Professional Documents
Culture Documents
TK 60690-3-MM X500 Rev.0.1 Print Date 2011-02-28
TK 60690-3-MM X500 Rev.0.1 Print Date 2011-02-28
X500 Cooling
X500 Heating & Cooling
Maintenance Manual
1
The maintenance information in this manual covers unit model:
X500 N - 1000, 24V 901717
X500 W - 1000, 24V 901719
X500 N - 1004, 24V 901718
X500 W - 1004, 24V 901721
This manual is published for informational purposes only and the information so provided
should not be considered as all-inclusive or covering all contingencies. If further information is
required, Ingersoll Rand / Thermo King Corporation should be consulted. The above manuals
may be purchased from your local Thermo King dealer.
Sale of product shown in this manual is subject to Thermo King’s terms and conditions
including, but not limited to, the Thermo King Limited Express Warranty. Such terms and
conditions are available upon request. Thermo King’s warranty will not apply to any equipment
which has been “so repaired or altered outside the manufacturer’s plants as, in the
manufacturer’s judgment, to effect its stability.”
2
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environment and limit
the potential harm to the ozone layer that can result from allowing refrigerant to
escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits the loss of
refrigerant into the atmosphere.
In addition, service personnel must be aware of Federal regulations concerning
the use of refrigerants and the certification of technicians. For additional
information on regulations and technician certification programs, contact your
local THERMO KING dealer.
R-134a
WARNING: Use only Polyol Ester-based refrigeration compressor oil in R-134a.
See Thermo King Parts Manual for part number.
Do not mix Polyol Ester and standard synthetic compressor oils. Keep
Polyol Ester compressor oil in tightly sealed containers. If Polyol Ester
oil becomes contaminated with moisture or standard oils, dispose of
properly – DO NOT USE.
When servicing Thermo King R-134a unit, use only those service tools
certified for and dedicated to R-134a refrigerant and Polyol Ester
compressor oils. Residual non-HFC refrigerants or oils will
contaminate R-134a systems.
3
1. About This Manual
Purpose
The purpose of this manual is to provide general maintenance information necessary to operate and
maintain the climate control unit (HVAC unit, A/C unit) at peak operating standards and best lifetime.
This includes safety information, unit information such as technical specification, general unit
description, maintenance procedures and some diagnostic and troubleshooting information.
Blank Pages
This manual may contain blank pages at the end of chapters. This is normal. There is no information
missing from the manual.
Roadside/Curbside Terminology
Roadside/Curbside terminology: These terms can be confusing because of differences between North
America and Europe. Please note:
Curbside: The side of the bus to the driver right when the driver is in his seat and facing
forward.
Roadside: The side of the bus to the driver left when the driver is in his seat and facing forward.
4
2. Table of Contents
1. About This Manual ...................................................................................................................................4
2. Table of Contents.....................................................................................................................................5
4. List of Abbreviations................................................................................................................................8
5. Safety Precautions...................................................................................................................................9
5.1. General Practices ...........................................................................................................................9
5.2. Electrical Hazards.........................................................................................................................10
5.3. Refrigerant Hazards......................................................................................................................11
5.4. Compressor Oil Hazards...............................................................................................................12
5.5. First Aid ........................................................................................................................................13
6. System Description................................................................................................................................14
7. Specifications.........................................................................................................................................15
7.1. HVAC System...............................................................................................................................15
7.2. Electrical System ..........................................................................................................................16
7.3. Compressor (Optional)..................................................................................................................17
7.4. Weight and dimensions.................................................................................................................18
9. Compressor Description........................................................................................................................25
9.1. General description.......................................................................................................................25
9.2. TM compressors ...........................................................................................................................25
9.3. Small Compressor Oil Charge Specifications - R134a ...................................................................26
5
12.1. Filter-Drier Replacement...............................................................................................................63
12.2. Thermostatic Expansion Valve Replacement ................................................................................64
12.3. Pressure Switches Replacement ..................................................................................................68
12.4. Relief Valve Replacement.............................................................................................................69
15. Troubleshooting..................................................................................................................................82
15.1. Air Conditioning Diagnosis and Analysis .......................................................................................82
15.2. Causes for Failure to Stay Within Temperature Range..................................................................83
15.3. Compressor suction pressure conditions.......................................................................................85
15.4. Compressor discharge pressure conditions...................................................................................86
6
3. List of Figures
Figure 1: X500 Unit dimensions .................................................................................................................... 18
Figure 2: X500 Rooftop unit .......................................................................................................................... 19
Figure 3: X500 Outside view......................................................................................................................... 23
Figure 4: X500 Inside view............................................................................................................................ 24
Figure 5: TM compressors (Illustration photo) ............................................................................................... 25
Figure 6: A/C refrigeration system (example) ................................................................................................ 27
Figure 7: Application diagram ....................................................................................................................... 29
Figure 8: CAID Driver panel.......................................................................................................................... 30
Figure 9: CAID Keys in Setup/Calibration/Test mode .................................................................................... 34
Figure 10: CAID Function menu structure ................................................................................................... 34
Figure 11: CAID List of functions................................................................................................................. 35
Figure 12: CAID Test mode 1 - Cooling/Heating control .............................................................................. 35
Figure 13: CAID Test mode 1- Blower control ............................................................................................. 35
Figure 14: CAID Test mode 1- Fresh air control .......................................................................................... 36
Figure 15: CAID Scheme of relay test procedure ........................................................................................ 36
Figure 16: CAID List of calibrations............................................................................................................. 37
Figure 17: CAID Calibration function structure............................................................................................. 38
Figure 18: CAID Setup function structure .................................................................................................... 39
Figure 19: CAID Controller parameters ....................................................................................................... 40
Figure 20: CAID Scheme of hourmeter ....................................................................................................... 42
Figure 21: CAID List of alarm codes............................................................................................................ 44
Figure 22: CAID Driver panel connectors .................................................................................................... 44
Figure 23: CAID List of inputs ..................................................................................................................... 45
Figure 24: CAID List of outputs ................................................................................................................... 45
Figure 25: Special Tools ............................................................................................................................. 49
Figure 26: Testing for Refrigeration Leaks .................................................................................................. 56
Figure 27: Evacuation Station and Unit Hookup (example).......................................................................... 58
Figure 28: Constant Pressure Rise After Evacuation Indicates System Leak............................................... 59
Figure 29: Pressure Rise that Levels Off After Evacuation Indicates Moisture in System ............................. 60
Figure 30: Typical pressurized gas bottle with pressure regulator and gauges............................................. 62
Figure 31: Filter-Drier Installation (example)................................................................................................ 63
Figure 32: Thermostatic expansion valve installation (example) .................................................................. 64
Figure 33: Example of solder type valve and sensor bulb position ............................................................... 65
Figure 34: Pressure switches installation (example) .................................................................................... 68
Figure 35: Electrical switchboard (example)................................................................................................ 70
Figure 36: Fuse extractor............................................................................................................................ 71
Figure 37: Evaporator blower installation (example) .................................................................................... 72
Figure 38: Condenser fan assembly (example) ........................................................................................... 73
Figure 39: Condenser fan (example)........................................................................................................... 74
Figure 40: Damper Connector Plug Wiring Diagram.................................................................................... 75
Figure 41: Fresh Air Damper Motor............................................................................................................. 76
Figure 42: Ambient temperature sensor (example)...................................................................................... 77
Figure 43: Fresh air filter (example) ............................................................................................................ 79
Figure 44: Return air filter (example)........................................................................................................... 80
Figure 45: Coil Air filter installation (illustrative picture)................................................................................ 81
Figure 46: Typical Operating Pressures ...................................................................................................... 82
7
4. List of Abbreviations
The following abbreviations are used in the text and in the drawings in appendix too.
8
5. Safety Precautions
Thermo King recommends that all services be performed by a Thermo King dealer. However, you
should be aware of several general safety practices:
WARNING: Before any repair or similar action the side covers must be completely
removed from the unit to access interior of unit. Insure you are using best practice for
working at height paying special attention during removal of cover as it could move
due to the influence of the wind.
DANGER: Do not operate the compressor with the discharge valve closed. This
condition increases internal pressure, which can cause an explosion
DANGER: Keep your hands, clothing and tools clear of fans, pulleys, or belts when
working on a unit that is running. Loose clothing might entangle moving fans, pulleys,
or belts, causing serious injury or possible death.
DANGER: Do not inhale refrigerant. Use caution when working with refrigerant or
a refrigeration system in any confined area with a limited air supply, such as a bus or
garage. Refrigerant displaces air and can cause oxygen depletion, resulting in
suffocation and possible death
WARNING: Make sure your gauge manifold hoses are in good condition before
using them. Never let them come in contact with moving belts, motors, pulleys or hot
surfaces. Defective gauge equipment can damage components or cause serious injury.
WARNING: Wear goggles or safety glasses when working around air conditioning
systems or batteries. Refrigerant liquid, oil and battery acid can permanently damage
your eyes.
9
WARNING: Use extreme caution when drilling. Holes might weaken structural
components. Holes drilled into electrical wiring can cause a fire or explosion.
WARNING: Exposed coil fins can cause lacerations. Service work on the evaporator
or condenser coils is best left to a certified Thermo King technician.
CAUTION: Make sure all mounting bolts are tight and are the correct length for
their applications. Improper torque and incorrect bolt lengths can damage equipment.
CAUTION: If soldering is required, use dry nitrogen to purge the system during any
solder operations. Refer to “Using Pressurized Nitrogen” at the end of the
Refrigeration Maintenance chapter
DANGER: Any time anybody entering the roof must be sure, that the main power
lines are OFF and nobody can switch it on if somebody is on the roof.
When servicing or repairing an air conditioning unit, the possibility of serious or even fatal injury from
electrical shock exists. Extreme care must be used when working with a air conditioning unit that is
connected to a source of operating power, even if the unit is not running. Lethal voltage potentials can
exist at the unit power cord, inside the electric switchboard box, at the motors, at any junction box and
within the wiring harnesses.
Precautions
Always turn the A/C Unit OFF. Then disconnect the unit from the primary power source (power
supply) before attempting repair or replacement of major components.
Use tools with insulated handles. Use tools that are in good condition. Never hold metal tools in
your hand if exposed, energized conductors are within reach.
Do not make any rapid moves when working with high voltage circuits. Do not grab a falling
tool or other object. People do not contact high voltage wires on purpose. It occurs from an
unplanned movement.
Treat all wires and connections as high voltage until ammeter and wiring diagram show
otherwise.
Never work alone on high voltage circuits on the refrigeration unit. Another person should
always be standing by in the event of an accident to shut OFF the refrigeration unit and to aid a
victim.
Have electrically insulated gloves, cable cutters and safety glasses available in the immediate
vicinity in the event of an accident.
10
WARNING: Control circuits used by air conditioners are low voltage (24 VDC for
example). This voltage is not dangerous, but the large amount of amperage available
from the alternator will cause severe burns if accidentally shorted to ground with metal
objects, such as tools.
WARNING: Do not wear jewelry, watches or rings because they increase the risk of
shorting out electrical circuits and damaging equipment or causing severe burns
WARNING: Use caution when working with electrical circuits that have capacitors.
Some capacitors hold a significant charge that will cause burns or shocks if
accidentally discharged. Make sure capacitors are discharged before working on
electrical circuits.
DANGER: Do not use a Halide torch. When a flame comes in contact with
refrigerant, toxic gases are produced that will cause suffocation, even death
DANGER: Store refrigerant in proper containers, out of direct sunlight and away
from intense heat. Heat increases pressure inside storage containers, which will cause
them to burst.
DANGER: Do not use oxygen (O2) or compressed air for leak testing systems.
Oxygen mixed with refrigerant is combustible.
WARNING: Wear protective garments and goggles or safety glasses when working
with refrigerant to prevent frostbite and eye injuries.
WARNING: Wear butyl lined gloves when handling refrigerant to help prevent
frostbite.
CAUTION: All charging using the newer refrigerants (Azeotropic blends) must be
done in liquid state. Failure to do this will decrease system operating efficiency. Refer
to the charging procedures found in this manual for your unit
11
refrigerant from escaping into the atmosphere. Refrigerant damages the earth’s upper
ozone layer.
WARNING: Protect your eyes from contact with compressor oil. The oil will cause
serious eye injuries. Avoid prolonged or repeated contact with compressor oil. To
prevent irritation, wash your hands and clothing thoroughly after handling the oil.
CAUTION: Do not mix compressor oils because that will cause system damage.
CAUTION: Use dedicated equipment to prevent contaminating the system with the
wrong type of oil or refrigerant.
CAUTION: Thermo King uses a variety of compressor oils. Oil used in the system
must be verified. Check “Specification” chapter in this manual for correct oil. Using
incorrect oil will invalidate the warranty.
CAUTION: Do not expose compressor oil to the air any longer than necessary. The
oil will absorb moisture, which results in much longer evacuation times and possible
system contamination.
CAUTION: Wipe up spills immediately. Compressor oil can damage paints and
rubber materials.
12
5.5. First Aid
Compressor Oil
Eyes
Immediately flush with water for at least 15 minutes. CALL A PHYSICIAN. Wash skin with soap and
water.
Ingestion
Do not induce vomiting. Immediately contact local poison control center or physician.
Refrigerant
In the event of frostbite, protect the frozen area from further injury, warm the area rapidly and maintain
respiration.
Eyes
Immediately flush eyes with large amounts of water. CALL A PHYSICIAN.
Skin
Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and
shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection. CALL A PHYSICIAN.
Wash contaminated clothing before reuse.
Inhalation
Move victim to fresh air and use CPR (cardio pulmonary resuscitation) or mouth-to-mouth resuscitation
to restore breathing, if necessary. Stay with victim until emergency personnel arrives.
13
6. System Description
General features
Thermo King’s SR rooftop air conditioning units delivers superior comfort to passenger's area. The
X500 system is one-piece rooftop HVAC unit uniquely designed to meet various customer requests and
expectations. From these reasons is X500 system available in two versions: 1000 and 1004.
The differences are:
1000 - version with cooling feature - the evaporator coil is simple
1004 - version with cooling and heating feature - the evaporator coil consists of two sections -
one for cooling, one for heating.
The X500 system is generally intended for small city. The X500 unit is always located on the bus roof
(in the text called rooftop unit). This location gives easy access from the top of the vehicle which
facilitates service and maintenance.
