Professional Documents
Culture Documents
Kolbeko PDF
Kolbeko PDF
MMMANMMMMMMANM
ANUAL
MODEL
VS22AⅣ / VS37AⅣ
VS55AⅣ / VS75AⅣ
All rights reserved. This publication may not be reproduced or distributed, in whole or
in part, without the prior written consent of Kobe Steel,Ltd./Kobelco Compressors CN_MANU_VS22375575A41_E-03
Manufacturing (Shanghai) Corporation [KOBELCO]. 1000164107-03
VS Series INSTRUCTION MANUAL
Contents
Contents...................................................... I 7 Operation ........................................... 7-1
Preface ....................................................... II 7.1 Procedures of Operation ................................. 7-1
1 Safety Information ............................ 1-1 7.2 Pre-operation Inection ..................................... 7-1
7.3 Default Settings ............................................... 7-2
1.1 General Precautions ....................................... 1-1
7.4 Operation Procedure ....................................... 7-3
1.2 Alert and Safety Symbols ................................ 1-1
7.5 Touch Screen Operation ................................. 7-5
1.3 Caution and Warning labels ............................ 1-1
7.6 Setting and Reset of Control Pressure ............ 7-6
1.4 Safety Rules.................................................... 1-2
7.7 Inverter Operation Mode .................................. 7-7
1.5 Precautions at Installation Site ........................ 1-4
7.8 Operational Logic ............................................ 7-8
1.6 Electric Wiring ................................................. 1-5
7.9 Condensate removal of compressor .............. 7-10
1.7 Operation ........................................................ 1-6
1.8 Shutdown ........................................................ 1-7 8 In Case of Emergency ....................... 8-1
1.9 Lubricant ......................................................... 1-8 8.1 Troubleshooting ............................................... 8-1
1.10 Overhaul ....................................................... 1-8 8.2 Interlock ........................................................... 8-6
1.11 Precautions for Inverter ................................. 1-9 8.3 Before Calling for Service ................................ 8-8
1.12 Precautions for Permanent Magnet Motor .. 1-10 9 Maintenance and Parts Replacement
2 Nomenclature.................................... 2-1 ............................................................ 9-1
2.1 Overview ......................................................... 2-1 9.1 Guideline for Maintenance and Parts Replacement
.................................................................... 9-1
2.2 Main Parts ....................................................... 2-3
9.2 Daily Maintenance ........................................... 9-5
2.3 Controller ........................................................ 2-5
9.3 Insulation Test Procedures for Compressor Unit
3 Installation Conditions ..................... 3-1 .................................................................... 9-5
3.1 Place to be installed ........................................ 3-1 10 Long Term Shutdown, Transfer and
3.2 Installation space for safe operation ............... 3-1 Disposal ........................................... 10-1
3.3 Location of Installation to be avoided .............. 3-5 10.1 Long Term Shutdown .................................. 10-1
4 Piping ................................................ 4-1 10.2 Transfer and Disposal ................................. 10-1
4.1 Piping installation ............................................ 4-1 11 Remote Control ............................... 11-1
5 Electric Power Supply ...................... 5-1 11.1 Handling External Signals ........................... 11-1
5.1 Selection of the earth leakage breaker ........... 5-1 12 Specifications .................................. 12-1
5.2 Selection of the power cables ......................... 5-1 12.1 Products Specifications ............................... 12-1
5.3 Selection of earth cables ................................. 5-2 12.2 Wiring Diagram ............................................ 12-3
5.4 Selection of the power transformer ................. 5-2 12.3 Connection Diagram .................................... 12-5
5.5 The Connection of the Power Cable ............... 5-3 12.4 System Diagram .......................................... 12-6
5.6 Harmonics ....................................................... 5-4
13 Warranty and Indemnity ................. 13-1
6 Lube Oil ............................................. 6-1 13.1 Warranty ...................................................... 13-1
6.1 Cautions for lube oil ........................................ 6-1 13.2 Warranty Period........................................... 13-1
6.2 How to refill lube oil ......................................... 6-2 13.3 Indemnity ..................................................... 13-1
6.3 How to drain oil ............................................... 6-2
Contents
I
VS Series INSTRUCTION MANUAL
Preface
Thank you very much for selecting “KOBELION series”, which is package type screw compressor of
Kobe Steel, Ltd (hereinafter referred to as KOBELCO)
Read this instruction manual carefully for proper installation, operation, and maintenance.
Keep this manual in a safe place near the unit for quick reference.
Model Code
◆ Model Code ◆
The KOBELION series is identified by the following code :
VS22AⅣ
VS ・・・KOBELION-VS series
22 ・・・Motor output 22:22 kW 37:37 kW 55:55kW 75:75 kW
A ・・・Cooling system A:Air cooled
Ⅳ ・・・Series type
Accessories
Model
VS22A Ⅳ VS37A Ⅳ VS55A Ⅳ VS75A Ⅳ
Parts name
Forklift hole cover Forklift hole cover
4 qty 4 qty 4 qty 4 qty (Magnet Sheet)
(Magnet Sheet)
Preface
II
VS Series INSTRUCTION MANUAL
1 Safety Information
1.1 General Precautions
・ Carrying-in work, installation, operation, maintenance and inspections of the
machine must be performed by the well-trained workers.
・ We will not be responsible for any injury and failure/damage of the machine
caused by modification by customer.
・ Strictly follow the local regulations and the safety standard established in the
respective region.
・ Do not use compressed air for any respiratory equipment.
Name plate
SCREW COMPRESSOR
MADE IN CHINA
ATTENTION ATTENTION
VS37AIV
Safety Information
1-1
VS Series INSTRUCTION MANUAL
Safety Information
1-2
VS Series INSTRUCTION MANUAL
When moving the unit, attach supports and fixtures to the oil separator
Oil separator
to prevent piping and anti-vibration rubber from any damages.
After installation, the supports and fixtures must be removed.
Keep the supports and fixtures as required during maintenance.
Holders
◎ Carring by a forklift
Insert forks into fork-holes of the base plate.
Place protector between the unit and the forklift to prevent damage.
Safety Information
1-3
VS Series INSTRUCTION MANUAL
Do not install in a site that contains toxic gas, it can cause deterioration
of lube oil and corrosion in parts.
Do not install the machine near work places where using flame or the
ambient temperature may exceed 45ºC.
Do not hold inflammable materials around the unit.
1.5.2 Installation
When installing the unit in a closed room, equip a ventilation system
that has an appropriate capacity.
In case of earthquakes, build a concrete basement and secure the unit
with anchor bolts.
The concrete basement and the bolts shall be installed according to the
latest seismic design method.
Safety Information
1-4
VS Series INSTRUCTION MANUAL
1.6.2 Breaker
Install an earth leakage breaker for the power source appropriate to the
model.
Do not install knife switch alone. It is insufficient for protection.
Safety Information
1-5
VS Series INSTRUCTION MANUAL
1.7 Operation
1.7.1 Operation
Do not hold any inflammable materials around the machine. Never use
flame near the machine.
Do not perform welding work around the machine. The compressor
may catch a fire from spark.
Do not touch exhaust outlet and the peripheral area, which are heated
up during the operation.
Turn off the main power when you need to touch any rotating parts,
such as a ventilating fan.
Be noted that the compressor automatically start when the pressure
drops to the recovery value.
