Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

INSTRUCTION MANUAL

MMMANMMMMMMANM
ANUAL

MODEL
VS22AⅣ / VS37AⅣ
VS55AⅣ / VS75AⅣ

<Cover image is VS22A Ⅳ model>

All rights reserved. This publication may not be reproduced or distributed, in whole or
in part, without the prior written consent of Kobe Steel,Ltd./Kobelco Compressors CN_MANU_VS22375575A41_E-03
Manufacturing (Shanghai) Corporation [KOBELCO]. 1000164107-03
VS Series INSTRUCTION MANUAL

Contents
Contents...................................................... I 7 Operation ........................................... 7-1
Preface ....................................................... II 7.1 Procedures of Operation ................................. 7-1
1 Safety Information ............................ 1-1 7.2 Pre-operation Inection ..................................... 7-1
7.3 Default Settings ............................................... 7-2
1.1 General Precautions ....................................... 1-1
7.4 Operation Procedure ....................................... 7-3
1.2 Alert and Safety Symbols ................................ 1-1
7.5 Touch Screen Operation ................................. 7-5
1.3 Caution and Warning labels ............................ 1-1
7.6 Setting and Reset of Control Pressure ............ 7-6
1.4 Safety Rules.................................................... 1-2
7.7 Inverter Operation Mode .................................. 7-7
1.5 Precautions at Installation Site ........................ 1-4
7.8 Operational Logic ............................................ 7-8
1.6 Electric Wiring ................................................. 1-5
7.9 Condensate removal of compressor .............. 7-10
1.7 Operation ........................................................ 1-6
1.8 Shutdown ........................................................ 1-7 8 In Case of Emergency ....................... 8-1
1.9 Lubricant ......................................................... 1-8 8.1 Troubleshooting ............................................... 8-1
1.10 Overhaul ....................................................... 1-8 8.2 Interlock ........................................................... 8-6
1.11 Precautions for Inverter ................................. 1-9 8.3 Before Calling for Service ................................ 8-8
1.12 Precautions for Permanent Magnet Motor .. 1-10 9 Maintenance and Parts Replacement
2 Nomenclature.................................... 2-1 ............................................................ 9-1
2.1 Overview ......................................................... 2-1 9.1 Guideline for Maintenance and Parts Replacement
.................................................................... 9-1
2.2 Main Parts ....................................................... 2-3
9.2 Daily Maintenance ........................................... 9-5
2.3 Controller ........................................................ 2-5
9.3 Insulation Test Procedures for Compressor Unit
3 Installation Conditions ..................... 3-1 .................................................................... 9-5
3.1 Place to be installed ........................................ 3-1 10 Long Term Shutdown, Transfer and
3.2 Installation space for safe operation ............... 3-1 Disposal ........................................... 10-1
3.3 Location of Installation to be avoided .............. 3-5 10.1 Long Term Shutdown .................................. 10-1
4 Piping ................................................ 4-1 10.2 Transfer and Disposal ................................. 10-1
4.1 Piping installation ............................................ 4-1 11 Remote Control ............................... 11-1
5 Electric Power Supply ...................... 5-1 11.1 Handling External Signals ........................... 11-1
5.1 Selection of the earth leakage breaker ........... 5-1 12 Specifications .................................. 12-1
5.2 Selection of the power cables ......................... 5-1 12.1 Products Specifications ............................... 12-1
5.3 Selection of earth cables ................................. 5-2 12.2 Wiring Diagram ............................................ 12-3
5.4 Selection of the power transformer ................. 5-2 12.3 Connection Diagram .................................... 12-5
5.5 The Connection of the Power Cable ............... 5-3 12.4 System Diagram .......................................... 12-6
5.6 Harmonics ....................................................... 5-4
13 Warranty and Indemnity ................. 13-1
6 Lube Oil ............................................. 6-1 13.1 Warranty ...................................................... 13-1
6.1 Cautions for lube oil ........................................ 6-1 13.2 Warranty Period........................................... 13-1
6.2 How to refill lube oil ......................................... 6-2 13.3 Indemnity ..................................................... 13-1
6.3 How to drain oil ............................................... 6-2

Contents
I
VS Series INSTRUCTION MANUAL

Preface
Thank you very much for selecting “KOBELION series”, which is package type screw compressor of
Kobe Steel, Ltd (hereinafter referred to as KOBELCO)
Read this instruction manual carefully for proper installation, operation, and maintenance.
Keep this manual in a safe place near the unit for quick reference.

 Model Code

◆ Model Code ◆
The KOBELION series is identified by the following code :
VS22AⅣ
VS ・・・KOBELION-VS series
22 ・・・Motor output 22:22 kW 37:37 kW 55:55kW 75:75 kW
A ・・・Cooling system A:Air cooled
Ⅳ ・・・Series type

Accessories

Model
VS22A Ⅳ VS37A Ⅳ VS55A Ⅳ VS75A Ⅳ
Parts name
Forklift hole cover Forklift hole cover
4 qty 4 qty 4 qty 4 qty (Magnet Sheet)
(Magnet Sheet)

Preface
II
VS Series INSTRUCTION MANUAL

1 Safety Information
1.1 General Precautions
・ Carrying-in work, installation, operation, maintenance and inspections of the
machine must be performed by the well-trained workers.
・ We will not be responsible for any injury and failure/damage of the machine
caused by modification by customer.
・ Strictly follow the local regulations and the safety standard established in the
respective region.
・ Do not use compressed air for any respiratory equipment.

1.2 Alert and Safety Symbols


For safety and trouble-free operation, the following alert and safety symbols, are attached major parts.
Be sure to observe them.
Read carefully and well understand the general precautions.
Alert symbols Safety symbols
Indicates a potentially hazardous situation Indicates “Prohibited”.
which can cause the risk of death or serious Description is written near the symbol.
injury.

Indicates a potentially hazardous situation Indicates “Mandatory”.


that can cause the risk of damage of Description is written near the symbol.
equipment or minor or moderate injury.
Equipment damage means the loss of the
machine itself and/or incidental or
sequential loss of peripheral equipment
and facility.

1.3 Caution and Warning labels


Make sure caution and warning labels attached on the compressor unit as shown below.
If the label is missing or not readable, contact KOBELCO service division to get a new one.

Name plate

SCREW COMPRESSOR

DISCHARGE/MAX PRESS. MPa


SPECIFIED PRESS. MPa
DISCHARGE VOLUME m 3/min
MOTOR OUTPUT kW
DIMENSIONS (D*W*H) mm
VS22AIV WEIGHT kg
SERIAL NO.
MANUFACTURING DATE

MADE IN CHINA
ATTENTION ATTENTION

Please inform the compressor model


and serial number when commissioning
repair or ordering spare parts.

VS37AIV

Safety Information
1-1
VS Series INSTRUCTION MANUAL

1.4 Safety Rules


1.4.1 General Rules for all works
 Carefully read and well understand the instruction manual before
operation, maintenance and inspection of the machine.
Only administrators and workers who understand the manual shall
operate the machine.

 Before disassembly and repair work, conduct a "risk assessment"


meeting, where all workers ensure signs of collaborative work to
prevent any injuries.

 Wear appropriate clothes and protectors during work, such as


installation, disassembly or assembly of the machine.
Workers must wear a helmet, safety shoes and safety glasses, which
protect eyes from pressurized air.
The safety rules are necessary where the machine is operating.

 Authorized technicians must perform inspection and maintenance.


Inexperienced technicians must be supervised by qualified person.

 Use only genuine KOBELCO parts or KOBELCO recommended parts.


Any other parts may cause malfunction and failure.

Safety Information
1-2
VS Series INSTRUCTION MANUAL

1.4.2 Lifting and carrying in

 When moving the unit, attach supports and fixtures to the oil separator
Oil separator
to prevent piping and anti-vibration rubber from any damages.
After installation, the supports and fixtures must be removed.
 Keep the supports and fixtures as required during maintenance.
Holders

◎ Carring by a forklift
 Insert forks into fork-holes of the base plate.
 Place protector between the unit and the forklift to prevent damage.

◎ Lifting with a crane


 Pass slings through fork-holes of the base plate and protect the unit
cover with cloths.
 Use appropriate capacity slings and shackles to the weight of the
machine.
The weight is shown on the data plate of the machine. (See page 1-1)

 Perform sling work concerning the center of gravity and weight.


Carefully lift up the machine keeping the horizontal level to prevent it
from slipping.
 Keep a 45ºdegree angle between slings and the top side of the unit

 Never stand under the heavy load during lifting work.


In case of fall accidents, it may cause serious injury.

Safety Information
1-3
VS Series INSTRUCTION MANUAL

1.5 Precautions at Installation Site


1.5.1 Installation site
 This machine is designed for indoor use only.
Do not install the machine outdoors or semi-outdoors.
 Do not Install in a site where it is exposed to rain or in high humidity
area. It can cause electric leaks, drain or rust.

 Do not install in a site that contains toxic gas, it can cause deterioration
of lube oil and corrosion in parts.
 Do not install the machine near work places where using flame or the
ambient temperature may exceed 45ºC.
 Do not hold inflammable materials around the unit.

 Do not install in a site where iron powder or sand is polluting air.


That may cause insulation failures to the electric devices and damages
to rotors

1.5.2 Installation
 When installing the unit in a closed room, equip a ventilation system
that has an appropriate capacity.
 In case of earthquakes, build a concrete basement and secure the unit
with anchor bolts.
The concrete basement and the bolts shall be installed according to the
latest seismic design method.

Safety Information
1-4
VS Series INSTRUCTION MANUAL

1.6 Electric Wiring


1.6.1 Electric Wiring
 Qualified electricians must conduct electric wiring work.
 Cable leading from the power source should be protected by suitable
cover.
All electric cables in the unit shall be protected attaching protective
bushings to the holes through which cables are passed.
 Electrical leakage, insulation deterioration, overcurrent, short circuit,
open phase operation, protection device failures may cause sparking
from the motor, wiring and electric circuit.
 Make sure to check all electric wiring before the first operation. Make a
maintenance plan and conduct periodical inspection for electric wiring.

1.6.2 Breaker
 Install an earth leakage breaker for the power source appropriate to the
model.
 Do not install knife switch alone. It is insufficient for protection.

1.6.3 Earth cable


 Connect the earth cable with the earth terminal (marked E) on the
compressor terminal board. The grounding work shall be of 10 Ω or
less.
 Qualified electricians must perform grounding work.
Be sure to connect the earth cable directly to the ground. Operation
without grounding work may cause electric shocks and failure in the
compressor.

1.6.4 Safety device


 Do not remove or modify safety devices. Do not change any setting of
the safety devices. It may cause accidents or failure in machine.

Safety Information
1-5
VS Series INSTRUCTION MANUAL

1.7 Operation
1.7.1 Operation
 Do not hold any inflammable materials around the machine. Never use
flame near the machine.
 Do not perform welding work around the machine. The compressor
may catch a fire from spark.

 Do not touch exhaust outlet and the peripheral area, which are heated
up during the operation.

 Keep terminal boxes close during operation to prevent electric shocks.


 At the first operation after overhauling, check settings of the safety
devices and the timer.

 Operate the machine within the specified limits mentioned in this


manual.
Conduct inspections and preventive maintenance to keep the machine
in good condition.

 Do not compress inflammable, poisonous or corrosive gas by the


compressor.

 If any abnormalities are found, stop the machine immediately to


prevent any injuries and damages.

1.7.2 Rotating parts


 Do not touch any rotating parts during the operation or even the
compressor has stopped.

 Turn off the main power when you need to touch any rotating parts,
such as a ventilating fan.
 Be noted that the compressor automatically start when the pressure
drops to the recovery value.

Safety Information
1-6
VS Series INSTRUCTION MANUAL

1.8 Shutdown
1.8.1 Parallel operation
 Stop the compressor, close the discharge valve and allow it drain.

1.8.2 Long-term shutdown


 Turn off the main power and close the discharge valve of the
compressor.

 Be sure to run compressor for 20 minutes, once a week without fail.


It will help to prevent rust in the compressor.

1.8.3 Inspection during shutdown (Pressure)


 For inspecting the compressor unit and refilling lube oil, press the stop
button on the control panel to stop the compressor. Turn off the earth
breaker and check “Oil Separator pressure” is “0 MPa” indicated on the
touch screen.

1.8.4 Inspection during shutdown (Power supply)


 For inspecting the operating panel and the inverter, turn off all the
power sources.
 For inverter inspection, make sure the CHARGE lamp of the inverter is
off.
While the CHARGE lamp is on, the voltage remains in the inverter even
it is powered off.

1.8.5 Inspection during shutdown (Safety valve)


 Do not disassemble the safety valves, which have been installed after
strict performance tests. If any problems occur, contact us.

1.8.6 Inspection during shutdown (Oil separator element cover, only for VS22/37A Ⅳ)
 Ask our certified technician to remove and install the oil separator
element cover.
 If you want to do it yourself, make sure to tighten all bolts of cover, to
appropriate torque values, by using torque wrench. Torque values are
mentioned on the data plate attached to the element cover.

Safety Information
1-7
VS Series INSTRUCTION MANUAL

1.9 Lubricant
1.9.1 Lube oil
 Be sure to use “KOBELCO GENUINE SCREW OIL” or “KOBELCO
EXTRA OIL.
 Never mix different brand oils or different grade oils.
 The poor circulations by downgraded oil, insufficient lubricant and high
viscosity occur. It causes abnormally high temperature and may cause
a fire.
Do visual check on oil conditions once a month. Refill or change the oil
as required.

