Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

 

 
 
 
 

WDZ-5211 Line Management Relay

Technical instruction

V1.02

Wiscom System Co., Ltd.


Preface

Thank you very much for purchasing WDZ-5211 manufactured by Wiscom(Stock code:
002090).

This technical instruction is for order only and has slight difference with the actual product.
Thus if needed, please ask our design engineers for relative design drawings for engineering.

For more product information, instruction manual updates and services, please visit the
Wiscom website http://www.wiscom.com.cn/.

_____________________________________________________________
Copyright © Wiscom System Co., Ltd, All rights reserved
Version: V 1.00
This instruction is for reference only.
目录 
WDZ‐5211 Line Management Relay .................................................................................................. 5 
1  General functions ...................................................................................................................... 5 
2  Protective functions and principles ........................................................................................... 5 
2.1  1st zone overcurrent ...................................................................................................... 5 
2.1.1  Logic diagram .................................................................................................... 5 
2.1.2  Action criterion.................................................................................................. 6 
nd
2.2  2  zone overcurrent ..................................................................................................... 6 
2.2.1  Logic diagram .................................................................................................... 6 
2.2.2  Action criterion.................................................................................................. 6 
rd
2.3  3  zone overcurrent ...................................................................................................... 7 
2.3.1  Logic diagram .................................................................................................... 7 
2.3.2  Action criterion.................................................................................................. 7 
2.4  After accelerated protection ......................................................................................... 7 
2.4.1  Logic diagram .................................................................................................... 7 
2.4.2  Action criterion.................................................................................................. 7 
2.5  Overload ........................................................................................................................ 7 
2.5.1  Logic diagram .................................................................................................... 8 
2.5.2  Definite time...................................................................................................... 8 
2.5.3  Inverse time ....................................................................................................... 8 
2.5.4  Very inverse time............................................................................................... 8 
2.5.5  Extremely inverse time ...................................................................................... 8 
st
2.6  1  zone ground fault protection.................................................................................... 8 
2.6.1  Logic diagram .................................................................................................... 9 
2.6.2  Action criterion.................................................................................................. 9 
nd
2.7  2  zone ground fault protection ................................................................................. 10 
2.7.1  Logic diagram .................................................................................................. 10 
2.7.2  Action criterion................................................................................................ 10 
2.8  Protection setpoint ..................................................................................................... 11 
2.9  Soft strap ..................................................................................................................... 11 
3  Measurement and control function ........................................................................................ 12 
3.1  Measurement function ............................................................................................... 12 
3.2  DIs................................................................................................................................ 12 
3.3  DOs .............................................................................................................................. 12 
3.4  Remote control............................................................................................................ 12 
3.5  Metering ...................................................................................................................... 12 
3.6  Operating circuit.......................................................................................................... 12 
3.7  DCS output .................................................................................................................. 12 
4  Backboard terminals and connection diagram ....................................................................... 12 
4.1  Analog inputs .............................................................................................................. 12 
4.2  Backboard terminals ................................................................................................... 12 
4.2.1  Basic configuration with Operation board ...................................................... 13 
4.2.2  Basic configuration without operation board ................................................. 16 
4.3  Terminal connection diagram...................................................................................... 18 
4.3.1  Analog input connection diagram ................................................................... 18 
4.3.2  DI、Central signal、network、AO and energy pulse output circuit connection 
diagram 19 
4.3.3  Operation board Operating‐circuit diagram .................................................... 20 
4.3.4  DO circuit connection diagram without operation board ............................... 21 
5  Order information ................................................................................................................... 21 
6  Settings explanation ................................................................................................................ 22 
6.1  General ........................................................................................................................ 22 
6.2  1st zone overcurrent protection .................................................................................. 22 
6.2.1  Action current Igl1 ............................................................................................ 22 
6.2.2  Action time tgl1................................................................................................. 23 
nd
6.3  2  zone overcurrent protection.................................................................................. 23 
6.3.1  Action current Igl2 ............................................................................................ 23 
6.3.2  Action time tgl2................................................................................................. 23 
rd
6.4  3  zone overcurrent protection .................................................................................. 23 
6.5  After‐accelerated protection ....................................................................................... 24 
6.5.1  Action current Ihjs............................................................................................. 24 
6.5.2  Action time thjs ................................................................................................. 24 
6.6  Overload protection .................................................................................................... 24 
6.6.1  Action current Igfh ............................................................................................ 24 
6.6.2  Action time tgfh ................................................................................................ 24 
6.7  Ground fault protection .............................................................................................. 24 
6.7.1  Neutral point non‐ground fault system ........................................................... 24 
6.7.2  Neutral point grounding system via resistance ............................................... 25 
WDZ-5211 Line Management Relay(V1.02)