Safety Information
1-6
VS Series INSTRUCTION MANUAL
1.8 Shutdown
1.8.1 Parallel operation
Stop the compressor, close the discharge valve and allow it drain.
1.8.6 Inspection during shutdown (Oil separator element cover, only for VS22/37A Ⅳ)
Ask our certified technician to remove and install the oil separator
element cover.
If you want to do it yourself, make sure to tighten all bolts of cover, to
appropriate torque values, by using torque wrench. Torque values are
mentioned on the data plate attached to the element cover.
Safety Information
1-7
VS Series INSTRUCTION MANUAL
1.9 Lubricant
1.9.1 Lube oil
Be sure to use “KOBELCO GENUINE SCREW OIL” or “KOBELCO
EXTRA OIL.
Never mix different brand oils or different grade oils.
The poor circulations by downgraded oil, insufficient lubricant and high
viscosity occur. It causes abnormally high temperature and may cause
a fire.
Do visual check on oil conditions once a month. Refill or change the oil
as required.
1.9.3 Refill
Refill oil when the oil level is below the low limit in the unit running.
Press the stop button on the controller panel to stop the compressor.
High limitt
Turn off the breaker. Check “Oil Separator pressure” is “0 MPa”
Low limit indicated on the touch screen.
Note that the pressure remains in the oil separator for two minutes after
the compressor unit is stopped.
Refill oil after making sure that the internal pressure is released.
1.10 Overhaul
Overhaul shall be performed after every six years, regardless of
operating hours.
Replace the main motor bearings and clean the motor coils.
Turn off the power before overhaul the compressor.
Oil separator
For maintenance (o/s element replacement), install fixtures the oil
separator to prevent piping and anti-vibration rubber from damages.
Keep the fixtures for next maintenance.
Fixture
Safety Information
1-8
VS Series INSTRUCTION MANUAL
For maintenance or inspection, turn off the main power, and check that
the motor has stopped and the CHARGE lamp of the inverter is off.
If touched right after power shutdown, it may cause an electric shock.
1.11.3 Modification
Never modify the unit.
It may cause electric shocks or injuries
Do not connect static capacitors between the inverter and the motor. Or
the capacitor and the inverter including their parts may be burnt or
damaged.
Do not connect any different motor (induction motor or others) with the
inverter, which is designed to KOBELCO products. Or it may cause
damages in the inverter.
1.11.4 Noise
A DC reactor is equipped with the unit. If radio or electronic devices are
around the compressor unit, install a noise filter to the power supply
side.
Safety Information
1-9
VS Series INSTRUCTION MANUAL
Carefully remove the motor rotor, which has magnetic attraction force.
Otherwise, the stator coil may be damaged.
Keep clock, watch, measuring instruments etc. away from the rotor.
Otherwise, they may malfunction or be damaged.
1.12.2 Wiring
Connect a suitable cable as specified to the inverter board.
Failure to observe this may result in abnormal operation, personal injury
or damage to equipment.
1.12.3 Disposal
Dispose the motor as general industrial waste. The rotor must be
disposed after demagnetization at a temperature of 500ºC (932 ºF) or
more with a gas burner or in a furnace.
Strictly follow the local applicable environmental legislations.
Safety Information
1-10
VS Series INSTRUCTION MANUAL
2 Nomenclature
2.1 Overview
VS22A Ⅳ/ VS37A Ⅳ
Controller NGSC-430
(Touch Screen, Operation panel)
(NGSC-700 OPTION)
Nomenclature
2-1
VS Series INSTRUCTION MANUAL
VS55A Ⅳ/ VS75A Ⅳ
Nomenclature
2-2
VS Series INSTRUCTION MANUAL
Operation panel
Blow-off solenoid valve
Opens to discharge compressed
air when the compressor is
stopped or moisture is removed.
Oil filter
Remove foreign materials in
lubricating oil.
Main motor
Nomenclature
2-3
VS Series INSTRUCTION MANUAL
VS55A Ⅳ/ VS75A Ⅳ
Operation panel
Suction filter
Oil cooler
Cools lubricating oil.
After-cooler
Cools compressed air.
Main motor
Air end
(KOBELION dedicated IPM
Has rotor with ideal profile to motor)It is a high efficiency
reduce vibration and noise level permanent magnet motor that
and improved performance. realizes Kobelco original
technology "wide range control".
Nomenclature
2-4
VS Series INSTRUCTION MANUAL
2.3 Controller
2.3.1 NGSC-430
The controller consists of a touch screen, operation panel, message lamps and operating condition
lamps, which are organized according to their functions for simple and accurate settings.
⑩
⑦
⑮ ⑧ ⑪
⑨
⑯
①
⑫
⑰
② ③
⑬ ⑭
④ ⑤
Operation Panel
② LOCAL button (available during the operation)
To select how to start or stop the compressor by local mode or remote mode.
The Local LED lamp is “on” in local mode or “off” in the remote mode.
③ RESET button
To reset EMERGENCY, CAUTION and MAINTENANCE alarms.
④ STOP button
● To stop compressor operations. To unlock the standby mode.
⑤ START button
● To start the compressor in local mode.
⑮ HOME button
● To go to the home screen, which will appear after the logo displays.
Nomenclature
2-5
VS Series INSTRUCTION MANUAL
⑩
⑦
⑮ ⑧ ⑪
⑨
⑯
⑫
⑰ ② ③
⑬ ⑭
④ ⑤
The LED lamps above indicate various conditions of the compressor by combination of
lighting and blinking.
Nomenclature
2-6
VS Series INSTRUCTION MANUAL
2.3.2 NGSC-700(OPTION)
The monitor consists of touch panel, operation panel with keys and various indicators LED lamps, in
order to set up and operate compressor easily and accurately according to the conditions of use.
Touch Panel
① Touch screen
● Indicates operating condition, various setting, and alarms.
● The lamp at the top-right corner indicates the status of
touch panel. (Green: in normal operation)
⑥
⑩
⑦
⑧ ⑪
①
⑨
② ③
⑬ ⑭
④ ⑤
Operation Panel
③ RESET button
Press it to reset alarms of EMERGENCY, CAUTION and MAINTENANCE.
④ STOP button
⑤ START button
● In local mode, press it to start the compressor.
Nomenclature
2-7
VS Series INSTRUCTION MANUAL
④ ⑤
Indications of LEDs
⑥ POWER (green)
⑫ LOCAL (green)
The LED lamps above indicate various conditions of the compressor by combination of lighting and blinking.
Refer to the next section for details.
Nomenclature
2-8
VS Series INSTRUCTION MANUAL
3 Installation Conditions
3.1 Place to be installed
Refer to the following points to select an installation location.
This machine is designed for indoors use only. Do not install it outdoors.
Install this machine at an altitude below 1,000 m. Contact us if installing the machine higher than 1,000 m.
This machine is equipped with the precision electronic components. Never expose the machine to the rain water.
Avoid installation in high humidity areas.
The temporary storage site also needs to be properly kept. Avoid damp places to prevent leakage and corrosion.
Do not install the machine at a place that contains a lot of dust and harmful gases such as chlorine gas,
hydrogen sulfide gas, sulfur dioxide, ozone of high density, etc.
Do not install the compressor unit at a place where it may inhale oil mist and coolant mist from the machining
center, smoke from the boiler or gas of decomposing plastics. It may cause clogging in the oil separator and an
emergency stop.
