Factory Test Report

Project Name: Power Grid Network Strengthening Project under PGCB (PGCB/GtoG/01)

Buyer: Jiangsu Etern Co.,Ltd

Production Name: LV AC Distribution Panel

Type and specification:GGD

Standard:IEC61439

Testing Date:

Place of test: Zhejiang, China

Zhejiang Mahalale Power Equipment Co., Ltd

page 1 of 3
LV AC Distribution Panel test report
Product NO.

SL Check item Check Standard Check Record Checkresult


1) Panel size and Position of components should be manufactured and
installed in accordance with the drawings and technical specifications;
2) All of the welding parts should be intalled symmetry. The parts should
without any abvious deformation; Meet the
1 Structure
3) All the assembly parts should be connected reliably as per design. requirement
4) The Doors can be easily opened to rotate over 90°without visible fricion and
elasticity.

1)The paint of surface should be in accordance with the drawings and


technical specifications;
2)As per the requirement of standard, The coating should be evenly, no
Appearance is
Painting phenomenons flowing , foaming, The painting should be without any abvious
2 consistent with
chromatism,lossing;
the standards
3)There should not be inferior by watching from 1m away panel under
sunshines.

Conform to the
drawings and
3 Plating component no bare part, scars and mildew.
technical
requirements
The modelof components should be in accordance with the drawings and According to
Components installation
4 technical specifications; the drawings to
install
All the nameplates, symbols must be correct & clear. Meet the
5 Mark
requirement
1)Material and section of Bus should be in accordance with the drawing and
workmanship.
2)The Bus should be insulated.
3) The color of Bus bar is below:
Meet the
6 Bus bar Rphase red
requirement
Yphase yellow
Bphase blue
Earthing:Green/Yellow

Connection of wires should be in accordance with the drawing and Comply with
7 Wires connection workmanship. the design
requirements
Earting point are well connected to the earth. Grounding
Earthing point
8 device is safe
and effective
Meet the
9 clearance two live part under 300~660V ≥8mm
requirement
All components operated reliable under rated voltage.
Safe and
10 Power-on test
trouble-free
Conductive part underIndustrial frequency electrical power(2500V , 50Hz ± Product no
High-voltage tolerance 5Hz), last for 1min, no breakdown or flashover. breakdown or
11
test for 1 min flashover
phenomenon

page 2 of 3
LV AC Distribution Panel test report
Product NO.

SL Check item Check Standard Check Record Checkresult


Resistance between earthing bar and earth are not less than 20MΩ
12 Insulation Resistance

13 AC input 415V±10%,50Hz 415V±10%


Output power is stable. Meet the
14 Feeder output
requirement
Automatic AC and DC voltage insulation tester CC2670A
Grounding resistance tester CC2521
Meg-ohmmeter ZC25-4
15 Test Instrument
Multimeter UT33B+
Vernier caliper
Tape

Operator: QC Inspector: Witness

Production past test and allow to leave factory :

Date: Result:

page 3 of 3