Fault diagnosis and maintenance of air circuit breaker


From: Quisure2020-10-27
There are many air circuit breakers in the distribution equipment of high-rise buildings,
which are generally used as low-voltage main switch or branch circuit switch with large
capacity, which plays a very important role in the power supply system. Once the fault
occurs, it will cause large-area power failure and economic loss. The following through
the maintenance work of some examples to illustrate the air circuit breaker operation
fault analysis and treatment methods.
Nader Air circuit breakers(ACBs)

Air circuit breaker tripped and reclosing failed


1. Firstly, determine whether the air circuit breaker is non accident trip
Non accident trip refers to tripping without short circuit and overload fault. There are
many reasons why the air circuit breaker can not be closed. First of all, it is necessary to
determine whether the trip is caused by the short circuit and overload of the circuit, or
due to the fault of itself or the control circuit. The following are the steps and methods to
find and determine whether it is a line fault or an air circuit breaker fault.
After it is determined that it is the fault of air circuit breaker, check it after pulling out
(drawer type air circuit breaker).

2. Air Circuit Breaker Common Troubleshooting


(1) Air circuit breaker cannot be closed due to the black out to the undervoltage
release
Too low voltage or power failure of the undervoltage release coil will also trip the air
circuit breaker and cannot reclose. The following four situations will cause the
undervoltage release coil to lose power:
The fuse of protection circuit, such as RT14, is fused, causing circuit blockage and
power failure of trip coil of undervoltage tripper.
Poor contacts such as closing buttons, relay contacts, auxiliary contacts of circuit
breakers, etc., and damaged components may lead to circuit blockage and power
failure of trip coils.
Broken wires and loose crimping screws in the circuit will also cause the circuit to be
blocked and the trip coil to be disconnected.
Because the coil of under-voltage tripper is in power-up state for a long time,
environmental pollution, inflexible engagement of armature or excessive air gap
between iron core and armature are easy to cause excessive current, which will cause
the tripping coil to heat and burn out and lose the function of tripping coil.
The above faults can be correctly judged through observation and simple inspection and
testing. Therefore, once the fault is found, it should be eliminated in time. If the contact
is loose, it must be tightened, the component is damaged or the coil is burned, it needs
to be replaced.

(2) Failure of mechanical system causes air circuit breaker not to close
After tripping and closing several times, the operating mechanism of air circuit breaker
is severely worn and the following faults may occur:
If the motor drive mechanism is worn out, such as the worm wheel and worm of the ME
switch are damaged, the operating mechanism of the air circuit breaker cannot be
driven to buckle and close. The replacement of worm gears and worms is complicated
and requires professional maintenance.
The wear of free tripping mechanism makes it difficult to close the air circuit breaker and
easy to trip. Sometimes it just barely closes. In case of vibration, it trips itself.
Sometimes once closed, it trips again.
At this time, the adjusting screw should be rotated to adjust the relative position of the
tripping half shaft and the tripping so that the contact area is about 2.5mm^2. Replace
the corresponding parts if necessary.
Failure of energy storage spring in operating mechanism.When closing, the four-link
mechanism of the air circuit breaker can not push to the dead point and the mechanism
can not self-maintain in the closing position. Therefore, the air circuit breaker can not
close properly, so the energy storage spring must be replaced.
Operating mechanism is inflexible and stuck.Because this type of circuit breaker is not
fully enclosed, inadvertently dropping screws, nuts and other foreign bodies in the
operating mechanism will cause stuck operation of air circuit breaker, which will affect
closing. In addition, lack of lubricating grease in the rotating and sliding parts will cause
slight deformation of the open energy storage spring of the operating mechanism and
the air circuit breaker will not close. Therefore, in addition to checking for foreign bodies
in the operating mechanism, lubricating grease should be injected into the rotating and
sliding parts when the above faults occur.
Structure of air circuit breaker

Press trip button, air circuit breaker refuses to break


The failure of the air circuit breaker to break normally may be due to the following
failures.
1. Button failure
Mechanical failure of the button or poor contact of the conductor will cause the trip
circuit to be blocked, which will lead to the deactivation of the shunt trip coil, the
armature can not be pull in and the air circuit breaker can not be broken.

2. Shunt trip failure


The tripping of air circuit breaker is affected by open or short circuit of shunt trip coil and
blockage of armature engagement. Therefore, regularly check the shunt trip, remove
the obstacles affecting the armature attraction, and replace the coils with open or short
circuit in time to ensure that the air circuit breaker can be quickly disconnected when the
circuit needs to be disconnected.

3. Failure of trip-free mechanism


The contact surface between the tripping half-shaft and the tripping of the trip-free
mechanism is too large (usually 2-3mm^2), which will make the circuit breaker refuse to
breaking. Therefore, by using the adjusting screw, the tripping half-shaft can rotate at an
angle to meet the requirements of the contact surface of 2-3mm^2, and the contact
surface is coated with low temperature extreme grease to reduce friction and facilitate
tripping.
Other faults
1. Noise of Undervoltage Tripper
Undervoltage tripper often produces abnormal noise after working for a period of time.
Oil and dust on working surface of iron core should be removed regularly. If short circuit
ring breaks, it needs to be replaced.

2. Burning out of mini-motors


Failure of the limit switch can cause the mini-motor in the electric operating mechanism
to burn out. If it is necessary to close the circuit breaker with the electric operation
mechanism, press the closing button, the power supply circuit of the motor will be
connected, and the motor rotates. After completing the energy storage or closing of the
mechanism, the power supply circuit of the micro motor should be disconnected by the
limit switch. However, it cannot be disconnected due to the failure of the limit switch,
which will cause the motor to overheat and burn out for a long time.