Do not install the machine where the ambient temperature exceeds 45ºC. It may cause severe accidents such
as fire and burning of the machine.
Install the machine horizontally. Do not place blocks or any other things under the machine, this may cause
improper functioning of the compressor.
Install the machine in a place that does not create vibrations.
Please note that the noise level may vary with building structure or where the machine is installed.
Upper side
Rear side
Front side
mm
Model Front side Right side Rear side Left side Upper side
VS22A Ⅳ 600 or more 600 or more 500 or more 600 or more 1000 or more
VS37A Ⅳ 750 or more 600 or more 500 or more 600 or more 1000 or more
VS55A Ⅳ
600 or more 600 or more 500 or more 600 or more 1000 or more
VS75A Ⅳ
Installation Conditions
3-1
VS Series INSTRUCTION MANUAL
Provide a suitable air intake area so as not to create negative pressure in the room.
Select a ventilating fan that is bigger than the air volume in the following table.
In case of low ceiling, exhaust heat circulates to the suction side and it may cause ambient temperature
rise.
It should be noted that when the ambient temperature exceeds 45 ℃, the compressor will shut down.
At this time, it is necessary to try to cool down.
(Note: 1) Local ventilation method is to install a ventilating fan near the compressor exhaust air outlet
and to directly exhaust 1/3 to 1/2 of emission air from the compressor.
(Note: 2) The volume of the ventilation determines the flow volume when allowable-temperature
range is set as 5ºC (9ºF) above ambient temperature.
Installation Conditions
3-2
VS Series INSTRUCTION MANUAL
Installation Conditions
3-3
VS Series INSTRUCTION MANUAL
• The volume of the ventilation • Calculate the pressure loss (resistance) • If the pressure loss (resistance) in the
determines the flow volume in the ventilating duct based on the ventilating duct is over 20 Pa (2
when allowable-temperature exhaust air volume of the compressor. mmH2O), install a ventilating fan with
range is set as 5ºC (9ºF) If the result is not more than 20 Pa (2 the specified capacity inside the duct
above ambient temperature. mmH2O) for air cooling type, the taking the pressure loss into
exhaust from the compressor exhaust consideration.
outlet through the duct will be possible.
• The opening area of air inlet • Connect the ventilating duct referring to
shall be adjusted to keep the the duct installation mark at the top of
flow rate of 2 m/s or less. the compressor. The duct should be
removable. Do not fix the duct with
screws. It may hinder repair and Caution
maintenance work.
(*1) • Minimize bends in the duct to avoid Clearance "H" must be secured 300 mm
Local ventilation method is to install resistance. to 400 mm between the ventilating duct
a ventilating fan near the inlet and the compressor exhaust outlet
compressor exhaust outlet and to
directly exhaust 1/3 to 1/2 of
emission air from the compressor.
• When installing the duct, provide a full • Turn on the ventilating fan while the
radius. Duct resistance over 20 Pa (2 compressor is running, and turn it
mmH2O) could reduce the exhaust off when the compressor stops.
volume, causing temperature rise and
may stop the compressor.
• Even if the duct is connected directly • The opening area of air inlet shall
to the compressor, the temperature be adjusted to keep the flow rate of
will rise. In such a case, install a 2 m/s or less.
ventilating fan mentioned on previous
page when allowable temperature
range is set as 5ºC (9ºF) above
ambient temperature.
• Prevent rain water from entering the
duct outlet.
• If the pressure loss in the ventilating
duct is over 20 Pa (2 mmH2O), install a
ventilating fan at the duct outlet. (See
method ③.)
• Follow the same installation procedure
to install a ventilating fan and air inlet as
that of entire ventilation. The opening
area for air supply shall be adjusted to
keep the flow rate of 2 m/s or less.
Installation Conditions
3-4
VS Series INSTRUCTION MANUAL
Install a suction fan and an exhaust fan, Do not install the compressor
or a suction duct. on the downstream side of gas.
Installation Conditions
3-5
VS Series INSTRUCTION MANUAL
4 Piping
4.1 Piping installation
Unsupported long piping may cause vibrations and could cause damages to devices connected with piping.
The piping must be properly supported using hangers, fasteners, columns, etc.
When more than two units of compressors are installed and their discharge piping is connected to the
same main header, be sure to provide the stop valves before the main header so that they can be closed
when any of compressors stop.
Incline the main piping toward the discharge air flow to drain through the pipe smoothly.
Provide drain valve at the bottom of the piping if there is a concave or riser piping.
To avoid the pressure fluctuating of exhaust pipe, please install the air tank with proper or larger capacity.
To prevent condensate reverse flow, connect a discharge piping at the top of the main piping.
When installing riser piping, provide a riser piping at least 600 mm away from the discharge outlet for the
maintenance.
Discharge air
Stop valve Inclination (Slope along Hanger
the air flow.)
Stop valve
Union ※ Union ※
Compressor Compressor
Note: Be sure to connect the compressor to user’s piping and with flanges or unions, in order to
separate piping from the compressor for maintenance.
Piping
4-1
VS Series INSTRUCTION MANUAL
VS22AⅣ 16
VS37AⅣ 25
380/415
VS55AⅣ 35
VS75AⅣ 35
VS22AⅣ 50 or more
VS37AⅣ 75 or more
VS55AⅣ 100 or more
VS75AⅣ 150 or more
Note: Use appropriate cables and a breaker as listed above. Use of any wrong size cable may
cause overheating or burning the motor and cables. Do not drive the motor with inverter
power.
Breaker
Earth
Breaker
Earth
5.6 Harmonics
5.6.1 Harmonic calculation
Inverters generate harmonics, whose voltage and current contained in the power supply system
may cause damages to electrical equipment.
In 1994, The Ministry of International Trade and Industry (present Ministry of Economy, Trade and
Industry) established the harmonic suppression guideline for consumers receiving power of high
voltage or especially high voltage.
Customers, who newly install, add or renew harmonic generation, must make calculations and
submit calculation sheets for outgoing harmonic currents from harmonic generating equipment to
the electric power company based on the current guidelines.
What is harmonics?
A sine wave of a commercial power supply is called a fundamental wave. A sine wave has a
frequency that is an integral multiple of the fundamental wave is called a harmonic wave. The
composition of a single fundamental wave and several harmonics is called a distorted wave.
1. Separately install the wiring of the main power supply, AC (control circuit signal etc.), and DC
(control circuit signal etc.) respectively, keeping clearance of 30 cm or more.
2. If you cannot install them separately, protect the main power supply wiring by conduits, use
shielded wires or twisted shielded wires for the AC/DC control wiring.
3. Perform appropriate grounding works and ground wiring. Ground the shield wire at single point
and minimize the ground wire length.
Note: The grounding wires also generate noises.
M ost of the noise troubles can be avoided by suppressing the influence of noise and harmonic
levels.
If the above precautions are insufficient in the certain environment, suppression devices (noise
filter, zero phase reactor, etc.) may be required.
Note: AC/DC reactor is installed to this unit to suppress harmonics.
6 Lube Oil
6.1 Cautions for lube oil
Lubricating oil drained from a compressor at the factory.
Use the genuine oil or recommended oil by KOBELCO for refilling or
replacing lubricant, (contact us to purchase).
Keep the oil level between the high limit and the low limit during operation.
Do not operate beyond the high limit. It will cause oil leaking into the
discharge air and other problems.
