already placed in a winding by
On-line Test the machine manufacturer can be used as high frequency
This on-line test was performed on a 7500 HP 13.8 kV motor. The antennas to collect partial discharge pulses from the depth of
motor is equipped with three permanent radio-frequency current the winding. The use of RTDs allows PD data to be obtained
transformers (RFCT) placed on the surge capacitor grounding without an outage to install invasive sensors into winding slots.
conductor in the motor terminal box and with 6 RTDs embedded
into the winding. RTD 1 & 4, RTD 2 & 5 and RTD 3 & 6 are 2. RTDs commonly have good sensitivity to PD originating
installed on the phases A, B and C respectively. RFVS sensors were nearby. Therefore, if used complimentary to conventional PD
used to utilize temporal connection to RTD terminals in the RTD detectors, these provide better information on partial discharges
connection box on the motor frame. in the entire stator winding and yield a more reliable winding
insulation assessment.
The flat projection of PRPDD from all available sensors is presented
on Figure 8, and maximum apparent charge is on Figure 9. It is very 3. RTDs were not designed for high frequency application.
important to mention that data presented for each sensor is unique Therefore, one can find different response to the same
for a particular sensor. Any possible crosscoupling from sensor to discharge on machines of different designs. Calibration is
sensor was rejected by the “Twins” analyzer. As one can see, both required to scale PD data taken from different machines to the
magnitudes from RFCT and RTDs are in approximately the same same base.
magnitude range and C-phase showed higher PD activity at line
terminals as well as inside the winding. 4. The calibration procedure was designed with the aim to scale
sensors of different design to the same base. Two terms
-
ma- CC-A ma- cc-B ,-cc-c “Sensitivity to PD at Sensor location” and “Zone of Sensor
w D.. D..
I Sensitivity” is suggested to perform sensor calibration in terms
of apparent charge.
’!
5. Over two years of practical experience confirms that RTDs can
be used as a very valuable tool for on-line and off-line PD
measurements on a rotating machine (with an adequate PD
analyzer that can process data and efficiently reject all types of
noise). The key advantage is that the use of PD predictive
technologies can be easily implemented with existing RTDs.
References
209
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.
3. Osman M. Nassar, Thani S. AI-Anizi. “Saudi Aramoco
experience with partial discharge on-line motor monitoring
equipment”, IRIS Rotating Machine Technical Conference,
March 10-13, 1998, Dallas, TX USA.
210
Authorized licensed use limited to: Chalmers University of Technology. Downloaded on November 19, 2008 at 06:36 from IEEE Xplore. Restrictions apply.