1.9.2 Oil change


 Under normal operational conditions, the service life of “KOBELCO
GENUINE SCREW OIL” is 3000 hours, or the service life of “KOBELCO
EXTRA OIL” is 6000hours. Be sure to change the full amount of oil
after the running hours.
 Once the compressor operated with deteriorated oil, overhauling of
airend will be required. Do not neglect oil change.
 Deteriorated oil contains deteriorated carbon, which is filtered through
the separator element. The deteriorated carbon may be partially heated
up by oxidation heat, and it can ignite or explode. Replace the oil
separator element as well, at oil change.

1.9.3 Refill
 Refill oil when the oil level is below the low limit in the unit running.
 Press the stop button on the controller panel to stop the compressor.
High limitt
Turn off the breaker. Check “Oil Separator pressure” is “0 MPa”
Low limit indicated on the touch screen.
 Note that the pressure remains in the oil separator for two minutes after
the compressor unit is stopped.
 Refill oil after making sure that the internal pressure is released.

1.10 Overhaul
 Overhaul shall be performed after every six years, regardless of
operating hours.
Replace the main motor bearings and clean the motor coils.
 Turn off the power before overhaul the compressor.

Oil separator
 For maintenance (o/s element replacement), install fixtures the oil
separator to prevent piping and anti-vibration rubber from damages.
 Keep the fixtures for next maintenance.
Fixture

Safety Information
1-8
VS Series INSTRUCTION MANUAL

1.11 Precautions for Inverter


1.11.1 Operation
 Do not touch the cooling fins and the discharge resistor, which are
heated, during operation.
 Do not change the inverter settings, which have been set appropriately
at the factory before shipping.
If changed, it may cause damages in the unit.

1.11.2 Maintenance and inspection


 Do not touch the high-voltage terminal of the inverter, which is
extremely dangerous.
If touched, it may cause an electric shock.

 For maintenance or inspection, turn off the main power, and check that
the motor has stopped and the CHARGE lamp of the inverter is off.
If touched right after power shutdown, it may cause an electric shock.

 Authorized personnel must perform maintenance, inspection and parts


replacement. Remove all metallic things, such as a watch, bracelet or
ring before starting work. Only use insulated tools.
Follow these instructions to prevent an electric shock.

1.11.3 Modification
 Never modify the unit.
It may cause electric shocks or injuries
 Do not connect static capacitors between the inverter and the motor. Or
the capacitor and the inverter including their parts may be burnt or
damaged.

 Do not connect any different motor (induction motor or others) with the
inverter, which is designed to KOBELCO products. Or it may cause
damages in the inverter.

1.11.4 Noise
 A DC reactor is equipped with the unit. If radio or electronic devices are
around the compressor unit, install a noise filter to the power supply
side.

Safety Information
1-9
VS Series INSTRUCTION MANUAL

1.12 Precautions for Permanent Magnet Motor


1.12.1 Repair and disassembly
 Ask certified technicians to repair and disassembly. They must perform
repair and disassembly.
Otherwise, it may cause electric shocks, injuries or fire,

 Carefully remove the motor rotor, which has magnetic attraction force.
Otherwise, the stator coil may be damaged.

 Those who have implanted electronic medical equipment such as


a pacemaker must not approach the removed motor rotor, which has
high magnetic fields.
Electronic medical equipment can be highly influenced.

 When assembling rotor in motor, make sure no foreign materials and


magnetic objects such as metal parts are around the motor, where the
rotor's magnetic field may remain. And then install the motor rotor into
the motor.
Otherwise, the stator coil may be damaged.

 Keep clock, watch, measuring instruments etc. away from the rotor.
Otherwise, they may malfunction or be damaged.

1.12.2 Wiring
 Connect a suitable cable as specified to the inverter board.
Failure to observe this may result in abnormal operation, personal injury
or damage to equipment.

1.12.3 Disposal
 Dispose the motor as general industrial waste. The rotor must be
disposed after demagnetization at a temperature of 500ºC (932 ºF) or
more with a gas burner or in a furnace.
Strictly follow the local applicable environmental legislations.

Safety Information
1-10
VS Series INSTRUCTION MANUAL

2 Nomenclature
2.1 Overview
VS22A Ⅳ/ VS37A Ⅳ

Compressed air discharge outlet Compressor exhaust outlet


(VS22AⅣ : R21) Discharges air heated through heat
(VS37AⅣ : R21 1/2) exchange in oil cooler, after-cooler
and motor.
Discharge compressed air.

Controller NGSC-430
(Touch Screen, Operation panel)
(NGSC-700 OPTION)

Used to start and stop the


compressor, perform various setting,
and display the status of compressor.
Control signal cable inlet (See page2-5.)
Used to lead the control signal cable
in order to enable remote operation.
(See page11-1.)

Power cable inlet(Φ86) Fork-holes


Connect a cable of proper size Used for moving the compressor.
referring to the power (voltage) After installation is completed, attach
specification. accessory covers for sound
(See page5-1) insulation.

Nomenclature
2-1
VS Series INSTRUCTION MANUAL

VS55A Ⅳ/ VS75A Ⅳ

Compressed air discharge outlet Compressor exhaust outlet


(VS55/75AⅣ R22) Discharges air heated through heat
exchange in oil cooler, after-cooler
Discharge compressed air. and motor.

Control signal cable inlet Controller NGSC-430


(Touch Screen, Operation panel)
(NGSC-700 OPTION)
Used to lead the control signal
cable in order to enable remote Used to start and stop the
operation.(See page11-1.) compressor, perform various setting,
and display the status of compressor.
(See page2-5.)

Power cable inlet(Φ86) Fork-holes


Connect a cable of proper size Used for moving the compressor.
referring to the power (voltage) After installation is completed, attach
specification. accessory covers for sound
(See page5-1) insulation.

Window for maintenance

Nomenclature
2-2
VS Series INSTRUCTION MANUAL

2.2 Main Parts


VS22A Ⅳ/ VS37A Ⅳ

Suction filter Oil separator element


Prevents external materials from Separates and recovers
entering. lubricating oil in compressed air.

Operation panel
Blow-off solenoid valve
Opens to discharge compressed
air when the compressor is
stopped or moisture is removed.

Oil filter
Remove foreign materials in
lubricating oil.

Oil supply port


Inverter
Oil separator
Responds to the KOBELION
dedicated high-speed IPM motor.
Oil level gauge
Oil cooler Indicates the oil level in the oil
separator tank. Keep the oil level
Cools lubricating oil. between the red lines during
operation.
After-cooler
Cools compressed air.

Cooling fan & fan motor


Cools oil cooler, after-cooler and
motor

Main motor

(KOBELION dedicated IPM


Air end motor)It is a high efficiency
permanent magnet motor that
Has rotor with ideal profile to reduce realizes Kobelco original
vibration and noise level and technology "wide range control".
improved performance.

Any modification without prior permission must invalidate the


warranty even within the warranty period.
Contact us whenever modification is required.

Nomenclature
2-3
VS Series INSTRUCTION MANUAL

VS55A Ⅳ/ VS75A Ⅳ

Blow-off solenoid valve

Opens to discharge compressed air


when the compressor is stopped or
moisture is removed.

Operation panel
Suction filter

Oil filter Prevents external materials from


entering.
Remove foreign materials in
lubricating oil.
Oil supply port
Oil separator element
Separates and recovers Oil separator
lubricating oil in compressed
air. Oil level gauge
Inverter Indicates the oil level in the oil
Responds to the KOBELION separator tank. Keep the oil
dedicated high-speed IPM level between the red lines
motor. during operation.

Oil cooler
Cools lubricating oil.

After-cooler
Cools compressed air.

Cooling fan & fan motor


Cools oil cooler, after-cooler
and motor

Main motor
Air end
(KOBELION dedicated IPM
Has rotor with ideal profile to motor)It is a high efficiency
reduce vibration and noise level permanent magnet motor that
and improved performance. realizes Kobelco original
technology "wide range control".

Any modification without prior permission must invalidate the


warranty even within the warranty period.
Contact us whenever modification is required.

Nomenclature
2-4
VS Series INSTRUCTION MANUAL

2.3 Controller
2.3.1 NGSC-430
The controller consists of a touch screen, operation panel, message lamps and operating condition
lamps, which are organized according to their functions for simple and accurate settings.

Touch Panel Screen


① Touch Panel Screen
● Indicates operating condition, various settings, and warning messages.



⑮ ⑧ ⑪





② ③
⑬ ⑭

④ ⑤

Operation Panel
② LOCAL button (available during the operation)
 To select how to start or stop the compressor by local mode or remote mode.
 The Local LED lamp is “on” in local mode or “off” in the remote mode.
③ RESET button
 To reset EMERGENCY, CAUTION and MAINTENANCE alarms.

④ STOP button
● To stop compressor operations. To unlock the standby mode.

⑤ START button
● To start the compressor in local mode.

⑮ HOME button
● To go to the home screen, which will appear after the logo displays.

⑯⑰ FUNC 1 and FUNC 2 (function)button


● Press and hold for 3 seconds to register the currently displayed screen. Press this key after login to jump to
the login screen. Each button of FUNC1 and FUNC2 can be registered to each screen separately.

Nomenclature
2-5
VS Series INSTRUCTION MANUAL

Operating Condition LEDs


⑦ EMERGENCY LED Lamp (red)
● Lights when compressor stopped in case of emergency situation.

⑧ CAUTION LED Lamp (orange)


● Lights when an alarm has been issued on the compressor and attention is required.

⑨ MAINTENANCE LED Lamp (yellow)


● Lights when maintenance is required.



⑮ ⑧ ⑪



⑰ ② ③
⑬ ⑭
④ ⑤

Indicator LED Lamps


⑥ POWER LED Lamp (green)
● Lights when the controller is powered on.

⑩ AUTO START LED Lamp (green)


● Lights while the weekly timer is activated. (Set as active).
● Blinks when discharge pressure exceeds the auto stop pressure and it leads to a compressor's
automatic stop (for capacity control).
⑪ LOAD LED Lamp (green)
● Lights while the motor is running.

⑫ LOCAL LED Lamp (green)


● Lights when the local mode is selected.

⑬ STOP LED Lamp (red)


● Lights when the compressor has stopped.

⑭ START LED Lamp (green)


● Lights when the compressor is running.
● Blinks during the alternate operation.

The LED lamps above indicate various conditions of the compressor by combination of
lighting and blinking.

Nomenclature
2-6
VS Series INSTRUCTION MANUAL

2.3.2 NGSC-700(OPTION)
The monitor consists of touch panel, operation panel with keys and various indicators LED lamps, in
order to set up and operate compressor easily and accurately according to the conditions of use.
Touch Panel
① Touch screen
● Indicates operating condition, various setting, and alarms.
● The lamp at the top-right corner indicates the status of
touch panel. (Green: in normal operation)




⑧ ⑪

② ③
⑬ ⑭
④ ⑤

Operation Panel

② LOCAL button (Selectable during the operation)


 To select how to start or stop the compressor by local mode or remote mode.
 In local mode, the local LED lamp is on. In the remote mode, the lamp is off.

③ RESET button
 Press it to reset alarms of EMERGENCY, CAUTION and MAINTENANCE.

④ STOP button

● Press it to stop compressor operations or to unlock the standby mode.


● Touch panel display will be in standby mode after 20 minutes of inactivity.

⑤ START button
● In local mode, press it to start the compressor.

Nomenclature
2-7
VS Series INSTRUCTION MANUAL

Operating Condition LEDs


⑦ EMERGENCY (red) ⑥

● It lights red when compressor stopped, in


case of emergency situation. ⑩

⑧ CAUTION (orange) ⑧ ⑪
● It lights orange when an alarm has been ⑨
issued on the compressor and attention is
required

⑨ MAINTENANCE (yellow)
② ③
It lights yellow when maintenance is
required. ⑬ ⑭

④ ⑤

Indications of LEDs
⑥ POWER (green)

● It lights green when the controller is powered on.

⑩ AUTO START (green)


● It lights green while the weekly timer is set as active.
● It blinks when discharge pressure exceeds the auto stop pressure and it leads to a compressor's
automatic stop (for capacity control).
⑪ LOAD (green)

● It lights green while the motor is running.

⑫ LOCAL (green)

● It lights green when the local mode is selected.


⑬ STOP (red)

● It lights red when the compressor has stopped.


⑭ START (green)
● It lights green when the compressor is running.
● It blinks green during the alternate operation.

 The LED lamps above indicate various conditions of the compressor by combination of lighting and blinking.
Refer to the next section for details.

Nomenclature
2-8
VS Series INSTRUCTION MANUAL

3 Installation Conditions
3.1 Place to be installed
Refer to the following points to select an installation location.

 This machine is designed for indoors use only. Do not install it outdoors.
 Install this machine at an altitude below 1,000 m. Contact us if installing the machine higher than 1,000 m.
 This machine is equipped with the precision electronic components. Never expose the machine to the rain water.
Avoid installation in high humidity areas.
 The temporary storage site also needs to be properly kept. Avoid damp places to prevent leakage and corrosion.
 Do not install the machine at a place that contains a lot of dust and harmful gases such as chlorine gas,
hydrogen sulfide gas, sulfur dioxide, ozone of high density, etc.
 Do not install the compressor unit at a place where it may inhale oil mist and coolant mist from the machining
center, smoke from the boiler or gas of decomposing plastics. It may cause clogging in the oil separator and an
emergency stop.
 Do not install the machine where the ambient temperature exceeds 45ºC. It may cause severe accidents such
as fire and burning of the machine.
 Install the machine horizontally. Do not place blocks or any other things under the machine, this may cause
improper functioning of the compressor.
 Install the machine in a place that does not create vibrations.
 Please note that the noise level may vary with building structure or where the machine is installed.

