Revision Summary
PKG-PRC012Q-EN (29 Jan 2014)
Remove corrosion resistant coating option.
PKG-PRC012P-EN (06 Nov 2013)
Updated for increased efficiency project - SCWH to SCWJ.
PKG-PRC012-EN (05 Sep 2012)
Corrected water connection size for SCWH075. Added CTA liquid and discharge line sizes. Added
power entry hole sizes. Miscellaneous minor corrections.
Trademarks
CompleteCoat,Trane and theTrane logo are trademarks ofTrane in the United States and other
countries. All trademarks referenced in this document are the trademarks of their respective
owners.
PKG-PRC012Q-EN 3
Features and Benefits
MidrangeVertical Self-Contained air conditioners, available in 3 to 15-tons, are single package units
designed for low cost installation in the conditioned space or equipment room. Durable
construction, strict quality control, and demanding factory testing ensure reliability from start-up
through years of operation. All units are shipped fully factory assembled and tested — thereby
reducing field labor, installation time, and costs.
Units are easy to convert from vertical to horizontal discharge arrangements. Unit return
convertible for front or rear return air offers flexibility to match most building configurations.
Discharge fan section removable to allow passage through standard height doorway.
Discharge can be either free or ducted. Power and water connections are available from either side
of the unit adding to the unit flexibility.
Standard Features
• 3 through 15-ton commercial self-contained units
• Water-cooled or air-cooled condensing applications
• Fits through standard 36-inch door. Discharge fan section removable to allow passage through
standard height doorway (on 10-15 ton units).
• Single point power connection
• Single point water connection on water-cooled units
• Both water and power connections are available on either side of the unit
• Rugged 1” double wall foamed panel construction
• Positively-sloped stainless steel IAQ drain pan
• Front or rear return air openings
• Vertical and horizontal discharge arrangements
• Decorative front return air grille on 3 - 7.5 tons
• ETL/CETL listing on standard unit
• AHRI certified performance
• All compressors are scroll type
• All remote air-cooled units have crankcase heaters as standard
• Variable pitch sheaves allow field adjustment of airflow
• High and low pressure cutout switches
4 PKG-PRC012Q-EN
Application Considerations
CTA Unit Location
Unobstructed condenser airflow is essential to maintain capacity and operating efficiency. When
determining unit placement, give careful consideration to assure sufficient airflow across the
condenser coils. Avoid these two detrimental conditions: warm air recirculation and coil starvation.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity
because of the higher head pressure associated with them. In more severe cases, nuisance unit
shutdowns will result from excessive head pressures.
Clearance
Ensure vertical condenser air discharge is unobstructed. While it is difficult to predict the degree
of warm air recirculation, a unit installed with a ceiling or other obstruction above it will experience
a capacity reduction that will reduce the maximum ambient operation. Nuisance high head
pressure trip outs may also occur.The coil inlet must also be unobstructed. A unit installed closer
than the minimum recommended distance to a wall or other vertical riser will experience a
combination of coil starvation and warm air recirculation.This may result in unit capacity and
efficiency reductions, as well as possible excessive head pressures.
Reference the service clearance section for recommended lateral distances.
Ambient Limitations
Standard ambient control allows operation down to 45°F (7.2°C) with cycling of condenser fans.
Units with the low ambient kit option are capable of starting and operating in ambient temperatures
down to 0°F (-17.8°C). Optional low ambient kit units use a condenser fan motor speed controller
that controls condenser capacity by modulating condenser airflow in response to saturated
condenser temperature or ambient temperature. Maximum cataloged ambient temperature
operation of a standard condenser is 125°F (46.1°C). Operation at design ambient above 125°F can
result in excessive head pressures. For operation above 125°F, contact the localTrane sales office.
PKG-PRC012Q-EN 5
Selection Procedure
Follow this process to select a midrange self-contained unit.
Step 1. Load
Determine the load requirements for heating and cooling, include outside air. UseTrane’s load
estimate program or any standard method.
Selection Example
Design conditions for a water-cooled unit with airflow = 2,000 cfm at 0.5-inch duct static pressure.
Entering air temperature = 80/67°F
Total gross capacity required = 66,400 Btu/h
Entering water temperature = 85°F
Leaving water temperature = 95°F
Unit Selection
Tentatively select a 5-ton unit, model SCWJ050. Refer to Table 19, p. 26 to obtain gross total and
sensible unit capacities, gpm, and leaving water temperature at nominal conditions:
Total capacity = 68.1 MBh
Sensible capacity = 49.2 MBh
Water flow rate = 16.2 gpm
Leaving water temperature = 95°F (all capacity tables assume 10° T)
The SCWJ050 meets the total and sensible capacities and other design requirements.
Refer to the fan data Table 4, p. 12 to determine approximate brake horsepower and fan rpm:
Fan brake horsepower = 0.73 bhp
Fan rpm = 1020 rpm
Determine net capacities by subtracting fan motor heat from gross capacities:
3.98 X 0.73 bhp = 2.9 MBh
Net total capacity = 68.1 MBh – 2.9 MBh = 65.2 MBh
Net sensible capacity = 49.2MBh - 2.9 MBh = 46.3 MBh
6 PKG-PRC012Q-EN
Model Number Descriptions
Midrange Model Remote Air-Cooled
Number Description Condenser
Digit 1 - Unit Model Digits 1, 2, 3 - Product Type
S = Self contained CTA = Remote air-cooled condenser
Digit 2 - Unit Type Digits 4, 5, 6 - Nominal Gross
C = Commercial Cooling Capacity (MBh)
Digit 3 - Condenser Medium 090 = 090 MBh (used with 3 & 5-ton
SCRJ)
R = Remote air-cooled 120 = 120 MBh (used with 7.5
W = Water cooled SCRJ)
Digit 4 - Development Sequence 180 = 180 MBh (used with 10, 12, 15-ton
J = Development series SCW/SCR* SCRJ)
PKG-PRC012Q-EN 7
General Data
Table 1. Water-Cooled Midrange General Data
8 PKG-PRC012Q-EN
General Data
Table 2. Air-cooled midrange self contained and matching CTA condenser general data
PKG-PRC012Q-EN 9
General Data
Table 2. Air-cooled midrange self contained and matching CTA condenser general data (continued)
10 PKG-PRC012Q-EN
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
960 1230 0.31 1280 0.34 1330 0.37 1430 0.43 1520 0.49 1610 0.56
1040 1260 0.35 1310 0.38 1360 0.41 1450 0.47 1530 0.53 1620 0.60
1120 1290 0.39 1340 0.42 1380 0.45 1470 0.51 1550 0.58 1640 0.65
1200 1320 0.44 1370 0.47 1410 0.50 1490 0.56 1580 0.63 1660 0.70