Note: when the compressor stops, the oil level will exceed the higher
limit because oil return from the parts to the oil separator. This is a
normal operation.
Refill oil, when oil level drops below the low limit during operation. We
recommend refilling the oil when the oil level is around the center between
the low limit and the high limit because the oil level could vary depending on
the load condition.
If the oil level rises much higher than the previous operation, stop the
compressor immediately and inspect it after removal of oil.
Approximate amount of supply
Before Amount of supply After
1.7 L
VS22AⅣ
2.7 L
VS37AⅣ
5.0 L
VS75AⅣ
Note:
In nominal pressure condition, if compressor running (especially high blast
running) for a long term, it will caused more oil consumption and shorter
lubricate preriod.
Lube Oil
6-1
VS Series INSTRUCTION MANUAL
Remove the front cover of the unit and loosen the plug of the oil separator
with a wrench, and then open the oil supply port.
Refill the oil. Wipe the spilled oil completely.
Securely tighten the plug to close the oil supply port.
● Within one minute after the compressor stopped, the pressure remains in the oil
separator.
Wait until pressure drop for two minutes or more, and then refill the oil.
● If refill the oil from any other inlets than the oil supply port, you cannot check the
oil level.
Refill the oil from the oil supply port only.
● Do not turn off the breaker within one minute after the compressor is stopped.
Because the pressure in the oil separator is being removed by regulating with the
blow-off solenoid valve.
Open the oil drain port to drain the oil. You can use other drain plugs that
are installed in the oil cooler and the discharge pipe of the compressor as
well.
Oil drain port
Lube Oil
6-2
VS Series INSTRUCTION MANUAL
7 Operation
7.1 Procedures of Operation
■ Read carefully before starting
compressoer operation. • Do not touch any rotating parts or heated parts during the compressor
operation or right after the compressor stopped, it is extremely dangerous.
For safety and noise prevention, all unit covers must be closed.
• When an alert lamp lights on, inspect errors.
Ensure the safety around the • Check the running hours. Inspect each part accordingly.
compressor and its peripheral
before start the compressor. • Check the oil level, alarms and cautions on the controller display, abnormal
Inform an “All Clear” sign to sound and so on.
people working around.
Startup
Note: During stop operation, the oil level in the tank is changing because the amount of the return oil flow
back from the oil cooler and other parts will vary due to the running condition before the stop. Make
sure the oil level to be between high limit and lower limit at the compressor startup. Do not overfill, it
may cause poor performance of the oil return and large oil consumption.
Operation
7-1
VS Series INSTRUCTION MANUAL
Group Control No
Operation
7-2
VS Series INSTRUCTION MANUAL
NGSC-430 NGSC-700
④ Push the Local button to select operation
modes.
Local: The〔Local〕lamp lights on.
Remote: The〔Local〕lamp lights off.
Operation
7-3
VS Series INSTRUCTION MANUAL
7.4.3 Stop
① Push the stop button to stop operating.
Check that “Oil Separator Pressure” is indicated “0
MPa.” on the touch screen
* Compressed air in the compressor is automatically
released.
② Switch off the earth leakage breaker.
● More than 3 minutes delay time is needed to restart operating after stopping operating.
● Do not turn off the breaker within 1 minute after stopping the compressor.
● The blow-off solenoid valve will regulate the pressure in the oil separator to release.
Operation
7-4
VS Series INSTRUCTION MANUAL
◆ Standby mode
The touch screen will go off automatically after 20 minutes of inactivity.
Touch the touch screen to bring back the display
Function select
etc. Activate or inactivate functions
tabs
[Keys]
ESC: Escape, back to the previous screen.
CLR: Clear
On-screen
ENT: Enter
Keypad
BS: Backspace
Operation
7-5
VS Series INSTRUCTION MANUAL
Operation
7-6
VS Series INSTRUCTION MANUAL
I : Integral
Pressure
sensor
P control : The discharge pressure approaches the set pressure, but a deviation occurs from the set pressure.
I control : Reduce the deviation caused by P control (however, the response will be poor).
0.81
← 0.7
Discharge pressure
0.5
0.4
93 100 110(VS22 VS55/75)
109(VS37)
Amount of discharge air(%)→
Operation
7-7
VS Series INSTRUCTION MANUAL
No
Fan inverter start : ON
Inverter start command : ON
In the water removal operation, drain is discharged by performing the purging operation (Blow-off
solenoid valve: open).
When the drain becomes more than a certain amount, the water removal operation starts.
During the water removal operation, the message "Water removal operation" is displayed on the
lower left of the touch screen and the LOAD lamp blinks.
No
During water removal
operation
Yes
Purge operation
(Blow-off solenoid valve : open)
Operation
7-8
VS Series INSTRUCTION MANUAL
◆Shutdown◆
local Operation remote
mode
Stop operation
Yes Stop
operation
No
Yes
Emergency stop input
Unload operation or
Fan inverter error
No
timer ≧10sec
No
No
Inverter start command : OFF Pd≧Auto stop pressure
Yes
Unload operation
timer 0~15sec
timer 0~10sec
No
timer ≧15sec
Yes
Yes Pd≦Auto start pressure Load operation
No
Fan inverter OFF
No
timer ≧10sec
Yes
Inverter start command : OFFOFF
timer 0~15sec
No
Pd≧Auto start pressure
Yes
Pd・・・Discharge pressure
Inverter start command : ON
Fan inverter ON
Operation
7-9
VS Series INSTRUCTION MANUAL
The compressed air condensation may cause rust in the unit, damages to the oil separator element and
degradation of the lubricant oil, eventually causing accidents, and damages to the airend.
In order to keep good performance of the compressor, our compressor unit has a basic function of the
condensate removal. It monitors the compressed air condensation and starts purging operation and draining
regularly when the drain volume exceeds the rated volume.
In the condensate removal operation, do not stop it with the emergency stop switch or any other ways. This will
cause failure or damages, because the removal operation isn’t complete and the condensate drain will remain.
To maintain good performance of the compressor, make sure to use KOBELCO water resistant oil filter (Parts No.
1000106735, only for VS22/37A Ⅳ ) and install an air tank that has an appropriate volume, if the compressor unit is
operated under conditions of frequently starting and stopping, or continuous low-load operation, which will cause
the drain to accumulate more.
Operation
7-10
VS Series INSTRUCTION MANUAL
8 In Case of Emergency
The emergency lamp lights red on the controller panel at
8.1 Troubleshooting emergency and the touch screen indicates errors. Until
remove causes of emergency stop and push the reset
8.1.1 Emergency stop button, the compressor will not restart.
Alarm Cause and Troubleshooting
Stop compressor and turn off the power supply.
After O/S Temp. High Release internal pressure and replace the oil
separator element at pressure 0 Mpa..
Ambient temperature is high.
Pressure settings failure.
Discharge Oil cooler clogged.
Temperature High Oil filter element clogged
Cooling water error.
Red highlighted cursor is error.
Tap the tab to go to the troubleshooting screen Dust filter clogged.
Fan inverter error occurred.
Fan Inverter Error
Contact KOBELCO service division.
Cooling Water
Shortage [water cooled Check pump and piping of the cooling water for
model only] failures, and resolve the problems.
No signal from the inverter.
Starter Error
Contact KOBELCO service division.
Sensor (Pd, Td, Po, Tc or To) detects an error.