The rooftop unit contains one refrigeration circuit. The refrigeration medium is charged/transported by
compressor via installation pipes & hoses. Compressor is an optional part, different types can be select
by car builder, Thermo King recommends TM compressors. The compressor is usually located in bus
engine area, can be also mounted on specially designed drive kit.
The X500 unit, compressor and other accessories is controlled by common ClimaAIRE control system
and individual switchboard installed inside of rooftop unit. This control system allows driver to control
the operating conditions via ClimaAIRE ID driver panel located on bus dashboard.
14
7. Specifications
7.1. HVAC System
System X500 - 1000 X500 - 1004
System nr. 901717 901719 901718 901721
Version narrow wide narrow wide
Cooling Capacity Rated 14.5 kW 14.5 kW
Test conditions Ambient temperature 35 °C 35 °C
Interior dry temperature 27 °C 27 °C
Interior wet temperature 19 °C 19 °C
-1 -1
Compressor RPM 4 000 min 4 000 min
Heating Capacity Total --- 34 kW
Test conditions Medium temp. inlet --- 80 °C
Return air temperature --- -20 °C
Medium flow --- 16.7 l/min
Air Flow at 0 mm water external pressure Return Air Return Air
3 3
High Speed 2 900 m /h 2 900 m /h
3 3
Middle Speed 2 130 m /h 2 130 m /h
3 3
Low Speed 1 527 m /h 1 527 m /h
Fresh Air (optional) Fresh Air (optional)
30 % 30 %
Refrigerant Type HFC R-134a
Charge 2.2 kg
Maximum ambient operating temperature 50 °C
Low Pressure Cutout Switch (LPCO) Open 69 ± 21 kPa (10 ± 3 psig)
Close 275 ± 34 kPa (40 ± 5 psig)
High Pressure Cutout Switch (HPCO) Open 2482 ± 69 kPa (360 ± 10 psig)
Close 1654 ± 69 kPa (240 ± 10 psig)
Condenser Pressure Switch (CPS) Open 1200 ± 69 kPa (174 ± 10 psig)
Close 1703 ± 69 kPa (247 ± 10 psig)
High Pressure Relief Valve (RV) Open 3447 +517/-103 kPa (500 +75/-15 psig)
15
7.2. Electrical System
X500 - 1000 X500 - 1004
Power Supply Voltage
Nominal 12 VDC 24 VDC
Maximal 13,5 VDC 27 VDC
Fuses
Controller power supply (PWR) 1x 5 A (32 VDC) 1x 5 A (32 VDC)
Evaporator blower motors (EFM1 - 4) 4x 10 A (32 VDC) 4x 10 A (32 VDC)
Condenser fan motors (CFM1 - 2) 2x 20 A (32 VDC) 2x 20 A (32 VDC)
Compressor clutch (CR) 1x 5 A (32 VDC) 1x 5 A (32 VDC)
Boost pump (optional) --- 1x 15 A (32 VDC)
Alternator (optional) 1x 80 A (32 VDC) 1x 50 A (32 VDC)
16
7.3. Compressor (Optional)
Compressor Model TM-16
Type Svash-plate type
Number of cylinders 6
Maximum speed 6 000 RPM
Refrigerant R-134a
1
Compressor oil type Polyol Ester Based Type (required) TK No. 203-515 *
2
Compressor oil charge 0.15 litre *
Temperature operating range -20 °C to +65 °C
Weight (approx., incl. oil and clutch) 7 - 10 kg (depends on clutch type and accessories)
Compressor Model TM-21
Type Svash-plate type
Number of cylinders 10
Maximum speed 6 000 RPM
Refrigerant R-134a
1
Compressor oil type Polyol Ester Based Type (required) TK No. 203-515 *
2
Compressor oil charge 0.18 litre *
Temperature operating range -20 °C to +65 °C
Weight (approx., incl. oil and clutch) 6 - 10 kg (depends on clutch type and accessories)
Compressor Model TM-31
Type Svash-plate type
Number of cylinders 10
Maximum speed 6000 RPM
Refrigerant R-134a
1
Compressor Oil Type Polyol Ester Based Type (required) TK No. 203-515 *
2
Compressor Oil charge 0.5 litre *
Temperature Operating Range -20 °C to +65 °C
Weight (approx., incl. oil and clutch) 14 - 18 kg (depends on clutch type and accessories)
*1
Do not use or add standard synthetic or mineral oils to the refrigeration system. If ester based oil becomes
contaminated with moisture or with standard oils, dispose of properly - DO NOT USE!
*2
When the compressor is removed from the unit, oil level should be noted or the oil removed from the
compressor should be measured so that the same amount of oil can be maintained in the replacement
compressor.
17
7.4. Weight and dimensions
X500 - 1000 X500 - 1004
Weight (net, without compressor)
NARROW 86 kg NARROW 94 kg
WIDE 93 kg WIDE 101 kg
Dimensions (max.)
Length 2200 mm
Width NARROW 1520 mm
WIDE 1800 mm
Height 184 mm
BEA730
18
8. Rooftop Unit Description
8.1. General description
The X500 air conditioning cooling or cooling & heating system provides the cooling, dehumidifying
and heating of the air for passenger area to keep the conditions comfortable.
The X500 unit can be easily accessed from the top of the vehicle which facilitates service and
maintenance. Important components (e.g. filter-drier) are arranged for easy access and service through
side covers.
The X500 system is equipped with refrigeration circuits with one compressor. Can be used several
different models of compressor. For details see Section 9.
Control system consists of ClimaAIRE driver panel in versions ClimaAIRE ID, located on driver's
dashboard, and electrical switchboard installed in the rooftop unit.
BEA718
Figure 2: X500 Rooftop unit
The X500 rooftop units in all versions consist of closed sealed refrigerant circuit with evaporator and
condenser coils, electrical circuit with evaporator blowers and condenser fans, control system, unit
frame and covers and auxiliary elements.
Cooling/heating is accomplished by drawing air (return air) from the cab interior to the entrance
chamber where is mixed with fresh air (in case of system with fresh air dumper otherwise is used return
air only). This mixed air (return air) passes through the evaporator coil, heater (optional) and then enters
the blower. The evaporator blowers pressurize the conditioned air and this pressure move the air from
HVAC unit into the vehicle air distribution system.
19
8.2. Main parts of rooftop units
The primary assemblies are:
Condenser coil with integrated liquid receiver tank
Condenser fans
Refrigeration circuit components
o Filter-drier
o Sight glass
o Liquid solenoid valve
o Evaporator coil assemblies incl. thermostatic expansion valve
o Heating coils - incorporated to evaporator coil (version 1004 only)
Evaporator blowers
Fresh air damper (optional)
Air filters (optional)
Control system - see Section 10.2, page 29.
Unit protections devices
Structural frame and covers
The complete HVAC system consists of rooftop unit and compressor. For compressor see Section 9,
page 25. For more information see also refrigerant circuit diagrams on page 27.
8.2.3. Filter-Drier
The filter-drier (dehydrator) is a cartridge soldered type unit intended for protection the refrigerant
against:
moisture - by absorbing and retaining it deep within the desiccant
foreign matter - the filter-drier will filter out scale, solder particles, carbon, sludge, dirt or any
other foreign matter with negligible pressure drop. Fine particles that would go through an
ordinary strainer are removed down to a minimum size in one pass filtration.
acid - the hydrochloric, hydrofluoric, and various organic acids are adsorbed and held by the
desiccant in a manner similar to the adsorption of moisture
20
oil sludge and varnish - all refrigeration oils break down to produce varnish, sludge and organic
acids and here are removed
For location of the filter-drier see "Figure 4: X500 Inside view" in following section, page 24.
22
8.3. Photos and Illustrations
5
4
1
3
BEA719
23
13
14
12
11
15 10
1
2 8
7
1
2 6
5
4 BEA720
3
24
9. Compressor Description
9.1. General description
For X500 systems can be used different models of compressor (see "Specification"). Model/type of
compressor depends on your HVAC system configuration and bus manufacturer. For exact
determination of used type and model see the nameplate on body of compressor.
9.2. TM compressors
The TM compressors are vehicle type small compressors designed for HVAC applications. The purpose
of this equipment is to deliver and energize the refrigerant to the rooftop air conditioning unit.
Main features of TM compressors:
Compact design
Balanced Swash Plate design offers low pulsation noise, quiet and smooth operation, less
vibration, and lower horsepower requirements.
High Efficiency
o Cooling capacity is stable throughout the entire RPM operating range.
High Durability
o MoS2 coated steel swash plate provides additional protection during liquid slugging and
high load conditions.
o Ball and shoe design promotes lubrication for better compressor durability.
o Needle bearings insure high durability for long life and high speed operation.
o Lip Shaft Seal insures excellent sealing integrity and extends compressor life.
Optimized lubrication system with oil pump and sight glass.
BEA646
25
9.3. Small Compressor Oil Charge Specifications - R134a
Refrigerant Charge
kg 0,5 0,9 1,4 1,8 2,3 2,7 3,2 3,6 4,1 4,5 5 5,4 5,9 6,4
pounds 1 2 3 4 5 6 7 8 9 10 11 12 13 14
TM-16
Initial oil charge Oil to add
150 ml (5 oz) (add 24 ml per 0.9 kg of refrigerant - 0.8 oz oil per 2 lb of refrigerant)
ml 22 44 68 88 112 133 157 177 201 222 245 266 290 325
oz 0,75 1,5 2,3 3 3,8 4,5 5,3 6 6,8 7,5 8,3 9 9,8 11
TM-21
Initial oil charge Oil to add
180 ml (6 oz) (add 24 ml per 0.9 kg of refrigerant - 0.8 oz oil per 2 lb of refrigerant)
ml 22 44 68 88 112 133 157 177 201 222 245 266 290 325
oz 0,75 1,5 2,3 3 3,8 4,5 5,3 6 6,8 7,5 8,3 9 9,8 11
TM-31
Initial oil charge Oil to add
500 ml (16,9 oz) (add 24 ml per 0.9 kg of refrigerant - 0.8 oz oil per 2 lb of refrigerant)
ml 12 23 35 47 59 71 83 95 106 118 130 142 154 177
oz 0,4 0,8 1,2 1,6 2,0 2,4 2,8 3,2 3,6 4,0 4,4 4,8 5,2 6
This table gives amounts of compressor oil to add to refrigerant circuit above the initial charge (given
on the left), per the amount of refrigerant in a HVAC system (for amount of refrigerant in HVAC refrig.
circuit see "Specifications" on page 15).
NOTE: Recommended values are intended as a guideline only. Amounts vary depending on amount
of oil in the compressor during operation. Compressors with larger oil sumps require less additional
oil. See the compressor maintenance chapter in next manual for all procedures.
NOTE: After oil replacement always check the oil level in compressor, use a flashlight to observe the
compressor oil sight glass located on compressor body. Oil level should be approximately in the
middle of the sight glass.
CAUTION: Do not overcharge the system with oil. Doing so will damage the compressor.
CAUTION: Do not mix PAG and POE oils. Verify that the oil type in the compressor and the
system match. Drain compressor oil and replace with system oil if necessary.
26
10.Operating Instructions
10.1. Basic A/C System - Theory of Operation
The major components of the A/C unit are all connected in a closed common system to form
a refrigerant circuit, other components are designed for heating feature and for control system.
BEA721
27
The refrigerant system circulates refrigerant (energized by compressor) between the evaporator coils
and the condenser coils to provide the requested exchange of heat energy.
The evaporator blowers drives the air with higher temperature (return air or mixed air) across the
evaporator coils. The heat energy is absorbed by the refrigerant (a low pressure, low temperature liquid)
that inside of the coils evaporates. The cooled air is discharged into vehicle air distribution system.
As the refrigerant evaporates, a low pressure, low temperature, heat-laden vapour is formed. The
refrigerant needs to release the heat energy. Compressor's suction continuously draws the heat-laden
vapours from the evaporator coils. As the vapours are compressed, it increases its pressure, changing it
to high pressure, high temperatured vapour. This increases the vapour temperature and pressure to
facilitate heat transfer to the ambient air and establish a condensing temperature.
As the high-temperature vapours travels through the condenser coils, the heat is dispersed into the
cooling fins, and ambient air is circulated by the condenser fans. As the heat is removed, the vapours
condenses back into a liquid. Thus, the heat absorbed by the refrigerant from the evaporator, is
transferred to the condenser and given off to ambient air.
The high temperature liquid is maintained under high pressure in the small receiver installed after the
condensers, where it is stored until needed. The receiver serves as a reservoir for the variable demands
of liquid refrigerant from the system.
From the receiver tank liquid refrigerant flows through the filter-drier (dehydrator), where impurities,
solids, and moisture are removed. From the filter-drier, the high temperature, high pressured liquid
flows through to the expansion valves. The expansion valves restrict and control the flow of liquid
refrigerant to the evaporator coils where it again absorbs heat from bus interior air (return air).
Before expansion valves can be added feeder branch designed for FrontBox (optional equipment)
connection.
Beside evaporator coils can be added heating coils (for cooling/heating 1004 systems only) intended for
heating feature, connected to bus heating system.
28
10.2. Control System
The control system handles all system functions to maintain the passenger's area at the proper
temperature. The control system consists of controller (driver panel) and control panel (electrical
switchboard) located inside of the rooftop unit.
For X500 system is intended ClimaAIRE ID control system.
The controller communicates with control panel (switchboard) and compressor or other optional
equipment via Thermo King uniquely designed harnesses.
BEA722
The control system is monitoring all important values through low voltage signal inputs and operates
the rooftop unit and compressor within normal conditions through low voltage signal outputs.
29
10.3. ClimaAIRE ID and ClimaAIRE II
The driver panel in X500 system usually works like a terminal (bus driver panel, HMI - Human
Machine Interface) and controller too. Collects and sends bus driver commands to the rooftop unit
switchboard (and compressor and other optional auxiliary equipment), and it conversely receives and
displays HVAC system status to her/him.
7 8 9 10 11 12
13 14 BEA133
1 2 3 4 5 6
A/C mode
Heat mode
Ventilation mode
30
Display Return air temperature icon
Setpoint icon
Red - Boost pump icon
Blue - Compressor clutch icon
31
Mode select
In normal operating mode - Auto mode - the controller selects the right mode (cool or heat or
ventilation) automatically.