  WDZ‐5211 Line Management Relay   

1 General functions 

WDZ‐5211  line  management  relay  is  mainly  applied  to  10KV  and  bellow  feeder  for 
protection, measurement and control function. 
WDZ‐5200  series  line  management  relay  also  includes  WDZ‐5215  Short  line  management 
relay. Compared with WDZ‐5211, their differences are showed as follows:   
  WDZ‐5211  WDZ‐5215 
Instantaneous differential protection    √ 
Ratio differential protection      √ 
st
1  zone overcurrent protection with LV 
√  √ 
block function 
2nd zone overcurrent protection with LV 
√  √ 
block function 
3‐zone overcurrent protection  √  √ 
After accelerated protection    √  √ 
Overload protection  √  √ 
st
Ground fault protection (1  zone)  √  √ 
nd
Ground fault protection (2  zone)  √  √ 
Measurement function  √  √ 
Control function  √  √ 
Hardware electrical energy metering    √  √ 
Operation circuit function    √  √ 
2 4~20mA outputs    √  √ 

2 Protective functions and principles   

2.1 1st zone overcurrent   
This protective function can be set with low voltage blocking function. When any voltage of 
the 3 line voltages is smaller than the LV blocking value, enable the blocking function.   

2.1.1 Logic diagram   

 
5
WDZ-5211 Line Management Relay(V1.02)

2.1.2 Action criterion 

 I max  I gl1

t  t gl1  

U min  U dybs
Where,Imax: The max. current of phaseA、B、C current(Ia,Ib,Ic)(A) 
Ia:Phase A current(A) 
Ib:Phase B current(A) 
Ic:Phase C current(A) 
Umin: The min. voltage of phase AB、BC、CA line voltage(Uab、Ubc、Uca)(V) 
Uab:Phase AB line voltage(V) 
Ubc:Phase BC line voltage(V) 
Uca:Phase CA line voltage(V) 
Igl1:Action current(A) 
tgl1:Time delay(s) 
Udybs:LV block value(V) 

2.2 2nd zone overcurrent   
This protective function can be set with low voltage blocking function. When any voltage of 
the 3 line voltages is smaller than the LV blocking value, enable the blocking function.   

2.2.1 Logic diagram 

 
2.2.2 Action criterion 

 I max  I gl 2

t  t gl 2  

U min  U dybs
Where,Igl2:Action current(A) 
tgl2:Time delay(s) 

6
WDZ-5211 Line Management Relay(V1.02)

2.3 3rd zone overcurrent   
2.3.1 Logic diagram 

 
2.3.2 Action criterion 

 I max  I gl 3
  
t  t gl 3
Where,Igl3:Action current(A) 
tgl3:Time delay(s) 

2.4 After accelerated protection   
This  kind  of  protection,  supporting  level  signals  and  pulse  signals  can  be  enabled  for  5s  to 
prevent closing at fault line when auto‐transfer operation is implemented. 

2.4.1 Logic diagram 

 
2.4.2 Action criterion 

 I max  I hjs

t  thjs  

 AAPon
Where, Ihjs: Action current(A) 
thjs:Time delay(s) 

2.5 Overload   
Overload  protection  has  4  kinds  of  time  characteristics:  definite  time,  inverse  time,  very 
inverse time and extreme inverse time. The inverse time curve accords with IEC 60255‐3.   

