Coupling Beam
Coupling Beam
Coupling Beam
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Coupling Beam Design Based on ACI 318-14 / 2015 IBC
INPUT DATA
CONCRETE STRENGTH fc' = 4 ksi
REBAR YIELD STRESS fy = 60 ksi
FACTORED SHEAR LOAD Vu = 239 k
WIDTH b = 16 in
OVERALL DEPTH h = 72 in
COUPLING BEAM DEPTH c = 16 in
CLEAR SPAN L = 6 ft
DIAGONAL BARS, Ad 4 # 9
DIAGONAL TIES, Ash # 4 @ 4
HORIZONTAL BARS, Avh 16 # 4 ( 2 layers @ 10 in o.c. )
VERTICAL TIES, Av 2 legs # 5 @ 4 in o.c.
ANALYSIS
CHECK DIAGONAL BARS REQUIREMENT (ACI 318-14 18.10.7)
< 4
L/h= 1.00
< 2
'
Vu < V n 4 bh fc 291 k [Coupling Beam Permitted]
'
Vu < V n MIN (2 f y A d sin , 10 bh f c) 240 k [Satisfactory]
200bd 3bd f
'
A s ,min MAX
c
, 3.07 in2 ==> ( 4 # 8 longitudinal bars both top & bottom)
f y f
y
(Note: These bars are not recommended by SEAOC to be used, and are not shown in figure above.)
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Coupling Beam Design Based on CBC 2001 / UBC 1997
INPUT DATA
CONCRETE STRENGTH fc' = 4 ksi
REBAR YIELD STRESS fy = 60 ksi
FACTORED SHEAR LOAD Vu = 254 k
WIDTH b = 16 in
OVERALL DEPTH h = 72 in
CLEAR SPAN L = 6 ft
DIAGONAL BARS, Ad 4 # 9
DIAGONAL TIES, Ash # 4 @ 4
HORIZONTAL BARS, Avh 16 # 4 ( 2 layers @ 10 in o.c. )
VERTICAL TIES, Av 2 legs # 3 @ 6 in o.c.
ANALYSIS
CHECK DIAGONAL BARS REQUIREMENT (SEC.1921.6.10.2)
200bd 3bd f c
'
A s ,min MAX , 3.07 in2 ==> ( 4 # 8 longitudinal bars both top & bottom)
fy f y
(Note: These bars are not recommended by SEAOC to be used, and are not shown in figure above.)