Reheat/Auto mode - unit will operate in cool or heat mode based on operating conditions to
ensure proper air temperature and humidity. The cooling and heating function can be used
simultaneously (this is "Reheat mode")
A/C mode - unit will operate in cool mode (based on operating conditions) or ventilation
Heat mode - unit will operate in heat mode (based on operating conditions) or ventilation
Ventilation mode - unit will be in ventilation only, cooling or heating will be disabled
NOTE: The Heat mode can be applicable only for HVAC units in 1004 version (cooling/heating).
Automatic ON feature
Depending on Ao parameter (see "Figure 19: CAID Controller ") the controller (driver panel) will be
switched ON or stays OFF depending on state when power supply was switched OFF:
If the driver panel was ON when power supply was switched OFF; on next system start -
power supply ON - the driver panel will also start (internal memory keeps the last operating
status; parameter Ao is set to 00)
If the driver panel was OFF when power supply was switched OFF; on next system start -
power supply ON - the driver panel will stay OFF (internal memory keeps the last operating
status; parameter Ao is set to 00)
OR the driver panel always will be switched ON when the power supply is switched ON
(parameter Ao is set to 01)
32
Lock function
Depending on Lc parameter (see "Figure 19: CAID Controller ") the driver panel buttons functions are
obvious or described further (factory settings) or:
blower speed key and fresh air select key are locked, have no response on pressing (Lc =01)
mode select key, blower speed key and fresh air select key are locked (Lc=02)
all buttons except ON/OFF key are locked (Lc=03)
Manual mode
ClimaAIRE ID can control HVAC unit in manual mode to operate system directly in heating or cooling.
Manual mode has to be enabled by parameter Lt in driver panel setup.
In automatic mode operator can change the setpoint in range from LS (minimal value of setpoint) to HS
(maximal value of setpoint), default range is from 17 °C to 27 °C. When the control mode is changed to
Manual mode then setpoint value can be set to Lo command instead of LS or to Hi command instead of
HS value:
Lo command switches ON continual signal for compressor/clutch (relay output CR = 1)
Hi command switches ON continual signal for boost pump (relay output BPR = 1)
With both commands red or blue icons on the right side of display are switched ON. These icons
indicate heating system (boost pump) or cooling (compressor) operation.
By Lt parameter (Lt=02) Manual mode can be enabled with limited duration for 5 minutes. The function
is the same as in above described Manual mode but after 5 minutes:
o Hi command switches back to HS value and thereafter driver panel operates HVAC system
automatically
o Lo command switches back to LS value and thereafter driver panel operates HVAC system
automatically
Here the described Manual mode is conditioned with a normal operation - Auto mode. By pressing of
Mode select key and selection of Ventilation or Heat or A/C mode the Manual mode is non-functional
(the Lo/Hi command can stay on display but blue/red icon will switch down).
NOTE: Direct heating command in manual mode is applicable only for HVAC units in 1004 version
(cooling/heating), in version 1000 (cooling) is used ventilation function only.
33
10.4.4. Setup/Calibration/Test mode
For access to Setup/Calibration/Test mode the driver panel needs to be in normal operation. Press
and hold the Temperature DOWN key and the Temperature UP key simultaneously for 3 seconds till
text (Function 1) "t-1" will be displayed.
In Setup/Calibration/Test mode the buttons on the panel uses different function - see following table.
ESCAPE key
ClimaAIRE ID functions
Press the UP or DOWN key repeatedly to scroll
through the function menu. In the
Test/Setup/Calibration mode the operator can
use functions listed in following table.
In main menu of Setup/Calibration/Test mode
the operator can switch the control system OFF
on every time by pressing of the ON/OFF key.
No changes will be applied.
When any function is selected and any value is
changed by DOWN key or UP key, in the same
moment is the change saved to memory.
The driver panel Setup/Calibration/Test mode
always waits for switching OFF (soft restart) -
the Setup/Calibration/Test mode must be
finished by pressing ON/OFF key. Next start
(soft restart) returns the system to the normal
operating mode immediately.
NOTE: In Setup/Calibration/Test mode the
HVAC unit is out of operation.
BEA688
34
Nr. Symbol Function
1 t1 Test mode 1 - basic test of HVAC unit
2 rt Relay test
3 Pr Set up of program number and reading of firmware version
4 CA Calibration of temperature sensors
5 SE Set Up of controller
6 AL Reading and clearing of alarms
7 Hr Reading of hourmeter
1. Cooling/Heating control
Press "Mode key" to change heating and cooling outputs. The following table is
used to verify of all relay outputs and function of heating and cooling
Ventilation
Heating BP, MCV CR Red - ON
Press "Blower speed key" to change evaporator blower speed. The following table
is used to verify of all relay outputs and functions of evaporator blowers.
Symbol Relay / output ON Relay / output OFF
LOW speed EFL EFH, EFM
MEDIUM speed EFL, EFM EFH
HIGH speed EFL, EFM, EFH -
Auto - EFL, EFM, EFH
35
3. Fresh Air control
Press "Fresh Air key" to change position of fresh air dampers and the following
table is used to verify of all relay outputs and functions of fresh air dampers.
Symbol Relay / output ON Relay / output OFF
Re-circulation - DM
Fresh air damper 50% open DM pulsing -
Fresh air damper 100% open DM -
After test press ESCAPE key to continue with another function or press ON/OFF key.
36
CAID - Function 4: Calibration (CA)
The controller is checked at factory but after HVAC unit installation the calibration mode should be
used to verify and adjust temperature sensors functionality in the field.
NOTE: Calibration is not a repair for defect sensors or bad connections.
In Setup/Calibration/Test mode select "CA" function with UP or DOWN key and press ENTER key. On
the display is shown name of parameter to calibration.
Press ENTER again to see its current value.
To leave the parameter unchanged press ESCAPE key.
To change the value press DOWN key or UP key as required.
Each press of UP or DOWN key is representing value change about 0.2 degree (0.2 °C). Example:
for increasing of current value for one degree up (+1 °C) press UP key five times.
Because the two digit display don't allow to shows decimal numbers every press of UP or DOWN
key isn't noticeable. However on the right side of display is small orange dot, if this dot is visible
the current value is higher about half degree or more than displayed value (e.g. if the value was 11
degree and the UP key was pressed three times the dot will appears, the value is now between
11.5 and 12 degree).
If the UP or DOWN key is pressed and hold than the value is changing quickly (repeatedly) until
the key is released.
The calibration range/correction for temperature sensors is from -1 °C to +26 °C.
Press ESCAPE to save new value and continue to next parameter.
If ON/OFF key is pressed now a new value is also saved and the system will restart (soft restart).
With UP or DOWN key select next parameter to continue in calibration.
After calibration press ESCAPE key to return to Function menu or press ON/OFF key to switch OFF
(soft restart) the system.
37
BEA689
38
Press MODE key to save and continue with another parameter or press ON/OFF key to switch OFF the
system. At the end always press ON/OFF key to save all changes and switch OFF (soft restart) the
system.
BEA690
39
Par. Preset Unit Min. value Name Description
value Max. value
Ab 07 °C 0 °C For compressor protection only. If ambient temp.
Ambient switch
is below this parameter the compressor (clutch)
15 °C point
will not start
Fr -3 °C -5 °C Evaporator Freeze protection of evaporator. If temperature
+5 °C antifreeze switch on evaporator coil (CTS) is lower than this
point parameter the compressor will be switched OFF.
NOTE: It is not recommended to change this
parameter.
rh 01 - - Reheat mode 00 - reheat mode disabled – economy auto mode
01 - reheat mode enabled
02 - DELTA T is enabled, reheat is disabled
03 - DELTA T is enabled, reheat is ensabled
dt 07 °C 1 °C Delta T Offset for control of return air temperature.
15 °C Set point SPc = Ambient temperature ATS minus
Delta T value.
If the result is less then 22, then SPc = 22 °C
The lowest possible SPc is the setpoint selected
Ao 00 - - Automatic On 00 = controller will operate the unit in the same
mode as when power was switched OFF
01 = controller will start the unit every time power
is switched on
LS 17 °C 15 °C Low set point Minimum value of set point.
30 °C
HS 27 °C 15 °C High set point Maximum value of set point.
30 °C
00 = Setpoint shown on display
Default value on the 01 = Return air temperature shown on display
rt 00 - -
display 02 = Blind display - setpoint value shown for
3 seconds after any change
Old ClimaAIRE I 00 = CAID as original
0C 00 - -
replacement 01 = CAID as replacement of ClimaAIRE I
°C = Temperature on the display in °C
un °C - - Celsius/Fahrenheit
°F = Temperature on the display in °F
EL 45 % 0% Low speed of Low value/frequency for PWM output *
100 % blower
En 66 % 0% Medium speed of Medium value/frequency for PWM output *
100 % blower
Eh 100 % 0% High speed of High value/frequency for PWM output *
100 % blower
00 - Automatic mode - no possibility to set Lo
Lt 00 - -
Limited temperature and Hi setpoint on display
setpoint 01 - Manual mode, Lo/Hi setpoint available
02 - Manual mode limited for 5 minutes only
EC 00 - - Economic cool 00 = Standard cool mode - default value
mode 01 = Economic cool mode
HO 0 °C 0 °C Setpoint for HEAT mode will be increased by
Heat offset
5 °C offset compare to COOL and REHEAT mode
Lc 00 - - Lock function 00 - no lock (default value)
01 - blower speed key and fresh air select key are
locked (have no function in operation)
02 - mode select key, blower speed key and fresh
air select key are locked
03 - all buttons except ON/OFF key are locked
* PWM output is used on the systems with blower speed controllers or brushless motors
40
CAID - Function 6: Reading and clearing of Alarms (AL)
In Setup/Calibration/Test mode select "AL" function with UP or DOWN key and press ENTER key. All
alarm codes will be displayed for 2 seconds and at the end will be displayed "dE".
For list of alarm codes see "Figure 21: CAID List of alarm codes"
If no alarm is stored (e.g. previously alarms were cleared) the "no" label will be displayed for 1
second and no more action will be executed.
NOTE: If necessary to keep the alarm codes in memory readable by this way, press ON/OFF key, the
driver panel will be switched OFF and the alarms remains recorded.
Press the ENTER key to clear all alarms. On the display appears "00" for a short time and then
the system returns to Function menu, on the display will show "AL".
NOTE: Alarms cleared through driver panel remain in internal memory - in history - and can be
read through connected PC with Service software.
At the end always press ON/OFF key to switch OFF (soft restart) the system.
41
CAID - Function 7: Reading of hourmeter (Hr)
In Setup/Calibration/Test mode with UP or DOWN key select "Hr" function and press ENTER key.
The symbols and each value will be automatically displayed in following scheme and at the end will be
again displayed "Hr".
NOTE: Detailed hourmeter (with minute resolution) is available via PC connection and Service
software.
The whole procedure can be repeated by pressing ENTER key again. With UP or DOWN key select
next function or press ON/OFF key to switch OFF the system.
42
10.4.5. ClimaAIRE ID Diagnostic System
After start the driver panel is in normal operating mode. In the normal operating mode is running the
built-in diagnostic system.
The ClimaAIRE I D driver panel uses dual alarm system with two levels of signals:
WARNING (yellow alarm symbol)
ALARM (red alarm symbol)
When any red alarm (ALARM) appears the alarm code will be blinking on the display until some button
is pushed. If any yellow alarm (WARNING) appears the alarm code will be blinking on the display
for 5 sec.
The alarm codes are stored in the memory to identify possible fault conditions. Up to 40 alarms codes
can be stored. The records can be displayed on the driver panel with the procedure described above. The
complete history can be read by the PC only.
Alarms description
The WARNING (yellow alarm) symbol will be ON in the case of:
Low value of any temperature sensor:
o temperature sensor defect
o short circuit of the harness to sensors
o temperature is lower than -35 °C (-31 °F) – resistance of the sensor or of the total circuit
is lower than 1,25 kOhm
High value of any temperature sensor:
o temperature sensor defect
o open circuit of the harness to sensors
o temperature is higher than 75 °C (167 °F) – resistance of the sensor or of the total circuit
is higher than 2,9 kOhm
With yellow alarm conditions the unit will continue in operation with the wrong data from the sensor.
The ALARM (red alarm) symbol will be ON or blinking in the case of:
HPCO or LPCO switch is open longer than 10 minutes (alarm code 6)
HPCO or LPCO switch is cycling - switched OFF 5 times per 10 minutes (alarm code 5)
Inverter alarm (alarm code 31 - 37, special program for electric bus units only)
Any red alarm will switch the unit to the VENTILATION mode with automatic blower speed. The
driver can change the blower speed manually. The compressor and condenser fans are stopped.
The alarm symbols can be removed by restart of control system (use the ON/OFF key to switch OFF,
wait for 2 seconds, switch ON). After restart - if the reason for alarm is still in existence - the alarm
symbol can appears again. If the alarm comes up again, don't restart the unit more times. In that case
immediately contact the service department or Thermo King representative.
For detail list and description of alarms refer to ClimaAIRE ID Service Manual (TK 60020-3-MM).
43
Alarm Code Name Symbol Description
01-04 not used -
HPCO or LPCO switch is switched off
05 Clutch cycling RED
5 times per 10 minutes
HPCO or LPCO switch is switched off
06 Long delay of HPCO or LPCO RED
longer than 10 minutes
07 RTS Low YELLOW RTS: Return Air Temperature
CTS: Evaporator Coil Temperature
08 RTS High YELLOW ATS: Ambient (Fresh) Air Temperature
09 CTS Low YELLOW
Low = short circuit or temperature is
10 CTS High YELLOW lower than -35 °C
(the limit value is -35 °C)
11 ATS Low YELLOW
12 ATS High YELLOW High = open circuit (disconnected
sensor) or temperature is higher than
13 - 30 not used - 75 °C (the limit value is 75 °C)
31 - 37 Inverter Alarms RED for SR10E only
Freeze Protection
Temperature of evaporator coil is measured by sensor (CTS). If this temperature is lower than value in
parameter Fr for more than 30 seconds - that can be dangerous for freezing - the compressor output
signal (CR) is switched OFF (see also "Figure 19: CAID Controller " on page 40). Compressor (and
condenser fan also) can return to operation if temperature of evaporator coil rises approx. 5 °C above
Fr parameter for more than 1 minute.
Compressor Protection
Compressor output (CR) can be switch ON (compressor can start) only if ambient temperature (ATS) is
higher than value of parameter Ab (see "Figure 19: CAID Controller " on page 40).