Sensor Error
Contact KOBELCO service division.
Reverse Phase Turn off power and ensure the power cable
connection is accurate
Power supply failure
Motor Coil
Temperature High Motor error.
Dust filter clogged.
Start button or stop button error occurred.
SW Input Error
Contact KOBELCO service division.
Emergency Stop Emergency stop pushbutton pushed.
(manual) Emergency stop signal occurred.
Discharge Pressure Check piping and valve for failures, and resolve
Rise the problems.
Inverter error occurred.
Inverter Error
Contact KOBELCO service division.
External Error External signal error
O/S Minimum Pressure
Error O/S minimum pressure is not maintained.
In Case of Emergency
8-1
VS Series INSTRUCTION MANUAL
8.1.2 Cautions
The highlighted items are detected alarms now.
Tap the tab to go to the caution screen.
Alarm list
Caution Cause and Troubleshooting
Stop compressor and turn off the power supply.
O/S Element Clogged Release internal pressure and replace the O/S
element at pressure 0 Mpa.
Stop compressor and turn off the power supply.
After O/S Temperature
Release internal pressure and replace the O/S
High
element at pressure 0 Mpa.
Ambient temperature is high,
Pressure setting error.
Discharge Oil cooler clogged.
Temperature High Oil filter element clogged.
Cooling water error.
Dust filter clogged.
Ambient Temperature The ambient temperature shall be below 45℃.
Cool down the ambient temperature by ensuring
High adequate ventilation.
100 hrs. Elapsed after More than 100 hours elapsed after maintenance
Maintenance Cautions cautions.
✐Note Contact KOBELCO service division.
Power supply failure.
Motor Coil
Temperature High Motor error.
Dust filter clogged.
Discharge Pressure Check piping and valve for failures, and resolve
Rise the problems.
External Cautions External cautions signal occurred.
Inverter cautions.
Inverter caution
Contact KOBELCO service division.
✐Note: The caution lamp will blink every second, if the maintenance
indicator lamp on the panel is lighting for more than 100 hours.
Resolve the error immediately, and then reset the indicator lamp.
Tap to next screen .
In Case of Emergency
8-2
VS Series INSTRUCTION MANUAL
8.1.3 Maintenance
Alarm list
Maintenance
Replace Suction Filter Clean suction filter from inside by air blower. Replace it if too dirty to clean
Stop compressor and turn off the power supply. Release internal pressure and
Replace O/S Element
replace the oil separator element at the pressure 0 MPa.
Stop compressor and turn off the power supply. Release internal pressure and
Replace Oil Filter
replace the oil filter at the pressure 0 MPa.
Cooler inspection required.
Inspect Cooler Inspect the cooler after stopping the compressor, make sure the cooling fan stopped
completely.
Stop compressor and turn off the power supply. Release internal pressure and
Change Lube Oil
change lube oil. Check the oil level and refill oil, if the oil level is below minimum level.
Annual Maintenance Cooler inspection and maintenance required. Contact KOBELCO service division.
In Case of Emergency
8-3
VS Series INSTRUCTION MANUAL
8.1.4 Troubleshooting
Troubleshoot the problem following instructions.
Error Troubleshooting
Stop compressor and turn off the power supply. Release internal pressure and
Oil Filter Clogged
replace the oil filter.
Wait more for than 3 minutes after starting and stopping operations.
Pressure Setting Error
Check pressure setting of the compressor and the volume of the air receiver tank.
Remove the dust filter and clean it by air blower and clean the filter attached below
Dust Filter clogged.
the controller as well.
In Case of Emergency
8-4
VS Series INSTRUCTION MANUAL
Select the item to reset and then press the Yes tab.
LED1
FAIL
LED2
Control panel
RUN
In Case of Emergency
8-5
VS Series INSTRUCTION MANUAL
8.2 Interlock
The KOBELION-VS series have the protection devices as follows, which can detect any abnormalities
to prevent failures.
In Case of Emergency
8-6
VS Series INSTRUCTION MANUAL
8.2.2 Caution
Caution Location Detector Condition 1 Condition 2 Note
Discharge Inside of the Oil
1 Thermocouple 105℃ or higher
Temperature High Separator
After the O/S after Oil
2 Thermocouple 105℃ or higher
Temperature High Separator
Pressure
difference
Oil separator between the Oil Pressure 0.12 MPa
3
Element clogged Separator and Sensor or more
after the After
Cooler
for
4 Inverter Error Inverter Inverter Inverter
model
Ambient Compressor Air
5 Thermocouple 47℃ or higher
Temperature High Inlet
100 hrs. elapsed
6 after maintenance Controller Controller
alarm
Main Motor Coil
7 Main Motor Coil Thermocouple 175℃, 3 secs.
Temperature High
Pressure setting
Discharge Pressure Pressure 0.75MPa,Pd≥0.82 MPa,1sec.
8 Controller 0.85MPa,Pd≥0.92 MPa,1sec.
Rise Sensor
1.05MPa,Pd≥1.12 MPa,1sec.
9 External Caution Controller Controller External contact Signal
8.2.3 Maintenance
Maintenance Condition Detector Condition 1 Condition 2
Replace Suction Operating Hours Operating Indicator
1 Controller 6000 hrs.
Filter difference of pressure Hours -6.23kPa
Operating
2 Replace Oil Filter Operating Hours Controller 6000 hrs.
Hours
Operating
3 Change Lube Oil Operating Hours Controller 6000 hrs.
Hours
Replace Oil Operating Hours Operating
4 Controller 6000 hrs. 0.11 MPa or more
Separator Element difference of pressure Hours
Operating
5 Inspect Cooler Operating Hours Controller 6000 hrs.
Hours
Ambient
6 Replace Sensor Thermocouple
Temperature
Operating Operation start
7 Annual Maintenance Operating Hours Controller 6000 hrs.
Hours to 1 year
Discharge of Line pressure-Discharge Using the line
8 Pressure Drop High Compressor, Line Controller pressure pressure
Pressure ≧Pressure loss settings (option)
Grease Motor [for
Operating
9 grease required Operating Hours Controller 2000 hrs.
Hours
motor]
Amount of drain>
Moisture Standard model
10 Controller Controller Amount of oil
Condensation only
replenishment 3.5%
Operating
11 Clean Dust Filter Operating Hours Controller 500 hrs.
Hours
12 Replace TP Battery Touch Screen Touch Screen Battery Voltage Reduction
In Case of Emergency
8-7
VS Series INSTRUCTION MANUAL
resistance check.
Motor is Wrong cable Replace the cable with the specified size.
humming only
Motor failure Repair or replace the motor. [call]
Blow-off solenoid valve failure Adjust or replace the solenoid valve. [call]
Pressure higher than the specified value Select an air reservoir with proper capacity.
Blow-off from
safety valve
Safety valve failure Replace the safety valve. [call]
Too short load cycle Increase the capacity of piping (air reservoir).
Capacity control failure
Improper pressure setting Reset the pressure setting.
Mixture of water Inspect the air inlet and drain the oil.
Deteriorated lube oil remains Perform flushing before changing the lube oil. [call]
In Case of Emergency
8-8
VS Series INSTRUCTION MANUAL
3. Turn on the breaker again and push the Reset button on the control panel. .
Check “Reverse phase” is not red in the alarm list and the motor rotates properly.