3.2 Installation space for safe operation


Refer to the following instructions to install the machine.

3.2.1 Recommended space


 Keep a vacant space around the unit, refer to following form.
 Secure sufficient space away from the outlet above the inlet on both side faces of the machine to ensure proper
functions.
 Secure sufficient space away from the front and upper faces of the machine to ensure proper opening and closing of
doors, operation, and maintenance
 The unit must be installed in horizontal.

Upper side

Rear side

Left side Right side

Front side
mm
Model Front side Right side Rear side Left side Upper side
VS22A Ⅳ 600 or more 600 or more 500 or more 600 or more 1000 or more

VS37A Ⅳ 750 or more 600 or more 500 or more 600 or more 1000 or more
VS55A Ⅳ
600 or more 600 or more 500 or more 600 or more 1000 or more
VS75A Ⅳ

Installation Conditions
3-1
VS Series INSTRUCTION MANUAL

3.2.2 Installing a ventilating fan


 Install a ventilating fan to provide fresh air into the closed room. Also Ventilation fan can be installed on the
exhaust pipe.

 Provide a suitable air intake area so as not to create negative pressure in the room.
 Select a ventilating fan that is bigger than the air volume in the following table.
 In case of low ceiling, exhaust heat circulates to the suction side and it may cause ambient temperature
rise.
 It should be noted that when the ambient temperature exceeds 45 ℃, the compressor will shut down.
At this time, it is necessary to try to cool down.

 Ventilating fan specifications


Compressor cooling air
Item
Heat generation Quantity of Exhaust duct
exhaust air allowable pressure loss
Model
[MJ/hr] [m3/min] [Pa] (mmH2O)
VS22AⅣ 97 50
VS37AⅣ 162 90
20 (2)
VS55AⅣ 249 140
VS75AⅣ 348 207

Volume of ventilation (Note:2)


Item Entire ventilation Ventilating duct
Ventilating duct
+
Local ventilation +
External exhaust
(Note:1) Built-in exhaust fan
Model fan
[m3/min] [m3/min] [m3/min] [m3/min]
VS22AⅣ 269 or more 127 or more 27 or more 77 or more
VS37AⅣ 451 or more 216 or more 45 or more 135 or more
VS55AⅣ 692 or more 333 or more 69 or more 209 or more
VS75AⅣ 966 or more 472 or more 97 or more 304 or more

(Note: 1) Local ventilation method is to install a ventilating fan near the compressor exhaust air outlet
and to directly exhaust 1/3 to 1/2 of emission air from the compressor.
(Note: 2) The volume of the ventilation determines the flow volume when allowable-temperature
range is set as 5ºC (9ºF) above ambient temperature.

Installation Conditions
3-2
VS Series INSTRUCTION MANUAL

3.2.3 Installation of ventilating exhaust duct


 Be sure to install an exhaust duct when a ventilating fan cannot be
installed to a fully-closed room.
 Do not connect the duct to the compressor with screws. For inspection,
Wire mesh
the duct should be easily removed.
 Attach a wire mesh cover to the duct outlet to keep out birds, dust or
other foreign matter.
 Prevent rain water from entering into the duct.
 Minimize bends in the duct (maximum tolerance of 20 Pa) to avoid
Ventilating fan
pressure loss.
 Maximize a radius when bending the duct.
 Install a ventilating fan to the duct outlet if the exhaust duct has a
pressure loss of more than 20 Pa (2 mmH2O).
 When installing a ventilating fan in the duct, select a heat resistant one
〔80ºC (176ºF)〕 and keep a space of 300-400 mm between the
ventilating duct and the exhaust air outlet of the compressor.

Installation Conditions
3-3
VS Series INSTRUCTION MANUAL

3.2.4 Installing a ventilating system and a ventilating duct


①Entire ventilation ②Ventilating Duct+ ③Ventilating Duct+
/ Local ventilation (*1) External exhaust fan Built-in exhaust fan

• The volume of the ventilation • Calculate the pressure loss (resistance) • If the pressure loss (resistance) in the
determines the flow volume in the ventilating duct based on the ventilating duct is over 20 Pa (2
when allowable-temperature exhaust air volume of the compressor. mmH2O), install a ventilating fan with
range is set as 5ºC (9ºF) If the result is not more than 20 Pa (2 the specified capacity inside the duct
above ambient temperature. mmH2O) for air cooling type, the taking the pressure loss into
exhaust from the compressor exhaust consideration.
outlet through the duct will be possible.
• The opening area of air inlet • Connect the ventilating duct referring to
shall be adjusted to keep the the duct installation mark at the top of
flow rate of 2 m/s or less. the compressor. The duct should be
removable. Do not fix the duct with
screws. It may hinder repair and Caution
maintenance work.
(*1) • Minimize bends in the duct to avoid Clearance "H" must be secured 300 mm
Local ventilation method is to install resistance. to 400 mm between the ventilating duct
a ventilating fan near the inlet and the compressor exhaust outlet
compressor exhaust outlet and to
directly exhaust 1/3 to 1/2 of
emission air from the compressor.

• When installing the duct, provide a full • Turn on the ventilating fan while the
radius. Duct resistance over 20 Pa (2 compressor is running, and turn it
mmH2O) could reduce the exhaust off when the compressor stops.
volume, causing temperature rise and
may stop the compressor.
• Even if the duct is connected directly • The opening area of air inlet shall
to the compressor, the temperature be adjusted to keep the flow rate of
will rise. In such a case, install a 2 m/s or less.
ventilating fan mentioned on previous
page when allowable temperature
range is set as 5ºC (9ºF) above
ambient temperature.
• Prevent rain water from entering the
duct outlet.
• If the pressure loss in the ventilating
duct is over 20 Pa (2 mmH2O), install a
ventilating fan at the duct outlet. (See
method ③.)
• Follow the same installation procedure
to install a ventilating fan and air inlet as
that of entire ventilation. The opening
area for air supply shall be adjusted to
keep the flow rate of 2 m/s or less.

Installation Conditions
3-4
VS Series INSTRUCTION MANUAL

3.3 Location of Installation to be avoided


When installing the compressor in the places shown below, the compressor may inhale mist, gas or
smoke, which will be compounded with moist in the oil and then deteriorate. This may cause clogging
and damage to the oil separator element. If location of the installation site cannot be avoided, lube oil
and oil separator element will be replaced more frequently than regular maintenance. Read the
instruction manual for further details.

3.3.1 Locations to be avoided


★Coolant mist from machining tools. ★ Smoke from the boiler.

★ Gas of decomposing plastic. ★ Effluent steam from food plant.

Caution ★Emission gas from vehicles.

Do not install the compressor in places where it may


inhale coolant mist from the machining tools, gas
from decomposing plastic, effluent steam from food
plant, smoke from the boiler, and emission gas from
vehicles.
Intake of these toxic gases or mist will cause
clogging of the oil separator element. This also may
cause an emergency stop of the compressor.

3.3.2 Ventilation method to avoid suction of toxic gas or mist

Install a suction fan and an exhaust fan, Do not install the compressor
or a suction duct. on the downstream side of gas.

Installation Conditions
3-5
VS Series INSTRUCTION MANUAL

4 Piping
4.1 Piping installation
 Unsupported long piping may cause vibrations and could cause damages to devices connected with piping.
The piping must be properly supported using hangers, fasteners, columns, etc.

 When more than two units of compressors are installed and their discharge piping is connected to the
same main header, be sure to provide the stop valves before the main header so that they can be closed
when any of compressors stop.

 Incline the main piping toward the discharge air flow to drain through the pipe smoothly.

 Provide drain valve at the bottom of the piping if there is a concave or riser piping.

 To avoid the pressure fluctuating of exhaust pipe, please install the air tank with proper or larger capacity.

 To prevent condensate reverse flow, connect a discharge piping at the top of the main piping.

 When installing riser piping, provide a riser piping at least 600 mm away from the discharge outlet for the
maintenance.

Recommended air tank capacity


When connecting to the
VS22/37A Ⅳ Min. 1.0m3 main piping, connect the
discharge piping from
VS55/75A Ⅳ Min. 2.0m3 Emergency valve (if you the above.
Main piping
add the compressor)
Discharge air
Hanger Main piping
To prevent the reverse flow such as drain.

Discharge air
Stop valve Inclination (Slope along Hanger
the air flow.)
Stop valve

Ball valve Ball valve

Drain valve Drain valve

Drain separator Drain separator

Union ※ Union ※

Work to be executed by the customer.

Compressor Compressor

Note: Be sure to connect the compressor to user’s piping and with flanges or unions, in order to
separate piping from the compressor for maintenance.

Piping
4-1
VS Series INSTRUCTION MANUAL

5 Electric Power Supply


Power supply of 380/415 V/50 Hz (3 φor 3 phase) is supplied to the unit. Remove the front cover and
pass the power cable through the opening on the left side. Then connect each cable correctly to the
terminal panel in the starter box. For normal operation, a suitable power source is required. Secure ±
5% of rated voltage during operation. In order to suppress the imbalance of the current, imbalance of
the voltage between phases shall be less than 2% is required.

5.1 Selection of the earth leakage breaker


Install an earth leakage breaker to prevent motor burnout, grounding fault, and electric shock.
(Sensitive current: 100 to 200 mA)
Recommend
Motor
Voltage Breaker
max. rated
(V) (Mitsubishi)
current
Model
VS22AⅣ 50 NV125-SV / 75A
VS37AⅣ 86 NV125-SV / 125A
380/415
VS55AⅣ 140 NV225-SV / 175A
VS75AⅣ 175 NV250-SV / 225A

5.2 Selection of the power cables


For the power cables, select EV or CV or VV cables for 600 V insulated by the polyvinyl chloride.
2
Power cable diameter (mm )
Voltage
With electric conduit pipe
Model [V]
5m or less 10m or less 20m or less
VS22AⅣ 16 16 25
VS37AⅣ 25 35 35
380/415
VS55AⅣ 70 70 70
VS75AⅣ 95 95 95
Note: If a power cable is longer than 20 m, the diameter shall be bigger than the cables
in the above table. Conduct wiring work that can arrange the cables to be the above size
by the side of the compressor unit, using the relay terminals and others.

Power cable terminal size (mm)


Voltage Power cable Earth cable
[V]
Model Terminal block Terminal block
Screw size Screw size
width width
VS22AⅣ M8 25 M6 -
VS37AⅣ M8 25 M6 -
380/415
VS55AⅣ M10 30 M10 -
VS75AⅣ M10 30 M10 -
Note: For details of the terminal block size, refer to electric wiring diagram.

Electric Power Supply


5-1
VS Series INSTRUCTION MANUAL

5.3 Selection of earth cables


Connect the earth cable to the earth terminal of the controller panel.
Apply the grounding work of 10 Ω (380/415 V) or less.
Ground the earth cable directly from the compressor.
Failure of grounding may cause electric shocks or accidents, and malfunctions of the compressor.

Voltage Earth cable size


Model [V] (mm2)

VS22AⅣ 16
VS37AⅣ 25
380/415
VS55AⅣ 35
VS75AⅣ 35

5.4 Selection of the power transformer


When the capacity of the transformer is too small, and/or the power cable is thin and long, the voltage
may drop sharply at startup, and the motor may not accelerate properly or cannot start. Therefore,
select an appropriate transformer for the motor capacity.

Capacity of transformer (kVA)


Model

VS22AⅣ 50 or more
VS37AⅣ 75 or more
VS55AⅣ 100 or more
VS75AⅣ 150 or more
Note: Use appropriate cables and a breaker as listed above. Use of any wrong size cable may
cause overheating or burning the motor and cables. Do not drive the motor with inverter
power.

Electric Power Supply


5-2
VS Series INSTRUCTION MANUAL

5.5 The Connection of the Power Cable


Remove the front cover and connect the cables to the terminal block 〔L1/R、L2/S、L3/T〕. Do not
connect to a wrong phase.
Connect the earth cable to the earth terminal 〔E〕. Be sure to protect cables in the terminal area not
to apply mechanical stress to them.

Breaker

Earth

Select the suitable


cable size.

< VS22/37A Ⅳ>

Breaker

Earth

Select the suitable


cable size.

< VS55/75A Ⅳ>

Electric Power Supply


5-3
VS Series INSTRUCTION MANUAL

5.6 Harmonics
5.6.1 Harmonic calculation
Inverters generate harmonics, whose voltage and current contained in the power supply system
may cause damages to electrical equipment.
In 1994, The Ministry of International Trade and Industry (present Ministry of Economy, Trade and
Industry) established the harmonic suppression guideline for consumers receiving power of high
voltage or especially high voltage.
Customers, who newly install, add or renew harmonic generation, must make calculations and
submit calculation sheets for outgoing harmonic currents from harmonic generating equipment to
the electric power company based on the current guidelines.

What is harmonics?

A sine wave of a commercial power supply is called a fundamental wave. A sine wave has a
frequency that is an integral multiple of the fundamental wave is called a harmonic wave. The
composition of a single fundamental wave and several harmonics is called a distorted wave.

Fundamental wave current Harmonic wave current Distorted wave current

5.6.2 Prevention of Harmonic noise trouble


Inverter's power supply harmonics may cause malfunctions or obstacles to peripheral devices.
Be sure to pay attention to harmonic noise when installing the inverter.