7
WDZ-5211 Line Management Relay(V1.02)

2.5.1 Logic diagram 

 
2.5.2 Definite time   

 I max  I gfh
  
t  t gfh
Where,Igfh:Action current(A) 
tgfh:time delay(s) 

2.5.3 Inverse time   

 I max  I gfh

t  0.14
 0.02
 t gfh  

  I max   1
 I 
  gfh 

2.5.4 Very inverse time 

 I max  I gfh

 13.5
t   t gfh  
 I max
1
 I gfh

2.5.5 Extremely inverse time   

 I max  I gfh

t  80
 2
 t gfh  

  max   1
I 
 I 
  gfh 

2.6 1st zone ground fault protection 
Zero sequence current is obtained from special zero sequence TA. The external zero sequence 
current range is 10mA~6A. 
If no special zero sequence TA is supplied, the zero sequence current can also be produced 

8
WDZ-5211 Line Management Relay(V1.02)

   
by device software, namely,  3 I 0  I a  I b  I c . In order to avoid mis‐operation of the ground 
fault  protection  due  to  unbalanced  current  caused  by  inconsistent  3‐phase  TA  characteristics, 
the device adopts Imax ( the maximum phase current) as the restraint variable.   

 
Ground fault protection with restraint current   

2.6.1 Logic diagram 

For external zero sequence current:   

 
For internal zero sequence current with current restraint logic:   

2.6.2 Action criterion 

Zero sequence overcurrent:   

 I 0  I 01dz
  
t0  t01dz
Phase current restraint:   

9
WDZ-5211 Line Management Relay(V1.02)

 I 0  I 01dz I max  1.05 I e



 I 0  1  I max I e  1.05 4I 01dz I max  1.05 I e  
t  t
 0 01dz
Where,I01dz: action current(A) 
t01dz:action time(s) 
Ie:rated line secondary current(A) 

2.7 2nd zone ground fault protection 
2.7.1 Logic diagram 

For external zero sequence current: 

 
For internal zero sequence current with current restraint logic: 

2.7.2 Action criterion 

Zero sequence overcurrent:   

 I 0  I 02 dz
  
t0  t02 dz
Phase current restraint: 

 I 0  I 02 dz I max  1.05 I e

 I 0  1  I max I e  1.05 4I 02 dz I max  1.05 I e  
t  t
 0 02 dz
Where,I02dz:action current(A) 
t02dz:action time(s) 
Ie:rated line secondary current(A) 
 

10
WDZ-5211 Line Management Relay(V1.02)

2.8 Protection setpoint   
No.  Name    Symbol  Unit Range 
1  Rated current  Ie  A  0.20In‐1.20In 
2  LV block value    Udybs  V  10.00‐90.00 
3  Overcurrent 1 current  Igl1  A  0.20In‐20.00In 
4  Overcurrent 1 time    tgl1  s  0.00‐10.00 
5  overcurrent1 with LV lock      On/Off 
6  Overcurrent 2 current            Igl2  A  0.20In‐20.00In 
7  Overcurrent 2 time    tgl2  s  0.10‐100.00 
8  overcurrent2 with LV lock      On/Off 
9  Overcurrent 3 current  Igl3  A  0.20In‐20.00In 
10  Overcurrent 3 time    tgl3  s  0.10‐100.00 
11  After‐accelerated current    Ihjs  A  0.20In‐20.00In 
12  After‐accelerated time    thjs  s  0.00‐4.90 
13  Overload current    Igfh  A  0.20In‐20.00In 
14  Overload time  tgfh  s  0.10‐650.00 
Definite  time/Inverse 
15  Overload curve        time/Very  inverse  time 
/Extreme inverse time 
16  Overload output mode      Alarm/Trip 
17  Zero sequence 1 current    I01dz  A  0.010‐6.000 
18  Zero sequence 1 time    t01dz  s  0.00‐10.00 
19  Ground fault 1 output mode      Alarm/Trip 
20  Zero sequence 2 current    I02dz  A  0.010‐6.000 
21  Zero sequence 2 time    t02dz  s  0.10‐100.00 
22  Ground fault 2 output mode        Alarm/Trip 

2.9 Soft strap   
During  the  soft  strap  on/off  process,  virtual  telesignal  status‐change  information  about  soft 
strap will be made.   
No.  Name    Symbol  Range 
1  Overcurrent1    On/Off 
2  Overcurrent2    On/Off 
3  Overcurrent3    On/Off 
4  After‐accelerated      On/Off 
5  Overload      On/Off 
6  Ground fault 1    On/Off 
7  Ground fault 2    On/Off 
 

11
WDZ-5211 Line Management Relay(V1.02)

3 Measurement and control function 

3.1 Measurement function 
3‐phase voltage, 3‐phase current, active power, reactive power, power factor and frequency 

3.2 DIs 
Standard 24 channel digital inputs.   

3.3 DOs 
Standard 5 channel relay outputs with 7 DO contacts. 

3.4 Remote control   
Remote CB trip/close operation 

3.5 Metering   
Positive active power, positive reactive power, negative active power, negative reactive power 
metering function and positive active/reactive power pulse output function. 
Accumulated active energy and reactive energy can be calculated. 