In Case of Emergency
8-9
VS Series INSTRUCTION MANUAL
VS22AⅣ / VS37AⅣ
●:required 〇:recommended △:inspection/cleaning ☆:visual check
0.7 MPa
Every Every 2 Every 4 Every 6 yrs.
Components year years years O/H
Daily
6,000 12,000 24,000 36,000
hrs. hrs. hrs. hrs.
Airend Air end inner parts
Bearings ●
O-rings ●
C snap rings ●
W - lip seal ●
Sleeve ●
O-rings ●
Anti-vibration rubber ●
Filters Suction fliter assembly
Filter element ● ● ● ●
Indicator △ △ △ ○
Oil separator element Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
O-rings
Element ● ● ● ●
Case ● ● ● ●
Tank ●
Base ●
Flange ●
Seal washers ● ● ● ●
Oil filter Note:1
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Dust filter ☆ △ △ △ △
Magnet filter ●
Electric parts Touch screen battery ●
☆ ☆ ☆
Pressure sensor ○
(*A) (*A) (*A)
☆ ☆ ☆
Temperature sensor ○
(*A) (*A) (*A)
Main motor △ △ △
Main motor
(*B) (*B) (*B)
Motor inverter Fan motor
Bearings (load side/unload side) ●
Main inverter
Cooling fan ○
Fan inverter ○
Cooling fan ●
*A: Difference check
*B: Insulation check Continued to the next page
Note: 1 Oil separator element and oil filter element shall be replaced
every year (or 6,000 hr.) if KOBELCO EXTRA OIL used.
every six months (or 3,000 hr.) if KOBELCO GENUINE SCREW OIL used.
every six months (or 3,000 hr.) if ANDEROL FGC32 used.
This guideline doesn’t define warranty period.
Replacement intervals can be shortened depend on how to use or where to install.
Replacement intervals are determined based on 6000 running hours per year, not exceed highest
temperature setting, and yearly average ambient temperature of 30℃ or below.
VS55A Ⅳ / VS75A Ⅳ
0.7MPa
Every
Every 2 Every 4
Components Daily Every year 6years
years years
O/H
6,000h 12,000h 24,000h 36,000h
Valves Capacity control valve
Valve body ● ● ●
O rings ● ● ●
U type packing ● ● ●
Spring coil ● ● ●
Pressure isolating check valve
Inner parts ● ● ● ●
Electro magnetic valve
silencer ○
suction control valve ●
Thermo control valve
Element ●
O rings ●
Safety valve △ △ △ △
Oil recovery valve ○ ○ ●
Cooler Oil cooler △ △ △ △
After cooler △ △ △ △
Others KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
☆
Oil level gauge (oil level ○ ○ ●
check)
Air exhaust silencer
Silencer ● ● ● ●
Cap ● ● ● ●
Filter ● ● ● ●
Rubber hose
Oil tank to AC ○
Rubber hose (oil supply line) ● ● ●
Synflex hose ○
Anti-vibration rubber ●
O rings
KOBELCO EXTRA OIL ● ● ● ●
KOBELCO GENUINE SCREW OIL Every 3,000 hrs. (3,000, 6,000, 9,000…)
ANDEROL FGC32 Every 3,000 hrs. (3,000, 6,000, 9,000…)
Others ●
N2 tube ○
Suction hose ○ ○ ○
Rubber seal for pipe coupling ● ● ●
1. Oil separator element and oil filter element shall be replaced
every year (or 6,000 hr.) if KOBELCO EXCELLENT OIL used.
every six months (or 3,000 hr.) if ANDEROL FGC32 used.
2. This guideline doesn’t define warranty period.
3. Replacement intervals can be shortened depend on how to use or where to install.
4. Replacement intervals are determined based on 6000 running hours per year, not exceed highest
temperature setting, and yearly average ambient temperature of 30℃ or below.
③ ① ③
① ②
②
VS22/37A Ⅳ VS55/75A Ⅳ
10.2.2 Disposal
Drain the lube oil, before disposing KOBELION-VS series compressor.
In case of disposal of consumable supplies such as elements, contact with an industrial waste
disposal contractor.
Dispose the motor as general industrial waste. The rotor must be disposed after demagnetization at
temperature of 500ºC (932ºF) of more with a gas burner or in a furnace.
For further instruction, contact the designated service shop, distributor, or KOBELCO service division.
11 Remote Control
11.1 Handling External Signals
The following external signals are provided.
(See the electric wiring diagram on page 12-3.)
《Input signals to compressor》
・Remote・Run (Terminal X8-COM2 → Closed : Runt)
・Remote・Stop (Terminal X9-COM2 → Open : STOP)
・Remote・Load (Terminal XA-COM2)
* Only for KOBELCO group control panel
・External Error (Terminal XB-COM2 → Emergency : STOP)
Item
Screw size Terminal block width
Model
VS22AⅣ
VS37AⅣ
M3.5 7.5 mm
VS55AⅣ
VS75AⅣ
Any modification without prior permission of KOBELCO shall invalidate the warranty
even within.
✓:active -:inactive
Mode Start button Stop button Remote ON Remote OFF
Local ✓ ✓ ― ―
Remote ― ✓ ✓ ✓
Remote Control
11-1
VS Series INSTRUCTION MANUAL
12 Specifications
12.1 Products Specifications
12.1.1 VS22AⅣ/ VS37AⅣ/ VS55AⅣ/ VS75AⅣ
Model
VS22AⅣ VS37AⅣ VS55AⅣ VS75AⅣ
Item
Voltage (V) 380/415
Frequency (Hz) 50
0.4 Mpa (m3/min) 4.72 7.6 11.8 15.1
13.1Air 0.7 Mpa 3
(m /min) 4.22 7.0 10.6 13.9
disc12.9harge
volume 0.80 Mpa (m3/min) 3.94 6.5 10 13.1
0.85 MPa (m3/min) 3.8 6.3 9.65 12.9
Pressure Atmospheric pressure (1 bar)
Suction
Temperature (ºC ) 2- 45 (36-113 °F)
condition
Altitude (m) <1000
Discharge Pressure (MPa) 0.4 – 0.85
condition Temperature (ºC ) below 45℃ (ambient temperature: 30℃)
Constant pressure control by inverter
Pressure control system
(Control pressure ±0.01Mpa)
Capacity range % 15 - 110 18 - 109 20~110 16~110
Normal output (kW) 22 37 55 75
Service factor 1.14 1.19 1.23 1.2
Type Permanent magnet type Three-phase synchronization