BEA691
For detail specification of CAID inputs/outputs refer to ClimaAIRE ID Service Manual (TK 60020-3-MM).
44
Operating range
Input Pin Description Note
(min - max)
Ambient temperature -35 °C +75 °C
ATS P1-09
sensor -31 °F 167 °F
Return air temperature -35 °C +75 °C
RTS P1-10
sensor -31 °F 167 °F
-35 °C +75 °C
CTS P1-11 Coil temperature sensor
-31 °F 167 °F
Pressure sensor/switch
31B P1-12 digital, high side input
(LPCO, HPCO)
Supply
P1-13 Supply ground 0 VDC 5 VDC
ground
Power
P1-14 Power supply 10 VDC 35 VDC max. 100 mA
supply
Figure 23: CAID List of inputs
NOTE: For temperature inputs must be used sensors TK 41-4157, TK 41-4335 or TK 41-8780 only.
EFRH P1-01 Blower speed (high) control 0/1 relay, low side output
EFRM P1-02 Blower speed (medium) control 0/1 relay, low side output
EFRL P1-06 Blower speed (low) control 0/1 relay, low side output
NOTE: Each output can be set as low side or high side output by the firmware. Outputs MCV and
DM - in configuration of replacement of ClimaAIRE I – low side outputs
The driver panel (controller) is equipped with communication connector and can be connected to
portable PC for testing and monitoring (use ClimaAIRE Computer Adapter Kit TK 204-1063).
For more information see ClimaAIRE ID Service Manual (TK 60020-3-MM).
45
10.5. Inspection Recommendations
To keep the correct functions of the A/C unit you must periodically execute the following maintenance
procedures. The schedules should be used during the initial service periods (at least during warranty
period).
WARNING: When inspecting or servicing the A/C system, follow all safety rules and
operating procedures, otherwise physical harm could result.
Thermo King reserves the right to deny warranty coverage on claims due to lack of maintenance or
neglect. Claims in question must be supported by maintenance records.
If you are not really experienced in following actions please call for help Thermo King Service Center
otherwise is here risk of damage or complications. In case of any question or unclear situation please
contact your supplier or directly Thermo King manufacturer.
All maintenance intervals are based on normal operating conditions. Unusual or extraordinary
conditions require more frequent service intervals. For example, high air pollution could require more
frequent replacement of air filters. Coordinate the maintenance inspection schedule with the Bus
Preventive Maintenance Schedule.
Wintertime Operation
The A/C system is operating in wintertime with heating and fresh air functions, periodical
maintenance also in off season is necessary to maintain the functions of the A/C system. Prior
to operating the compressor during winter months, you must warm up the coach interior to
normal operating temperature (15 to 21°C [60 to 76°F]). Unless this precaution is taken, liquid
refrigerant might be forced into the compressor, causing severe damage.
WARNING: Covers must be completely removed from the unit to access interior of
unit. Insure you are using best practice for working at height paying special attention
during removal of cover as it could move due to the influence of the wind.
46
10.6. Maintenance Inspection Schedule
10.6.1. Intervals
The following intervals are just a recommendation. The periods may vary - this depends on ambient
conditions, pollution or local transportation laws. Please use common sense then judging replacement of
filters and cleanliness based on first four months of service.
If you need any help please contact Thermo King Representative or Service.
10.6.3. Compressor
47
10.6.4. Electrical and Control System
Semi-annually Check condenser fan motor speed, voltage and amperes (all
motors).
48
10.7. Special Tools, Equipments and Supplies
For maintenance and repairs use basic hand tools in size and type corresponding to intended task.
For replacement parts (air filters, filter-drier etc.) please refer to Parts Manual (see the Thermo King
publication number on page 3).
On some tasks can be necessary to use a special tools or equipments listed in following figure or in a
chapter 11.1 on page 53.
NOTE: Types and suppliers of suitable tools can vary from country to country, usually more products
are available in open market. In any doubt about suitable tool please contact your local Thermo King
dealer or directly Thermo King Representative.
Refrigerant gauge manifold set Reads system pressures and allows for correct
1.
system servicing.
Quick disconnect access valves Keep pressure in gauge lines when gauge
2.
manifold is removed from compressor.
2-Stage vacuum pump (greatly See chapter 11.1 on page 53.
3.
reduces evacuation time)
4. Portable Reclaim Unit See chapter 11.1 on page 53.
Electronic micron gauge Must have vacuum level readings from 25,000 to
5.
50 microns.
6. Electronic Leak Detector Use an electronic halogen leak detector or soap
solution.
WARNING: Do not use a Halide torch to
detect leaks. When a flame comes in contact
with refrigerant, toxic gases are produced that
might cause suffocation.
49
10.8. Tightening Torque Requirements
Step 1: Locate both groups for bolt and nut in following table:
Strength
Group Fastener Material Finish Marking
Class
A Head bolt, machinery type Steel Zn Pl 5.8 5.8
B Head bolt, machinery type Steel Zn Pl 5.8 8.8
C Head bolt, machinery type Steel Zn Pl 10.9 10.9
D Head bolt, machinery type Steel Blk Ox Wx 12.9 12.9
E Head bolt, machinery type St. Steel Passiv
B Nut, Regular Steel Zn Pl 8
C Nut, Regular Steel Zn Pl 10
GRA2-
- Nut, Regular St. Steel Passiv None
CL70
- Nut, Prev Torq Lock Steel Zn Pl ISO-2320 None
A Head bolt, machinery type Steel Zn Pl 5.8 5.8
50
Step 3: Adjust both numbers for special conditions:
Condition Adjustment
Fine Threads +10%
-50%
Thin or Jam Nut
(do not add to Schedule E - see Note 3)
Anti-Seize Lubricant -20%
Unplated Carbon Steel +10%
Step 4: Choose the lower value of the nut and bolt values.
IMPORTANT:
Every time when you will tighten stainless steel screws or nuts use anti-seize thread lubricant.
51
11.Refrigeration System Maintenance
Some these service procedures on the refrigeration system can be regulated by Federal, State or Local
laws. Please check the situation and coordinate all the actions with this regulations and Health&Safety
rules.
All regulated refrigeration service procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State and Local laws.
WARNING: Make sure the unit and bus cannot start while servicing the system.
WARNING: Covers must be completely removed from the unit to access interior of
unit. Insure you are using best practice for working at height paying special attention
during removal of cover as it could move due to the influence of the wind.
IMPORTANT:
When charging the refrigeration system, always charge from liquid side and use the refrigerant in a
liquid state. Don't charge vapor in the system!
Thermo King recommend always to replace the whole (remaining) refrigerant and recycle the
retrieved portion properly per governing laws. Then use new refrigeration charge by correct
recommended weight in liquid state. In case of leak do not “top off” the refrigeration system.
General information
If refrigerant has leaked or been removed from the system, check entire system for possible component
damage and compressor oil loss.
If any system leak or damage was found, repair the system, recheck the system after repair and conduct
system evacuation.
If the system has some remaining pressure (some refrigerant is present in the system), and the leak is
NOT found, using a leak detector is recommended. Soap and bubbles is the best tool to check minute
leaks that the electronic leak detectors cannot find.
52
If the leak is already found and the system is almost flat (empty), we recommend evacuating the system
AFTER the repair is done (for example after tightening a fitting).
After any repair we recommend to execute the Leak Test to be sure that system is tight.
As the oil used in scroll compressor is very viscous, rarely an oil charge would be lost. If this happens,
the compressor would have failed already and it that case we recommend replacing the compressor (or
two compressors in sets of 2, depending on unit design), charging the proper oil charge for new
compressor(s) and do the evacuation and charging procedures described further. After compressor
replacement recheck the system again.
It is generally good practice to replace the filter-drier whenever the system is opened and exposed to
ambient for an extended period of time. Refer to the Refrigeration Manual (Thermo King Manual TK
50951) for system cleanup after a compressor failure or repair or replacement of basic components.
IF THERE IS A SUSPICION OF BIG LEAK, IT IS RECOMMENDED THE WHOLE CHARGE IS
RETRIEVED (REMOVED) AND A NEW CHARGE IS PLACED INTO THE SYSTEM AFTER
PERFORMING THE EVACUATION AND CLEANUP STEPS - SEE IMPORTANT NOTE ABOVE.
In the following text are procedures usually described by using of Thermo King evacuation station.
Always follow the safety instructions, procedures and working instructions in specific equipment
manufacturer’s documentation.
CAUTION: When servicing Thermo King R-134a refrigeration systems, use only
service tools (i.e., vacuum pump, refrigerant recovery equipment, gauge hoses, and
gauge manifold set) certified for and dedicated to R-134a refrigerant and Polyol Ester
based compressor oils. Residual non-HFC refrigerants or non-Ester based oils will
contaminate HFC systems.
Leak Detectors
Detect leaks with soap bubbles and with Halogen leak detector such us model H10G (TK 204-712) or
portable model H10N (TK 204-756) Or certified 407C leak detector from respectable suppliers.
Evacuation Station
A key element in maintaining high efficiency and low maintenance cost in a transport refrigeration
system is the ability to keep the system free of moisture a non condensable materials. Contaminants and
moisture are best removed by a vacuum system. The Thermo King Evacuation Station TK 204-725 has
been designed to efficiently evacuate the refrigeration system for all Thermo King products.
53
Vacuum Pump
Use a two-stage (for example TK 204-713 or TK 204-699), three-stage, or five-stage pump for
evacuation. Because residual refrigerant may be present in used vacuum pumps, a new pump should be
used and dedicated strictly as an R-134a refrigerant pump. Use only recommended vacuum pump oils
and change oil after every major evacuation. Because vacuum pump oils are highly refined to obtain
low vacuums, failure to follow these recommendations may result in acidic conditions that will destroy
the pump.
Refrigerant Recovery
Use only refrigerant recovery equipment approved for and dedicated to R-134a recovery.
11.2. Contamination
When contaminants have entered the system, a thorough cleanup is required to prevent damage or loss
of compressor. The purpose of evacuation is to remove moisture and air from the refrigeration system.
Even small quantities of air or moisture in a system can cause severe problems.
The presence of moisture, oxygen, and heat under certain conditions can result in many forms of
drainage. Corrosion, sludge, copper plating, oil breakdown, carbon formation, and eventual compressor
failure can be caused by these contaminants. Things that will contaminate a system are (in order of
importance):
Air (oxygen as a contaminant). Oxygen in the air reacts with the oil. The oil begins to break
down and can eventually lead to carbonization in the compressor and acid buildup. The longer
this breakdown process goes on, the darker the compressor oil becomes until finally the color is
black, indicating major system contamination.
Moisture in a system will cause metal corrosion and plating. It can freeze in the expansion valve
and cause intermittent operational problems. It reacts in the oil to begin acid buildup.
Dirt, dust, metal particles, other foreign materials. Particles in the system will cause severe
damage to all close tolerance items. Don't leave a system open to the infiltration of dirt. If you
must open a system for any reason, seal off the open areas as soon as possible. Don't work in a
dirty environment.
Acid. Air and moisture cause a chemical breakdown of the oil and the refrigerant. The acid will
accelerate the deterioration of the softer metals (i.e., copper) and cause metal plating as the
softer material begins to cover the inside of the system. This condition can result in the total
destruction of your equipment.
IF ANY OF THE ABOVE CONDITIONS ARE PRESENT PLEASE RECYCLE THE REFRIGERANT,
PERFORM A REFRIGERATION SYSTEM CLEANUP - USE A NEW REFRIGERANT THAT HAS NOT
BEEN CONTAMINATED.
54
11.3. Compressor Oil Color Code
When unusual color of oil is detected or presence of moisture is signalized by moisture indicator then
perform a compressor oil acid test.
Black oil indicates carbonization caused by air in the system.
Brown oil indicates copper plating caused by moisture in the system.
Gray or metallic oil indicates bearing wear or piston scoring.
IF THE COMPRESSOR OIL SHOWS AN ACID CONDITION, CHANGE THE OIL, THE IN-LINE
OIL FILTER, THE FILTER-DRIER AND PERFORM A REFRIGERATION SYSTEM CLEANUP.
CAUTION: Use only refrigerant recovery equipment approved for and dedicated to
R-134a recovery.
It is recommended the whole charge is retrieved and a new charge is placed into the system after
performing the leak and evacuation steps.
When removing refrigerant from a Thermo King refrigeration system, use a recovery process that
prevents or absolutely minimizes the refrigerant that can escape to the atmosphere. Typical service
procedures that require removal of refrigerant from the system include:
Reducing the refrigerant pressure to a safe working level when maintenance must be performed
on high-pressure side components.
Emptying the system of refrigerant when an unknown amount of charge is in the system and a
proper charge is required.
Emptying the system of contaminated refrigerant when the system has become contaminated.
Procedure
1. Locate the service (access) ports on high pressure side (compressor output pipe) and low pressure
side (compressor input line). Carefully remove the caps from ports. If no service (access) ports are
present then fittings under low (LPCO) or high (HPCO) pressure switches can be used.
2. Install a gauge manifold low pressure line to the service (access) ports on low pressure side
(compressor input pipe). Attach the gauge manifold high pressure line to the service (access) ports
on high pressure side (discharge line - compressor output pipe). Attach the service line to the
recovery station. Purge the lines.
Vapor Recovery
1. Install a gauge manifold on the system. Attach the service line to the recovery machine and purge
the lines. Set the recovery machine for vapor recovery.
2. Keep the system OFF and partially open (mid-seat) the discharge line service valve.
3. Turn on the recovery machine and open (back seat) both gauge manifold and hand valves.
4. Continue to operate the recovery machine until system pressures drop to 0 kPa (0 bar, 0 psig)
pressure. Follow the liquid recovery instruction in next section.
55
Liquid Recovery
1. Switch ON and operate the system to build discharge pressures to approximately 1380 kPa (13.80
bar, 200 psig).
2. Stop the refrigeration system. Set the recovery station for liquid recovery and turn the station on.
3. Open (back seat) the manifold gauge high pressure hand valve.
4. Operate the recovery machine until the system pressures reach approx. 0 kPa (0 bar, 0 psig).
5. Close the manifold gauge valves, stop the recovery station and disconnect the lines.
Procedure
1. Locate the service (access) ports on high pressure side (compressor output pipe) and low pressure
side (compressor input line). Carefully remove the caps from ports. If no service (access) ports are
present then fittings under low (LPCO) or high (HPCO) pressure switches can be used.