1280 1360 0.49 1400 0.52 1440 0.55 1520 0.62 1600 0.69 1680 0.77
1360 1390 0.55 1430 0.58 1470 0.61 1550 0.68 1630 0.76 1700 0.83
1440 1430 0.61 1470 0.64 1510 0.68 1580 0.75 1660 0.82 1730 0.90
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
PKG-PRC012Q-EN 11
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
1600 1040 0.56 1080 0.60 1120 0.64 1200 0.72 1270 0.80 1340 0.89
1750 1070 0.66 1110 0.70 1150 0.74 1220 0.83 1290 0.92 1360 1.01
1850 1100 0.73 1130 0.78 1170 0.82 1240 0.91 1310 1.00 1370 1.09
2000 1130 0.86 1170 0.90 1200 0.95 1270 1.04 1330 1.13 1390 1.23
2150 1170 0.99 1200 1.04 1230 1.09 1300 1.19 1360 1.29 — —
2250 1200 1.10 1230 1.15 1260 1.20 1320 1.30 1380 1.40 — —
2400 1240 1.26 1270 1.32 1300 1.37 1350 1.47 — — — —
Field Installed High Static Pressure Drive(d)
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
12 PKG-PRC012Q-EN
Fan Performance Data
PKG-PRC012Q-EN 13
Fan Performance Data
14 PKG-PRC012Q-EN
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4000 1020 1.61 1060 1.75 1150 2.10 1240 2.49 1320 2.90 1370 3.22 1440 3.71 — —
4300 1040 1.78 1080 1.92 1170 2.29 1250 2.68 1330 3.09 1380 3.37 1450 3.85 — —
4650 1060 2.01 1100 2.15 1190 2.52 1270 2.93 1350 3.35 1400 3.59 1460 4.05 — —
5000 1090 2.26 1120 2.41 1210 2.80 1290 3.20 1360 3.63 1410 3.85 — — — —
5350 1110 2.55 1150 2.71 1230 3.11 1310 3.53 1380 3.97 1430 4.16 — — — —
5700 1140 2.88 1180 3.04 1260 3.45 1330 3.88 1390 4.10 1450 4.53 — — — —
6000 1170 3.18 1200 3.35 1280 3.77 1340 4.03 1400 4.44 — — — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
PKG-PRC012Q-EN 15
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4800 1020 1.91 1060 2.05 1150 2.42 1230 2.81 1310 3.22 1390 3.65 1440 3.89 — —
5200 1040 2.18 1080 2.33 1170 2.71 1250 3.11 1330 3.53 1400 3.74 1450 4.18 — —
5600 1070 2.48 1100 2.61 1190 3.02 1260 3.43 1340 3.87 1410 4.08 1460 4.52 — —
6000 1090 2.83 1130 2.98 1210 3.39 1290 3.81 1350 4.08 1420 4.49 — — — —
6400 1120 3.20 1150 3.36 1230 3.78 1300 4.13 1360 4.52 1430 4.94 — — — —
6800 1150 3.62 1180 3.80 1240 4.23 1310 4.62 — — — — — — — —
7200 1160 4.21 1190 4.37 1260 4.76 — — — — — — — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
16 PKG-PRC012Q-EN
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
960 1230 0.31 1280 0.34 1330 0.37 1430 0.43 1520 0.49 1610 0.56
1040 1260 0.35 1310 0.38 1360 0.41 1450 0.47 1530 0.53 1620 0.60
1120 1290 0.39 1340 0.42 1380 0.45 1470 0.51 1550 0.58 1640 0.65
1200 1320 0.44 1370 0.47 1410 0.50 1490 0.56 1580 0.63 1660 0.70
1280 1360 0.49 1400 0.52 1440 0.55 1520 0.62 1600 0.69 1680 0.77
1360 1390 0.55 1430 0.58 1470 0.61 1550 0.68 1630 0.76 1700 0.83
1440 1430 0.61 1470 0.64 1510 0.68 1580 0.75 1660 0.82 1730 0.90
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
PKG-PRC012Q-EN 17
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
1600 1040 0.56 1080 0.60 1120 0.64 1200 0.72 1270 0.80 1340 0.89
1750 1070 0.66 1110 0.70 1150 0.74 1220 0.83 1290 0.92 1360 1.01
1850 1100 0.73 1130 0.78 1170 0.82 1240 0.91 1310 1.00 1370 1.09
2000 1130 0.86 1170 0.90 1200 0.95 1270 1.04 1330 1.13 1390 1.23
2150 1170 0.99 1200 1.04 1230 1.09 1300 1.19 1360 1.29 — —
2250 1200 1.10 1230 1.15 1260 1.20 1320 1.30 1380 1.40 — —
2400 1240 1.26 1270 1.32 1300 1.37 1350 1.47 — — — —
Field Installed High Static Pressure Drive(d)
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
18 PKG-PRC012Q-EN
Fan Performance Data
Standard Drive(d)
continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
2400 1320 0.84 1370 0.91 1410 0.97 1510 1.11 1590 1.25 1680 1.40
2600 1360 0.97 1400 1.03 1450 1.10 1540 1.25 1620 1.39 1700 1.55
2800 1390 1.10 1440 1.17 1480 1.25 1570 1.39 1650 1.55 1730 1.71
3000 1440 1.26 1480 1.33 1520 1.41 1610 1.56 1680 1.72 1760 1.89
3200 1480 1.44 1520 1.51 1560 1.59 1640 1.75 1720 1.92 1790 2.09(e)
3400 1530 1.63 1570 1.71 1610 1.79 1690 1.96 1760 2.13 — —
3600 1580 1.85 1620 1.93 1650 2.01 1730 2.19 — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE
52.1-1992.
(b) SCWH/SCRJ 7.5T standard and oversize motors are both 2.0 hp motors. Oversize motor is not required for 7.5T unit unless electric
heat is installed in the unit.
(c) Standard Motor - low static pressure drive, field installed
(d) Standard Motor 2.0HP Weg - Frame: Nema A56 ODP
(e) Oversized Motor - high static pressure drive, field installed
PKG-PRC012Q-EN 19
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
3200 980 1.24 1020 1.38 1100 1.67 1190 2.07 1270 2.51 1350 3.01 1420 3.54 — —
3500 1000 1.37 1040 1.50 1130 1.85 1200 2.15 1280 2.58 1360 3.05 1430 3.57 — —
3750 1010 1.48 1050 1.61 1140 1.97 1230 2.36 1290 2.67 1370 3.13 1440 3.62 — ---
4000 1020 1.61 1060 1.74 1150 2.11 1240 2.50 1320 2.91 1380 3.22 1450 3.71 — —
4250 1040 1.75 1080 1.90 1170 2.26 1250 2.65 1330 3.07 1390 3.52 1460 3.82 — —
4500 1050 1.91 1090 2.05 1180 2.43 1260 2.83 1340 3.24 1400 3.59 — — — —
4800 1070 2.11 1110 2.26 1200 2.65 1280 3.06 1360 3.49 1410 3.69 — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
20 PKG-PRC012Q-EN
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4000 1020 1.61 1060 1.75 1150 2.10 1240 2.49 1320 2.90 1370 3.22 1440 3.71 — —
4300 1040 1.78 1080 1.92 1170 2.29 1250 2.68 1330 3.09 1380 3.37 1450 3.85 — —
4650 1060 2.01 1100 2.15 1190 2.52 1270 2.93 1350 3.35 1400 3.59 1460 4.05 — —
5000 1090 2.26 1120 2.41 1210 2.80 1290 3.20 1360 3.63 1410 3.85 — — — —
5350 1110 2.55 1150 2.71 1230 3.11 1310 3.53 1380 3.97 1430 4.16 — — — —
5700 1140 2.88 1180 3.04 1260 3.45 1330 3.88 1390 4.10 1450 4.53 — — — —
6000 1170 3.18 1200 3.35 1280 3.77 1340 4.03 1400 4.44 — — — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
PKG-PRC012Q-EN 21
Fan Performance Data
continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4800 1020 1.91 1060 2.05 1150 2.42 1230 2.81 1310 3.22 1390 3.65 1440 3.89 — —
5200 1040 2.18 1080 2.33 1170 2.71 1250 3.11 1330 3.53 1400 3.74 1450 4.18 — —
5600 1070 2.48 1100 2.61 1190 3.02 1260 3.43 1340 3.87 1410 4.08 1460 4.52 — —
6000 1090 2.83 1130 2.98 1210 3.39 1290 3.81 1350 4.08 1420 4.49 — — — —
6400 1120 3.20 1150 3.36 1230 3.78 1300 4.13 1360 4.52 1430 4.94 — — — —
6800 1150 3.62 1180 3.80 1240 4.23 1310 4.62 — — — — — — — —
7200 1160 4.21 1190 4.37 1260 4.76 — — — — — — — — — —
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed
22 PKG-PRC012Q-EN
Pressure Drop Performance Data
SCWJ tons
Waterflow
(gpm) 3 5 7.5 10 12 15
5 4.6
6 6.1
7 7.8
8 9.5 5.3
9 11.4 5.3
10 13.5 7.5 4.7
12 18.9 9.9 6.5
14 23.1 12.7 8.6 6.8
16 28.8 16.0 10.9 7.9
18 35.3 19.2 13.4 9.0
20 43.1 22.5 16.2 10.2 10.2
24 28.1 22.3 12.7 12.7 3.6
28 35.9 29.3 15.3 15.3 5.2
32 44.9 37.0 18.0 18.0 7.0
36 55.5 45.6 20.9 20.9 9.0
40 54.8 23.9 23.9 11.4
45 27.9 27.9 14.7
50 32.1 32.1 18.4
55 36.5 36.5 22.5
60 41.1 41.1 27.0
Note: Water pressure drop values include factory piping and condenser.