Precautions for prevention of harmonic noise trouble

1. Separately install the wiring of the main power supply, AC (control circuit signal etc.), and DC
(control circuit signal etc.) respectively, keeping clearance of 30 cm or more.
2. If you cannot install them separately, protect the main power supply wiring by conduits, use
shielded wires or twisted shielded wires for the AC/DC control wiring.
3. Perform appropriate grounding works and ground wiring. Ground the shield wire at single point
and minimize the ground wire length.
Note: The grounding wires also generate noises.

M ost of the noise troubles can be avoided by suppressing the influence of noise and harmonic
levels.
If the above precautions are insufficient in the certain environment, suppression devices (noise
filter, zero phase reactor, etc.) may be required.
Note: AC/DC reactor is installed to this unit to suppress harmonics.

Electric Power Supply


5-4
VS Series INSTRUCTION MANUAL

6 Lube Oil
6.1 Cautions for lube oil
 Lubricating oil drained from a compressor at the factory.
 Use the genuine oil or recommended oil by KOBELCO for refilling or
replacing lubricant, (contact us to purchase).

Definition of Genuine Oil


Brand Intervals(hr) size Part number
KOBELCO GENUINE
3000 20 L 1000095875
GENUINE SCREW OIL
LUBRICATING 4L 1000094619
OIL KOBELCO EXTRA OIL 6000
20 L 1000094625
 Never mix different brands/different grade oils.
If the compressed air is expected to be used for food production, use
food application oil "Anderol FGC 32". This oil shall be replaced every
3,000 hours of running.
For further information, contact us.
 Definition of food application oil “Anderol FGC32”
Size Part number Recommended change cycle
3,000 hours or six months
20 L 1000118851
whichever comes first

 Keep the oil level between the high limit and the low limit during operation.
 Do not operate beyond the high limit. It will cause oil leaking into the
discharge air and other problems.
Note: when the compressor stops, the oil level will exceed the higher
limit because oil return from the parts to the oil separator. This is a
normal operation.
 Refill oil, when oil level drops below the low limit during operation. We
recommend refilling the oil when the oil level is around the center between
the low limit and the high limit because the oil level could vary depending on
the load condition.

If the oil level rises much higher than the previous operation, stop the
compressor immediately and inspect it after removal of oil.
 Approximate amount of supply
Before Amount of supply After
1.7 L
VS22AⅣ

2.7 L
VS37AⅣ

High limit 5.0 L High limit


VS55AⅣ
Low limit Low limit

5.0 L
VS75AⅣ

Note:
In nominal pressure condition, if compressor running (especially high blast
running) for a long term, it will caused more oil consumption and shorter
lubricate preriod.

Lube Oil
6-1
VS Series INSTRUCTION MANUAL

6.2 How to refill lube oil


Press the stop button to stop the compressor and confirm that the [oil
separator pressure 0 Mpa] displays on the touch screen.

Turn off the earth leakage breaker

Remove the front cover of the unit and loosen the plug of the oil separator
with a wrench, and then open the oil supply port.
Refill the oil. Wipe the spilled oil completely.
Securely tighten the plug to close the oil supply port.

tighten The amount of oil at maintenance shown below.


Amount of oil
Model
loosen
Oil supply port VS22A Ⅳ 12L(13L)
VS37A Ⅳ 19L(21L)
VS55A Ⅳ 32L(40L)
VS75A Ⅳ 32L(40L)

( ) for the required amount of replacement oil during an overhaul.

● Within one minute after the compressor stopped, the pressure remains in the oil
separator.
Wait until pressure drop for two minutes or more, and then refill the oil.
● If refill the oil from any other inlets than the oil supply port, you cannot check the
oil level.
Refill the oil from the oil supply port only.
● Do not turn off the breaker within one minute after the compressor is stopped.
Because the pressure in the oil separator is being removed by regulating with the
blow-off solenoid valve.

6.3 How to drain oil


Press the stop button to stop the compressor and confirm that the [oil
Oil separator separator pressure 0 Mpa] displays on the touch screen.

Turn off the earth leakage breaker.

Open the oil drain port to drain the oil. You can use other drain plugs that
are installed in the oil cooler and the discharge pipe of the compressor as
well.
Oil drain port

Lube Oil
6-2
VS Series INSTRUCTION MANUAL

7 Operation
7.1 Procedures of Operation
■ Read carefully before starting
compressoer operation. • Do not touch any rotating parts or heated parts during the compressor
operation or right after the compressor stopped, it is extremely dangerous.
For safety and noise prevention, all unit covers must be closed.
• When an alert lamp lights on, inspect errors.
Ensure the safety around the • Check the running hours. Inspect each part accordingly.
compressor and its peripheral
before start the compressor. • Check the oil level, alarms and cautions on the controller display, abnormal
Inform an “All Clear” sign to sound and so on.
people working around.

Startup

Surely perform a “pre-


Before
operation inspection operation During
whenever to start Operation
operation.
Right after the compressor is
stopped, the pressure
remains in it, and the inverter
Stop
Perform inspection and still has the voltage.
maintenance of each part For inspections and
according to running hours maintenance, turn off the
or operating time. In case of Periodic breaker after check the
inspection
storage for a prolonged pressure 0 Mpa and make
period, store the Shutdown for sure the voltage 0 in the
a prolonged
compressor inside and period inverter to prevent any
keep it dry. electrical accidents.
Disposal

7.2 Pre-operation Inspection


① Are anything covering or blocking the air
inlets of the right side, the left side and the
exhaust outlet on the top side of the
compressor?

② Is the oil level proper?


If the oil level is lower than the low limit
when the compressor stops, refill the oil up
to the high limit,referring to the following
quantity.

The oil, which circulates through the oil High limit


cooler and piping, is proper level between Low limit
high limit and low limit in the oil separator,
when the compressor is operating.

Note: During stop operation, the oil level in the tank is changing because the amount of the return oil flow
back from the oil cooler and other parts will vary due to the running condition before the stop. Make
sure the oil level to be between high limit and lower limit at the compressor startup. Do not overfill, it
may cause poor performance of the oil return and large oil consumption.

Operation
7-1
VS Series INSTRUCTION MANUAL

7.3 Default Settings

Screen Contents Default

Power Recovery Time Inactive / 0.1 secs.

Power Failure Auto Restart Time Inactive / 1 secs.

Power Recovery Delay Time Inactive / 5 secs.

Presssure Loss Setting 0.00 MPa

Compressor Setting Communication Address 0

Communication Mode LINK

Group Control No

100 hrs. Elapsed after Maintenance Caution Yes

Pressure Detection COMP

Constant Pressure 0.60 MPa

Pressure Setting Auto Stop Pressure 0.70 MPa

Auto Restart Pressure 0.55 MPa

Replace Suction Filter 6000 hrs.

Replace Oil Filter 6000 hrs.

Change Lube Oil 6000 hrs.


Maintenance Interval
Replace O/S Element 6000 hrs.
Setting
Inspect Cooler 6000 hrs.

Annual Maintenance 6000 hrs.

Clean Dust Filter 500 hrs.

Weekly Timer Setting Inactive

Starting Delay 5 mins.

Sequence Start Delay Time 2 mins.

Sequence Stop Delay Time 2 mins.

Next Compressor Pressure Difference (DIFF) 0.02 MPa


Group Control
Advanced Compressor Switch Time 0 mins.
Load Recovery Time 8 secs.

Maximum Pressure 0.65 MPa

Minimum Pressure 0.55 Mpa

Operation
7-2
VS Series INSTRUCTION MANUAL

7.4 Operation Procedure


7.4.1 Start up
① Turn on the main power.

② Turn on the earth leakage breaker and check


the POWER lamp lights on the operation
panel.

③ Select the “Pressure Setting” on the home


screen of the touch screen.
Check settings and reset as required.

NGSC-430 NGSC-700
④ Push the Local button to select operation
modes.
Local: The〔Local〕lamp lights on.
Remote: The〔Local〕lamp lights off.

⑤ Push the Start button to start the motor while


“Local” mode is selected

⑥ Check the operating condition.


 Is the oil level in the middle of the red lines?
 Is discharge pressure or discharge
temperature abnormally high?

7.4.2 Local and Remote Switch


 By two second long press of the local button, you
can select the local mode or remote mode.
 While the Local mode is selected, the Local lamp
lights green. This setting is available during
operation.
 You can stop the compressor with the stop button
regardless of the Local / Remote mode.
 This function is available when the remote mode
is selected.

Operation
7-3
VS Series INSTRUCTION MANUAL

7.4.3 Stop
① Push the stop button to stop operating.
Check that “Oil Separator Pressure” is indicated “0
MPa.” on the touch screen
* Compressed air in the compressor is automatically
released.
② Switch off the earth leakage breaker.

● More than 3 minutes delay time is needed to restart operating after stopping operating.
● Do not turn off the breaker within 1 minute after stopping the compressor.
● The blow-off solenoid valve will regulate the pressure in the oil separator to release.

Operation
7-4
VS Series INSTRUCTION MANUAL

7.5 Touch Screen Operation


The settings of active/inactive, Yes/No, can be selected, and activated by the reset tab on the touch
screen.

◆ Standby mode
The touch screen will go off automatically after 20 minutes of inactivity.
Touch the touch screen to bring back the display

◆ Buttons on the touch screen


Screen transition Menu tabs are shown on the bottom of the screen. Tap a tab
etc.
tabs to open its screen.

Back tab Return to the previous screen.

Edit tab Open the edit screen.

Arrow keys Scroll the screen.

Function select
etc. Activate or inactivate functions
tabs

Enter tab Enter editing and input data.

Icon Open the screen to edit

Enter and modify values by on-screen keypad.

[Keys]
ESC: Escape, back to the previous screen.
CLR: Clear
On-screen
ENT: Enter
Keypad
BS: Backspace

Arrow keys: moves cursor for digits.


DEL: Delete
CANCEL: can cancel or reset operation.

Operation
7-5
VS Series INSTRUCTION MANUAL

7.6 Setting and Reset of Control Pressure


The screen of [Pressure Setting] is used when you want to change the setting of compressor.

7.6.1 Pressure Setting


These are the currently indicated number.
[Pressure setting]
NGSC-430 The pressure setting value can be
changed on the screen [Pressure
Settings
 Select Pressure settings.
You can set three different pressure
values.
Tap a tab of “No.1”, “No.2” and “No3.
The selected No. will be highlighted as
the currently selected No. Tap a value to display the shown adjacent image.
on-screen keypad.  change pressure setting value
1. Tap a [No.] tab that you want to
change.
2. Tap the edit tab.
3. On-screen keypad will pop up.
NGSC-700 (OPTION) Input new value with keys

Tap a value to display the


the currently selected No. on-screen keypad.

Pressure setting range


Possible range of pressure setting is as follows. [MPa]

Contents Default Set Range

Constant Pressure 0.60 0.40~0.85


Auto Stop Pressure 0.70 0.41~0.86
Auto Restart Pressure 0.55 0.30~0.84

Operation
7-6
VS Series INSTRUCTION MANUAL

7.7 Inverter Operation Mode


KOBELION-VS is under constant pressure control.
The discharge pressure of the compressor is continuously detected by pressure sensor, and it sends signal
to control the inverter proportionally. The motor speed is adjusted accordingly to deliver constant pressure.

Set P : Proportional Operating Inverter Motor Discharge


Compressor
pressure frequency pressure

I : Integral
Pressure
sensor

P control : The discharge pressure approaches the set pressure, but a deviation occurs from the set pressure.
I control : Reduce the deviation caused by P control (however, the response will be poor).

 Wide Range Control


The wide range control, which is newly developed ahead of all competitors worldwide, is KOBELCO’s
unique technology. It can bring the maximum capability (discharged air volume) at the user-specified
operating pressure, and it is suitable for the users who operate the compressor at the lower
discharge pressure for energy saving.

Conventional compressors  In conventional compressors, power


consumption is reduced when the discharge
Discharge
pressure pressure is decreased (which spares the motor
capacity), but the discharged air volume will not
Power change.
consumption  The wide range control technology is to supply a
maximum amount of compressed air to the user
Discharged air line by increasing the compressor speed under
volume
the optimum pressure required by the user,
(rotating speed) using spare capacity of the motor.

0.81

← 0.7
Discharge pressure

Wide range area

0.5

0.4
93 100 110(VS22 VS55/75)
109(VS37)
Amount of discharge air(%)→

Operation
7-7
VS Series INSTRUCTION MANUAL

7.8 Operational Logic


◆Operation◆
Local Operation Remote
START(Monitor) mode Remote start : ON

Weekly timer start

Start operation Start operation


No Yes
Emergency To stop
stop operation

Po≧0.2MPa Po・・・Pressure internal oil separator


Residual pressure Yes
start prevention

No
Fan inverter start : ON
Inverter start command : ON

◆Moisture purging operation◆

In the water removal operation, drain is discharged by performing the purging operation (Blow-off
solenoid valve: open).
When the drain becomes more than a certain amount, the water removal operation starts.
During the water removal operation, the message "Water removal operation" is displayed on the
lower left of the touch screen and the LOAD lamp blinks.