2. Attach gauge manifold compound gauge line to the port on low pressure side (near low pressure
cutout switch, LPCO). Attach high pressure gauge line to the port on high pressure side (near high
pressure cutout switch, HPCO).
3. Attach a refrigerant bottle charging hose to center of manifold gauge set. Purge charging hose of
air.
4. Connect the charging hose to a source of nitrogen - see chapter „Using Pressurized Nitrogen“
below, carefully follow the safety precautions!
CAUTION: Nitrogen (N2) is under 15,170 kPa (151.70 bar) pressure in a full
cylinder at 21°C. Do not use oxygen, acetylene, or any other type of pressurized gas in
the system.
56
5. Pressurize the system with neutral Nitrogen (gas) until 345 kPa (3.45 bar) vapor pressure is
achieved.
6. Close both hand valves on manifold gauge (front seated).
7. Close the supply valve on the nitrogen bottle.
8. Disconnect the refrigerant charging hose.
9. Check the system with an electronic leak detector to inspect all joints and connections. (Use soap
solution as an alternative test component.)
10. Release pressure and reclaim nitrogen back from system.
11.6. Evacuation
Before performing an evacuation be sure you have conducted the leak check and the system is repaired
and no leaks are found.
CAUTION: Do not evacuate a system until you are certain that the system is leak
free. A system with less than a full charge of refrigerant should be thoroughly leak
tested. Leaks found must be repaired.
1. Recover refrigerant from the system - see Chapter „Refrigerant Recovery“ and reduce the system
pressure to the proper level (US Federal Law requires a -17 to -34 kPa [-0.17 to -0.34 bar, 5 to 10
in. Hg] vacuum that is dependent upon the recovery equipment used).
2. Break vacuum with refrigerant and equalize system pressure to 0 kPa (0 bar, 0 psig). Replace the
liquid line filter-drier (dehydrator) in refrigeration system.
3. Confirm that the evacuation station functions properly and determine “Blank Off” Pressure. The
Blank Off Pressure of the Vacuum Pump is the deepest vacuum that the vacuum pump an attain
when isolated from the rest of the system. If a vacuum pump (isolated from a system) is started and
the micron meter responds quickly by going to a deep vacuum, the operator can be confident that
the pump and oil are in good condition. If the vacuum pump fails to reach a deep vacuum within 5
minutes, the operator should suspect the condition of the oil or the pump. It is recommended that
the pump oil be changed first to see if the rate of reaching a deep vacuum is improved.
4. Connect the evacuation station and refrigerant tank with manifold gauge set (optional) to the
system as indicated in example on the diagram on Figure 29 on page 58. Connect evacuation hoses
to the fittings (service access ports) installed on the suction line and liquid line - see high pressure
side (compressor output pipe) and low pressure side (discharge line - compressor output pipe). If
no service (access) ports are present then fittings under low (LPCO) or high (HPCO) pressure
switches can be used.
5. Open evacuation station valves (V1, V3 and V4). It is only necessary to open valve V2 when a
reading on the Micron Meter is desired. This is especially true when starting to evacuate a system
and large amounts of moisture and oil will be passing by the sensor.
6. Open the vacuum pump „Iso Valve“ built into the pump housing below the handle. It is
recommended that the valve be kept open at all times.
7. If connecting a refrigerant tank and gauge manifold to the evacuation station, close the manifold
gauge and refrigerant tank valves to prevent refrigerant from being drawn from the tank.
57
1
V4
V3
V2
2
V1
3
4
6
5 7
8 BEA700
System Evacuation
1. Turn on the vacuum pump. Open the gas ballast valve located on top of the pump housing behind
the handle (the valve is fully open at two turns counterclockwise). Evacuate the system to 500
microns to achieve a final equilibrium pressure of 2000 microns or less. The final equilibrium
pressure is determined with the Thermo King Evacuation Station using the following procedure
(called a pressure-rise test):
a. Evacuate the system using the evacuation station until the vacuum level reaches 1000 microns.
Then close the gas ballast valve.
b. Continue evacuation to 500 microns or until vacuum stabilizes at its lowest level. Contamination
may delay reaching the lowest level for a period of several or more hours.
c. Close valve to isolate the vacuum pump from the system.
d. Observe the vacuum level on the micron meter. When the meter has stabilized, the value indica-
ted on the micron meter is the equilibrium pressure. This reading must be 2000 microns or less.
NOTE: The presence of refrigerant in the compressor oil may prevent a low vacuum reading from
being achieved. Compressor oil can continue to outages for long periods of time.
58
2. If the vacuum level appears to stall above 500 microns, back seat the discharge service valve and
observe the micron meter.
3. Close valve V1 when the desired vacuum level has been reached.
4. Wait five minutes then read the micron meter.
5. If the vacuum level remained below 2000 microns for five minutes, the system is ready to charge.
a. A system that is leak free and dry will remain below 2000 microns for five minutes.
b. A system that rises above 2000 microns but stabilizes below atmospheric pressure is probably
contaminated with moisture or has refrigerant outgassing from the compressor oil. Additional
evacuation is required.
c. A drop in pressure indicates that the compressor oil is out-gassing and further evacuation is
necessary.
d. An increase in pressure indicates that a leak exists or there is moisture in the system. Perform a
“Pressure Rise Test” and evaluate.
e. A system that continues to rise without stabilizing has a leak and must be repaired.
Figure 28: Constant Pressure Rise After Evacuation Indicates System Leak
59
Moisture
When the pressure rise and then stabilizes at a level below atmospheric pressure, this indicates
that the system is vacuum tight, but is still wet and requires additional dehydration and
evacuation time.
4
2
Figure 29: Pressure Rise that Levels Off After Evacuation Indicates Moisture in System
WARNING: Do not use a torch or other concentrated heat source to heat the
compressor or other refrigeration system component.
60
11.7. System Charging from an Evacuated Condition
IMPORTANT:
When charging the system, always charge from liquid side and use the refrigerant in a liquid
state. Do not charge vapor in the system!
In case of leak do not “top off” the refrigeration system. Always reclaim all remaining charge
(and send it to special recycling stores) and use new refrigeration charge by correct
recommended weight in liquid state.
1. Connect the charging hose to the port on high pressure side (on liquid line, near high pressure
cutout switch, HPCO). if no service (access) port is present then fitting under high (HPCO)
pressure switch can be used.
2. Charge the proper amount of liquid refrigerant into system, for example by using a „push/pull“
reclaim unit. For amount of the R-134a refrigerant see “Specifications”.
3. Close the refrigerant tank valve when the correct amount (by weight) of refrigerant has been added.
4. Remove charging hose and reinstall caps on service (access) ports (or high pressure cutout HPCO
valve if necessary). Check this connecting points with an electronic leak detector.
5. Perform a system functional check out.
WARNING: Nitrogen (N2) is under 15,170 kPa (151.70 bar, 2200 psig) or greater
pressure. Pressure is for full cylinder at 21 C (70 F). Do not use Oxygen (02),
acetylene, or any other pressurized gas on refrigeration systems or any component of a
system.
Safety Precautions
Observe the proper handling of cylinders:
Keep protective cap on cylinder when not in use.
Secure cylinder in proper storage area or fastened to cart.
Do not expose to excessive heat or direct sun light.
Do not drop, dent, or damage cylinder.
Use a pressure regulator and a safety pressure relief valve as part of the pressure testing
equipment. The safety pressure relief valve should be the non- adjustable, non-tempering type.
The valve should bypass any time the pressure exceeds its setting.
Open valve slowly. Use regulators and safety valves that are in good working order.
The regulator should have two gauges: one to read tank pressure, the other to read line pressure.
Properly maintained equipment will allow leak testing, purging, and dehydration to be done
safely.
61
1 Line Pressure
2 Tank Pressure
3 Tank
4 Pressure Test Line to System
5 Safety Valve
6 Pressure Regulator
Figure 30: Typical pressurized gas bottle with pressure regulator and gauges
With dry nitrogen (N2), you can dehydrate, pressure test, purge, and solder refrigeration systems.
Always use the correct equipment in the correct way to ensure safety.
WARNING: Improper use of high pressure cylinders can cause physical damage to
components, personal injury, and cause stress that leads to failure of components.
Procedure
1. Attach a gauge manifold. Close both hand valves on the gauge manifold (front seated).
2. Connect charging hose to nitrogen source. Adjust pressure regulator to the proper pressure for the
required procedure.
3. Purge system high side to low side. The following procedures should use the following maximum
gas pressures:
Leak Testing: 1034 to 1200 kPa
Purging/Dehydration: 69 to 138 kPa
Soldering: 35 kPa
62
12.Refrigeration/Heating Repairs
WARNING: Make sure the unit and bus cannot start while servicing the system.
WARNING: Before any repair the side covers must be completely removed from the
unit to access interior of unit. Insure you are using best practice for working at height
paying special attention during removal of cover as it could move due to the influence
of the wind.
8
2
BEA723
4 5 6
Installation
1. Clean connection fittings.
2. Remove the protective plugs from the new filter-drier, install new O-rings (supplied with new
filter-drier), and apply to the threads appropriate amount of oil of the same type used in the
63
compressor to the O-rings and threads.
3. Install the new filter-drier as quickly as possible and observe the following considerations:
Observe the “IN” designation printed on the inlet side of the filter-drier. To prevent improper
installation of the filter-drier, ensure the arrow on the filter-drier points in the direction of
refrigerant flow.
Hold the filter-drier with a backup wrench to keep from twisting the tubes when tightening or
removing the nuts.
The longer the filter-drier remains open to air, the more moisture it will absorb.
4. Fix the filter drier with clamp.
5. Evacuate the filter-drier section - filter-drier and tubing between the two service valves:
Hook the evacuation equipment hoses to the service ports on the filter-drier inlet valve and
outlet valve.
Evacuate the filter-drier section (for more information refer to chapter 11).
6. Leak test all fittings, secure the valve packing, to prevent leakage of refrigerant.
7. Switch ON A/C system and test the functionality.
8. Close covers and fix cover with fixing bolts.
BEA724
Figure 32: Thermostatic expansion valve installation (example)
64
Usually two services are performed on the expansion valve:
1. Replacing a damaged power element. A broken power element causes the valve to close and the
unit to operate in a vacuum.
2. Cleaning and securing the power element sensor bulb to the suction line. Poor contact of the sensor
bulb causes the valve to operate by air temperature, indicated by frosting of the suction line and a
slight rise in suction pressure to flooding of the coil. Wrap the bulb and suction line with insulating
tape, TK Part No. 203-428.
C
4
5
B
1
6 BEA427
Figure 33: Example of solder type valve and sensor bulb position
65
Superheat: Measurement and Adjustment
NOTE: Be sure the temperature reading instrument and compound pressure gauge are calibrated.
Measurement
1. Install a pressure gauge in the expansion valve external equalizer line. This will indicate the
pressure.
2. Run the unit. Allow the system to run until the interior of the bus has cooled to within 5 degrees of
thermostat set point.
3. Subtract the temperature reading obtained from the suction line near the expansion valve sensor
bulb on the unit suction line to obtain the expansion valve superheat setting. Using the Pressure-
Temperature Chart in this manual, convert the pressure measured at the equalizer line to the
equivalent temperature.
Example:
Sensor Bulb Suction Line Temperature (°C/F)
-Suction Pressure Temperature Conversion (°C/F)
=Superheat (K)
NOTE: To properly check the superheat, you must have a stable condition. To establish a stable
operating condition, run the unit at least 15 minutes so the evaporator air inlet temperature reaches
21 °C to 27 °C (70 °F to 80 °F). Read the pressure and temperature difference simultaneously.
Temperature difference should be 5.5 to 8 K.
CAUTION: Thermo King expansion valves are factory preset and do not require
adjustment. Establishing controlled conditions in the field is difficult. Before adjusting
the expansion valve, check the following causes for an out-of-range reading.
Adjustment
1. Remove the cap over the adjusting stem.
2. To reduce superheat, turn the adjusting stem counterclockwise.
3. Make no more than one turn of the stem at one time. Observe the change in superheat closely to
prevent overshooting the desired setting. As much as 30 minutes may be required to obtain the new
balance after the adjustment has been made.
4. Remove the pressure gauge and thermometer from the equalizer line.
5. Return bus to service.
66
Thermostatic Expansion Valve Removal
DANGER: Do not solder on a closed system. Pressure can build up and may cause
an explosion. If soldering is required, use dry nitrogen to purge the system during any
solder operations. Refer to “Using Pressurized Nitrogen”.
Removal
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Locate the expansion valve, release and remove the cover from top or side cover (always remove
the cover to avoid any damage).
3. Recover the refrigerant from the system. See chapter 11 and refer to “Evacuation procedure”.
4. Remove the insulation.
5. Remove the sensor bulb from the clamps, taking care not to kink the capillary tube.
6. Unsolder the equalizer and the inlet and outlet line connections. Remove the expansion valve.
Installation
1. Clean tubing connections before installing the valve.
2. Compare the new valve to the one removed. Adjust the length of the sensor bulb capillary tube.
Secure it to the valve body in the same manner as the original valve. This prevents damage to the
tube by vibration-induced chafing. Once the length is adjusted, feed the bulb through the required
routing.
3. Position the valve in the unit, insert the grommet if necessary and solder the equalizer and the inlet
and outlet lines. Use a heat sink to prevent damage to the valve.
4. Taking care not to kink the capillary tube, position the remote sensor bulb in the clamp on the side
of the suction line in exactly the same spot from which it was removed.
5. Charge the system, once the charging has been completed pressurize the unit and check for leaks.
6. Add insulation where necessary.
7. Switch ON A/C system, start the unit and test the functionality.
67
12.3. Pressure Switches Replacement
The rooftop unit contains three pressure switches - HPCO, CPS, LPCO. These switches are basically
the same design, located in one place, the replacement procedure is very similar.
NOTE: Before starting replacement procedure, use your parts manual to identify the correct spare
pressure switch for your unit.
1 2 3 4
BEA725
5 6 7
Removal
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Release fixing bolts, carefully open and remove side cover.
3. Fix the cover in open position by cover support.
4. Locate the non-functional pressure switch.
5. Check and ensure there is no voltage present, disconnect pressure switch connector, release the
wires, remove fixing binders.
6. Remove the pressure switch.
NOTE: Install the new switch immediately to minimize the amount of air entering the system.