PKG-PRC012Q-EN 23
Performance Data
Correction Factor & Heat of Rejection
350
300
Heat of Rejection (MBh)
250
CTA180
200
CTA120
150
CTA090
100
50
0
0 10 20 30 40
InItial Temperature Difference (ITD)
24 PKG-PRC012Q-EN
Water-Cooled Performance Data
Table 18. SCWJ030 gross cooling capacity, 10°F T
62 67 70
Entering Air
Water Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F CFM EDB °F MBh MBh Gpm MBh MBh gpm MBh MBh Gpm
70 36.6 22.7 8.4 40.1 17.5 9.1 42.2 14.5 9.5
75 36.6 27.6 8.4 40.0 22.5 9.0 42.2 19.3 9.5
960
80 36.6 32.5 8.4 40.0 27.4 9.0 42.1 24.3 9.5
85 37.0 36.8 8.4 40.0 32.3 9.0 42.1 29.2 9.5
70 38.0 24.5 8.7 41.5 18.3 9.3 43.6 14.6 9.8
75 38.0 30.5 8.6 41.4 24.3 9.3 43.6 20.5 9.7
65 1200
80 38.1 36.3 8.7 41.4 30.3 9.3 43.5 26.5 9.7
85 39.6 39.5 9.0 41.4 36.3 9.3 43.5 32.6 9.7
70 39.0 26.3 8.8 42.4 19.0 9.5 44.6 14.6 9.9
75 38.9 33.3 8.8 42.4 26.0 9.5 44.6 21.6 9.9
1440
80 39.5 39.3 8.9 42.4 33.0 9.5 44.5 28.6 9.9
85 41.7 41.6 9.4 42.5 39.8 9.5 44.5 35.7 9.9
70 34.9 21.9 8.3 38.2 16.7 8.9 40.2 13.7 9.3
75 34.9 26.8 8.3 38.2 21.7 8.9 40.2 18.5 9.3
960
80 34.9 31.7 8.3 38.1 26.6 8.9 40.1 23.5 9.3
85 35.6 35.5 8.4 38.1 31.6 8.9 40.1 28.5 9.3
70 36.2 23.7 8.5 39.4 17.5 9.2 41.5 13.7 9.6
75 36.2 29.7 8.5 39.4 23.5 9.2 41.4 19.7 9.6
75 1200
80 36.4 35.4 8.6 39.4 29.5 9.2 41.4 25.7 9.6
85 38.1 38.0 8.9 39.4 35.4 9.2 41.4 31.8 9.6
70 37.0 25.5 8.7 40.3 18.2 9.4 42.4 13.8 9.8
75 37.0 32.4 8.7 40.3 25.2 9.4 42.3 20.8 9.8
1440
80 37.8 37.7 8.9 40.3 32.2 9.3 42.3 27.8 9.7
85 40.0 39.9 9.3 40.5 38.8 9.4 42.3 34.8 9.7
70 33.0 21.0 8.2 36.1 15.9 8.8 38.0 12.8 9.2
75 33.0 25.9 8.2 36.1 20.8 8.8 38.0 17.7 9.2
960
80 33.1 30.8 8.2 36.0 25.8 8.8 38.0 22.7 9.2
85 34.0 33.9 8.4 36.0 30.7 8.8 37.9 27.6 9.2
70 34.1 22.8 8.4 37.2 16.6 9.0 39.1 12.9 9.4
75 34.1 28.8 8.4 37.2 22.6 9.0 39.1 18.8 9.4
85 1200
80 34.5 34.2 8.5 37.2 28.6 9.0 39.1 24.9 9.4
85 36.3 36.2 8.9 37.3 34.5 9.0 39.1 30.9 9.4
70 34.9 24.6 8.6 38.0 17.3 9.2 39.9 12.9 9.6
75 34.9 31.5 8.6 38.0 24.3 9.2 39.9 19.9 9.6
1440
80 36.0 35.9 8.8 38.0 31.3 9.2 39.9 26.9 9.5
85 38.1 38.0 9.2 38.3 37.7 9.2 39.9 33.9 9.5
70 30.9 20.1 8.1 33.8 14.9 8.7 35.6 11.9 9.0
75 30.9 25.0 8.1 33.8 19.9 8.7 35.6 16.8 9.0
960
80 31.0 29.7 8.1 33.8 24.8 8.7 35.5 21.7 9.0
85 32.3 32.2 8.4 33.8 29.7 8.7 35.5 26.7 9.0
70 31.9 21.9 8.3 34.8 15.7 8.9 36.6 11.9 9.2
75 31.9 27.9 8.3 34.8 21.7 8.9 36.6 17.9 9.2
95 1200
80 32.5 32.4 8.4 34.7 27.7 8.8 36.5 23.9 9.2
85 34.4 34.3 8.8 34.9 33.4 8.9 36.5 30.0 9.2
70 32.6 23.6 8.4 35.5 16.3 9.0 37.3 12.0 9.3
75 32.6 30.4 8.4 35.4 23.4 9.0 37.2 19.0 9.3
1440
80 34.0 33.9 8.7 35.4 30.4 9.0 37.2 26.0 9.3
85 36.0 35.9 9.1 36.0 35.9 9.1 37.2 33.0 9.3
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x
fan motor bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24
PKG-PRC012Q-EN 25
Water-Cooled Performance Data
62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F CFM EDB °F MBh MBh Gpm MBh MBh Gpm Mbh Mbh Gpm
70 66.2 40.7 15.0 72.5 31.7 16.3 76.5 26.2 17.1
75 66.1 49.4 15.0 72.4 40.4 16.3 76.4 34.9 17.0
1800
80 66.1 58.0 15.0 72.4 49.1 16.3 76.4 43.7 17.0
85 66.7 65.9 15.2 72.3 57.8 16.2 76.3 52.4 17.0
70 67.4 42.2 15.3 73.8 32.3 16.5 77.8 26.4 17.3
75 67.4 51.7 15.3 73.8 41.9 16.5 77.8 35.9 17.3
65 2000
80 67.4 61.1 15.3 73.7 51.4 16.5 77.7 45.5 17.3
85 68.7 68.6 15.5 73.7 60.9 16.5 77.7 55.0 17.3
70 68.5 43.6 15.5 74.9 32.9 16.7 78.9 26.5 17.5
75 68.4 53.9 15.5 74.9 43.3 16.7 78.9 36.8 17.5
2200
80 68.6 64.0 15.5 74.8 53.7 16.7 78.8 47.2 17.5
85 70.8 70.7 15.5 74.8 64.0 16.7 78.8 57.5 17.5
70 63.9 39.6 14.9 70.0 30.6 16.1 73.8 25.2 16.8
75 63.9 48.3 14.9 69.9 39.4 16.0 73.7 33.8 16.8
1800
80 63.9 56.9 14.9 69.9 48.1 16.0 73.7 42.6 16.8
85 64.7 64.5 15.0 69.8 56.3 16.0 73.6 51.2 16.8
70 65.1 41.1 15.1 71.2 31.3 16.3 75.0 25.3 17.0
75 65.0 50.6 15.1 71.1 40.8 16.3 75.0 34.8 17.0
75 2000
80 65.1 60.0 15.1 71.1 50.4 16.3 74.9 44.4 17.0
85 66.8 66.7 15.4 71.1 59.9 16.3 74.9 53.9 17.0
70 66.1 42.5 15.3 72.2 31.8 16.5 76.1 25.4 17.2
75 66.0 52.9 15.3 72.2 42.2 16.5 76.0 35.7 17.2
