Closing Graph - Annexture A PDF
Closing Graph - Annexture A PDF
SETTINGS :
Trigger Option Close Sampling Speed (kC) 5
Plot Length(ms) 400 Delay tco (ms) 100 Delay toc (ms) 150
Current Range C1(A) 25 Current Range C2(A) 25 Current Range C3(A) 10
Current Range C4(A) 10 Current Range C5(A) 10 Current Range C6(A) 10
Velocity Enabled PIR Disabled Auxiliary Enabled
Analog Channels Enabled Linkage Ratio 1
GRAPH :
This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 01/02/2023 Page 1 of 2
HISAC Ultima - Test Report
Timing Results :
Close
R Y B
Contact Time (ms) 60.4 59 58.6
Pole Mismatch (ms) 1.8
Break Mismatch (ms) NA NA NA
Travel Results :
This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 01/02/2023 Page 2 of 2