68
Installation
1. Clean connection thread from rests of sealing.
2. Apply threadlocker Loctite(TM) to the threads of the new switch.
3. Install new switch, connect the wires, fix the wires with binders.
4. Pressurize the unit and check for leaks.
5. Switch ON A/C system and test the functionality.
6. Insert and close side cover, fix the cover with fixing bolts.
Removal
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Carefully open and remove both side covers.
3. Release, disconnect and remove both condenser fans, unrivet the condenser cover (remove all
rivets on perimeter and 6 rivets from central part of cover), remove the condenser cover.
4. Recover the refrigerant from the system. See chapter 11 and refer to “Evacuation procedure”.
5. Remove the valve.
NOTE: Install the new switch immediately to minimize the amount of air entering the system
Installation
1. Apply threadlocker Loctite(TM) to the threads of the new sensor.
2. Install and tighten new valve.
3. Evacuate the system (for more information refer to chapter 11 Refrigeration System Maintenance).
4. Charge the system - see chapter 12 on page 61.
5. Once the charging has been completed pressurize the unit and check for leaks.
6. Return the condenser cover in original position, use appropriate rivets to fix the cover, insert and
connect the condenser fans, fix the fans with bolts.
7. Close and fix both side cover with fixing bolts.
8. Switch ON A/C system and test the functionality.
69
13.Electrical Maintenance & Repairs
IMPORTANT: SAFETY FIRST! When servicing or repairing an air conditioning unit, the
possibility of serious or even fatal injury from electrical shock exists. Extreme care must be
used when working with a air conditioning unit. Always respect safety rules, follow “Safety
Precautions”, respect valid local laws and general Health&Safety prescripts.
WARNING: Make sure the unit and bus cannot start while servicing the system.
WARNING: Before any repair the side covers must be completely removed from the
unit to access interior of unit. Insure you are using best practice for working at height
paying special attention during removal of cover as it could move due to the influence
of the wind.
Inspect and maintain electrical parts under “Maintenance Inspection Schedule”.
Preventively spray contacts and terminals with an electrical cleaner. A good grade of cleaner will also
provide waterproofing that can help prevent voltage leaks.
BEA726
6 7 8
70
Procedure - Relays
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Release all fixing bolts on top rear cover, carefully remove the top rear cover.
3. Check and ensure there is no voltage present.
4. Locate the reason of dysfunction, check why the relay was broken. Eliminate the problem first.
5. For more details refer to schematic and wiring diagrams. In case of any question or unclear
situation please contact your supplier or directly Thermo King manufacturer.
6. Pull out damaged relay, install new relay (parameters of new part must correspond to the old one).
7. Return the top rear cover in original position, use appropriate bolts to fix the cover.
8. Switch ON A/C system and test the functionality.
Procedure - Fuses
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Release and open return air grille: use cross-head screwdriver, unscrew all bolts and slowly swing
down the return air grille.
3. Check and ensure there is no voltage present.
4. Locate the reason of dysfunction, check why the fuse was broken. Eliminate the problem first.
5. For more details refer to schematic and wiring diagrams. In case of any question or unclear
situation please contact your supplier or directly Thermo King manufacturer.
6. Pull out damaged part, to remove damaged fuse always use the fuse extractor tool.
BEA435
7. Install new fuse, parameters of new part must correspond to the old one.
8. Install the return air grille with filter, close the grille, carefully fix the grille with fixing bolts.
9. Switch ON A/C system and test the functionality.
Overvoltage Suppressor
To the power supply terminals is connected overvoltage suppressor. If replacement is necessary just
release and remove the bolts from terminal, unscrew the fixing bolts. Take a care of connection of new
suppressor, assure the correct polarity, red wire connects to (+) terminal, blue wire to (-) terminal.
71
13.2. Evaporator Blower Replacement
Removal
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Release all 3 fixing bolts, carefully open and remove side cover.
3. Check and ensure there is no voltage present.
4. Disconnect the connectors of blower wiring from resistor block, tag the connector's position.
5. Remove fixing binder where necessary.
6. Unscrew fixing bolts and release blower holders on both sides of blower.
7. Lift the entire blower assembly from unit. 10 9
1
8
2
5
7
6
BEA727
Installation
1. Insert a new blower into unit, insert blower holders and tighten the fixing bolts.
2. Connect the connector of blower wiring to resistor block (check the tags for the same position), fix
the wires with fixing binder where necessary.
72
3. Switch ON A/C system and test the functionality.
4. Return the side cover into original position, fix cover with fixing bolts.
BEA030
The condenser axial fan is a non-repairable assembly with non-detachable motor. When this motor
malfunctions, the complete fan assembly must be replaced.
Fan Removal
1. Switch OFF the unit/control system.Turn OFF all power supply.
2. Check and ensure there is no voltage present and the fan cannot start.
3. Release 4 fixing bolts on the perimeter of fan, remove the fan from his position and move the fan
on the top of cover.
4. Locate and disconnect fan cable.
73
3. Disconnect the black wire from ground and the motor should stop. If the motor fails this test, it
must be replaced.
BEA677
3
4
Installation
1. Check the electrical parameters on new fan.
2. Set new fan on the top of cover, connect the fan connector, fix the cable with fixing binders. Use
the grommet to safe the fan cable on the cover edge.
3. Insert the fan into operating position, insert the fixing bolts with washers, tighten the bolts.
4. Switch ON A/C system and test the functionality.
74
13.4. Fresh Air Damper Motor Replacement
NOTE: Fresh air damper is optional accessories, not all units are equipped with fresh air
damper motor.
The damper motor (TK 41-2755) is a non-repairable DC motor used for fresh air damper applications in
bus A/C units.
Before damper motor replacement use following tests to determine if the motor is functioning correctly.
AFR73
Figure 40: Damper Connector Plug Wiring Diagram
Rotation Test
1. Apply + 24 Vdc on Pin 6 and ground Pin 4. The actuator shaft should turn counter clockwise.
2. Apply + 24 Vdc on Pin 4 and ground Pin 6. The actuator shaft should turn clockwise.
Ohmmeter Test
1. Place an ohmmeter between pins 1 and 3.
2. The ohmmeter should read 4.7 KOhm ± 20 percent.
3. Place the ohmmeter test leads between pins 1and 2. Apply + 24 Vdc on Pin 6 and ground Pin 4.
The actuator shaft should turn counter clockwise.
4. The ohmmeter should read less than 1 KOhm.
5. Apply + 24 Vdc on Pin 4 and ground Pin 6. The actuator shaft should turn clockwise.
6. The ohmmeter should read greater than 3 KOhm.
NOTE: If actuator fails these tests, it must be replaced.
75
2
AFR74
Installation
1. Insert new or repaired damper motor into original position, insert the fixing bolts with washers,
tight the bolts.
2. Connect the damper motor connector, fix the cable with fixing binders where necessary.
3. Return the top rear cover in original position, use appropriate bolts to fix the cover.
4. Switch ON A/C system and test the functionality.
76
1
3 7
BEA728
4 2 5 6
Installation
1. Pull up the grommet on new sensor wires, the sensor pull through the hole in unit frame.
2. Fix the sensor with binders to the frame, set the grommet to correct position, connect the
connectors.
3. Return the condenser cover in original position, use appropriate rivets to fix the cover, insert and
connect the condenser fans, fix the fans with bolts.
4. Close and fix both side cover with fixing bolts.
5. Switch ON A/C system and test the functionality.
6. Insert and close both side covers, fix the covers with fixing bolts.
77
14.Mechanical Maintenance & Repairs
WARNING: Make sure the unit and bus cannot start while servicing the system.
WARNING: Before any repair the side covers must be completely removed from the
unit to access interior of unit. Insure you are using best practice for working at height
paying special attention during removal of cover as it could move due to the influence
of the wind.
14.2. Cleaning
HVAC Unit Box and Covers
Use a mild alkaline cleaner or common cleaning agent to clean the cover.
Frequently open both side covers and fresh air damper cover and use vacuum cleaner to dirt, debris,
impurities from coils, grilles and complete unit inside area.
CAUTION: Before cleaning (opening the rooftop unit) always switch OFF the
unit/control system.
78
Apply the solution using a pressure spray/wash type apparatus. Spray the condenser coil thoroughly
from both the inside and outside of the coil. Always thoroughly rinse the coil with a fresh water spray.
CAUTION: Air pressure or water spray pressure must not be too high to prevent
from damage of coil fins.
CAUTION: When using a water spray, isolate the return air plenum to prevent water
spray from entering the passenger compartment.
8 7
1
BEA792
2 3 4 5 6
Procedure:
1. Switch OFF the unit/control system.
2. Release all 5 fixing bolts on fresh air damper cover, remove the cover.
3. Remove air filter from filter holders, carefully pull the whole air filter out.
79
4. Clean the internal return air grille, the vacuum cleaner can be also used.
5. Clean the filter or install new filter medium.
6. Put the fresh air damper cover back on its place, tighten the fixing bolts.
IMPORTANT: Used air filter medium waste disposal can be subject to local laws. Never mix
the filter medium with household trash.
BEA136
Procedure:
1. Use cross-head screwdriver, unscrew all bolts and slowly swing down the return air grille. Release
and remove the clip, remove the return air filter.
NOTE: Use care when removing dirty filters from the unit. Vacuum any loose dirt or debris
from air intake prior to installing new filter.
2. Clean or replace filter as necessary.
3. For cleaning use compressed air, blow in direction opposite normal air flow to remove accumulated
dust. Wash filter material in warm soapy water. Flush water in direction opposite to normal air
flow. Remove excess water and install filter.
4. Install clean or new filter medium, close return air filter grille.
5. Press all bolt heads to fix the return air grille (additional screw not needed).
IMPORTANT: Used air filter medium waste disposal can be subject to local laws. Never mix the
filter medium with household trash.
80
14.5. Coil Air Filter Replacement
1 4
BEA443
Procedure:
1. Switch OFF the unit/control system. Turn OFF all power supply.
2. Carefully open and remove left or right side cover.
3. Locate the coil air filter, remove filter holders and carefully pull the whole air filter out.
4. Clean the filter or install new filter medium.
NOTE: Use care when removing dirty filters from the unit. Vacuum any loose dirt or debris
from air intake prior to installing new filter.
5. Put the filter back on its place.
IMPORTANT: Used air filter medium waste disposal can be subject to local laws. Never mix
the filter medium with household trash.
6. Switch ON A/C system and test the functionality.
7. Insert and close side cover, fix the cover with fixing bolts.
81
15.Troubleshooting
15.1. Air Conditioning Diagnosis and Analysis
Analysis Overview
Servicing a system consists of checking system pressures and temperatures. You should be familiar with
the system you are working with.
Diagnosis Procedure
1. Identify components in the system. To identify components, see your unit service manual, parts
manual and the unit itself.
2. Verify that the bus has the proper air flow throughout the system. The air conditioning ducts must
be free from obstructions.
3. Determine that each component is working correctly.
Are the evaporator blowers running and in the proper range of speed?
Need the air filters cleaning?
Are the condenser coils or evaporator coils clean?
Are the condenser fans running and at proper speed?
What is the unit thermostat set point and what is the interior temperature of the bus?
Is there refrigerant in the system in a proper volume?
If the system does not function, is power supply present? Is there control system switched on
and operating?
What are the compressor discharge and suction pressures while the unit is operating? (Refer to
Temperature Pressure Table.)
System Analysis
Failure of the system to stay within normal ranges can have several causes. Causes and solutions of
these problems are described in the System Analysis Table on the following pages.
82
15.2. Causes for Failure to Stay Within Temperature Range
Condition / Possible cause Remedy
Excessive load
Frequent stops 1. Perform structural maintenance inspections
Long loading stops regularly.
Open or loose windows and doors 2. Repair leaks.
Loose body panels
Poor insulation
Too many passengers
Blocked filter or dirt on coils
Dust and lint buildup on evaporator air filter 1. Clean the evaporator air filter by reverse
flushing with warm, soapy water. Recoat the
filter with RP Filter Coat, TK# 203-334 or
equivalent.
Dirt buildup on condenser or evaporator coils 2. Flush the coils with warm soapy water at
medium pressure.
Excessive oil in circulation
Restriction in filter-drier causing low suction Remove excess oil. See the “Removing Excess
pressure Oil” procedure in this manual.
NOTE: For accurate results, check the oil when
Restriction in expansion valve causing low suction
the compressor is warm and the system is
pressure
operating in normal range.
Restriction of liquid line
Low suction pressure at high speeds Check the filter-drier.
Temperature change at point of restriction Check the in-line service valves.
Flashing of refrigerant is occurring Check the expansion valve inlet screen.
See the procedures in this manual for replacing
the filter-drier, in-line service valves, and
expansion valve, and for checking for moisture
content.
Low refrigerant charge
Low suction pressure Charge the system. See the Charging procedures
in the Refrigeration Maintenance chapter in this
Hot liquid line
manual.
Warm suction line
Hotter than normal compressor discharge
temperatures
Decreased cooling capacity
High refrigerant charge
High compressor discharge pressure Evacuate and recharge the system. See the
Evacuation and Charging procedures in this
Malfunction of loaders manual.
Air in refrigeration system
Dark oil 1. Test for air in the system. See “Removing
High compressor discharge temperatures Contaminants” in this manual.
2. Evacuate and recharge the system See the
High compressor discharge pressure Evacuation and Charging procedures in this
False refrigerant level indication (air trapped in manual.
receiver tank)
Erratic action of expansion valve (possibly hissing
noises at expansion valve)
83
Condition / Possible cause Remedy
Expansion valve set incorrectly
1. Low superheat:
Adjust the expansion valve. See the Expansion
Flooding at the compressor Valve section in this manual.
High suction pressures
Decreased cooling capacity NOTE: The expansion valve is preset and
should not require adjustment. Verify that the
2. High superheat: expansion valve is the problem by rechecking
Warm suction line temperature all other components before adjusting.
Low suction pressures
Decreased cooling capacity
Expansion valve malfunctioning
1. Valve sticks open due to dirt or ice in the valve: Verify that the expansion valve is the cause by
Excessive sweat on suction line checking all other possible causes (the expansion
valve rarely fails).