2200
80 66.3 62.8 15.3 72.1 52.6 16.5 76.0 46.1 17.2
85 68.8 68.7 15.8 72.1 62.8 16.5 75.9 56.4 17.2
70 61.3 38.4 14.7 67.1 29.4 15.8 70.8 24.0 16.5
75 61.3 47.1 14.7 67.1 38.2 15.8 70.7 32.7 16.5
1800
80 61.3 55.7 14.7 67.0 46.9 15.8 70.7 41.4 16.5
85 62.5 62.4 14.9 67.0 55.6 15.8 70.6 50.1 16.5
70 62.4 39.9 14.9 68.1 30.0 16.2 71.9 24.1 16.7
75 62.4 49.4 14.9 68.1 39.6 16.2 71.9 33.6 16.7
85 2000
80 62.5 58.7 14.9 68.1 49.2 16.2 71.8 43.2 16.7
85 64.6 64.5 15.3 68.0 58.6 16.2 71.8 52.7 16.7
70 63.3 41.3 15.1 69.2 30.6 16.2 72.9 24.1 16.9
75 63.3 51.6 15.1 69.1 41.0 16.2 72.8 34.5 16.9
2200
80 63.6 61.4 15.1 69.1 51.3 16.2 72.8 44.9 16.9
85 66.5 66.4 15.7 69.1 61.6 16.2 72.7 55.2 16.9
70 58.4 37.1 14.5 63.9 28.1 15.5 67.4 22.6 16.2
75 58.4 45.8 14.5 63.9 36.8 15.5 67.4 31.4 16.2
1800
80 58.5 54.3 14.5 63.9 45.6 15.5 67.3 40.1 16.2
85 60.2 60.1 14.8 63.8 54.2 15.5 67.3 48.8 16.2
70 59.4 38.6 14.7 65.0 28.7 15.7 68.4 22.7 16.4
75 59.4 48.1 14.6 64.9 38.3 15.7 68.4 32.3 16.4
95 2000
80 59.6 57.2 14.7 64.9 47.8 15.7 68.3 41.9 16.4
85 62.1 60.0 15.2 64.9 57.3 15.7 68.3 51.4 16.4
70 60.2 40.0 14.8 65.8 29.3 15.9 69.3 22.8 16.6
75 60.2 50.3 14.8 65.7 39.7 15.9 69.2 33.1 16.6
2200
80 60.7 59.7 14.9 65.7 50.0 15.9 69.2 43.5 16.6
85 63.9 63.8 15.5 65.8 60.1 15.9 69.1 53.9 16.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp
[Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.
26 PKG-PRC012Q-EN
Water-Cooled Performance Data
62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 92.8 55.3 21.2 100.1 39.7 22.7 104.6 29.9 23.6
75 92.3 68.6 21.1 99.5 53.3 22.6 103.7 42.8 23.5
2400
80 91.0 81.3 20.9 97.8 66.1 22.3 102.6 56.5 23.2
85 91.2 91.2 20.9 96.4 79.0 22.0 100.2 69.5 22.7
70 96.7 60.2 22.0 103.7 40.9 23.4 108.3 28.9 24.4
75 95.2 76.6 21.7 102.2 57.6 23.2 106.7 45.7 24.1
65 3000
80 94.2 92.5 21.5 100.7 73.9 22.9 104.8 62.2 23.7
85 96.6 96.6 22.1 98.8 90.2 22.5 103.1 78.7 23.4
70 98.8 65.1 22.4 106.0 42.5 23.9 111.0 28.2 24.9
75 97.4 84.5 22.2 104.4 62.0 23.6 109.0 48.3 24.5
3600
80 97.6 97.6 22.2 102.7 81.8 23.3 106.9 68.1 24.2
85 100.7 100.7 22.9 101.3 100.3 23.0 104.7 87.8 23.7
70 90.4 54.2 21.1 97.4 38.5 22.5 101.8 28.7 23.4
75 90.1 67.5 21.0 97.1 52.2 22.5 101.4 43.0 23.4
2400
80 88.7 80.3 20.8 95.4 65.1 22.1 99.7 56.2 23.0
85 89.6 89.6 21.0 93.9 78.1 21.9 97.9 68.8 22.7
70 94.1 59.2 21.8 101.1 39.8 23.3 105.3 27.8 24.1
75 93.2 75.6 21.7 99.9 56.8 23.1 103.9 45.1 23.9
75 3000
80 91.9 91.0 21.4 98.0 72.9 22.7 102.1 61.1 23.5
85 94.5 94.5 22.0 96.2 89.4 22.3 100.3 77.9 23.2
70 96.4 64.1 22.3 103.6 41.1 23.8 108.4 27.3 24.8
75 95.0 83.6 22.0 101.8 61.2 23.5 106.4 47.4 24.4
3600
80 95.4 95.4 22.1 101.8 87.0 23.5 104.1 67.3 23.9
85 98.1 98.1 22.7 98.5 98.0 22.8 101.8 87.0 23.5
70 87.0 52.6 20.8 93.9 37.1 22.2 98.1 27.4 23.1
75 87.2 66.3 20.8 93.7 50.8 22.2 97.4 41.8 22.9
2400
80 85.6 79.0 20.5 92.1 63.8 21.8 95.9 54.1 22.6
85 87.1 87.1 20.8 90.4 76.8 21.5 94.3 67.4 22.3
70 90.5 57.8 21.5 97.1 38.5 22.9 101.8 26.5 23.8
75 89.8 74.2 21.4 96.5 55.3 22.7 100.7 43.9 23.6
85 3000
80 88.8 88.6 21.2 94.6 71.7 22.4 98.5 59.9 23.2
85 91.5 91.5 21.8 91.4 87.6 21.7 96.5 76.6 22.8
70 92.6 62.6 21.9 100.0 40.3 23.5 104.4 25.9 24.3
75 91.5 82.2 21.7 98.3 59.8 23.1 102.7 45.9 24.0
3600
80 92.7 92.7 22.0 96.6 79.7 22.8 100.3 66.2 23.6
85 95.2 95.2 22.5 95.0 94.9 22.5 97.7 85.9 23.1
70 83.1 51.0 20.4 89.7 35.5 21.8 93.8 26.0 22.6
75 82.9 64.4 20.4 89.2 48.9 21.7 93.4 39.6 22.5
2400
80 81.6 77.4 20.1 87.5 62.1 21.4 91.3 52.7 22.1
85 83.5 83.5 20.5 85.8 75.2 21.0 89.3 65.7 21.7
70 86.4 56.1 21.1 93.0 37.1 22.4 97.1 24.9 23.3
75 85.6 72.5 20.9 92.0 53.9 22.3 96.5 42.4 23.2
95 3000
80 85.3 85.3 20.9 89.8 70.1 21.8 93.6 58.5 22.6
85 87.7 87.7 21.4 87.9 86.2 21.4 91.2 74.9 22.1
70 88.4 61.0 21.5 95.4 38.7 22.9 99.3 24.3 23.7
75 87.1 80.5 21.3 93.5 58.5 22.6 97.6 44.7 23.4
3600
80 88.3 88.3 21.5 91.2 78.0 22.1 95.1 64.5 22.9
85 90.7 90.7 22.1 90.8 90.8 22.1 92.2 84.0 22.4
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.
