Professional Documents
Culture Documents
Tel20104 Assignment 2 Digital Protective Relay PDF
Tel20104 Assignment 2 Digital Protective Relay PDF
ASSIGNMENT 2
A digital (numeric) multifunction protective relay for distribution networks. A single such
device can replace many single-function electromechanical relays, and provides self-testing
and communication functions.
NUMERICAL RELAY
The distinction between digital and numerical protection relay rests on points of fine technical
detail, and is rarely found in areas other than Protection. Numerical relays are the product of
the advances in technology from digital relays. Generally, there are several different types of
numerical protection relays. Each type, however, shares a similar architecture, thus enabling
designers to build an entire system solution that is based on a relatively small number of
flexible components. They use high speed processors executing appropriate algorithms. Most
numerical relays are also multifunctional and have multiple setting groups each often with
tens or hundreds of settings.
ELECTROMECHANICAL RELAY
The electrical and electronics circuits are usually operated over a wide range of voltage,
current, and power ratings. For every circuit or equipment or electrical network or power
system protection system is desired to avoid the breakdown or temporary or permanent
damage. Such that, equipment’s or circuits used for protecting are called as protecting
equipment or circuit. In case of a small amount of voltage ratings, protection of the circuit
depends on the cost of the original circuit to be protected and cost of the protection system
essential to protect the circuit. But, in case of high-cost circuits or equipment’s, it is desired
to adopt a protection system or protection circuit and controlling device or controlling
circuit to avoid economical loss and damage.
Electromechanical relays can be classified into several different types as follows:
"Armature"-type relays have a pivoted lever supported on a hinge or knife-edge pivot, which
carries a moving contact. These relays may work on either alternating or direct current, but
for alternating current, a shading coil on the pole is used to maintain contact force
throughout the alternating current cycle. Because the air gap between the fixed coil and the
moving armature becomes much smaller when the relay has operated, the current required
to maintain the relay closed is much smaller than the current to first operate it. The
"returning ratio" or "differential" is the measure of how much the current must be reduced
to reset the relay.
A variant application of the attraction principle is the plunger-type or solenoid operator.
A reed relay is another example of the attraction principle.
"Moving coil" meters use a loop of wire turns in a stationary magnet, similar to
a galvanometer but with a contact lever instead of a pointer. These can be made with very
high sensitivity. Another type of moving coil suspends the coil from two conductive
ligaments, allowing very long travel of the coil.
When the input current is above the current limit, the disk rotates, the contact moves left
and reaches the fixed contact. The scale above the plate indicates the delay-time.
"Induction" disk meters work by inducing currents in a disk that is free to rotate; the rotary
motion of the disk operates a contact. Induction relays require alternating current; if two or
more coils are used, they must be at the same frequency otherwise no net operating force is
produced. These electromagnetic relays use the induction principle discovered by Galileo
Ferraris in the late 19th century. The magnetic system in induction disc overcurrent relays is
designed to detect overcurrent’s in a power system and operate with a pre-determined time
delay when certain overcurrent limits have been reached. In order to operate, the magnetic
system in the relays produces torque that acts on a metal disc to make contact, according to
the following basic current/torque equation.
Where and are the two fluxes and is the phase angle between the fluxes
The following important conclusions can be drawn from the above equation.
• Two alternating fluxes with a phase shift are needed for torque production.
• Maximum torque is produced when the two alternating fluxes are 90 degrees apart.
• The resultant torque is steady and not a function of time.
The relay's primary winding is supplied from the power systems current transformer via a
plug bridge, which is called the plug setting multiplier (psm). Usually, seven equally spaced
tapping’s or operating bands determine the relays sensitivity. The primary winding is located
on the upper electromagnet. The secondary winding has connections on the upper
electromagnet that are energised from the primary winding and connected to the lower
electromagnet. Once the upper and lower electromagnets are energised, they produce eddy
currents that are induced onto the metal disc and flow through the flux paths. This
relationship of eddy currents and fluxes creates torque proportional to the input current of
the primary winding, due to the two flux paths being out of phase by 90°.
In an overcurrent condition, a value of current will be reached that overcomes the control
spring pressure on the spindle and the braking magnet, causing the metal disc to rotate
towards the fixed contact.
Providing the relay is free from dirt, the metal disc and the spindle with its contact will reach
the fixed contact, thus sending a signal to trip and isolate the circuit, within its designed
time and current specifications. Drop off current of the relay is much lower than its
operating value, and once reached the relay will be reset in a reverse motion by the
pressure of the control spring governed by the braking magnet.
STATIC RELAY
Application of electronic amplifiers to protective relays was described as early as 1928,
using vacuum tube amplifiers and continued up to 1956. Devices using electron tubes were
studied but never applied as commercial products, because of the limitations of vacuum
tube amplifiers. A relatively large standby current is required to maintain the tube filament
temperature; inconvenient high voltages are required for the circuits, and vacuum tube
amplifiers had difficulty with incorrect operation due to noise disturbances.
Static relays have no or few moving parts, and became practical with the introduction of
the transistor. Measuring elements of static relays have been successfully and economically
built up from diodes, Zener diodes, avalanche diodes, unijunction transistors, p-n-p and n-p-
n bipolar transistors, field effect transistors or their combinations. Static relays offer the
advantage of higher sensitivity than purely electromechanical relays, because power to
operate output contacts is derived from a separate supply, not from the signal circuits.
Static relays eliminated or reduced contact bounce, and could provide fast operation, long
life and low maintenance.