High compressor oil level, indicated by sump being
cool to the touch If the expansion valve is bad, replace it. See the
Refrigerant charge level appears low Expansion Valve Removal and Installation section
2. Valve sticks closed due to loss of charge in sensor in this manual.
bulb:
High discharge pressure Check the compressor operating conditions,
Low suction pressure repair or replace compressor
No cooling
Warm suction line and coil
Low oil level in compressor
3. Valve operation is erratic:
Low system charge level
Air in the system
Moisture frozen in valve
Dirt in valve inlet screen
Block in liquid line before expansion valve
Sensing bulb not in good contact with suction line
Plugged filter-drier
Restriction of refrigerant at filter-drier
To prevent plugging, perform routine maintenance
Outlet line cooler than inlet line inspection of the filter
Frost or sweating on outlet line To replace, see the Filter-Drier Removal and
Particles in the system caused by breakdown of Installation section in this manual.
filter-drier (extreme cases only)
84
15.3. Compressor suction pressure conditions
Condition / Possible cause Remedy
LOW compressor suction pressure
Frosty/Cold 1. Normal operation
Suction Bus is controlling on thermostat with No action.
Line light load and/or at higher speeds
2. Air flow through evaporator is restricted:
Air filter dirty Clean or replace air filters.
Evaporator coil dirty Clean or defrost evaporator coil.
3. Evaporator blower motor problem
Electrical malfunction Check electricity, relays, controller.
Fan blades broken or damaged Replace condenser fan.
HIGH compressor suction pressure
1. Normal operation
Heavy load on the evaporator No action.
2. Expansion valve malfunction
Feeler bulb making poor contact with Fix the feeler bulb in correct operating
suction line position.
Needle eroded-valve cannot control
Repair/replace expansion valve.
properly
Adjustment has been incorrectly set
Repair/adjust/replace expansion valve.
(low superheat)
Recover the refrigerant from the system.
See chapter 11 and refer to “Evacuation
3. Overcharge of refrigerant
procedure”. Evacuate and recharge the
system properly.
Condition / Possible cause Remedy
LOW compressor suction pressure
Recover the refrigerant from the system. See
1. Low refrigerant charge
chapter 11 and refer to “Evacuation
Dry/Warm
procedure”. Evacuate and recharge the
system properly.
Suction
2. Restriction in liquid line Check/replace filter-drier.
Line
3. Expansion valve malfunction:
Inlet screen plugged
Sensor bulb lost charge
Repair/adjust/replace expansion valve.
Adjustment has been incorrectly set
(high superheat)
Recover the refrigerant from the system.
4. Too much oil in system
Clean, evacuate and recharge the system
properly.
5. Restricted suction line Check the piping system. Recover the
refrigerant from the system. Clean,
evacuate and recharge the system properly.
6. Air flow through condenser coil too cold No action.
HIGH compressor suction pressure
1. Compressor malfunction
Leaking discharge valves
Leaking piston reeds
Repair or replace compressor.
Worn piston/sleeve assembly (blow-
by)
2. Heavy load on evaporator No action
3. Compressor turning too slowly Check the compressor operating conditions,
repair or replace compressor.
85
15.4. Compressor discharge pressure conditions
Condition / Possible cause Remedy
LOW side compressor discharge pressure
Recover the refrigerant from the system. Clean,
1. Low refrigerant charge
evacuate and recharge the system properly.
Check the compressor operating conditions,
2. Compressor speed low
repair or replace compressor.
3. Air flow through condenser is cold No action.
4. Restrictions to refrigerant flow:
Liquid line restricted Check/replace filter-drier.
Suction line blockage Check the piping system. Recover the refrigerant
from the system. Clean, evacuate and recharge
the system properly.
5. Compressor malfunction:
Leaking discharge valves
Leaking piston reeds Repair or replace compressor.
Worn piston/sleeve assembly (blow-by)
HIGH side compressor discharge pressure
1. Air flow into condenser is low or restricted
Dirty coil Clean condenser coil
Debris in the coil inlet Clean air grilles
2. Condenser fan or motor problem:
Motor running on low speed Check fan operating conditions, repair or replace
condenser fan
Motor not running - electrical malfunction Check electricity, relays, controller.
Fan blades broken or damaged Replace condenser fan.
3. Restriction on high side of the system:
In-line service valves (shut-off valves) partially Open valves.
closed
4. Non-condensables in the system:
Air, nitrogen, and other gases (?) Recover the refrigerant from the system. Clean,
evacuate and recharge the system properly.
5. Hot air entering the condenser coil No action.
6. Overcharge of refrigerant Recover the refrigerant from the system. See
chapter 11 and refer to “Evacuation procedure”.
Evacuate and recharge the system properly.
86
16.Temperature-Pressure Chart
Temperature Pressure Relationship - Vapor Pressure, kPa, psig
Temperature R-22 R-134a R-407C
F C kPa psig kPa psig kPa psig
-50 -45.6 42 6.1 128 18.5 76 11.0
-48 -44.4 33 4.8 120 17.4 68 9.9
-46 -43.3 23 3.4 117 16.9 60 8.7
-44 -42.2 19 2.7 112 16.2 52 7.5
-42 -41.1 14 2.0 106 15.4 43 6.2
-40 -40.0 3 0.5 101 14.7 33 4.8
-38 -38.9 9 1.3 94 13.7 23 3.4
-36 -37.8 15 2.2 88 12.7 13 1.9
-34 -36.7 21 3.0 81 11.7 2 0.3
-32 -35.6 27 3.9 74 10.7 4 0.6
-30 -34.4 33 4.8 68 9.8 10 1.5
-28 -33.3 40 5.8 59 8.6 16 2.3
-26 -32.2 48 6.9 51 7.4 22 3.2
-24 -31.1 54 7.9 43 6.2 29 4.2
-22 -30.0 62 9.0 34 5.0 36 5.2
-20 -28.9 70 10.1 26 3.8 43 6.2
-18 -27.8 78 11.3 15 2.2 50 7.2
-16 -26.7 87 12.6 5 0.7 57 8.3
-14 -25.6 95 13.8 2 0.3 66 9.5
-12 -24.4 104 15.1 7 1.0 74 10.7
-10 -23.3 113 16.4 12 1.8 82 11.9
-8 -22.2 123 17.9 19 2.7 91 13.2
-6 -21.1 134 19.4 25 3.6 100 14.5
-4 -20.0 144 20.9 31 4.5 110 15.9
-2 -18.9 154 22.4 37 5.4 120 17.4
0 -17.8 165 23.9 43 6.3 130 18.9
2 -16.7 177 25.6 50 7.3 141 20.4
4 -15.6 189 27.4 58 8.4 152 22.0
6 -14.4 201 29.1 65 9.4 163 23.7
8 -13.3 213 30.9 72 10.5 175 25.4
10 -12.2 225 32.7 80 11.6 187 27.1
12 -11.1 239 34.7 88 12.8 200 29.0
14 -10.0 254 36.8 97 14.1 212 30.8
16 -8.9 268 38.8 106 15.4 226 32.8
18 -7.8 282 40.9 115 16.7 240 34.8
20 -6.7 296 43.0 124 18.0 254 36.9
22 -5.6 312 45.3 134 19.5 270 39.1
24 -4.4 329 47.7 145 21.0 285 41.3
26 -3.3 345 50.0 155 22.5 301 43.6
28 -2.2 361 52.4 165 24.0 316 45.9
30 -1.1 378 54.8 177 25.6 334 48.4
32 0.0 396 57.5 188 27.3 351 50.9
34 1.1 415 60.2 201 29.1 369 53.5
36 2.2 434 63.0 213 30.9 387 56.1
38 3.3 453 65.7 225 32.7 406 58.9
40 4.4 472 68.5 238 34.5 425 61.7
42 5.6 494 71.6 252 36.5 445 64.6
44 6.7 515 74.7 266 38.6 466 67.6
46 7.8 536 77.8 281 40.7 487 70.7
48 8.9 558 80.9 295 42.8 509 73.8
50 10.0 579 84.0 310 44.9 532 77.1
87
Temperature Pressure Relationship - Vapor Pressure, kPa, psig
Temperature R-22 R-134a R-407C
F C kPa psig kPa psig kPa psig
52 11.1 603 87.5 326 47.3 554 80.4
54 12.2 627 91.0 343 49.7 578 83.9
56 13.3 652 94.5 359 52.1 603 87.4
58 14.4 676 98.0 376 54.5 627 91.0
60 15.6 701 101.6 392 56.9 654 94.8
62 16.7 727 105.5 411 59.6 680 98.6
64 17.8 755 109.5 430 62.4 707 102.5
66 18.9 782 113.4 449 65.1 734 106.5
68 20.0 809 117.4 468 67.9 763 110.7
70 21.1 837 121.4 487 70.7 792 114.9
72 22.2 867 125.8 509 73.8 823 119.3
74 23.3 898 130.2 530 76.9 853 123.7
76 24.4 929 134.7 552 80.1 885 128.3
78 25.6 959 139.1 574 83.2 917 133.0
80 26.7 990 143.6 596 86.4 950 137.8
82 27.8 1024 148.5 620 89.9 984 142.7
84 28.9 1058 153.5 645 93.5 1019 147.8
86 30.0 1092 158.4 669 97.0 1055 153.0
88 31.1 1127 163.4 694 100.6 1091 158.3
90 32.2 1161 168.4 718 104.2 1129 163.7
92 33.3 1199 173.9 746 108.2 1167 169.2
94 34.4 1237 179.4 774 112.2 1206 174.9
96 35.6 1275 184.9 801 116.2 1246 180.7
98 36.7 1313 190.4 829 120.2 1287 186.7
100 37.8 1351 195.9 857 124.3 1329 192.8
102 38.9 1392 201.9 889 128.9 1372 199.0
104 40.0 1434 208.0 919 133.3 1415 205.3
106 41.1 1476 214.1 950 137.8 1461 211.9
108 42.2 1518 220.2 981 142.3 1507 218.5
110 43.3 1560 226.3 1012 146.8 1553 225.3
112 44.4 1606 233.0 1047 151.8 1602 232.3
114 45.6 1653 239.7 1081 156.8 1651 239.4
116 46.7 1699 246.4 1116 161.8 1701 246.7
118 47.8 1745 253.1 1150 166.8 1752 254.1
120 48.9 1792 259.9 1185 171.9 1804 261.7
122 50.0 1842 267.2 1223 177.4 1857 269.4
124 51.1 1893 274.6 1262 183.0 1913 277.4
126 52.2 1944 282.0 1300 188.6 1968 285.5
128 53.3 1995 289.4 1339 194.2 2025 293.7
130 54.4 2046 296.8 1378 199.8 2084 302.2
132 55.6 2102 304.8 1420 205.9 2143 310.8
134 56.7 2157 312.9 1462 212.0 2204 319.6
136 57.8 2213 321.0 1504 218.2 2266 328.6
138 58.9 2269 329.1 1546 224.3 2328 337.7
140 60.0 2325 337.2 1589 230.5 2393 347.1
142 61.1 2386 346.0 1635 237.2 2459 356.7
144 62.2 2447 354.9 1682 244.0 2526 366.4
146 63.3 2508 363.7 1729 250.8 2595 376.4
148 64.4 2569 372.6 1776 257.6 2665 386.5
150 65.6 2630 381.5 1823 264.4 2737 396.9
88
17.Index
89
L S
leak detector, 53, 56 safety, 9, 52, 61, 62, 70
leak test, 52 safety relief valve, 22, 27, 61, 69
liquid receiver, 20 schematics diagram, 93
liquid recovery, 52, 56 sensor bulb, 65, 66, 67, 85
lock function, 33, 40 serial number, 22
low suction pressure, 84, 85 set point, 83
LPCO, 15, 22, 27, 43, 48, 53-57, 68 sight glass, 20, 27, 47
M solenoid valve, 20
specifications, 15
maintenance, 52
superheat, 66, 85, 86
maintenance intervals, 46
maintenance procedures, 46 T
maintenance records, 46 tank receiver, 24
manual mode, 31, 33 temperature sensor, 43, 77
mode select, 32 temperature tester, 49
moisture, 12, 17, 20, 28, 47, 53-60, 64, 84, 85 theory of operation, 27
N thermometer, 49, 66
threadlocker, 49, 69
nitrogen, 10, 56, 57, 61, 67
TM compressor, 25
normal operating mode, 43
tools, 10, 49, 53
O torque special conditions, 51
off season, 46 torques, 50
oil test kit, 49, 54 U
overvoltage suppressor, 71
unit decals, 22
oxygen, 9, 11, 54, 56
unit protection devices, 20, 21
P V
power supply, 16
vacuum, 49, 53, 54, 57-60, 65, 79
pressure relief valve, 15
vacuum cleaner, 79, 81
pressure rise test, 59
vacuum pump, 49, 54, 57, 60
program number, 36
vapor recovery, 52, 55
R ventilation mode, 43
receiver tank, 20, 21, 27, 28, 84 W
recovery station, 55, 56
warranty, 2, 12, 46
red alarm, 43
water valve, 47
refrigerant hazards, 11
weight, 18
reheat mode, 32
wintertime, 46
relay, 70, 71
wiring diagram, 93
relay test, 36
return air filter, 21 Y
return air grille, 21 yellow alarm, 43
rooftop unit, 14, 19, 20, 22, 79
RTS, 27
90
18.Schemes, Diagrams and Drawings Index
91
19.Appendix
92
Compressor
Service
Manual
for
TM-08
TM-13
TM-15
TM-16
TM-21
TM-31
Compressors
INTERNATIONAL
COMPONENTS ENGINEERING
Copyright 2003 • International Components Engineering
Minneapolis, MN, U.S.A. • Printed in U.S.A.
ICE No. 51068 (Rev. 2a, 12/03)
This manual is published for informational purposes only and the information so provided
should not be considered as all-inclusive or covering all contingencies. If further information is
required, International Components Engineering should be consulted.
Sale of product shown in this manual is subject to International Components Engineering terms
and conditions including, but not limited to, the International Components Engineering Limited
Express Warranty. Such terms and conditions are available upon request.
International Components Engineering warranty will not apply to any equipment which has been
“so repaired or altered outside the manufacturer’s plants as, in the manufacturer’s judgment, to
effect its stability.”
The compressor is designed for use with R-12 and R-134a for vehicle air conditioning
only. Use with other refrigerants will void any warranty.
The ICE compressor is not intended nor designed for use on aircraft.
2
TM Advantages
Smooth Operation
• Balanced Swash Plate design offers low pulsation noise, quiet and smooth operation, less
vibration, and lower horsepower requirements.
High Efficiency
• Cooling capacity is stable throughout the entire RPM operating range.
High Durability
• MoS2 coated steel swash plate provides additional protection during liquid slugging and high load
conditions.