3.6 Operating circuit   
Operating  circuit  covers  tripping  coil,  closing  coil,  tripping  position  supervision,  closing 
position supervision、tripping position signal output、closing position signal output、control circuit 
fuse‐loss output、relay tripping output、remote tripping output、remote closing output、manual 
tripping input、manual closing input、DCS tripping input、relay tripping input 、2 channels of 
position intertripping or relay intertripping output etc.   

3.7 DCS output   
1 channels of 4~20mA output is supplied and 2 4~20mA outputs are optional.   
 

4 Backboard terminals and connection diagram 

4.1 Analog inputs 
Ua、Ub、Uc: bus line voltage (rated: 100A), used by protection and measurement functions. 
IA、IB、IC: Measured current (rated: 5A or 1A), imported from special measurement TA. 
Ia、Ib、Ic: 3‐phase protective current (rated: 5A or 1A).   
3I0: ZS current, imported from special ZS TA. Secondary ZS current range:10mA~6A. 

4.2 Backboard terminals   
From the front view, the slots are arranged with number from 1 to 5 from left to right.   
Terminal number has 3 digits. The first digit is the slot number and the last two digits are the 
12
WDZ-5211 Line Management Relay(V1.02)

terminal series number from above to below. Take 301 for example, it means the first terminal in 
slot3.   

4.2.1 Basic configuration with Operation board 

13
WDZ-5211 Line Management Relay(V1.02)

 
Slot1:AI board   
Terminal 101、103 and 105: Line voltage inputs; 
Terminal 107~108: Phase‐A measured current input; 
Terminal 109~110: Phase‐B measured current input;   
Terminal 111~112: Phase‐C measured current input; 
Terminal 113~114: Phase‐A protective current input;   
Terminal 115~116: Phase‐B protective current input; 
Terminal 117~118: Phase‐C protective current input;   
Terminal 119~120: Zero sequence current 3I0 input; 
Slot 2:Blank board 
14
WDZ-5211 Line Management Relay(V1.02)

Slot 3: OPR board 
Terminal 301~303: Position status output. 302~301: trip‐position status output; 303~
301:Close‐position status output;   
Terminal 304~305: Control circuit fuse‐loss output;   
Terminal 306: ‐Closing position supervision relay; 
Terminal 307: ‐Trip position supervision relay; 
Terminal  308:  Relay  tripping  output(BTJ),which  can  be  connected  to  Terminal  318 
directly or via press strap;     
Terminal 309: + remote PWR input. Only when it is connected to positive power source, 
remote tripping/ closing functions can be enabled;   
Terminal 310: Remote closing output(YHJ),which can be connected to Terminal 317 
directly or via press strap; 
Terminal 311: Remote tripping output (YTJ),which can be connected to Terminal 319 
directly or via press strap;   
Terminal 312: +control power source input; 
Terminal 313: ‐control power source input; 
Terminal 314: CB closing coil;   
Terminal 315: CB tripping coil;   
Terminal 317: Manual closing input;   
Terminal 318: Relay tripping input;   
Terminal 319: Manual tripping input;   
Terminal 320: DCS tripping input;   
Terminal 321~322: DO4, Defaulted relay intertripping output, or position intertripping 
via jumper selection;   
Terminal 323~324: DO5, Defaulted relay intertripping output, or position intertripping 
via jumper selection; 
Terminal 325~326: Device fault alarm signal output;   
Terminal 327~328: Relay tripping signal output;   
Terminal 329~330: Relay alarm signal output;   
Terminal  331~332:  Action  alarm  signal  output,  when  relay  acts  or  alarms,  the  signal 
will be issued. 
Slot 4: IN board 
Terminal 401~402: Field bus 1 input,401: positive,402: Negative. CAN or ProfiBus 
interface is ok.   
Terminal 403: signal earth;   