PKG-PRC012Q-EN 27
Water-Cooled Performance Data
62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °f Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 124.0 72.2 30.9 133.6 52.6 32.9 139.5 39.4 34.1
75 125.1 89.6 31.1 134.7 70.0 33.1 140.8 57.4 34.2
3200
80 126.5 107.3 31.4 135.6 87.2 33.3 141.7 75.0 34.6
85 128.3 125.4 31.8 137.0 105.0 33.6 142.8 92.7 34.8
70 129.8 78.7 32.1 139.6 54.1 34.1 145.7 38.5 35.4
75 131.2 100.6 32.3 140.7 76.0 34.3 147.0 60.7 35.6
65 4000
80 133.2 123.0 32.8 142.1 97.9 34.6 148.2 82.7 35.9
85 135.8 135.8 33.3 143.5 119.8 34.9 149.7 104.8 36.2
70 134.1 85.2 33.0 144.0 56.3 35.0 150.2 36.6 36.3
75 135.7 111.4 33.3 145.3 82.7 35.3 151.5 64.1 36.6
4800
80 138.4 136.7 33.8 146.9 108.5 35.6 153.0 89.6 36.9
85 143.4 143.4 34.9 149.2 135.3 36.1 154.7 116.9 37.2
70 119.6 70.1 30.7 128.9 50.3 32.6 134.5 37.4 33.8
75 120.7 87.5 30.9 129.7 67.7 32.8 135.6 55.5 34.0
3200
80 122.0 105.2 31.2 130.9 85.2 33.0 136.6 73.0 34.2
85 124.0 122.9 31.6 132.1 102.9 33.3 137.9 90.7 34.5
70 125.0 76.9 31.8 134.4 52.6 33.8 140.2 36.0 35.0
75 126.5 98.5 32.1 135.6 73.4 34.0 141.5 58.8 35.2
75 4000
80 128.5 120.9 32.5 136.9 95.8 34.3 142.8 80.7 35.5
85 131.7 131.7 33.2 138.6 118.0 34.6 144.2 102.7 35.8
70 129.0 83.0 32.6 138.4 54.1 34.6 144.4 34.8 35.8
75 130.6 109.2 33.0 139.8 78.9 34.9 145.9 62.3 36.1
4800
80 133.1 132.5 33.5 141.3 106.3 35.2 147.2 89.1 36.4
85 138.9 138.9 34.7 143.8 133.5 35.7 148.7 114.7 36.7
70 114.9 68.0 30.5 123.8 48.2 32.3 129.1 35.3 33.5
75 115.9 85.3 30.7 124.6 65.7 32.5 130.3 53.4 33.7
3200
80 117.3 103.0 31.0 125.8 83.1 32.7 131.3 70.9 33.9
85 119.2 119.1 31.4 126.9 100.7 33.0 132.4 88.5 34.1
70 119.9 74.4 31.5 128.9 50.2 33.4 134.4 34.4 34.6
75 121.2 95.9 31.8 130.0 71.6 33.6 135.8 56.7 34.8
85 4000
80 123.6 118.8 32.2 131.4 93.6 33.9 137.0 79.2 35.1
85 127.3 127.3 33.0 133.1 116.0 34.2 138.4 100.4 35.3
70 123.6 80.8 32.3 132.6 51.8 34.2 138.0 32.8 35.3
75 125.3 107.1 32.6 134.0 78.2 34.4 139.7 59.9 35.6
4800
80 127.4 127.4 33.1 135.5 104.2 34.7 141.0 86.3 35.9
85 134.1 134.1 34.4 138.1 131.5 35.3 142.6 112.8 36.2
70 109.7 65.5 30.3 118.2 46.1 32.0 123.3 32.7 33.1
75 110.8 82.9 30.5 119.2 63.3 32.2 124.6 51.1 33.4
3200
80 112.2 100.8 30.8 120.2 80.8 32.4 125.6 69.1 33.6
85 114.2 114.2 31.2 121.4 98.4 32.7 126.7 86.5 33.8
70 114.5 72.0 31.2 123.0 47.6 33.0 128.0 31.3 34.1
75 115.7 93.9 31.5 124.2 69.5 33.3 129.6 54.5 34.4
95 4000
80 117.9 116.0 32.0 125.5 91.4 33.5 130.9 76.5 34.6
85 122.5 122.5 32.9 127.3 114.0 33.9 132.0 98.3 34.9
70 117.9 78.5 31.9 126.1 49.3 33.7 131.3 30.5 34.8
75 119.6 104.9 32.3 127.8 75.8 34.0 133.2 58.6 35.1
4800
80 121.8 121.8 32.8 129.3 102.0 34.3 134.5 84.2 35.4
85 128.9 128.9 34.2 131.9 128.7 34.8 136.2 110.8 35.7
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.
28 PKG-PRC012Q-EN
Water-Cooled Performance Data
62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °f Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 127.8 71.5 34.9 137.1 47.5 37.1 141.6 30.8 38.2
75 129.6 91.6 35.3 138.8 67.7 37.5 144.8 52.8 38.9
3840
80 131.8 111.8 35.9 140.5 87.8 37.9 146.5 73.1 39.3
85 135.2 131.8 36.7 142.4 107.9 38.4 148.3 93.2 39.7
70 134.8 79.1 36.6 144.4 49.9 38.8 149.4 30.3 40.0
75 136.9 103.9 37.0 146.3 74.8 39.2 152.5 56.7 40.7
65 4800
80 140.2 129.1 37.8 148.3 99.8 39.7 154.4 81.6 41.1
85 142.1 142.0 38.3 151.0 125.2 40.4 156.4 106.8 41.6
70 140.1 86.6 37.8 149.9 52.4 40.1 155.3 30.0 41.3
75 142.6 116.0 38.4 151.9 81.9 40.6 158.3 61.0 42.0
5760
80 146.7 142.9 39.4 154.2 111.7 41.1 160.3 90.6 42.5
85 147.5 147.5 39.6 157.9 141.8 42.0 162.8 120.6 43.1
70 122.9 69.5 34.5 131.9 45.6 36.6 136.2 28.9 37.7
75 124.7 89.5 34.9 133.6 65.8 37.0 139.5 51.0 38.4
3840
80 127.0 109.9 35.5 135.3 85.8 37.4 141.1 71.2 38.8
85 130.5 128.9 36.3 137.2 106.0 37.9 142.8 91.3 39.2
70 129.5 77.0 36.0 138.8 47.9 38.2 143.6 28.4 39.4
75 131.6 101.8 36.5 140.7 72.9 38.7 146.7 54.9 40.1
75 4800
80 134.8 126.7 37.3 142.7 97.8 39.1 148.5 79.9 40.5
85 136.0 136.0 37.6 145.5 123.4 39.8 150.5 104.8 41.0
70 134.4 84.5 37.2 143.9 50.5 39.4 149.1 28.2 40.7
75 137.0 114.0 37.8 145.9 80.0 39.9 152.1 59.2 41.4
5760
80 141.3 139.4 38.8 148.3 109.8 40.4 154.1 88.9 41.8
85 142.7 142.7 39.2 152.1 139.7 41.3 156.7 119.0 42.4
70 117.6 67.2 34.1 126.3 43.6 36.1 130.4 26.9 37.1
75 119.3 87.2 34.5 128.0 63.7 36.5 133.6 49.0 37.8
3840
80 121.8 107.8 35.0 129.7 83.8 36.9 135.3 69.3 38.2
85 124.9 124.4 35.8 131.7 104.1 37.4 137.0 89.3 38.6
70 123.7 74.8 35.5 132.6 45.8 37.6 137.2 26.4 38.7
75 125.8 99.6 36.0 134.6 70.9 38.0 140.4 53.1 39.4
85 4800
80 129.3 124.1 36.8 136.5 95.8 38.5 142.2 78.1 39.8
85 130.2 130.2 37.0 139.5 121.6 9.2 144.2 103.2 40.3
70 128.3 82.3 36.5 137.4 48.3 38.7 142.4 26.2 39.9
75 131.0 111.7 37.2 139.5 78.0 39.2 145.4 57.3 40.6
5760
80 134.8 134.1 38.1 141.8 107.8 39.7 147.4 87.1 41.0
85 137.5 137.5 38.7 145.7 137.1 40.6 150.0 117.3 41.7
70 111.9 64.9 33.6 120.4 41.4 35.6 124.3 24.8 36.5
75 113.7 85.0 34.0 122.0 61.6 36.0 127.5 47.0 37.2
3840
80 116.3 105.7 34.6 123.7 81.7 36.4 129.1 67.3 37.6
85 118.2 118.1 35.0 125.7 102.2 36.8 130.7 87.4 38.0
70 117.6 72.5 34.9 126.2 43.7 36.9 130.6 24.4 38.0
75 119.8 97.4 35.4 128.1 68.9 37.4 133.6 51.0 38.7
95 4800
80 123.3 120.7 36.3 130.0 93.8 37.8 135.5 76.2 39.1
85 125.1 125.1 36.7 133.1 119.6 38.5 137.5 101.4 39.6
70 121.9 79.9 35.9 130.6 46.2 38.0 135.4 24.3 39.1
75 124.6 109.5 36.5 132.6 76.0 38.4 138.2 55.3 39.8
5760
80 127.2 126.9 37.1 135.0 105.9 39.0 140.3 85.2 40.2
85 131.9 131.9 38.3 138.9 133.8 39.9 143.0 115.6 40.8
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.