• Ball and shoe design promotes lubrication for better compressor durability.
• Needle bearings insure high durability for long life and high speed operation.
• Lip Shaft Seal insures excellent sealing integrity and extends compressor life.
3
Recover Refrigerant
At International Components Engineering, we recognize the need to
preserve the environment and limit potential harm to the ozone layer
that can result from allowing refrigerant to escape into the
atmosphere.
4
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Safety Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigerant Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Leak Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
R-134a Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Oil Handling Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 9
Equipment for R-134a Use Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compressor Identification Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Swash Plate System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Piston Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Compressor System Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Suggested Operating Region . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Clutch Application Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compressor Clutch and Fitting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TM-08 Ear Mount Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TM-08 Alternator Mount Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TM-08 Ear Mount Pad-Type Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TM-13 Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TM-15 Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TM-15 Direct Mount Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
TM-16 Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
TM-21 Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TM-31HD Dimensions and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TM-08 Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
TM-13, TM-15, TM-16, TM-21 Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
TM-31 Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Compressor Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Operating Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Non-Operating Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installation Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Mounting Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Leak Testing the Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Compressor Oil Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Compressor Oil Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Oil Charge Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Oil Type Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Oil Check Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Oil Check Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5
Table of Contents
6
Safety Precautions
7
Safety Precautions
8
Safety Precautions
Compressor Oil
Handling Procedures
9
Safety Precautions
10
Introduction
1. Radial Bearing
2. Thrust Bearing
1. Suction
2. Compression
3. Pistons
4. Ball
5. Shoe Disk
11
Introduction
12
Introduction
2
1
3
2
3
4
AEA1878
1. Magnetic Clutch
2. Idle Pulley
3. Drive Pulley
13
Introduction
14
Compressor Clutch and Fitting Options
Compatible
with
R-134a & R-12
Clutch Options
15
Compressor Clutch and Fitting Options
Compatible
with
R-134a & R-12
16
Dimensions and Specifications
17
Dimensions and Specifications
18
Dimensions and Specifications
19
Dimensions and Specifications
20
Dimensions and Specifications
21
Dimensions and Specifications
22
Dimensions and Specifications
23
Dimensions and Specifications
Bore 1.26 in. (32 mm) Current Consumption 3.75 amperes (MAX)
Stroke 1.05 in. (26.7 mm) Stalling Torque 59 N•m (43.5 ft. lb)
Permissible Speed 700 to 6000 rpm Mass 6.8 lbs (3.1 kg)
Refrigerant R-134a
Compressor Oil 1 See note below CAUTION: Check system decals and
Mass 11.3 lbs (3.1 kg) operation manual for oil type. Mixing
1 Depending on application, this compressor can incompatible oils causes system damage.
be used with different and non-compatible compressor
oils. See unit labels for proper oil. The initial installer is
responsible for proper labeling.
24
Dimensions and Specifications
1. Drive Shaft
2. Radial Bearing
3. Piston
4. Radial Bearing
5. Thrust Bearing
6. Swash Plate
25
Dimensions and Specifications
Figure 2: TM-31
26
Dimensions and Specifications
Model TM-31
Type Swash Plate
Number of Cylinders 10
Bore 36 mm (1.42 in.)
Stroke 30.7 mm (1.21 in.)
Displacement 313 cm3 (19.1 cu. in.)
Maximum Speed 6000 rpm
Direction of Rotation Clockwise, viewed from clutch
Lubrication System Gear Driven Positive Pressure
Lubricant Oil - I see system specification
Oil Charge 500 cc (16.9 fl. oz.)
Refrigerant R-134a
Shaft Seal Shaft Seal Lip Seal Type
Weight 9.5 kg (21 lbs)
27
Dimensions and Specifications
28
Dimensions and Specifications
29
Dimensions and Specifications
20 16
19
20 2
21 3
19
17
12
21
6 10 13
8
11
9
4 1
15
14
15
14
7
18 5
23
30
Dimensions and Specifications
Tightening Torques
6
1
31
Dimensions and Specifications
32
Compressor Maintenance: TM-08, TM-13,
TM-15, TM-16, TM-21
33
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
Non-Operating Compressor
1. Perform the Refrigerant Recovery” (For more
information, see “Refrigerant Recovery” on
page 33.)
2. Remove the compressor from the system.
34
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
Mounting Compressors
CAUTION: Do not let oil escape.
1. Range of Motion. Verify the range of motion
positioning at both extremes of the belt
• Manually rotate the drive shaft several times adjustment. Figure 4 shows the range of
to distribute oil that has settled in the motion for the compressor.
cylinders. 2. Clearance. Clearance between the
compressor mounting supports and bracket
must be less than 0.004 inches (0.10 mm). Use
shims as necessary to adjust this clearance
(Shim Kit ICE No. 2570101). This reduces
stress on the compressor.
3. Pulley alignment. Maintain correct pulley
alignment for the drive belt.
Installation Position
Install the compressor within the range shown in
Figure 4 below.
1. Bracket
NOTE: The compressor has a pressure-feed
2. Shim ICE No. 257101
lubrication system that cannot function if the
compressor is installed outside this range. 3. Compressor
35
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
36
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
• Drain and inspect the oil. 6. Drain the oil as described below.
Oil return, draining, and inspection procedures are Draining the Oil
described in this section. For compressor removal,
see “Compressor Removal” on page 34. For 1. Perform the “Returning Oil to the
refrigerant recovery, consult your system and Compressor” procedure above.
recovery unit manuals. 2. Remove the drain plug from the compressor.
3. Drain oil from the compressor drain plug and
all other ports.
4. Remove remaining oil through the discharge
side connector by manually rotating the drive
plate until all oil is removed.
5. Measure oil in a measuring cylinder.
NOTE: See your application specifications
for the correct oil amount.
6. Inspect oil for contamination (see “Checking
1. Return Oil to Compressor Compressor Oil for Contamination” on
2. Recover Refrigerant
page 38).
37
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
7. Replace the oil drain plug and tighten it per 2. Verify the correct oil amount in your system
specifications (see “Tightening Torques” on specifications.
page 31).
3. If oil is contaminated, replace old oil with new
8. If necessary add oil. See “Adding Compressor oil.
Oil” on page 38.
4. Add oil to the compressor through the suction
9. Install the compressor (see “Compressor port as shown in Figure 8.
Installation” on page 34). Tighten bolts to the
5. Turn the shaft manually several times while
specified torque (see “Tightening Torques” on
adding oil to distribute oil evenly.
page 31).
NOTE: Replace oil with fresh oil taken only
from a sealed metal container.
38
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
Clutch Procedures
For application guidelines, see “Clutch
Application Guidelines” on page 13.
Clutch Run-In
Use this procedure to break in a new magnetic
clutch.
1. Install the clutch on the compressor. For more
information, see “Clutch Installation” on page
41.
2. Install the compressor on the engine. Charge
the system. Operate the compressor by
running the system. 1. Holder
3. Maintain the compressor speed at idle. Figure 9: Remove Center Bolt
Operate the A/C Switch through the on/off
cycle at least 10 times (on for 10 seconds, off 2. Remove the armature plate using the armature
for 10 seconds). plate puller. Remove the shims from the
armature shaft or the armature plate.
Clutch Test
If the field coil lead wire is broken, replace the
field coil. Check the amperage and voltage. The
amperage range should be:
System Amperage
12 Volt System 3.6 to 4.2
24 Volt System 1.8 to 2.1
Amperage indications:
• A very high amperage reading indicates a
short within the field coil.
Figure 10: Remove Drive Plate
• No amperage reading indicates an open circuit
in the winding. 3. Remove the snap ring using external snap ring
pliers. Remove the cover (if equipped).
• An intermittent or poor system ground results
in lower voltage at the clutch. Check for a
tight fit on the coil retaining snap ring, or for
good ground at the coil retaining screws.
Clutch Removal
NOTE: See the Appendix for correct tools.
Contact your local International Components
Engineering Dealer for more information.
1. Remove the center armature bolt.
39
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
40
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
Clutch Installation
See “Clutch Inspection” before installing the
clutch.
1. Install the coil on the compressor with the lead
wire on top. Tighten the mounting screws to
the specified torque. See “Tightening
Torques” on page 31.
2. Install the lead wire in the wire holder on the
compressor.
1. Snap Ring
2. Cover (If Equipped)
Figure 17: Install Cover and Snap Ring (1)
1. Snap Ring
2. Cover (If Equipped)
Figure 18: Install Cover and Snap Ring (2)
41
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
After tightening the bolt, ensure that the Shaft Seal Procedures
pulley rotates smoothly.
Shaft Seal Removal
1. Remove the magnetic clutch assembly See
“Clutch Removal” on page 39.
2. Use the seal remover (from the shaft seal kit
ICE No. 2590114) to remove the shaft seal
cover. Turn the seal remover to engage the
hook on the seal remover with the hook on the
shaft seal cover, then slowly pull the shaft seal
cover out of the cylinder head (some models).
3. Remove the snap ring using internal snap ring
pliers.
1. Shims
Figure 19: Install Shims and Drive Plate
7. Ensure that the clutch clearance is as
specified. If necessary, adjust the clearance
using shims.
NOTE: Adjusting shims are available in the
clutch Hardware kit ICE No. 2530109.
NOTE: Specified clearance: 0.012 to 0.024
in. (0.3 to 0.6 mm).
1. Snap Ring
2. Cover (When equipped)
Electrical Connection
1. Connect the lead wire to the electrical circuit.
NOTE: The stationary field is grounded at
the factory. Connect the hot (lead) wire only.
2. Engage and disengage the clutch several times
to check the engagement. The disc should
snap firmly against the pulley. 1. Shaft Seal Cover (Some Models)
Figure 21: Remove Shaft Seal Cover
42
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
4. Use the seal remover (from the shaft seal kit dry the clean surfaces, and apply clean
(ICE No. 259114) to remove the shaft seal. compressor oil. Use the same oil in the
Turn the seal remover to engage the hook on system.
the seal remover with the hook on the shaft
3. Place the seal guide (from the shaft seal kit
seal, then slowly pull the shaft seal housing
ICE No. 2590114) on the end of the spline
out of the cylinder head.
shaft.
1. Shaft Seal
43
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
Figure 26: Press Seal Into Cylinder Head Figure 27: Shaft Seal Cover (When equipped)
7. Install the snap ring using internal snap ring 3. Use the seal installer (from the shaft seal kit
pliers. Press the snap ring using the installing ICE No. 2590114) to press the shaft seal cover
end of the remover until you hear a “click.” into the cylinder.
4. Remove the seal guide from the spline shaft.
NOTE: Position the shaft seal cover as shown in
the illustration.
1. Shaft Seal
2. Guide
3. Snap Ring
44
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
1. O-ring
2. Gasket
3. Front Cylinder Head
1. Valve Plate
6. Remove the O-ring from the front cylinder 2. Suction Valve
head. Remove the gasket material from the
front cylinder head. 8. To remove the rear cylinder head, alternately
tap the projections on the circumference of the
rear head with a screwdriver and a plastic
mallet.
45
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
1. O-ring
2. Gasket
46
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
47
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
1. Escape Groove
2. Suction Valve
3. Piston
Front Cylinder Head 4. Coat the new gasket with clean compressor oil
1. Place the cylinder shaft assembly on the bench (same oil used in the system). Install it on the
with the front side up. front valve plate.
2. Install the front suction valve so that it aligns 5. Thinly coat the new O-ring with clean
with alignment pin. compressor oil (same oil used in the system).
Install it on the front cylinder head.
6. Install the front cylinder head. If the front
cylinder head is difficult to install, tap the
cylinder head lightly with a plastic mallet.
48
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
49
Compressor Maintenance: TM-08, TM-13, TM-15, TM-16, TM-21
50
Compressor Maintenance: TM-31
51
Compressor Maintenance: TM-31
Compressor Storage
Store new and rebuilt compressors:
• With the correct oil charge.
• Within the orientation range shown in Figure
31 on page 52. If the compressor sits outside
that orientation for more than one minute, turn
compressor manually (slowly) to clear oil
from the cylinders. Figure 31: Inclination Limit
• With a holding charge of refrigerant or NOTE: Inclination limit at installation must
nitrogen to a pressure of 7 to 21 psig (48 to be within the range shown above.
145 kPa). This protects internal parts from
moisture and corrosion. NOTE: If mounting shims are required for
installation, use Shim Kit (ICE No.
2570101).
Compressor Removal
See “Compressor Removal” on page 34.
52
Compressor Maintenance: TM-31
CAUTION: If compressor installation 1. Remove the center bolt using a drive plate
does not permit easy viewing, use a mirror holder to prevent armature assembly rotation.
to view the sight glass. Be careful of
moving belts and pulleys. 1
1
AEA1742
AEA1880
Clutch Run-In
See“Clutch Run-In” on page 39.
53
Compressor Maintenance: TM-31
1 2
AEA1881
CAUTION: Do not hold the field coil by
1. Snap Ring Pliers ICE No. the harness.
2590117
2. Snap Ring Clutch Inspection
3. Remove the snap ring using external snap ring 1 2 3
pliers.
AEA1884
1. Armature Assembly
2. Pulley Assembly
3. Field Coil
54
Compressor Maintenance: TM-31
Clutch Installation
AEA1885
3. Install the pulley assembly using the pulley CAUTION: After tightening the center
installer and a hand press. bolt, check that the pulley rotates smoothly
AEA1888
55
Compressor Maintenance: TM-31
56
Compressor Maintenance: TM-31
AEA1893
1. Guide
2. Shaft
3. Gasket
4. O-ring
AEA1895
4. Thinly coat the new O-ring and gasket with
clean compressor oil. Use the same oil used in 1. Handle
the system.
8. Turn the drive shaft two or three times
5. Fit the guide onto the end of the drive shaft. manually to ensure that the shaft rotates
Install the front cylinder head. If the front smoothly.
cylinder head is difficult to install, tap the
cylinder head lightly with a plastic or rubber 9. Fill the compressor with the specified amount
mallet. of clean compressor oil through the oil filler.
Tighten the oil filler plug to the specified
torque.
AEA1894
57
Compressor Maintenance: TM-31
58
Appendix – Tools and Kits
59
Appendix – Tools and Kits
Clutch Installation Kit – ICE No. 2590118 Shaft Seal Kit – ICE No. 2590114
60
Appendix – Tools and Kits
Clutch Hardware Kit – ICE No. 2530109 Shim Kit – ICE No. 2570101
61
Appendix – Tools and Kits
62