WORKING PRINCIPLE
Input processing
Low voltage and low current signals (i.e., at the secondary of a voltage
transformers and current transformers) are brought into a low pass filter that
removes frequency content above about 1/3 of the sampling frequency (a relay A/D
converter needs to sample faster than twice per cycle of the highest frequency that it is to
monitor). The AC signal is then sampled by the relay's analog-to-digital converter from 4 to
64 (varies by relay) samples per power system cycle. As a minimum, magnitude of the
incoming quantity, commonly using Fourier transform concepts (RMS and some form of
averaging) would be used in a simple relay function. More advanced analysis can be used to
determine phase angles, power, reactive power, impedance, waveform distortion, and
other complex quantities.
Only the fundamental component is needed for most protection algorithms, unless a high-
speed algorithm is used that uses sub cycle data to monitor for fast changing issues. The
sampled data is then passed through a low pass filter that numerically removes the
frequency content that is above the fundamental frequency of interest (i.e., nominal system
frequency), and uses Fourier transform algorithms to extract the fundamental frequency
magnitude and angle.
Logic processing
The relay analyses the resultant A/D converter outputs to determine if action is required
under its protection algorithm(s). Protection algorithms are a set of logic equations in part
designed by the protection engineer, and in part designed by the relay manufacturer. The
relay is capable of applying advanced logic. It is capable of analysing whether the relay should
trip or restrain from tripping based on parameters set by the user, compared against many
functions of its analogue inputs, relay contact inputs, timing and order of event sequences.
If a fault condition is detected, output contacts operate to trip the associated circuit
breaker(s).
Parameter setting
The logic is user-configurable and can vary from simply changing front panel switches or
moving of circuit board jumpers to accessing the relay's internal parameter setting webpage
via communications link on another computer hundreds of kilometres away.
The relay may have an extensive collection of settings, beyond what can be entered via front
panel knobs and dials, and these settings are transferred to the relay via an interface with a
PC (personal computer), and this same PC interface may be used to collect event reports from
the relay.
Event recording
In some relays, a short history of the entire sampled data is kept for oscillography records.
The event recording would include some means for the user to see the timing of key logic
decisions, relay I/O (input/output) changes, and see, in an oscillography fashion, at least the
fundamental component of the incoming analogue parameters.
Data display
Digital/numerical relays provide a front panel display, or display on a terminal through a
communication interface. This is used to display relay settings and real-time current/voltage
values, etc.
Protective relays can also be classified by the type of measurement they make. A protective
relay may respond to the magnitude of a quantity such as voltage or current. Induction relays
can respond to the product of two quantities in two field coils, which could for example
represent the power in a circuit.
"It is not practical to make a relay that develops a torque equal to the quotient of two AC
quantities. This, however is not important; the only significant condition for a relay is its
setting and the setting can be made to correspond to a ratio regardless of the component
values over a wide range.”
Several operating coils can be used to provide "bias" to the relay, allowing the sensitivity of
response in one circuit to be controlled by another. Various combinations of "operate torque"
and "restraint torque" can be produced in the relay.
Lightweight contacts make for sensitive relays that operate quickly, but small contacts can't
carry or break heavy currents. Often the measuring relay will trigger auxiliary telephone-type
armature relays.
The electromechanical relay consists of various parts such as movable armature, movable
contact & stationary contact or fixed contact, spring, electromagnet (coil), the wire wrapped
as coil with its terminals represented as ‘C’ which are connected as shown in the below figure
to form electromechanical relay.
CONCLUSION
Digital protective relay is placed on the system to avoiding equipment from damage and
limiting it to the single component that may be in trouble. The relays quickly locate the fault
and trip circuit breakers and will interrupt the flow of current into the defective component.
Easy to say, this protective relay is a device designed to trip a circuit breaker when a fault is
detected. Digital relays offer much better accuracy and timing characteristics, compared
with E/M and static relays. They also provide much better visibility into what signal relay is
responding to, what relay is measuring and all sequential digital indications about elements
operation from pre-fault to post-fault.
REFERENCES
1. "Schweitzer Programmable Automation Controller". Schweitzer Engineering
Laboratories. Archived from the original on 9 September 2015. Retrieved 21
November 2012.
2. ^ "George Dorwart Rockefeller - Engineering and Technology History Wiki". ethw.org.
Retrieved 2019-02-13.
3. ^ Rockefeller, George D. (1968-05-31). "Fault protection with a digital
computer". Theses. 88 (4): 438–
464. Bibcode:1969ITPAS..88..438R. doi:10.1109/TPAS.1969.292466.
4. ^ Rockefeller, G.D. (1969). "Fault Protection with a Digital Computer". IEEE
Transactions on Power Apparatus and Systems. 88 (4): 438–
464. Bibcode:1969ITPAS..88..438R. doi:10.1109/TPAS.1969.292466.
5. ^ Rockefeller, G.D.; Udren, E.A.; Gilcrest, G.B. (1972). "High-Speed Distance Relaying
Using a Digital Computer I - System Description". IEEE Transactions on Power
Apparatus and Systems. 91 (3): 1235–
1243. Bibcode:1972ITPAS..91.1235G. doi:10.1109/TPAS.1972.293482.
6. ^ Rockefeller, G.D.; Udren, E.A. (1972). "High-Speed Distance Relaying Using a Digital
Computer II-Test Results". IEEE Transactions on Power Apparatus and
Systems. 91 (3): 1244–
1258. Bibcode:1972ITPAS..91.1244R. doi:10.1109/TPAS.1972.293483.
7. ^ "IEEE Herman Halperin Electric Transmission and Distribution Award".
8. ^ Ramamoorty, M. (1971). "A note on impedance measurement using digital
computers". IEE-IERE Proceedings - India. 9 (6): 243. doi:10.1049/iipi.1971.0062.