PKG-PRC012Q-EN 29
Water-Cooled Performance Data
30 PKG-PRC012Q-EN
Air-Cooled Performance Data
PKG-PRC012Q-EN 31
Air-Cooled Performance Data
32 PKG-PRC012Q-EN
Air-Cooled Performance Data
PKG-PRC012Q-EN 33
Air-Cooled Performance Data
34 PKG-PRC012Q-EN
Air-Cooled Performance Data
PKG-PRC012Q-EN 35
Air-Cooled Performance Data
36 PKG-PRC012Q-EN
Air-Cooled Performance Data
PKG-PRC012Q-EN 37
Air-Cooled Performance Data
38 PKG-PRC012Q-EN
Air-Cooled Performance Data
PKG-PRC012Q-EN 39
Heating Coil Performance Data
Table 31. Hot water coil heating capacity, 180°F entering water temperature
40 PKG-PRC012Q-EN
Heating Coil Performance Data
Table 31. Hot water coil heating capacity, 180°F entering water temperature (continued)
Table 32. Hot water coil heating capacity, 200°F entering water temperature
PKG-PRC012Q-EN 41
Heating Coil Performance Data
Table 32. Hot water coil heating capacity, 200°F entering water temperature (continued)
7.5 40 149.6 86.0 15.4 6.9 141.3 83.4 9.7 3.2 132.9 80.8 6.8 1.7
ton 3000 0.44 60 128.9 99.6 13.3 5.3 120.7 97.1 8.3 2.3 112.3 94.5 5.8 1.2
SCRJ 80 108.2 113.2 11.1 3.9 100.0 110.7 6.9 1.8 91.8 108.2 4.7 0.9
40 161.7 81.4 16.7 8.0 152.7 79.1 10.5 3.5 143.6 76.8 7.4 1.9
3600 0.60 60 139.3 95.7 14.3 6.1 130.3 93.4 8.9 2.7 121.3 91.1 6.2 1.4
80 117.0 110.0 12.0 4.5 108.0 107.6 7.4 1.9 99.0 105.3 5.1 1.0
40 168.6 104.8 16.8 15.3 161.0 101.9 10.7 6.9 153.3 98.9 7.6 3.8
2400 0.14 60 145.7 116.0 14.5 11.7 138.1 113.1 9.2 5.2 130.4 110.1 6.5 2.9
80 122.7 127.2 12.2 8.6 115.2 124.2 7.7 3.8 107.3 121.2 5.4 2.0
7.5 40 190.7 98.6 19.0 19.1 182.0 95.9 12.1 8.6 173.1 93.2 8.6 4.7
ton 3000 0.21 60 164.7 110.6 16.4 14.7 156.0 108.0 10.4 6.5 147.1 105.2 7.3 3.5
SCWJ 80 138.8 122.7 13.8 10.8 130.0 120.0 8.6 4.7 121.1 117.2 6.0 2.5
40 209.1 93.6 20.8 22.5 199.4 91.1 13.3 10.1 189.6 88.6 9.5 5.6
3600 0.28 60 180.6 106.3 18.0 17.3 170.9 103.8 11.4 7.7 161.0 101.2 8.0 4.2
80 152.1 119.0 15.2 12.7 142.4 116.5 9.5 5.5 132.6 114.0 6.6 2.9
40 214.2 101.7 22.1 5.7 203.3 98.6 13.9 2.5 192.2 95.4 9.9 1.4
3200 0.17 60 184.8 113.2 19.0 4.3 174.0 110.1 11.9 1.9 162.8 106.9 8.4 1.0
80 155.4 124.8 16.0 3.2 144.5 121.6 9.9 1.4 133.3 118.4 6.8 0.7
40 240.8 95.5 24.8 7.0 228.3 92.6 15.7 3.1 215.6 89.7 11.1 1.7
10 ton 4000 0.25 60 207.7 107.9 21.4 5.4 195.3 105.0 13.4 2.4 182.5 102.1 9.4 1.3
80 174.6 120.2 18.0 3.9 162.2 117.4 11.1 1.7 149.4 114.4 7.7 0.9
40 263.3 90.6 27.1 8.2 249.5 87.9 17.1 3.7 235.4 85.2 12.1 2.0
4800 0.34 60 227.1 103.6 23.4 6.3 213.2 100.9 14.6 2.8 199.1 98.2 10.2 1.5
80 190.8 116.6 19.6 4.6 176.9 114.0 12.1 2.0 163 111.3 8.4 1.0
40 235.9 96.6 24.3 6.7 223.7 93.7 15.3 3.0 211.3 90.7 10.9 1.6
3840 0.23 60 203.5 108.8 21.0 5.2 191.3 105.9 13.1 2.3 178.8 102.9 9.2 1.2
80 171.0 121.0 17.6 3.8 158.9 118.1 10.9 1.6 146.3 115.1 7.5 0.9
40 263.3 90.6 27.1 8.2 249.5 87.9 17.1 3.7 235.4 85.2 12.1 2.0
12 ton 4800 0.34 60 227.1 103.6 23.4 6.3 213.2 100.9 14.6 2.8 199.1 98.2 10.2 1.5
80 190.8 116.6 19.6 4.6 176.9 114.0 12.1 2.0 163.0 111.3 8.4 1.0
40 286.4 85.8 29.5 9.6 271.0 83.4 18.6 4.2 255.4 80.9 13.1 2.3
5760 0.45 60 246.9 99.5 25.4 7.3 231.6 97.1 15.9 3.2 216.1 94.6 11.1 1.7
80 207.4 113.2 21.3 5.3 192.2 110.7 13.2 2.3 176.8 108.3 9.1 1.2
40 297.7 97.2 30.7 12.8 283.5 94.4 19.4 5.7 268.9 91.6 13.8 3.2
4800 0.23 60 257.0 109.4 26.5 9.8 242.8 106.6 16.7 4.3 228.2 103.8 11.7 2.4
80 216.4 121.5 22.3 7.2 202.1 118.8 13.9 3.1 187.4 116.0 9.6 1.7
40 332.6 91.1 34.2 15.6 316.3 88.6 21.7 7.0 299.7 86.0 15.4 3.8
15 ton 6000 0.33 60 287.0 104.1 29.6 12.0 270.8 101.6 18.6 5.3 254.2 99.0 13.1 2.9
80 241.6 117.1 24.9 8.8 225.3 114.6 15.4 3.8 208.7 112.1 10.7 2
40 361.7 86.3 37.2 18.2 343.7 84 23.6 8.1 325.4 81.7 16.7 4.4
7200 0.45 60 312.1 100.0 30.2 13.9 294.2 97.7 20.2 6.1 275.9 95.3 14.2 3.3
80 262.5 113.6 27.0 10.2 244.6 111.3 16.8 4.4 227.5 109.1 11.6 2.3
42 PKG-PRC012Q-EN
Heating Coil Performance Data
PKG-PRC012Q-EN 43
Heating Coil Performance Data
44 PKG-PRC012Q-EN
Electrical Data
Electrical Data Calculations
RLA = rated load amps.