Operating the compressor

No
During water removal
operation

Yes

Purge operation
(Blow-off solenoid valve : open)

Operation
7-8
VS Series INSTRUCTION MANUAL

◆Shutdown◆
local Operation remote
mode

Weekly timer stop STOPbutton (monitor) Remote stop ON (open)

Stop operation

During operation of the compressor

Yes Stop
operation

No

Yes
Emergency stop input
Unload operation or
Fan inverter error

No Inverter start command : OFF


timer 0~10sec Fan inverter OFF

No

timer ≧10sec

Yes Yes Other


emergency
stops

No

No
Inverter start command : OFF Pd≧Auto stop pressure

Yes
Unload operation
timer 0~15sec

timer 0~10sec
No
timer ≧15sec
Yes
Yes Pd≦Auto start pressure Load operation

No
Fan inverter OFF
No
timer ≧10sec
Yes
Inverter start command : OFFOFF

timer 0~15sec

Pd≧Auto start pressure


Yes
No
No
timer ≧15sec
Motor start ON
Yes
Fan inverter OFF

No
Pd≧Auto start pressure

Yes
Pd・・・Discharge pressure
Inverter start command : ON
Fan inverter ON

Operation
7-9
VS Series INSTRUCTION MANUAL

7.9 Condensate removal of compressor


Compressor suctions the moisture contained in the air and is condensed into water inside the unit.

The compressed air condensation may cause rust in the unit, damages to the oil separator element and
degradation of the lubricant oil, eventually causing accidents, and damages to the airend.

In order to keep good performance of the compressor, our compressor unit has a basic function of the
condensate removal. It monitors the compressed air condensation and starts purging operation and draining
regularly when the drain volume exceeds the rated volume.

In the condensate removal operation, do not stop it with the emergency stop switch or any other ways. This will
cause failure or damages, because the removal operation isn’t complete and the condensate drain will remain.

To maintain good performance of the compressor, make sure to use KOBELCO water resistant oil filter (Parts No.
1000106735, only for VS22/37A Ⅳ ) and install an air tank that has an appropriate volume, if the compressor unit is
operated under conditions of frequently starting and stopping, or continuous low-load operation, which will cause
the drain to accumulate more.

Operation
7-10
VS Series INSTRUCTION MANUAL

8 In Case of Emergency
The emergency lamp lights red on the controller panel at
8.1 Troubleshooting emergency and the touch screen indicates errors. Until
remove causes of emergency stop and push the reset
8.1.1 Emergency stop button, the compressor will not restart.
Alarm Cause and Troubleshooting
Stop compressor and turn off the power supply.
After O/S Temp. High Release internal pressure and replace the oil
separator element at pressure 0 Mpa..
Ambient temperature is high.
Pressure settings failure.
Discharge Oil cooler clogged.
Temperature High Oil filter element clogged
Cooling water error.
Red highlighted cursor is error.
Tap the tab to go to the troubleshooting screen Dust filter clogged.
Fan inverter error occurred.
Fan Inverter Error
Contact KOBELCO service division.
Cooling Water
Shortage [water cooled Check pump and piping of the cooling water for
model only] failures, and resolve the problems.
No signal from the inverter.
Starter Error
Contact KOBELCO service division.
Sensor (Pd, Td, Po, Tc or To) detects an error.
Sensor Error
Contact KOBELCO service division.
Reverse Phase Turn off power and ensure the power cable
connection is accurate
Power supply failure
Motor Coil
Temperature High Motor error.
Dust filter clogged.
Start button or stop button error occurred.
SW Input Error
Contact KOBELCO service division.
Emergency Stop Emergency stop pushbutton pushed.
(manual) Emergency stop signal occurred.
Discharge Pressure Check piping and valve for failures, and resolve
Rise the problems.
Inverter error occurred.
Inverter Error
Contact KOBELCO service division.
External Error External signal error
O/S Minimum Pressure
Error O/S minimum pressure is not maintained.

In Case of Emergency
8-1
VS Series INSTRUCTION MANUAL

8.1.2 Cautions
The highlighted items are detected alarms now.
Tap the tab to go to the caution screen.

Alarm list
Caution Cause and Troubleshooting
Stop compressor and turn off the power supply.
O/S Element Clogged Release internal pressure and replace the O/S
element at pressure 0 Mpa.
Stop compressor and turn off the power supply.
After O/S Temperature
Release internal pressure and replace the O/S
High
element at pressure 0 Mpa.
Ambient temperature is high,
Pressure setting error.
Discharge Oil cooler clogged.
Temperature High Oil filter element clogged.
Cooling water error.
Dust filter clogged.
Ambient Temperature The ambient temperature shall be below 45℃.
Cool down the ambient temperature by ensuring
High adequate ventilation.
100 hrs. Elapsed after More than 100 hours elapsed after maintenance
Maintenance Cautions cautions.
✐Note Contact KOBELCO service division.
Power supply failure.
Motor Coil
Temperature High Motor error.
Dust filter clogged.
Discharge Pressure Check piping and valve for failures, and resolve
Rise the problems.
External Cautions External cautions signal occurred.
Inverter cautions.
Inverter caution
Contact KOBELCO service division.

✐Note: The caution lamp will blink every second, if the maintenance
indicator lamp on the panel is lighting for more than 100 hours.
Resolve the error immediately, and then reset the indicator lamp.
Tap to next screen .

In Case of Emergency
8-2
VS Series INSTRUCTION MANUAL

8.1.3 Maintenance

The highlighted items are detected maintenance alarm now.


Tap the tab to go to the maintenance screen.

Alarm list
Maintenance

Replace Suction Filter Clean suction filter from inside by air blower. Replace it if too dirty to clean

Stop compressor and turn off the power supply. Release internal pressure and
Replace O/S Element
replace the oil separator element at the pressure 0 MPa.
Stop compressor and turn off the power supply. Release internal pressure and
Replace Oil Filter
replace the oil filter at the pressure 0 MPa.
Cooler inspection required.
Inspect Cooler Inspect the cooler after stopping the compressor, make sure the cooling fan stopped
completely.
Stop compressor and turn off the power supply. Release internal pressure and
Change Lube Oil
change lube oil. Check the oil level and refill oil, if the oil level is below minimum level.

Sensor error Contact KOBELCO service division.

Annual Maintenance Cooler inspection and maintenance required. Contact KOBELCO service division.

Grease Motor Regrease the motor. (grease required motor only)


Discharge pressure exceeds the set value.
Pressure Drop High
Reduce pressure loss and lower the set value.
Dust filter clogged.
Clean Dust Filter
Remove the dust filter and clean by vacuum or water-wash.
Require to replace backup battery. Open the rear cover of the touch panel to replace
Replace TP Battery
the backup battery.
The drain is accumulated. Keep the compressor loading
Moisture Condensation Do not stop the compressor until complete maintenance caution reset, which can be
reset when the drain volume is lower than the rated volume.

In Case of Emergency
8-3
VS Series INSTRUCTION MANUAL

8.1.4 Troubleshooting
Troubleshoot the problem following instructions.

Error Troubleshooting

Stop compressor and turn off the power supply. Release internal pressure and
Oil Filter Clogged
replace the oil filter.

1.Cooling water temperature high


Cool down the temperature of the cooling water
Cooling Water Error
2. Cooling water shortage
Check pump and piping for failures and resolve the problems.

Stop the compressor.


Condensor Fins Clogged.
Clean the condenser fins.

Stop the compressor.


Circuit Error
Turn off power, and check wiring.
Cooler cleaning required.
Oil Cooler Clogged Clean the cooler after stopping the compressor and make sure the cooling fan is
stopped completely.
Stop the compressor.
Power Supply Failure Check voltage drop, voltage imbalance and single phase operating for failures,
and resolve problems.
Stop the compressor.
Motor Error. Check the coil resistance.
If lower than 10 MΩ, contact KOBELCO service division.
The ambient temperature shall be below 45℃.
Ambient Temperature High
Cool down the ambient temperature by ensuring adequate ventilation.
Minimum 3 minutes of operation required.
Stopping the compressor within 3 minutes after starting may cause dryer failure.
Frequent Starts and Stops
Starting the compressor within 3 minutes after stopping may cause overcurrent in
the dryer motor and may activate the interlock of the dryer motor.

Wait more for than 3 minutes after starting and stopping operations.
Pressure Setting Error
Check pressure setting of the compressor and the volume of the air receiver tank.

Remove the dust filter and clean it by air blower and clean the filter attached below
Dust Filter clogged.
the controller as well.

In Case of Emergency
8-4
VS Series INSTRUCTION MANUAL

8.1.5 How to reset Maintenance Timer


After maintenance work, reset the maintenance timer as follows.

Long press the reset tab for three seconds.

[Maintenance Reset] screen will be displayed.

Select the item to reset and then press the Yes tab.

The confirmation window of the maintenance reset will


pop up.

The reset is completed. The maintenance indicator lamp


will light off.

Tap [Yes] tab to reset


✐Note:
Make sure all of maintenance is done properly, and then reset the timer.

8.1.6 How to check Operation Panel

LED1
FAIL

LED2
Control panel
RUN

The “RUN” LED lamp lights green, when the


Normal control panel works normally.

The “FAIL” LED lamp lights red, when the


Abnormal control panel works abnormally.

In Case of Emergency
8-5
VS Series INSTRUCTION MANUAL

8.2 Interlock
The KOBELION-VS series have the protection devices as follows, which can detect any abnormalities
to prevent failures.

8.2.1 Emergency Stop


Error Location Detector Condition 1 Condition 2 Note
Main Motor Coil
1 Main Motor Coil Thermocouple 180℃, 3 secs. 175℃, 3 mins.
Temperature High
Discharge Inside of the Oil
2 Thermocouple 110℃ or higher
Temperature High Separator
Temperature after
3 after Oil Separator Thermocouple 110℃ or higher
O/S High
Discharge
Temperature Controller
Thermocouple
After O/S
Temperature High Controller
Thermocouple
Discharge Zero error>
Controller
4 Sensor Error Pressure Sensor Cut off
Oil Recovery Unit 5%
Controller
Pressure Sensor
External Pressure
Controller
Sensor (option)
Main Motor Coil
Temperature Controller
Thermocouple
5 Input Phases Loss Inverter Inverter Input Phases Loss

6 Main Motor Overload Inverter Inverter Overload

7 Inverter Overload Inverter Inverter Overload


for Inverter
8 Inverter Derating Inverter Inverter Inverter Derating
model
9 Instant Overcurrent Inverter Inverter Overcurrent

10 Cooling fin Overheat Inverter Inverter Cooling fin overheat

11 Inverter Error Inverter Inverter -


Inverter
No startup signal for 1
12 Starter Error [for inverter Controller
minute. .
equipped model]
for
13 Main Motor overload Main Motor Thermal SW start up standard
model
Error of the
14 Fan Motor Overload Fan Motor Thermal SW start up
fan inverter
20 secs.
20 secs. passed after passed after
15 SW Input Error Controller Controller
pressing the START button pressing the
STOP button
Emergency
Emergency Stop
Emergency Stop Emergency Stop Signal stop
16 Pushbutton Switch Controller
Pushbutton Switch (Auto) pushbutton
Push
pressed
Pressure setting
Discharge Pressure Pressure 0.75MPa,Pd≥0.85MPa,1sec.
17 after After Cooler
High Sensor 0.85MPa,Pd≥0.95MPa,1sec.
1.05MPa,Pd≥1.15MPa,1sec.
18 External Error Controller Controller External Contact Error
Minimum Pressure Inside of Oil Pressure 1 mins. passed after start up
19
Error Separator Sensor Po<0.3 MPa
RST wiring
20 Reverse Phase Controller Controller
Connection Error

In Case of Emergency
8-6
VS Series INSTRUCTION MANUAL

8.2.2 Caution
Caution Location Detector Condition 1 Condition 2 Note
Discharge Inside of the Oil
1 Thermocouple 105℃ or higher
Temperature High Separator
After the O/S after Oil
2 Thermocouple 105℃ or higher
Temperature High Separator
Pressure
difference
Oil separator between the Oil Pressure 0.12 MPa
3
Element clogged Separator and Sensor or more
after the After
Cooler
for
4 Inverter Error Inverter Inverter Inverter
model
Ambient Compressor Air
5 Thermocouple 47℃ or higher
Temperature High Inlet
100 hrs. elapsed
6 after maintenance Controller Controller
alarm
Main Motor Coil
7 Main Motor Coil Thermocouple 175℃, 3 secs.
Temperature High
Pressure setting
Discharge Pressure Pressure 0.75MPa,Pd≥0.82 MPa,1sec.
8 Controller 0.85MPa,Pd≥0.92 MPa,1sec.
Rise Sensor
1.05MPa,Pd≥1.12 MPa,1sec.
9 External Caution Controller Controller External contact Signal

8.2.3 Maintenance
Maintenance Condition Detector Condition 1 Condition 2
Replace Suction Operating Hours Operating Indicator
1 Controller 6000 hrs.
Filter difference of pressure Hours -6.23kPa
Operating
2 Replace Oil Filter Operating Hours Controller 6000 hrs.
Hours
Operating
3 Change Lube Oil Operating Hours Controller 6000 hrs.
Hours
Replace Oil Operating Hours Operating
4 Controller 6000 hrs. 0.11 MPa or more
Separator Element difference of pressure Hours
Operating
5 Inspect Cooler Operating Hours Controller 6000 hrs.
Hours
Ambient
6 Replace Sensor Thermocouple
Temperature
Operating Operation start
7 Annual Maintenance Operating Hours Controller 6000 hrs.
Hours to 1 year
Discharge of Line pressure-Discharge Using the line
8 Pressure Drop High Compressor, Line Controller pressure pressure
Pressure ≧Pressure loss settings (option)
Grease Motor [for
Operating
9 grease required Operating Hours Controller 2000 hrs.
Hours
motor]
Amount of drain>
Moisture Standard model
10 Controller Controller Amount of oil
Condensation only
replenishment 3.5%
Operating
11 Clean Dust Filter Operating Hours Controller 500 hrs.
Hours
12 Replace TP Battery Touch Screen Touch Screen Battery Voltage Reduction

In Case of Emergency
8-7
VS Series INSTRUCTION MANUAL

8.3 Before Calling for Service


When the compressor doesn’t work properly, check to resolve problems following the below
instructions before calling a repair service.
For [call] indicated problems, contact a specified service shop, dealer or KOBELCO service division.