3. Short circuit due to poor insulation


The insulation performance of air circuit breaker will gradually deteriorate after long-
term use. If improper maintenance is carried out in ordinary times, dust accumulation on
the surface of insulating parts and moisture erosion will accelerate insulation aging,
which may cause short circuit between phases or relative ground during power
distribution operation or when short-circuit current is cut off.Therefore, it is necessary to
keep the insulation surface clean and prevent the insulation performance from
deteriorating so as to prolong the service life of the circuit breaker.

Measures required for air circuit breaker after breaking short-circuit current
After each short-circuit current cut-off, the air circuit breaker shall be checked as
follows:
1. Contact system
(1) Smoke marks on the main and arc contacts are wiped off with alcohol.
(2) If small metal particles form on the contact surface, they should be cleaned and
smoothed.
(3) If the thickness of silver alloy contact layer on the main contacts (dynamic and static
contacts) is less than 1mm due to electric wear, it must be replaced, and the dynamic
and static contacts should be replaced at the same time.
(4) Check the contact pressure spring, if it fails due to overheating, replace it in time.
(5) Check whether the flexible connection is broken or not. A few of the broken zones
should be removed. If most of the zones are broken, the flexible connection should be
replaced.

2. Arc Extinguishing System


(1) Clean the metal particles and soot on the wall and grids of the arc extinguishing
chamber. If the grids are welded or burnt seriously, they should be replaced.
(2) If the arc extinguishing chamber is damaged, it is not allowed to be used again and
must be replaced.
(3) The newly exchanged arc extinguishing chamber should be dried before use to
ensure good insulation.
3. Operating mechanism and trip-free mechanism
(1) Lubricating oil can be properly filled first.
(2) Operate closing several times with electric operating mechanism and manual handle
respectively. The operating mechanism should be flexible and the air circuit breaker
should be closed reliably. When the switch-off button is pressed, the air circuit breaker
should trip and break instantaneously.
Prev: What is a Buzzer?

Next: What is the difference between MCCB and ACB?


Find more products in China
Importing from China, One-stop purchase replace a step by step learn guide.
Your Email:
Sub:

Remaining:500
Need technical support?
Submit RFQ

Related articles

What Is a Circuit Breaker


Circuit breaker refers to a switching device that can close, carry and break current under
normal circuit conditions and can close, carry and break...


What is a Residual Current Circuit Breaker?
Residual current circuit breaker(RCCB) is a switch that can act automatically when the
leakage current in the circuit exceeds a predetermined value...

What is a Buzzer?
Buzzer is a kind of voice device that converts audio model into sound signal. It is mainly
used to prompt or alarm. According to different design...

What is the difference between MCCB and ACB?


Moulded case circuit breaker and air circuit breaker are very common products, but many
people do not understand the difference between them...

What is an air circuit breaker?


Air circuit breaker(ACB) is a mechanical switching device which can turn on, carry and break
current under normal circuit conditions, and also turn...


What is a molded case circuit breaker?
Molded case circuit breakers(MCCBs) automatically cut off current when the current exceeds
the trip setting. Plastic housing refers to the housing...

What is the working principle of the buzzer?


The buzzer is a sounding device that can convert audio signals into sound signals. It is
usually powered by DC voltage. It is mainly divided into...

What is the difference between MCB and RCCB?


What are the similarities and differences between miniature circuit breaker(MCB) and
residual current circuit breaker(RCCB)?

Popular Articles
More


How does an emergency stop button work?
Emergency stop button switch is a fail-safe control switch that provides safety for the
machinery and for the person using the machinery.
2020-08-09

What is the working principle of the buzzer?


The buzzer is a sounding device that can convert audio signals into sound signals. It is
usually powered by DC voltage. It is mainly divided into...
2020-10-12

What is the principle of the push button switches?


We encounter various push button switches almost every day, such as medical equipment,
automated production lines, and communication equipment.
2020-08-18


What are the common faults of relays?
During the use of the relay, due to various reasons, such as poor product quality, improper
use, poor maintenance, etc., various failures often occur.
2020-09-01

What is the principle and function of the relay?


A relay is an electronic control device, which has a control system and a controlled system ,
and is usually used in automatic control circuits.
2020-08-22

What is a Buzzer?
Buzzer is a kind of voice device that converts audio model into sound signal. It is mainly
used to prompt or alarm. According to different design...
2020-10-28

Popular products
More

Miniature Circuit Breakers


Miniature circuit breakers(MCBs) - 1pole, 2poles, 3poles, 4p...

DC Miniature Circuit Breakers


DC Miniature circuit breakers(MCBs) - 1pole, 2poles, 3poles,...

Molded Case Circuit Breaker


Molded Case Circuit Breakesr(MCCBs) - 2poles, 3poles, 4poles...

Air Circuit Breaker


Air Circuit Breakers(ACBs) - 3poles and 4poles; Rated curren...

Emergency Stop Switch


Emergency Stop Switches(E-Stops), also known emergency stop ...


Key Lock Switch
Key Lock Switches or Keylock Switches are electrical switch ...

Quisure.com
User Center

 Log in

 Sign up
Services

 Sourcing in China

 Free samples

 P/N library

 Blog

 Solutions
About us

 Our Mission

 Our Vision

 Our Business

You might also like