Main motor
Specifications
12-1
VS Series INSTRUCTION MANUAL
Frequency (Hz) 50
Output rating
Frequency (Hz) 50
specification
Electrical
Specifications
12-2
WIRING DIAGRAM (VS22A VS37A)
AC380/415V
50/50Hz
Kobelink
VS Series
T10
R10
S10
415/200V 50Hz PROTECTOR OPERATION PANEL
※OPTION L1/R L2/R L3/T E 3A
CONTROLLER TR E
R1 R2 PB-EMS R11
1 2 R10
1 K K
S1 S2 3 4 S10
2 T1 T2 5 6 T10
L
COM6
COM8
CT 0~800A
CN20
XAP-02V-1 R S T E 9 INSIDE OF CONTROLLER 5 CN9
PB-EMS 88A VHR-05N
MAIN INV MINOR FAILURE CN10
X1 Y1 X5 VHR-10N
U V W
CM MAIN ANSWER SK SK SK
SR SK
12.2 Wiring Diagram
RY1 Y2 X6
12.2.1 VS22A Ⅳ / VS37 AⅣ
CN12 7 8 5 6 1 2 3 4 10 1 2 3 4
FWD X Y Z
INV START XAP-03V-1 Y28 Y29 Y2A Y2B
CM CMY COM1
Y2D
Y2C
CONTROLLER R ST E
MAIN VIC ED
F1
1A
F2
1A
INVERTER CC CC RY1 RY2 RY3 88A
INSIDE OF MONITOR
FAN ROTATION SPEED COMMAND S2
COMMUNICATION IMPUT P1 DC4~20mA FAN INVERTER
RS485 DC REACTOR CC
A 1 DX+ FLA
COM1
S10
RY2
SV2C
P+
SV1C
B 2 DX- RES RESET
FG 3 SD X4 FLC RY3
F START
30C
SV4S SV4C
CN-15 COM1 FAN INV ERROR U VW SV1 SV SV SV2
XAP-03V-1 30B U V W
MAIN INV ERROR
MAIN INV
MAIN MAIN INV FAN INV 30A X7 IM
MINOR FAN MOTOR
ANSWER FAILURE ERROR ERROR
SV1S
SV2S
12-3
U VW
E
X7 X4 DRYER CAUTION
X6 X5 U V W XD COM3 (OPTION)
COM1 S10
IPM
7 6 8 5 9 E
INSIDE OF CONTROLLER 6 7 8 9 10 CN7 INSIDE OF CONTROLLER CN8 INSIDE OF CONTROLLER
CN5 MAIN MOTOR
CN6 INSIDE OF CONTROLLER VHR-6N VHR-4N
XAP-10V-1
INVERTER START
SOLENOID VALVE
RESET COMMAND
1 4 2 3 XAP-10V-1
FAN MOTOR START
1 2 3 4 5
BLOW-OFF SOLENOID
DRYER START COMMAND
6 1 2 3 4 5 6 1 2 3
DRYER DRAIN SOLENOID VALVE
2 8.2
FOR CAPACITY CONTROL VALVE
X0 X3 X1 X2
X9
X8
XA
XB
COM2
COM2
COM2
COM2
INSIDE OF CONTROLLER
※JUMP WIRE COM4 Y20 Y21 Y22 Y23 Y24 COM5 Y25 Y26 Y27
LT
BO
P1 P2 T1 T2 T3 T4 M3
1 2 1 2 1 2 1 2 1 2 1 2
( PREPARED BY CUSTOMER )
PB-EMS
( PREPARED BY CUSTOMER )
X8-COM2 CLOSE:START
X9-COM2 OPEN:STOP
RUNNING OUTPUT
CAUTION OUTPUT
PT PT 6.5
DRYER ERROR
MAINTENANCE OUTPUT
EMERGENCY STOP
DETAIL OF CONTROL TERMINAL BLOCK
EXTERNAL ERROR
SUCTION INDICATOR
EMERGENCY STOP OUTPUT
REMOTE START ON
REMOTE SELESTION OUTPUT
※1 Input signals should be no-voltage contact input. Electric current of 24V is supplied from the controller side.
·REMOTE LOAD (TERMINAL XA-COM2 ) ※ Only for KOBELCO group control board ※2 The allowable contact capacity of output signal is AC250V/3A, DC30V/3A. The minimum load is DC5V/100mA.
·EXTERNAL ERROR(TERMINAL XB-COM2→ EMERGENVY:STOP) ※3 The terminal X9-COM2 has been short-circuited at the factory.Remove this terminal in the remote control mode.
Output signals from compressor ※4 Remote (input signal to controller) should be input by one shot at 500ms or more. shorter pulse signals may not be recognized.
·EMERGENCY STOP OUTPUT (TERMINAL Y20-COM4→CLOSE:ERROR)
·CAUTION OUTPUT (TERMINAL Y21-COM4→CLOSE:CAUTION) <CAUTION> 25
·MAINTENANCE OUTPUT (TERMINAL Y22-COM4→CLOSE:MAINTENANCE)
Any modification without prior permission of KOBE STEEL may void the warranty even within the warranty period.
·REMOTE SELESTION OUTPUT (TERMINAL Y23-COM4→CLOSE:REMOTE) DETAIL OF POWER TERMINAL BLOCK
·RUNNING OUTPUT (TERMINAL Y24-COM4→CLOSE:RUNNING ) ISSUE
INSTRUCTION MANUAL
Specifications
WIRING DIAGRAM (VS55A VS75A)
Kobelink
CN19
VS Series
R10
S10
T10
E OPERATION PANEL
PROTECTOR
L1 L2L3 E
TR E PB-EMS
※OPTION R1 R2 1 2 R10 R11
1 k K
S1 S2 3 4 S10
CONTROLLER
2 T1 T2 5 6 T10
COM8
COM6
CN20 L
CT 0~800A CP1
R S TE 9 INSIDE OF CONTROLLER 5
88A
MAIN INV MINOR FAILURE
PB-EMS U V W
INV EMERGENCY STOP I-X1 Y1 X5
CM MAIN ANSWER SR SK SK SK
SK
Y2 X6 CN12
RY1 XAP-03V-1 X Y Z 1 2 3 4 5 6 7 8 9 1 2 3 4
FWD
INV START CONTROLLER E ED CN10 Y28 Y29 Y2A Y2B
CMY COM1 CN9
12.2.2 VS55A Ⅳ / VS75A Ⅳ
CM + R S T
VHR-10N VHR-05N
Y2D
Y2C
- AI
AC
FU1
MAIN
FU2
CN-15 FAN ROTATION SPEED COMMAND FAN RY1 RY2 RY3 88A
XAP-03V-1 INVERTER DC4~20mA INVERTER
Y2E
Y2F
SV4S
COM7
COM1 MC SC
RS485 DX+ P+ FAN INV
DC REACTOR S4 RY2 RESET
DX- P1 ERROR X4 MA
RY3 START
SV2C
SV1C
SD U V W S1
30C COM1
INSIDE OF MONITOR U V W SV1 SV2
COMMUNICATION IMPUT 30B INSIDE OF OPERATION PANEL
MAIN INV ERROR IM CN2
30A FAN MOTOR E XAP-02V-1
X7
1 2
SV1S
SV2S
UVW
U VW MAIN INV COM7
FAN INV MINOR MAIN MAIN INV
S10
12-4
MAIN MOTOR ERROR FAILURE ANSWER ERROR
IPM
E XC COM3XDCOM3 XECOM3XFCOM3
X4 X5 X6 X7 COM1
FUNCTION BUTTON
DRYER START
INVERTER START
VHR-6N
SOLENOID VALVE
5 6 7 8 9 6 7 8 9 10
BLOW-OFF SOLENOID
+ +
PT PT
- -
XA
X8
X9
COM2
XB
COM2
COM2
COM2
PB-EMS
TEMPERATURE
( PREPARED BY CUSTOMER )
CAUTION OUTPUT
RUNNING OUTPUT
X8-COM2 CLOSE:START
X9-COM2 OPEN:STOP
MAINTENANCE OUTPUT
DRYER ERROR
WATER-BREAK
DISCHARGE PRESSURE
AFTER OIL SEPARATOR
AMBIENT TEMPERATURE
EXTERNAL ERROR
REMOTE START ON
MOTOR COILTEMPERATURE
SUCTION INDICATOR
35 33
REMOTE LOAD COMMAND
EXTERNAL SIGNAL
2 6.5
The following signals are prepared as external signals. 31
M3 BOLT
Input signals to compressor
·REMOTE RUN (TERMINAL X8-COM2→ CLOSE:RUN)
·REMOTE STOP (TERMINAL X9-COM2→ OPEN:STOP)
·REMOTE LOAD (TERMINAL XA-COM2 ) ※ Only for KOBELCO group control board ※1 Input signals should be no-voltage contact input. Electric current of 24V is supplied from the controller side.