Problems Causes Troubleshooting [call]


Cut off cable Replace the cable.

No sound from Circuit board failure. Relay failure. Blown


Replace defective parts.
Motor fuse Transformer failure

Repair or replace the motor after insulation


Motor failure
No rotating

resistance check.

For low capacity power supply, change


Low voltage
the capacity of the transformer.

Motor is Wrong cable Replace the cable with the specified size.
humming only
Motor failure Repair or replace the motor. [call]

Rotor is not rotating Overhaul the compressor [call]

Blow-off solenoid valve failure Adjust or replace the solenoid valve. [call]

Leakage from piping Tighten the fitting or replace the packing.


Discharge pressure
drop
Suction filter clogged Clean or replace the element.

Oil separator element clogged Replace the O/S element.

Pressure higher than the specified value Select an air reservoir with proper capacity.
Blow-off from
safety valve
Safety valve failure Replace the safety valve. [call]

Too short load cycle Increase the capacity of piping (air reservoir).
Capacity control failure
Improper pressure setting Reset the pressure setting.

Different brand oil used, not KOBELCO


genuine oil. (KOBELCO GENUINE SCREW Change lube oil with KOBELCO GENUINE SCREW OIL
OIL or KOBELCO EXTRA OIL) or not or KOBELCO EXTRA OIL or specified oil.
specified oil used.

Lube oil deterioration in Lower the temperature by ensuring


a short running High ambient temperature
adequate ventilation.

Mixture of water Inspect the air inlet and drain the oil.

Deteriorated lube oil remains Perform flushing before changing the lube oil. [call]

Foreign material entered in the compressor Overhaul and repair. [call]


Abnormal sound in the
airend.
Worn or damaged bearings Replace the bearing. [call]

Loosen bolts or screws Tighten the bolt or screw.


Other abnormal sound
Improper installation Fill mortar and level the compressor
horizontally.
Loosen bolts or screws Tighten the bolt or screw.

Improper installation Fill mortar and level the compressor


Excessive vibration horizontally.
Unbalance of cooling fan by being
Clean the blades.
contaminated

In Case of Emergency
8-8
VS Series INSTRUCTION MANUAL

8.3.1 When motor does not rotate


This machine is equipped with the reversed-phase relay. The motor will not rotate if wiring connection
is made reversed-phase.
“Reversed phase” appears on the alarm screen when power supply has reversed-phase.

[Alarm Menu (Emergency Stop) ]

The highlighted item shows a detected failure.


Tap the tab to view the details.

1. First, turn off the breaker.

2. Connect power cables accurately as per wiring diagram.

3. Turn on the breaker again and push the Reset button on the control panel. .
Check “Reverse phase” is not red in the alarm list and the motor rotates properly.

In Case of Emergency
8-9
VS Series INSTRUCTION MANUAL

9 Maintenance and Parts Replacement


9.1 Guideline for Maintenance and Parts Replacement
Inspection intervals and part replacement depend on the installation site as well as operating
conditions.
Refer the below table for your trouble free operation.

VS22AⅣ / VS37AⅣ
●:required 〇:recommended △:inspection/cleaning ☆:visual check

0.7 MPa
Every Every 2 Every 4 Every 6 yrs.
Components year years years O/H
Daily
6,000 12,000 24,000 36,000
hrs. hrs. hrs. hrs.
Airend Air end inner parts
Bearings ●
O-rings ●
C snap rings ●
W - lip seal ●
Sleeve ●
O-rings ●
Anti-vibration rubber ●
Filters Suction fliter assembly
Filter element ● ● ● ●
Indicator △ △ △ ○
Oil separator element Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
O-rings
Element ● ● ● ●
Case ● ● ● ●
Tank ●
Base ●
Flange ●
Seal washers ● ● ● ●
Oil filter Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Dust filter ☆ △ △ △ △
Magnet filter ●
Electric parts Touch screen battery ●
☆ ☆ ☆
Pressure sensor ○
(*A) (*A) (*A)
☆ ☆ ☆
Temperature sensor ○
(*A) (*A) (*A)
Main motor △ △ △
Main motor
(*B) (*B) (*B)
Motor inverter Fan motor
Bearings (load side/unload side) ●
Main inverter
Cooling fan ○
Fan inverter ○
Cooling fan ●
*A: Difference check
*B: Insulation check Continued to the next page

Maintenance and Parts Replacement


9-1
VS Series INSTRUCTION MANUAL

Continued from the previous page


0.7 MPa
Every 2 Every 4 Every 6 yrs.
Components Every year
years years O/H
Daily
6,000 12,000 24,000 36,000
hrs. hrs. hrs. hrs.
Valves Capacity control valve
valve body ● ● ●
O-rings ● ● ●
Seal Ring ● ● ●
Springs ● ● ●
Pressure isolating check valve
Internal parts ● ● ●
Electro magnetic valve ○
Thermo control valve
Element ●
O-rings ●
Safety Valve △ △ △ △
Oil recovery valve ○ ○ ●
Coolers Oil cooler △ △ △ △
After cooler △ △ △ △
Others KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)

Oil level gauge check oil ○ ○ ●
level
Air exhaust silencer
silencer ● ● ● ●
Cap ● ● ● ●
Filter ● ● ● ●
Rubber hose
Rubber hose (discharge line) ○ ○ ○
Rubber hose(others) ○
Rubber hose (oil supply line) ● ● ●
Synflex Hose ○
Anti-vibration rubber ●
Suction hose ○ ○ ○
O-rings
Oil inlet
(KOBELCO EXTRA OIL ) ● ● ● ●
Oil inlet
(KOBELCO GENUINE SCREW OIL ) Every 3,000 hrs. (3,000, 6,000, 9,000…)
Oil inlet Every 3,000 hrs. (3,000, 6,000, 9,000…)
(ANDEROL FGC32)
Others ●
N2 tube ○

Note: 1 Oil separator element and oil filter element shall be replaced
 every year (or 6,000 hr.) if KOBELCO EXTRA OIL used.
 every six months (or 3,000 hr.) if KOBELCO GENUINE SCREW OIL used.
 every six months (or 3,000 hr.) if ANDEROL FGC32 used.
This guideline doesn’t define warranty period.
Replacement intervals can be shortened depend on how to use or where to install.
Replacement intervals are determined based on 6000 running hours per year, not exceed highest
temperature setting, and yearly average ambient temperature of 30℃ or below.

Maintenance and Parts Replacement


9-2
VS Series INSTRUCTION MANUAL

VS55A Ⅳ / VS75A Ⅳ

●:required 〇:recommended △:inspection/cleaning ☆:visual check


0.7MPa
Every Every 2 Every 4 Every 6years
Components
Daily year years years O/H
6,000h 12,000h 24,000h 36,000h
Airend Air end inner parts
bearings ●
O rings ●
C snap rings ●
W-lip seal ●
Sleeve ●
O rings ●
Anti-vibration rubber ●
Filters Suction filter assembly
Filter element ● ● ● ●
Indicator △ △ △ ○
Oil separator element Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Seal washer Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
O rings
Pressure isolating valve ●
Oil filter ※1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Dust filter ☆
Magnet filter ●
Electric parts Touch panel battery ●
☆ ☆ ☆
Pressure sensor ○
(*A) (*A) (*A)
☆ ☆ ☆
Temperature sensor ○
(*A) (*A) (*A)
Main motor △ △ △
Main motor
(*B) (*B) (*B)
Motor ·Inverter Fan motor
Bearings (load side/unload side) ●
Main inverter
Cooling fan ○
Fan inverter ○
Cooling fan ● ○

*A: Difference check


*B: Insulation check

Maintenance and Parts Replacement


9-3
VS Series INSTRUCTION MANUAL

0.7MPa
Every
Every 2 Every 4
Components Daily Every year 6years
years years
O/H
6,000h 12,000h 24,000h 36,000h
Valves Capacity control valve
Valve body ● ● ●
O rings ● ● ●
U type packing ● ● ●
Spring coil ● ● ●
Pressure isolating check valve
Inner parts ● ● ● ●
Electro magnetic valve
silencer ○
suction control valve ●
Thermo control valve
Element ●
O rings ●
Safety valve △ △ △ △
Oil recovery valve ○ ○ ●
Cooler Oil cooler △ △ △ △
After cooler △ △ △ △
Others KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)

Oil level gauge (oil level ○ ○ ●
check)
Air exhaust silencer
Silencer ● ● ● ●
Cap ● ● ● ●
Filter ● ● ● ●
Rubber hose
Oil tank to AC ○
Rubber hose (oil supply line) ● ● ●
Synflex hose ○
Anti-vibration rubber ●
O rings
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Others ●
N2 tube ○
Suction hose ○ ○ ○
Rubber seal for pipe coupling ● ● ●
1. Oil separator element and oil filter element shall be replaced
 every year (or 6,000 hr.) if KOBELCO EXCELLENT OIL used.
 every six months (or 3,000 hr.) if ANDEROL FGC32 used.
2. This guideline doesn’t define warranty period.
3. Replacement intervals can be shortened depend on how to use or where to install.
4. Replacement intervals are determined based on 6000 running hours per year, not exceed highest
temperature setting, and yearly average ambient temperature of 30℃ or below.

Maintenance and Parts Replacement


9-4
VS Series INSTRUCTION MANUAL

9.2 Daily Maintenance


9.2.1 Cleaning dust filter
 Remove the dust filter cover and remove the filter.
 The dust filter should be cleaned either with vacuum or water.

③ ① ③

① ②


VS22/37A Ⅳ VS55/75A Ⅳ

9.2.2 Cleaning of suction filter


 Open front cover and remove an element, and then clean the element from inside by air blower.
Replace the element, if too dirty to clean.
 After cleaning, attach the element into the body firmly and attach the cover.
 The suction filter may be clogged early under operating environments where the dust filter is clogged early. In
such cases, early replacement is recommended.
 Operation continued without replacing or cleaning the suction filter may cause damage to the duct hose.

Model Part No.


VS22AⅣ 1000093982
VS37AⅣ 1000085237
VS55AⅣ 1000084242
VS75AⅣ 1000084225

9.3 Insulation Test Procedures for Compressor Unit


 This compressor has a controller, which consists of electronic parts, and an inverter. Various kinds of serge
absorbers are also equipped for noise prevention. Therefore, if insulation tests are made on the unit at the
voltage beyond the setting for the serge absorbers, it could cause wrong test results and damage on the
controller.
Perform insulation tests, following the procedures shown below.
Test voltage: Criteria for evaluation
DC 500 V or less (at normal temperature) :
R-FG 500 V DC 10 MΩ or more
S-FG 500 V DC 10 MΩ or more
T-FG 500 V DC 10 MΩ or more
【Insulation test for motor】
Disconnect the power cables (U,V,W) connected to the inverter
panel.
Measure the insulation of terminals for the motor lead wires and the
base plate (FG: frame ground).
【Insulation test for control circuit】
Disconnect the power cables (R,S,T) connected to the inverter panel.
Then remove all the connectors inserted into the controller.
Measure the insulation of terminals on the terminal block of control panel and the base plate
(FG: frame ground).
The insulation test procedures mentioned above conform to the local law about electrical appliance and
material control.

Maintenance and Parts Replacement


9-5
VS Series INSTRUCTION MANUAL

10 Long Term Shutdown, Transfer and Disposal


10.1 Long Term Shutdown
 Be sure to switch off the short circuit breaker.
 Be sure to close the discharge valve.
 To maintain good conditions of the unit, operate it once a week
for 20 minutes according to chapter 7 “Operation”.
 When any problem is found, resolve it for your trouble free
operation.
 Before restarting the compressor, see chapter 7 “Operation”.
 Compressor unit must be stored inside.

Do not store the compressor outdoor.

10.2 Transfer and Disposal


10.2.1 Transfer
 For further information, contact the designated service shop, distributor, or KOBELCO service
division.

10.2.2 Disposal
 Drain the lube oil, before disposing KOBELION-VS series compressor.
 In case of disposal of consumable supplies such as elements, contact with an industrial waste
disposal contractor.
 Dispose the motor as general industrial waste. The rotor must be disposed after demagnetization at
temperature of 500ºC (932ºF) of more with a gas burner or in a furnace.
 For further instruction, contact the designated service shop, distributor, or KOBELCO service division.

Long Term Shutdown, Transfer and Disposal


10-1
VS Series INSTRUCTION MANUAL

11 Remote Control
11.1 Handling External Signals
 The following external signals are provided.
(See the electric wiring diagram on page 12-3.)
《Input signals to compressor》
・Remote・Run (Terminal X8-COM2 → Closed : Runt)
・Remote・Stop (Terminal X9-COM2 → Open : STOP)
・Remote・Load (Terminal XA-COM2)
* Only for KOBELCO group control panel
・External Error (Terminal XB-COM2 → Emergency : STOP)

《Output signals from compressor》


・Emergency stop Output (Terminal Y20-COM4 → Closed : ERROR)
・Caution Output (Terminal Y21-COM4 → Closed :CAUTION)
・Maintenance Output (Terminal Y22-COM4 → Closed :MAINTENANCE)
・Remote Selestion Output (Terminal Y23-COM4 → Closed : REMOTE)
・Running Output (Terminal Y24-COM4→ Closed : RUNNING)

Item
Screw size Terminal block width
Model
VS22AⅣ
VS37AⅣ
M3.5 7.5 mm
VS55AⅣ
VS75AⅣ

1. Input signals should be no-voltage contact input.


Electric current of 24 V is supplied from the controller side.
2. The allowable contact capacity of output signal is AC 250 V / 3 A, DC 30 V / 3 A.
The minimum load is DC 5 V / 100 mA.
3. The terminal X9-COM2 has been short-circuited at the factory.
Remove this terminal in the remote control mode.
4. Remote (input signal to controller) should be input by one shot at 500 ms or more.
Shorter pulse signals may not be recognized.