Compressor LRA = locked rotor amps.
Fan motor LRA = locked rotor amps,
N.E.C.Table 430 - 151.
FLA = Full load amps, N.E.C.Table 430 - 150
Voltage utilization range is ±10%
Minimum circuit ampacity (MCA)
= 1.25 x largest motor amps (FLA or RLA) + the sum of the remaining motor amps.
Maximum fuse size (MFS) and maximum circuit breaker size (MCB) = 2.25 x largest motor amps
(FLA or RLA) + the sum of the remaining motor amps.
Note: If the rating value determined does not equal a standard current rating of over current
protective device, use the next lower standard rating for the marked maximum rating.
Table 34. SCWJ Electrical data
Evaporator Standard Motor Evaporator Oversized Motor
Compressor Evap Fan Motor Evap Fan Motor
Min Ckt MFS/ Min Ckt MFS/
Model Tons Voltage RLA LRA QTY HP FLA Qty Ampacity MCB HP FLA Qty Ampacity MCB
SCWJ0303 208-230V/60Hz/3Ph 12.9 77.0 2.21 18.30 30 3.15 19.3 30
SCWJ0304 3 460V/60Hz/3Ph 5.7 35.0 1 0.5 1.00 1 8.10 15 1 1.42 1 8.5 15
SCWJ0305 575V/60Hz/3Ph 4.8 31.0 0.80 6.80 15 1.14 7.1 15
SCWJ0503 208-230V/60Hz/3Ph 22.9 155.0 5.00 33.6 50 5.81 34.4 50
SCWJ0504 5 460V/60Hz/3Ph 10.7 75.0 1 1 2.50 1 15.9 25 2 2.63 1 16.0 25
SCWJ0505 575V/60Hz/3Ph 8.5 54.0 1.50 12.1 20 2.10 12.7 20
SCWJ0753 208-230V/60Hz/3Ph 25.0 164.0 6.13 37.4 60 6.13 37.4 60
SCWJ0754 7.5 460V/60Hz/3Ph 12.8 100.0 1 2 2.77 1 18.8 30 2 2.77 1 18.8 30
SCWJ0755 575V/60Hz/3Ph 9.6 78.0 2.22 14.2 20 2.22 14.2 25
SCWJ1003 208-230V/60Hz/3Ph 22.9 155.0 6.30 57.8 80 13.7 65.2 80
SCWJ1004 10 460V/60Hz/3Ph 10.7 75.0 2 2 3.10 1 27.2 35 5 6.18 1 30.3 40
SCWJ1005 575V/60Hz/3Ph 8.5 54.0 2.40 21.5 30 4.94 24.1 30
SCWJ1203 208-230V/60Hz/3Ph 25.4 147.7 9.40 66.5 90 13.70 70.8 90
SCWJ1204 12 460V/60Hz/3Ph 11.8 75.0 2 3 4.60 1 31.2 40 5 6.18 1 32.7 45
SCWJ1205 575V/60Hz/3Ph 9.3 59.6 3.40 24.4 30 4.94 25.9 35
SCWJ1503 208-230V/60Hz/3Ph 27.9 164.0 9.40 1 72.2 100 13.70 76.5 100
SCWJ1504 15 460V/60Hz/3Ph 13.6 100.0 2 3 4.60 35.2 45 5 6.18 1 36.8 50
SCWJ1505 575V/60Hz/3Ph 10.9 78.0 3.40 27.9 35 4.94 29.5 35
PKG-PRC012Q-EN 45
Electrical Data
46 PKG-PRC012Q-EN
Dimensions and Weights
Figure 3. 3 & 5-tons SCWJ/SCRJ
VERTICAL DISCHARGE
HORIZONTAL DISCHARGE
(FIELD CONVERTED)
FIELD REAR
RETURN OPENING
“ NPT
SCWH SCRJ
Note: See Table 2, p. 9 for SCRJ discharge and liquid line sizes.
Unit Voltage
Unit Size 208-230V 460V 575V
3 Ton 7/8 7/8 7/8
5 Ton 1 3/8 7/8 7/8
PKG-PRC012Q-EN 47
Dimensions and Weights
Note: See Table 2, p. 9 for SCRJ discharge and liquid line sizes.
Table 39. SCWJ/SCRJ 7.5 ton dimensions and weights, in-lbs (mm-kg)
Unit Voltage
Unit Size 208-230V 460V 575V
7.5 Ton 1 3/8 7/8 7/8
48 PKG-PRC012Q-EN
Dimensions and Weights
Unit Voltage
Unit Size 208-230V 460V 575V
10 Ton 13/8 7/8 7/8
12 Ton 1 5/8 1 3/8 7/8
15 Ton 1 5/8 1 3/8 7/8
PKG-PRC012Q-EN 49
Dimensions and Weights
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SEE NOTE 4
HAIL GUARD
(OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE) SEE NOTE 1
35 15/16"
HAIL GUARD (912.8) REFRIGERANT ACCESS
(OPTIONAL) LINE VOLTAGE WITH HAIL GUARD
1 3/8” dia. 33 7/8"
(860.4)
CONTROL WIRING
1/16"
7 15/16" (1.59) 6" (152.4) 2 7/8"
(201.6) 6" (152.4) (73)
DISCHARGE LINE 1 7/8"
7/8” 21 11/16"
(550.9) (47.6) 40 15/16"
LIQUID LINE (1039.8)
1/2” 33 13/16" 41 15/16"
(858.8) (1065.2)
WITH HAIL GUARD
SERVICE PANEL SIDE
40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT
4 3/16"
(106.36)
1 13/16" 27 11/16" 2 5/16"
(46) (703.3) (58.7)
50 PKG-PRC012Q-EN
Dimensions and Weights
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
SERVICE PANEL WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
HAIL GUARD
SEE NOTE 4 (OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE
SEE NOTE 1
39 15/16"
(1014.4) REFRIGERANT ACCESS
HAIL GUARD 4 1/4" WITH HAIL GUARD
(OPTIONAL) (108)
1 1/4" 37 15/16"
(31.7) LINE VOLTAGE
1 3/8” dia (963.6)
CONTROL WIRING
39 1/8"
SERVICE PANEL (993.8)
34 1/16" (865.2)
29 3/4" 26 7/8"
(755.6) (682.6)
14 5/16"
7 1/2" 8 1/4" (363.5)
(190.5) (209.5)
1/16"
DISCHARGE LINE (1.6) 1 7/8"
7/8” 1 15/16" (49.2) 6" 25 11/16" 6" (47.6)
LIQUID LINE (152.4) (652.5) (152.4) 2 7/8" (73)
1/2” 4 15/16" 50 15/16"
(125.4) 37 11/16" (1294)
(957.3)
51 15/16"
(1319.2)
WITH HAIL GUARD
50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)
3 13/16"
(96.8)
PKG-PRC012Q-EN 51
Dimensions and Weights
HAIL GUARD
(OPTIONAL)
SEE NOTE 3
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 1
FOR CLEARANCE)
SERVICE PANEL
DETAIL A 46"
95 7/16" (1168.4)
(2424) WITH HAIL GUARD
WITH HAIL GUARD
41 7/16" 44"
(1052.5) (1117.6)
HAIL GUARD
(OPTIONAL) HAIL GUARD
(OPTIONAL)
45 1/8"
(1146.2)
3 3/8" 1/16"
(85.7) 3/16"
SERVICE (1.6)
6 5/8" (4.8)
PANEL
(168.3) 41 3/8"
(1051) 9" 25 11/16" 9"
(228.6) (652.5) (228.6)
93 5/16"
(2370.1)
9 1/4" (235)
6 13/16" (173)
7/16" (11.1) DIA. ISOLATOR MOUNTING 1 3/16" (30.2)
CONTROL
HOLES (OUTSIDE HOLES - 4 PLACES) LINE VOLTAGE WIRING
1 1/4” dia
SERVICE PANEL SIDE
DISCHARGE LINE
REFRIGERANT ACCESS
41 5/8"
39 7/8" (1057.3)
(1012.8)
18 3/4"
BOTTOM OF UNIT
41 1/2" (476.2) 14 5/8"
36 7/8" (1054) (371.5)
(936.6)
12 9/16"
(319.1) LIQUID LINES
5 9/16" 5/8”
4 3/8"
(141.3)
(111.1)
3" (76.2) 2 3/16" 6 13/16" DISCHARGE LINE 6 5/16" (160.3)
87" (55.6) (173) 7/8”