15
WDZ-5211 Line Management Relay(V1.02)

Terminal  404~405:  Fieldbus  2  input,404:  positive,405:  Negative.  CAN  or  ProfiBus 


interface is ok.   
Terminal 406~407: GPS timing input, connected to 485 differential level.   
Terminal 408: signal earth;   
Terminal  410~411:  Active  energy  pulse  output,  24V  dry  idle  contact  output.  410: 
positive, 411: Negative. 
Terminal  412~413:  Reactive  energy  pulse  output,24V  dry  idle  contact  output.  412: 
positive, 413: Negative. 
Terminal  414~416:  2  4~20mA  outputs.  414~416:  the  first  channel  of  4~20mA 
output,414: positive, 416: Negative;415~416: the second channel of 4~20mA output,
415: positive, 416: Negative. 
Grounding screw must be connected to earth mat reliably and tightly. 
Slot 5:PWR board 
Terminal  503~504:  Device  power  source  input,  DC/AC  220V  or  DC/AC110V.  503: 
‐Device power source input,504: + Device power source input;   
Terminal  506~530:  24  channels  of  DC  110V  or  DC220V  strong  current  inputs.  506: 
‐common DI, 507~530: 24 DIs. 509: defaulted after‐accelerated contact. 
Terminal  531~532:  Device  blocking  output,  break  contact.  When  the  device  24V 
power is lost or internal CPU fails, the contact will be closed. 

4.2.2 Basic configuration without operation board 

16
WDZ-5211 Line Management Relay(V1.02)

 
Slot 1:AI board 
The same as explained in operation board configuration. 
Slot 2:Blank board 
Slot 3:OUT board 
Terminal 301~304: Relay intertripping outputs. 301~302: one pair of contact output;
203~204: The other pair of contact output.   
Terminal 305~308: DO2. 305~306: one pair of contact output;207~208: the other 
pair of contact output. 
Terminal 309~310: Relay tripping output;   
Terminal 311~312: Remote closing output;   
17
WDZ-5211 Line Management Relay(V1.02)

Terminal 313~314: Remote tripping output;   
Terminal 325~326: Device fault alarm signal output;   
Terminal 327~328: Relay tripping signal output;   
Terminal 329~330: Relay alarm signal output;   
Terminal  331~332:  Action  alarm  signal  output,  when  relay  acts  or  alarms,  the  signal 
will be issued.   
Slot 4:IN board 
The same as explained in operation board configuration. 
Slot 5:PWR board 
510:  default  remote  position,  511  and  512:  Defaulted  CB  trip‐position,  close‐position 
input. Others are the same as explained in operation board configuration. 

4.3 Terminal connection diagram   
4.3.1 Analog input connection diagram 

1LHa
Protective Current

113 114
1LHb

115 116
1LHc

UA

Bus Line Voltage


117 118
101

Voltage Circuit
LH0
Current Circuit

UB
Zero Sequence

103
Current

119 120

UC
105
2LHa

107 108
2LHb
Measured Current

109 110
2LHc

111 112

18
WDZ-5211 Line Management Relay(V1.02)

4.3.2 DI、Central signal、network、AO and energy pulse output circuit connection diagram 

-KM +KM
Mini Bus
3 1 531
Device Blocking
1Q Air Switch
4 2 532

Central Signal
Device Power
325
Device Fault
L/DC+
504 326
L/DC- 327
503 Relay Tripping
328
DI 1
507
329 Relay Alarm
DI 2
508
330
After-accelerated
509 331 Action Alarm
Note 1 Remote Position
510 332
Trip-position
511
NET1-A
Closing-position 401
512 Fieldbus 1
DI 7 NET1-B
513 402
DI 8 Signal Earth
514
403

Communication
DI 9
515 NET2-A
Telesignal Acquisition

404 Fieldbus 2
DI 10
516
NET2-B
DI 11 405
517
DI 12 GPS+
518 406
DI 13 GPS- GPS
519
407
DI 14
520 Signal Earth
DI 15 408
521
DI 16
522 Note 2

Energy Pulse Output


410 Active Energy Pulse+
DI 17
523
DI 18 Active Energy Pulse-
524 411
DI 19
525 Reactive Energy Pulse+
412
DI 20
526
413 Reactive Energy Pulse-
DI 21
527 Note 3
4~20mA Output

DI 22 4~20mA Output 1
528 414
DI 23
529 4~20mA Output 2
415
DI 24
530
4~20mA Common
Common DI 416
506
Note 1:If operation board is supplied, remote,closing and trip position signals are not connected.
2:Energy pulse outputs:24V idle contact output,reactive contact.
3:R:External resistance should be smaller than 500Ω,250Ω is suggested.