Any modification without prior permission of KOBELCO shall invalidate the warranty
even within.

✓:active -:inactive
Mode Start button Stop button Remote ON Remote OFF

Local ✓ ✓ ― ―

Remote ― ✓ ✓ ✓

Remote Control
11-1
VS Series INSTRUCTION MANUAL

12 Specifications
12.1 Products Specifications
12.1.1 VS22AⅣ/ VS37AⅣ/ VS55AⅣ/ VS75AⅣ
Model
VS22AⅣ VS37AⅣ VS55AⅣ VS75AⅣ
Item
Voltage (V) 380/415
Frequency (Hz) 50
0.4 Mpa (m3/min) 4.72 7.6 11.8 15.1
13.1Air 0.7 Mpa 3
(m /min) 4.22 7.0 10.6 13.9
disc12.9harge
volume 0.80 Mpa (m3/min) 3.94 6.5 10 13.1
0.85 MPa (m3/min) 3.8 6.3 9.65 12.9
Pressure Atmospheric pressure (1 bar)
Suction
Temperature (ºC ) 2- 45 (36-113 °F)
condition
Altitude (m) <1000
Discharge Pressure (MPa) 0.4 – 0.85
condition Temperature (ºC ) below 45℃ (ambient temperature: 30℃)
Constant pressure control by inverter
Pressure control system
(Control pressure ±0.01Mpa)
Capacity range % 15 - 110 18 - 109 20~110 16~110
Normal output (kW) 22 37 55 75
Service factor 1.14 1.19 1.23 1.2
Type Permanent magnet type Three-phase synchronization
Main motor

Voltage (V) 380/415


Number of poles 6P
Protection system Fully closed
Cooling system Oil cooled
Starter system Inverter
Insulation class H
Output (kW) 0.55 1.1 1.5 3
Fan motor

Type Three phase asynchronous motor


Number of poles 4P
Insulation class F
Discharge pipe size R2 1 R2 1 1/2 R2 2
Lubricating oil (L) 12(13) 19(21) 32(40)
Dimensions (W × D × H) (mm) 1250x850x1500 1550x950x1600 2200 x1200 x1700
Weight (kgs) 560 720 1330 1400
Noise level (dB【A】) 55 58 63 65
(1)The air discharge volumes are converted to the suction condition (20ºC, 1bar, 0%RH) of compressor.
Measurement guidelines for air discharge volume in accordance with ISO1217 Appendix C equivalent.
(2) Discharge pressure measured at the outlet of the after cooler.
(3) Lubricating oil drained from a compressor at the factory. Be sure to use “KOBELCO GENUINE SCREW OIL” or
“KOBELCO EXTRA OIL” at the time of exchange.
(4) The noise data is measured in an anechoic room, at a point which is 1.0 meter from the floor and 1.5 meter from all
directions of the unit (Noise level ±3dB(A)). The noise value will be larger than the mentioned value when the unit is
installed in a room that creates echoes.
(5) The compressed air must not be used for any respiratory equipment.
(6) As for the guaranteed values, contact us.
(7) Anchor bolts and mounting brackets for the base plate are not provided with standard unit.
(8) The quantity of lubricating oil is for the required amount during maintenance. The quantity in bracket is for the required
amount of oil during an overhaul.
(9)Please contact our distributor if you will use compressors above 1000 meters of sea level.

Specifications
12-1
VS Series INSTRUCTION MANUAL

12.1.2 Inverter Specifications


Main Inverter
Model
(For IPM Motor)
Item
VS22A Ⅳ VS37A Ⅳ VS55A Ⅳ VS75A Ⅳ

Frequency (Hz) 50
Output rating

Voltage (V) Three phase 380/415

Capacity (kVA) 45 69 114 134

Current (A) 60 91 150 176

Cooling Method Air cooled


Functions

Control Method Sine wave PWM

Harmonic Protection DC reactor

12.1.3 Fan Inverter Specifications

Model Fan Inverter


Item
VS22A Ⅳ VS37A Ⅳ VS55A Ⅳ VS75A Ⅳ

Frequency (Hz) 50
specification
Electrical

Voltage (V) Three phase 380/415

Capacity (kVA) 2.7 4.7 3.9 8.6

Current (A) 2.3 4.1 4.1 8.8

Cooling Method Air cooled


Functions

Control Method Sine wave PWM

Harmonic Protection AC Input reactor

Specifications
12-2
WIRING DIAGRAM (VS22A VS37A)
AC380/415V
50/50Hz
Kobelink
VS Series

CN19 TOUCH PANEL


5
※ For compressor without dryer, single phase transformer. GW MiniDin 8P 4
CN1 CN2 CN3 CN13 CN4 CN14 3 COM1
L1/R L2/R L3/T E VHR-7N VHR-3N VHR-6N XAP-15V-1 VHR-2N XAP-05V-1 2
1 2 15 1 2 1
1 3 5 7 1 3 1 2
ELB +V -V
EARTH LEAKAGE PS1
BREAKER
CP (L)(N)
380/200V 50Hz CIRCUIT E

T10

R10
S10
415/200V 50Hz PROTECTOR OPERATION PANEL
※OPTION L1/R L2/R L3/T E 3A
CONTROLLER TR E
R1 R2 PB-EMS R11
1 2 R10
1 K K
S1 S2 3 4 S10
2 T1 T2 5 6 T10
L

COM6

COM8
CT 0~800A
CN20
XAP-02V-1 R S T E 9 INSIDE OF CONTROLLER 5 CN9
PB-EMS 88A VHR-05N
MAIN INV MINOR FAILURE CN10
X1 Y1 X5 VHR-10N
U V W
CM MAIN ANSWER SK SK SK
SR SK
12.2 Wiring Diagram

RY1 Y2 X6
12.2.1 VS22A Ⅳ / VS37 AⅣ

CN12 7 8 5 6 1 2 3 4 10 1 2 3 4
FWD X Y Z
INV START XAP-03V-1 Y28 Y29 Y2A Y2B
CM CMY COM1

Y2D

Y2C
CONTROLLER R ST E
MAIN VIC ED

F1
1A
F2
1A
INVERTER CC CC RY1 RY2 RY3 88A
INSIDE OF MONITOR
FAN ROTATION SPEED COMMAND S2
COMMUNICATION IMPUT P1 DC4~20mA FAN INVERTER
RS485 DC REACTOR CC
A 1 DX+ FLA
COM1
S10

RY2
SV2C

P+
SV1C
B 2 DX- RES RESET
FG 3 SD X4 FLC RY3
F START
30C

SV4S SV4C
CN-15 COM1 FAN INV ERROR U VW SV1 SV SV SV2
XAP-03V-1 30B U V W
MAIN INV ERROR
MAIN INV
MAIN MAIN INV FAN INV 30A X7 IM
MINOR FAN MOTOR
ANSWER FAILURE ERROR ERROR
SV1S
SV2S

12-3
U VW
E
X7 X4 DRYER CAUTION
X6 X5 U V W XD COM3 (OPTION)
COM1 S10
IPM
7 6 8 5 9 E
INSIDE OF CONTROLLER 6 7 8 9 10 CN7 INSIDE OF CONTROLLER CN8 INSIDE OF CONTROLLER
CN5 MAIN MOTOR
CN6 INSIDE OF CONTROLLER VHR-6N VHR-4N
XAP-10V-1
INVERTER START

SOLENOID VALVE
RESET COMMAND

1 4 2 3 XAP-10V-1
FAN MOTOR START

1 2 3 4 5
BLOW-OFF SOLENOID
DRYER START COMMAND

6 1 2 3 4 5 6 1 2 3
DRYER DRAIN SOLENOID VALVE

2 8.2
FOR CAPACITY CONTROL VALVE

X0 X3 X1 X2

X9

X8
XA
XB

COM2
COM2

COM2
COM2
INSIDE OF CONTROLLER
※JUMP WIRE COM4 Y20 Y21 Y22 Y23 Y24 COM5 Y25 Y26 Y27
LT
BO
P1 P2 T1 T2 T3 T4 M3

1 2 1 2 1 2 1 2 1 2 1 2
( PREPARED BY CUSTOMER )

PB-EMS
( PREPARED BY CUSTOMER )
X8-COM2 CLOSE:START
X9-COM2 OPEN:STOP
RUNNING OUTPUT

CAUTION OUTPUT
PT PT 6.5

DRYER ERROR
MAINTENANCE OUTPUT

EMERGENCY STOP
DETAIL OF CONTROL TERMINAL BLOCK

EXTERNAL ERROR

SUCTION INDICATOR
EMERGENCY STOP OUTPUT

REMOTE STOP OFF

REMOTE START ON
REMOTE SELESTION OUTPUT

OIL MOTOR AMBIENT AFTER OIL


DISCHARGE SEPARATOR DISCHARGE
COIL TEMPERATURE SEPARATOR LT
( PREPARED BY CUSTOMER ) PRESSURE PRESSURE TEMPERATURE
TEMPERATURE TEMPERATURE BO

REMOTE LOAD COMMAND


EXTERNAL SIGNAL M8
4 22.5

The following signals are prepared as external signals.


Input signals to compressor
·REMOTE RUN (TERMINAL X8-COM2→ CLOSE:RUN)
·REMOTE STOP (TERMINAL X9-COM2→ OPEN:STOP)
62

※1 Input signals should be no-voltage contact input. Electric current of 24V is supplied from the controller side.
·REMOTE LOAD (TERMINAL XA-COM2 ) ※ Only for KOBELCO group control board ※2 The allowable contact capacity of output signal is AC250V/3A, DC30V/3A. The minimum load is DC5V/100mA.
·EXTERNAL ERROR(TERMINAL XB-COM2→ EMERGENVY:STOP) ※3 The terminal X9-COM2 has been short-circuited at the factory.Remove this terminal in the remote control mode.
Output signals from compressor ※4 Remote (input signal to controller) should be input by one shot at 500ms or more. shorter pulse signals may not be recognized.
·EMERGENCY STOP OUTPUT (TERMINAL Y20-COM4→CLOSE:ERROR)
·CAUTION OUTPUT (TERMINAL Y21-COM4→CLOSE:CAUTION) <CAUTION> 25
·MAINTENANCE OUTPUT (TERMINAL Y22-COM4→CLOSE:MAINTENANCE)
Any modification without prior permission of KOBE STEEL may void the warranty even within the warranty period. 
·REMOTE SELESTION OUTPUT (TERMINAL Y23-COM4→CLOSE:REMOTE) DETAIL OF POWER TERMINAL BLOCK
·RUNNING OUTPUT (TERMINAL Y24-COM4→CLOSE:RUNNING ) ISSUE
INSTRUCTION MANUAL

DRAWING NO. A000149884 02

Specifications
WIRING DIAGRAM (VS55A VS75A)

Kobelink
CN19
VS Series

INSIDE OF CONTROLLER 5 5 TOUCH PANEL


AC380/415V MiniDin 8P
GW 4 4
CN1 CN2 CN3 CN13 CN4 CN14 3
50Hz + - 3 COM1
VHR-7N VHR-3N VHR-6N XAP-15V-1 VHR-2N XAP-05V-1
2 9
ELB 1
L1 L2 L3 E +V -V
1357 1 3 1 2 12 15 12 8 - +
EARTH LEAKAGE TR
BREAKER PS1 E
380,415/200V 50Hz CP
(L)(N)
380,415/200V 60Hz CIRCUIT

R10
S10
T10
E OPERATION PANEL
PROTECTOR
L1 L2L3 E
TR E PB-EMS
※OPTION R1 R2 1 2 R10 R11
1 k K
S1 S2 3 4 S10
CONTROLLER
2 T1 T2 5 6 T10

COM8
COM6
CN20 L
CT 0~800A CP1
R S TE 9 INSIDE OF CONTROLLER 5
88A
MAIN INV MINOR FAILURE
PB-EMS U V W
INV EMERGENCY STOP I-X1 Y1 X5
CM MAIN ANSWER SR SK SK SK
SK
Y2 X6 CN12
RY1 XAP-03V-1 X Y Z 1 2 3 4 5 6 7 8 9 1 2 3 4
FWD
INV START CONTROLLER E ED CN10 Y28 Y29 Y2A Y2B
CMY COM1 CN9
12.2.2 VS55A Ⅳ / VS75A Ⅳ

CM + R S T
VHR-10N VHR-05N

Y2D

Y2C
- AI
AC

FU1
MAIN

FU2
CN-15 FAN ROTATION SPEED COMMAND FAN RY1 RY2 RY3 88A
XAP-03V-1 INVERTER DC4~20mA INVERTER
Y2E
Y2F
SV4S

COM7

COM1 MC SC
RS485 DX+ P+ FAN INV
DC REACTOR S4 RY2 RESET
DX- P1 ERROR X4 MA
RY3 START
SV2C

SV1C

SD U V W S1
30C COM1
INSIDE OF MONITOR U V W SV1 SV2
COMMUNICATION IMPUT 30B INSIDE OF OPERATION PANEL
MAIN INV ERROR IM CN2
30A FAN MOTOR E XAP-02V-1
X7
1 2
SV1S
SV2S