·EXTERNAL ERROR(TERMINAL XB-COM2→ EMERGENVY:STOP) ※2 The allowable contact capacity of output signal is AC250V/3A, DC30V/3A. The minimum load is DC5V/100mA.
※3 The terminal X9-COM2 has been short-circuited at the factory.Remove this terminal in the remote control mode. M10 BOLT
※4 Remote (input signal to controller) should be input by one shot at 500ms or more. shorter pulse signals may not be recognized. 8.2
Output signals from compressor
<CAUTION> VS55/75A 380/415V
·EMERGENCY STOP OUTPUT (TERMINAL Y20-COM4→CLOSE:ERROR)
INSTRUCTION MANUAL
·CAUTION OUTPUT (TERMINAL Y21-COM4→CLOSE:CAUTION) DETAIL OF CONTROL TERMINAL BLOCK DETAIL OF POWER TERMINAL BLOCK
Any modification without prior permission of KOBE STEEL may void the warranty even within the warranty period.
·MAINTENANCE OUTPUT (TERMINAL Y22-COM4→CLOSE:MAINTENANCE) ISSUE
·REMOTE SELESTION OUTPUT (TERMINAL Y23-COM4→CLOSE:REMOTE)
·RUNNING OUTPUT (TERMINAL Y24-COM4→CLOSE:RUNNING ) DRAWING NO. A000179381 01
Specifications
CONNECTION DIAGRAM(VS22 VS37A VS55A VS75A)
MAIN INVERTER
VS Series
P4 P3 P2 P1 CN12
CN14 CN17 CN15 T6 T5 T4 T3 T2 T1 CN20
P5
CN4
CN18 CN6
CN13
CN3
TO CONTROLLER(NGSC-430)
OPERATION
BOARD TB1
CN6
TO OPERATION BOARD CN2
12.3 Connection Diagram
TRANSFORMER
CN5
CN10 CN9 CN8 CN7 CN1
CONTROLLER BOARD
TO OPERATION BOARD
12-5
AC REACTOR
PB-
EMS
RUN STOP TO OPERATION CN1,5,6,7,8,9,10
COOLING FAN
TERMINAL
BLOCK
TR CP2 CP1 88A TB1
M4
DRAWING NO.
INSTRUCTION MANUAL
A000149719 02
Specifications
FLOW DIAGRAM(VS22A VS37A)
VS Series
AIR EXHAUST
Pd
COMPRESSED AIR
AFTER
COOLER OIL COOLER
DISCHARGE
12.4 System Diagram
USER’S SCOPE
V2
12.4.1 VS22A Ⅳ / VS37A Ⅳ
SILENCER COVER
FAN
INVERTER
SILENCER
12-6
SUCTION FILTER SAFETY
OIL RECOVERY VALVE
Si CHECK VALVE
Ts
CHECK VALVE
MIN.PRESSURE
Tc VALVE
MAIN MOTOR
Po
OIL FILTER
COMPRESSOR
OIL SEPARATOR
Td
Ta ISSUE
DRAWING NO. A000149679 01
INSTRUCTION MANUAL
Specifications
FLOW DIAGRAM (VS55A VS75A)
VS Series
AIR EXHAUST
Pd
12.4.2 VS55A Ⅳ / VS75A Ⅳ
USER’S SCOPE
V2
SILENCER COVER
FAN
INVERTER
SILENCER
3-WAY BLOW-OFF
FAN
SOLENOID VALVE SOLENOID
MOTOR VALVE
12-7
COOLING FAN CAPACITY
CONTROL VALVE THERMOSTAT VALVE
SUCTION FILTER SAFETY
OIL RECOVERY VALVE
Si CHECK VALVE
Ts
CHECK VALVE
Min. PRESSURE
VALVE
Tc
MAIN MOTOR Po
OIL FILTER
Td
ISSUE
INSTRUCTION MANUAL
Ta
DRAWING NO. A000179396 01
Specifications
VS Series INSTRUCTION MANUAL
Failure and damage caused by the natural disasters or accidents beyond human
control.
Failure and damage caused by materials selected or supplied by customer, or
caused by defects of specifications (design, materials and others) required by
customer..
Failure and damage caused by repair or modification conducted by customer
without notifying us first.
Failure and damage caused by not adhering to the operating procedures,
periodical inspections, maintenance and storage described in the specification
sheets and instruction manuals issued by KOBELCO.
Failure and damage caused by defective foundation, building and/or equipment
other than this machine.
Consult with our distributor for repairs on the machine after the warranty period is expired. Repairs will be
made on the customer's expense upon request. The repairs can maintain the performance.
13.3 Indemnity
Under no circumstances, including any illegality, KOBELCO is not liable for indirect, incidental,
consequential or any kind of damages, including, but not limited to, loss of production, loss of anticipated
profits, loss of operational profits, loss of materials and products, or indirect losses, however same shall be
caused by any other similar responsibility.
【THAILAND】
KOBELCO COMPRESSORS (THAILAND) LTD.
2170 Bangkok Tower, Room No.1102, 11th Floor, New Petchburi Road, Bangkapi, Huaykwang, Bangkok 10310
Tel: (66) 2 308 0211 , Fax: (66) 2 308 0214
【MALAYSIA】
KOBELCO COMPRESSORS MALAYSIA SDN . BHD.
No 9, Jalan Sepadu 25/123A, Seksyen 25,40400 Shah Alam Selangor, Malaysia
Tel : +60-3-5525-2757 Fax : +60-3-5525-3596
【VIETNAM】
KOBELCO COMPRESSORS VIETNAM CO., LTD.
43-45 Lam Ha Street, Bo De Ward, Long Bien District, Hanoi, Vietn am
Tel : +84-4-3944-7781 Fax : +84-24-3944-7780
【INDONESIA】
PT KOBELINDO COMPRESSORS
JL. RAYA TANJUNG BARAT NO . 85. TANJUNG BARAT, JAGAKARSA JAKARTA SELATAN, 12530 , INDONESIA.
Tel : +62-21-782-7002 Fax : +62-21-782-7025
【PHILIPPINES】
KOBELCO COMPRESSORS AND MACHINERY PHILIPPINES CORPORATION
19th Floor Panorama Tower, 34th Street Corner Lane A, Bonifacio Glob al City, Taguig City
Tel : +632-897-8736 +632-899-1997 Fax : +632-897-8737
【INDIA】
KOBELCO COMPRESSORS INDIA PVT.LTD.
249G, 3rd Floor AIHP TOWER Udyog Vihar, Phase IV, Near India Bulls Building, 122015 Gurgaon
Tel +91-124-4380750 Fax +91-124 438 0770
www.kobelco-comp.co.jp
Address inquiries to……