19
WDZ-5211 Line Management Relay(V1.02)

4.3.3 Operation board Operating‐circuit diagram   

301 Trip-position
Output
302
Close-position
303 Output

304 Control Circuit


Fuse-loss Output
305

321
DO 4
322

323
DO 5
324

20
WDZ-5211 Line Management Relay(V1.02)

4.3.4 DO circuit connection diagram without operation board 

301

302 Relay
303 Intertripping

304

Trip & Close Output


305

306 Do 2
307

308

309 Relay
Tripping
310

311 Remote
Closing
312

313 Remote
Tripping
314
 

5 Order information   

WDZ-5211

Network configuration
1:CAN Network
2:ProfiBus Network

Energy board configuration


0:No energy
1:Have energy
Operating circuit
0:None
1:with anti-trip function
2:without anti-trip function

DC power source
1:DC110V
2:DC 220V
Rated secondary current
1:In 1A
5:In 5A  
(1) Optional CAN or ProfiBus communication interface, which are redundant configuration. 
If RS485 interface is needed, please make order especially;   
(2) Optional hardware energy board is supported;   

21
WDZ-5211 Line Management Relay(V1.02)

(3) Operating‐circuit  is  optional  and  the  anti‐trip  function  can  be  enabled/disabled 
manually.  Defaulted  intertripping  relay  is  protection  intertripping  and  the  defaulted 
operating‐circuit tripping/closing current is self‐adapted 0.3~4A,if 0.05~0.3A or 4~10A is 
needed, please note especially;   
(4) Operating‐circuit power source and DI power source can be DC110V or DC220V; while 
the device power source has no such kind of discrimination;   
(5) Rated secondary current, as the protective and measured current, can be 1A or 5A;   
(6) The device is equipped with 1 channel of 4~20mA output, if no such output is needed 
or 2 channels 4~20mA are needed, please order it specially;   
(7) ZS TA working range: 10mA~6A. If the zero sequence current is out of the range, just 
make a special note. 
(8) Secondary rated voltage is 100V、50Hz,line voltage input; 
(9) The device can extend DI, DO. If needed, please say it specially.   
 

6 Settings explanation   

6.1 General 
This part is for reference only.   

6.2 1st zone overcurrent protection 
6.2.1 Action current Igl1 

(1) Calculated to avoid 3‐phase short current in cable terminal: 

Action current:  I gl1  K rel I K . f  


( 3)

Sensitive coefficient:  K sen  0.866 I k .i / I op  2  


( 2) ( 3)

Where,Krel:Reliability coefficient,1.2~1.25 

I k( 3. f) :Secondary 3‐phase short current in cable terminal(A) 

I k( 3.i) :Secondary 3‐phase short current in cable start(A) 

( 2)
K sen :Sensitivity of 2‐phase short circuit in terminal start   

If  the  cable  is  too  long  and  the  sensitivity  is  not  easily  met,  voltage  blocking  instantaneous 
protection can be adopted.   
(2) Current  element  is  calculated  when  there  is  enough  sensitivity  when  cable  terminal 
short  circuit  occurs  while  voltage  element  is  calculated  to  avoid  cable  terminal  3‐phase 
short circuit:   
22
WDZ-5211 Line Management Relay(V1.02)

Action current I gl1  I K . f / K sen  


( 2) ( 2)

ZL
Per‐unit value of action voltage  U dybs 
*
 
K rel ( X S  X L )

( 2)
Where, I k . f :Secondary 2‐phase short current in cable terminal(A) 

ZL:Per‐unit value of cable line impedance   
XS:Per‐unit value of 6KV/10KV bus system reactance   
XL:Per‐unit value of cable line reactance   