UVW
U VW MAIN INV COM7
FAN INV MINOR MAIN MAIN INV
S10

12-4
MAIN MOTOR ERROR FAILURE ANSWER ERROR
IPM
E XC COM3XDCOM3 XECOM3XFCOM3

X4 X5 X6 X7 COM1

FUNCTION BUTTON
DRYER START

CN7 INSIDE OF CONTROLLER


FAN INV RESET
FAN INV START

INVERTER START

VHR-6N
SOLENOID VALVE

5 6 7 8 9 6 7 8 9 10
BLOW-OFF SOLENOID

CN5 INSIDE OF CONTROLLER CN6 INSIDE OF CONTROLLER


XAP-10V-1 INSIDE OF CONTROLLER
1 2 3 4 5 6 XAP-09V-1
1 2 3 4 1 2 3 4 5 P1 P2 T1 T2 T3 T4
FOR CAPACITY CONTROL VALVE
DRYER DRAIN SOLENOID VALVE

+ +
PT PT

- -
XA

X8
X9
COM2
XB
COM2

COM2
COM2

Y20 Y21 Y22 Y23 Y24 X0 X1 X2 + - + - + - + -


COM4
※JUMP WIRE

PB-EMS
TEMPERATURE

( PREPARED BY CUSTOMER )

CAUTION OUTPUT
RUNNING OUTPUT
X8-COM2 CLOSE:START
X9-COM2 OPEN:STOP

MAINTENANCE OUTPUT
DRYER ERROR

WATER-BREAK
DISCHARGE PRESSURE
AFTER OIL SEPARATOR

AMBIENT TEMPERATURE

EMERGENCY STOP OUTPUT


OILSEPARAOR PRESSURE

EXTERNAL ERROR

REMOTE SELESTION OUTPUT


EMERGENCY STOP
DISCHARGE TEMPERATURE

REMOTE STOP OFF

REMOTE START ON
MOTOR COILTEMPERATURE

SUCTION INDICATOR
35 33
REMOTE LOAD COMMAND

EXTERNAL SIGNAL
2 6.5
The following signals are prepared as external signals. 31
M3 BOLT
Input signals to compressor
·REMOTE RUN (TERMINAL X8-COM2→ CLOSE:RUN)
·REMOTE STOP (TERMINAL X9-COM2→ OPEN:STOP)
·REMOTE LOAD (TERMINAL XA-COM2 ) ※ Only for KOBELCO group control board ※1 Input signals should be no-voltage contact input. Electric current of 24V is supplied from the controller side.
·EXTERNAL ERROR(TERMINAL XB-COM2→ EMERGENVY:STOP) ※2 The allowable contact capacity of output signal is AC250V/3A, DC30V/3A. The minimum load is DC5V/100mA.
※3 The terminal X9-COM2 has been short-circuited at the factory.Remove this terminal in the remote control mode. M10 BOLT
※4 Remote (input signal to controller) should be input by one shot at 500ms or more. shorter pulse signals may not be recognized. 8.2
Output signals from compressor
<CAUTION> VS55/75A 380/415V
·EMERGENCY STOP OUTPUT (TERMINAL Y20-COM4→CLOSE:ERROR)
INSTRUCTION MANUAL

·CAUTION OUTPUT (TERMINAL Y21-COM4→CLOSE:CAUTION) DETAIL OF CONTROL TERMINAL BLOCK DETAIL OF POWER TERMINAL BLOCK
Any modification without prior permission of KOBE STEEL may void the warranty even within the warranty period. 
·MAINTENANCE OUTPUT (TERMINAL Y22-COM4→CLOSE:MAINTENANCE) ISSUE
·REMOTE SELESTION OUTPUT (TERMINAL Y23-COM4→CLOSE:REMOTE)
·RUNNING OUTPUT (TERMINAL Y24-COM4→CLOSE:RUNNING ) DRAWING NO. A000179381 01

Specifications
CONNECTION DIAGRAM(VS22 VS37A VS55A VS75A)
MAIN INVERTER
VS Series

TEMPERATURE SENSOR, AMBIENT TEMPERATURE SENSOR, MOTOR COIL

TEMPERATURE SENSOR, AFTER OIL SEPARATOR TEMPERATURE SENSOR, DISCHARGE

PRESSURE SENSOR, OIL SEPARATOR

PRESSURE SENSOR, DISCHARGE

P4 P3 P2 P1 CN12
CN14 CN17 CN15 T6 T5 T4 T3 T2 T1 CN20
P5

CN4
CN18 CN6

CN13
CN3
TO CONTROLLER(NGSC-430)
OPERATION
BOARD TB1

CN6
TO OPERATION BOARD CN2
12.3 Connection Diagram

TRANSFORMER

CN5
CN10 CN9 CN8 CN7 CN1

CONTROLLER BOARD
TO OPERATION BOARD

12-5
AC REACTOR

BLOW-OFF SOLENOID VALVE FOR SUCTION


SOLENOID CAPACITY CONTROL VALVE INDICATOR
FAN INVERTER
SV1 SV2
DC EMERGENCY
REACTOR STOP SWITCH
12.3.1 VS22A Ⅳ / VS37A Ⅳ / VS 55A Ⅳ / VS75A Ⅳ

PB-
EMS
RUN STOP TO OPERATION CN1,5,6,7,8,9,10

TB2 RY1 RY2 FU1 FU2


CT SENSOR
(OPTION)

COOLING FAN
TERMINAL
BLOCK
TR CP2 CP1 88A TB1

M4

TEMPERATURE SENSOR, MOTOR COIL


OPERATION BOARD TO INVERTER TERMINAL BLOCK

MAIN MOTOR ISSUE

DRAWING NO.
INSTRUCTION MANUAL

A000149719 02

Specifications
FLOW DIAGRAM(VS22A VS37A)
VS Series

COMPRESSED AIR COOLING AIR LUBRICATING OIL

SYMBOL NAME SYMBOL NAME


Po PRESSURE SENSOR ( OIL SEPARATOR ) Tc TEMPERATURE SENSOR ( MAIN MOTOR COIL )

Pd PRESSURE SENSOR ( DISCHARGE ) V1/V2 INVERTER ERROR (INCLUDE OVERCURRENT)


Td TEMPERATURE SENSOR ( DISCHARGE ) Ta TEMPERATURE SENSOR ( AMBIENT )
Ts TEMPERATURE SENSOR ( AFTER OIL SEPARATOR ) Si SUCTION INDICATON

AIR EXHAUST

Pd

COMPRESSED AIR
AFTER
COOLER OIL COOLER
DISCHARGE
12.4 System Diagram

USER’S SCOPE
V2
12.4.1 VS22A Ⅳ / VS37A Ⅳ

SILENCER COVER
FAN
INVERTER
SILENCER

FAN THREE-WAY BLOW-OFF


SOLENOID VALVE SOLENOID
MOTOR
OIL SEPARATOR ELEMENT VALVE

COOLING FAN CAPACITY


CONTROL VALVE THERMOSTAT VALVE

12-6
SUCTION FILTER SAFETY
OIL RECOVERY VALVE
Si CHECK VALVE
Ts

CHECK VALVE

MIN.PRESSURE
Tc VALVE

MAIN MOTOR
Po
OIL FILTER

COMPRESSOR

OIL SEPARATOR

Td

AIR INLET MAGNET FILTER AIR INLET


MAIN INVERTER
V1

Ta ISSUE
DRAWING NO. A000149679 01
INSTRUCTION MANUAL

Specifications
FLOW DIAGRAM (VS55A VS75A)
VS Series

COMPRESSED AIR COOLING AIR LUBRICATING OIL


SYMBOL NAME SYMBOL NAME
Po PRESSURE SENSOR ( OIL SEPARATOR ) Tc TEMPERATURE SENSOR ( MAIN MOTOR COIL )

Pd PRESSURE SENSOR ( DISCHARGE ) V1/V2 INVERTER ERROR (INCLUDE OVERCURRENT)


Td TEMPERATURE SENSOR ( DISCHARGE ) Ta TEMPERATURE SENSOR ( AMBIENT )
Ts TEMPERATURE SENSOR ( AFTER OIL SEPARATOR ) Si SUCTION INDICATON

AIR EXHAUST

Pd
12.4.2 VS55A Ⅳ / VS75A Ⅳ

COMPRESSED AIR DISCHARGE AFTER


OIL COOLER
COOLER

USER’S SCOPE
V2
SILENCER COVER
FAN
INVERTER
SILENCER

3-WAY BLOW-OFF
FAN
SOLENOID VALVE SOLENOID
MOTOR VALVE

12-7
COOLING FAN CAPACITY
CONTROL VALVE THERMOSTAT VALVE
SUCTION FILTER SAFETY
OIL RECOVERY VALVE
Si CHECK VALVE
Ts

CHECK VALVE
Min. PRESSURE
VALVE
Tc
MAIN MOTOR Po
OIL FILTER

COMPRESSOR OIL SEPARATIOR


ELEMENT
OIL SEPARATION

Td

AIR INLET AIR INLET


MAGNET FILTER
MAIN INVERTER
V1

ISSUE
INSTRUCTION MANUAL

Ta
DRAWING NO. A000179396 01

Specifications
VS Series INSTRUCTION MANUAL

13 Warranty and Indemnity


13.1 Warranty
 In case failure occur during the normal use as per the instruction manual and other precautions has been
followed correctly, we will repair it free of charge under certain conditions and for a certain period. Contact
your local dealer.

13.2 Warranty Period


 The warranty period of this machine shall be 12 months from the date of the test run completion or 18
months from the date of shipment, whichever comes first.
Note: “After the test run completion” means; at the time when the test run (procedure and activities of
receiving materials test) is completed.
 In case problems occur within the warranty period and when it is determined that the problems are caused
clearly by our defective design or manufacturing work, we will repair or replace the parts free of charge
without delay.
 Even within the warranty period of this machine, the warranty does not cover the following cases:

 Failure and damage caused by the natural disasters or accidents beyond human
control.
 Failure and damage caused by materials selected or supplied by customer, or
caused by defects of specifications (design, materials and others) required by
customer..
 Failure and damage caused by repair or modification conducted by customer
without notifying us first.
 Failure and damage caused by not adhering to the operating procedures,
periodical inspections, maintenance and storage described in the specification
sheets and instruction manuals issued by KOBELCO.
Failure and damage caused by defective foundation, building and/or equipment
other than this machine.

 Consult with our distributor for repairs on the machine after the warranty period is expired. Repairs will be
made on the customer's expense upon request. The repairs can maintain the performance.

13.3 Indemnity
 Under no circumstances, including any illegality, KOBELCO is not liable for indirect, incidental,
consequential or any kind of damages, including, but not limited to, loss of production, loss of anticipated
profits, loss of operational profits, loss of materials and products, or indirect losses, however same shall be
caused by any other similar responsibility.

Warranty and Indemnity


13-1
【SINGAPORE】
KOBELCO MACHINERY ASIA PTE. LTD.
20 Pioneer Crescent #04-01West Park Bizcentral, 628555 SINGAPORE
Tel : +65-6261-9621 Fax : +65-6261-3719

【THAILAND】
KOBELCO COMPRESSORS (THAILAND) LTD.
2170 Bangkok Tower, Room No.1102, 11th Floor, New Petchburi Road, Bangkapi, Huaykwang, Bangkok 10310
Tel: (66) 2 308 0211 , Fax: (66) 2 308 0214

【MALAYSIA】
KOBELCO COMPRESSORS MALAYSIA SDN . BHD.
 No 9, Jalan Sepadu 25/123A, Seksyen 25,40400 Shah Alam Selangor, Malaysia
Tel : +60-3-5525-2757 Fax : +60-3-5525-3596

【VIETNAM】
KOBELCO COMPRESSORS VIETNAM CO., LTD.
43-45 Lam Ha Street, Bo De Ward, Long Bien District, Hanoi, Vietn am
Tel : +84-4-3944-7781 Fax : +84-24-3944-7780

【INDONESIA】
PT KOBELINDO COMPRESSORS
JL. RAYA TANJUNG BARAT NO . 85. TANJUNG BARAT, JAGAKARSA JAKARTA SELATAN, 12530 , INDONESIA.
Tel : +62-21-782-7002 Fax : +62-21-782-7025

【PHILIPPINES】
KOBELCO COMPRESSORS AND MACHINERY PHILIPPINES CORPORATION
19th Floor Panorama Tower, 34th Street Corner Lane A, Bonifacio Glob al City, Taguig City
Tel : +632-897-8736 +632-899-1997 Fax : +632-897-8737

【INDIA】
KOBELCO COMPRESSORS INDIA PVT.LTD.
249G, 3rd Floor AIHP TOWER Udyog Vihar, Phase IV, Near India Bulls Building, 122015 Gurgaon
Tel +91-124-4380750 Fax +91-124 438 0770

Machinery Business / Compressor Division Kobelco Compressors Manufacturing (Shanghai) Corporation


9-12, Kita-Shinagawa 5-Chome, Shinagawa-ku, Tokyo 141-8688, JAPAN 1515 Xing Rong Road Jiading Industrial District Shanghai,
Tel : +81-3-5739-5342 Fax : +81-3-5739-534 5 201815, People's Republic of China

www.kobelco-comp.co.jp
Address inquiries to……

You might also like