6.2.2 Action time tgl1 

Basically tgl1=0 

6.3 2nd zone overcurrent protection 
6.3.1 Action current Igl2 

(1) Calculated to avoid motor self‐initiating current:   

I gl 2  K rel I st .all / nTA  

Where,Krel:Reliability coefficient, 1.15~1.2 
Iat.all:self‐initiating current connected to feeder(A) 
nTA:TA ratio 
(2) Calculated according to the max. instantaneous current of lower‐level equipment:   

I gl 2  K rel I op. max / nTA  

Where,Krel:Reliability coefficient,1.15~1.2 
Iop.max:maximum instantaneous current of lower‐level equipment(A) 
If sensitivity is enough, please take the larger action current better.   

6.3.2 Action time tgl2 

(1) Matched with instantaneous protection:   

t gl 2  0  t  t  

Where, t :time difference, 0.3s 
(2) Matched with overcurrent protection: 

t gl 2  t gl . max  t  

Where, t : Time difference, 0.3s 

6.4 3rd zone overcurrent protection 
Usually, this protection can be unused.   
23
WDZ-5211 Line Management Relay(V1.02)

6.5 After‐accelerated protection 
6.5.1 Action current Ihjs 

(1) Calculated to avoid motor self‐initiating current;   
(2) Calculated to avoid excitation surge of line transformer. 

6.5.2 Action time thjs 

Basically thjs=0 

6.6 Overload protection   
6.6.1 Action current Igfh 

Igfh=(1.15~1.3)Ie 

6.6.2 Action time tgfh 

tgfh=5~10s (signal)   

6.7 Ground fault protection   
6.7.1 Neutral point non‐ground fault system 

(1) ZS action current I0dz 
Calculated to avoid single‐phase ground current passed in protected point: 

I 0 dz  K rel I K(1)  K rel 3I c  

Where,Krel:Reliability coefficient, 2~2.5(Alarm); 2.5~3(Trip) 

I K(1) :single‐phase ground current in short‐circuit point supplied by protected device 

when single‐phase ground fault occurs(A) 
Ic:single‐phase capacitive current of protected device(A) 
(2) Action time t0dz 
a) When 6KV/10KV ground current is larger than 10A, the protection will act to trip and 

the action time is t 0 dz  t 0.op. max  t .   

Where,t0.op.max: max. action time of lower single‐phase ground fault protection(s) 
t :Time difference, 0.3~0.4s 
b) When 6KV/10KV ground current is smaller than 10A,for 300MW or above unit, if the 
selectivity and sensitivity are met, we suggest the protection act to trip and the action 

time is t 0 dz  t 0.op. max  t .   

c) When  6KV/10KV  ground  current  is  smaller  than  10A,if  the  selectivity  and  sensitivity 
cannot be met, we suggest the protection act to issue alarm signals and the action time 
t0dz=0~0.5s.   

24
WDZ-5211 Line Management Relay(V1.02)

(3) Attention 
ZS  action  current  of  the  ground  fault  protection  is  the  primary  current,  while  the  action 
criterion  and  set  value  are  secondary  value.  Since  TA0  ratio  has  relation  with  zero  sequence 
current  circuit  impedance  and  TA0  primary  current  and  secondary  current  are  non‐linear 
relationship, thus in local debugging, primary action current should be imported and secondary 
current is showed.   

6.7.2 Neutral point grounding system via resistance 

(1) ZS action currentI0dz 
a) Calculated to avoid single‐phase ground current passed in protected point:   

I 0 dz  K rel I K(1)  

Where,Krel:Reliability coefficient,2~2.5(Alarm); 2.5~3(Trip) 

I K(1) :single‐phase ground current in short‐circuit point supplied by protected device when 

single‐phase ground fault occurs(A) 
b) Match with lower single‐phase ground fault protection:   

I 0 dz  K rel I 0.op. max  

Where,Krel:Reliability coefficient, 1.1~1.15 
I0.op.max: max. action current of lower single‐phase ground fault protection(A) 
ZS Action current should get the max of a)and b).   
(2) Action time t0dz 
Match with maxium action time of lower single‐phase ground fault protection:   

t 0 dz  t 0.op. max  t .   

Where,t0.op.max: max. action time of lower single‐phase ground fault protection(s) 
t :Time difference, 0.3~0.4s 

25

You might also like