(2210) 3 11/16" (93.7)
93" 15/16" (23.8)
(2362.2)
FRONT DETAIL A
DIMENSIONAL DETAIL
52 PKG-PRC012Q-EN
Dimensions and Weights
Figure 9. Plenum
Figure 10. Hot water coil 3 & 5-ton units (coils are field installed)
0.59 (15)
A
3.15 (80)
5.91 (150) B 1.57
(40)
(35)
1.38
2.18
(55)
D
(213)
8.39
G F
0.28
(6.4)
E
2.18
(55)
(35)
1.38
0.59
0.39 0.39
(15)
C
(9.9) (9.9)
1.03 1.03 (26)
(26)
1.08 (27)
Table 47. SCWJ/SCRJ Hot water coil dimensions & weights, 3 & 5-ton units, in-lbs (mm-kg)
Size A B C D E F G Weight
3-ton 26.46 (672) 18.98 (482) 25.67 (652) 5.79 (147) 5.79 (147) 10.00 (254) 12.76 (324) 13 (5.9)
5-ton 30.98 (787) 23.50 (597) 30.20 (767) 7.040 (179) 7.040 (179) 12.50 (318) 15.26 (388) 18 (8.2)
PKG-PRC012Q-EN 53
Dimensions and Weights
Figure 11. Hot water coil 7.5-ton units (coils are field installed)
Table 48. SCWJ/SCRJ Hot water coil dimensions & weights, in-lbs. (mm-kg)
Unit Size A B C D E F G Weight
7.5-ton SCRJ 35.5 (902) 28.0 (712) 34.7 (882) 8.5 (215) 8.5 (215) 17 (432) 20.7 (526) 24 (10.9)
7.5-ton SCWJ 52.2 (1327) 44.8 (1137) 51.1 (1299) 8.5 (215) 8.5 (215) 17 (432) 20.7 (526) 30 (13.6)
54 PKG-PRC012Q-EN
Dimensions and Weights
Figure 12. Hot water coil 10 thru 15-ton units (coils are field installed)
1.03 (26)
0.39 (9.9) A 0.39 1.08 (27)
(9.9) 1.03
1.38 (35)
1.38 (35)
2.18 (55)
(26)
0.59
(15)
(242)
9.54
15.89 (404)
17.50 (445)
20.26 (515)
0.28
(7.1)
2.18 (55)
(242)
9.54
8.27 (210)
(230)
9.07
0.59
(190)
1.38
(35)
7.48
0.43 C B 1.57 (40)
(10.9) 3.19
D (81)
BLOCKOFF (SHIPS DISASSEMBLED)
1.00 NPT
(25.4) 0.75 (19.1) 0.75 (19.1)
5.90
(150)
Table 49. SCWJ/SCRJ Hot water coil dimensions & weights, in-lbs. (mm-kg)
Unit Size A B C D Weight
10 & 12-ton 58.72 (1491) 50.98 (1295) 6.95 (177) 59.51 (1512) 49 (22.2)
15-ton 73.29 (1862) 63.98 (1625) 8.52 (216) 74.07 (1881) 55 (25)
PKG-PRC012Q-EN 55
Dimensions and Weights
Figure 13. Steam coil: 10, 12, & 15-ton units (all coils are field installed)
3.15”
C
MPT INLET
B
D
MPT OUTLET
6.89”
3.15”
C
MPT INLET
D
MPT OUTLET
56 PKG-PRC012Q-EN
Dimensions and Weights
Figure 16. Service clearance recommendations (side-mounted fan configuration, field converted on sizes 10, 12, & 15)
RIGHT SIDE
24"
TXV ACCESS
(RIGHT SIDE)
UNIT-MOUNTEDT-STAT
OPENING (BOTH SIDES)
POWER ENTR
(BOTH SIDES)
CONTROL ENTR
FRONT RETURN FAN ACCESS
24" (BOTH SIDES)
PKG-PRC012Q-EN 57
Mechanical Specifications
Midrange Self-Contained Models SCWJ/SCRJ
General
The units shall be completely factory assembled, tested, piped, internally wired, and fully charged
with R410A (water-cooled only). Remote air-cooled units shall be charged in field, after refrigerant
interconnecting lines are brazed and the system vacuum pumped.Units are in compliance with
ASHRAE 90.1 equipment efficiency requirements. All units shall go through a factory run test
before shipment. All equipment shall have factory-installed decals and labels to aid in servicing and
indicate caution areas.
Cabinet
The cabinet shall be constructed with galvanized steel with aluminum frame. All exterior panels
shall be 1” double wall foamed panels with allen head fasteners for easy removal and access. All
panels shall be painted with anticorrosive primer and high resistance synthetic enamel.The unit
shall be construct for vertical discharge with front return on 3, 5, and 7.5-ton units or rear return
on 10, 12, and 15-ton units. Air discharge and return is field convertible to different configurations.
Evaporator Coil
The evaporator coil shall be constructed with 3/8”OD, internally enhanced copper tubes, which are
mechanically bonded to aluminum fins. Coils shall be factory leak tested to 600 psig.The drain pan
shall be constructed of stainless steel and positively sloped.
Supply Fan
The evaporator fan shall be statically and dynamically balanced, forward curve centrifugal fans,
and galvanized steel construction.The fans shall be provided with permanently lubricated bearings
with a design life (L10) of at least 200,000 hours. Motors shall be open drip proof type. Drive
assemblies shall consist of V-belts and variable pitch drive sheaves.
Filters
Units shall come standard with one-inch, fiberglass, throwaway filters.The filter rack can
accommodate a one or two-inch filter.
Compressors
The compressors shall all be scroll compressors each with their own independent circuit.
Compressors shall be mounted on rubber isolators for vibration isolation.The 3, 5, and 7.5-ton units
shall have a single compressor.The 10, 12, and 15-ton units shall have dual compressors.
Crankcase heaters shall be provided on remote air-cooled units.
Refrigeration Circuit
Refrigeration circuits shall be independent and completely piped including: filter driers, sight glass,
distributors, thermal expansion valves, and Schrader access valve in the suction / liquid lines. Each
circuit shall be equipped with high and low-pressure switches.The high-pressure switch shall be
rated at 450±10 psig open / 348±14.5 psig close (water cooled, except 12 ton) and 624±17.5 psig open
/ 464±29 psig close (remote air-cooled and 12-ton water-cooled).The low-pressure switch shall be
rated at 51±7 psig open / 94±7 psig close. Each circuit shall be leak tested, dehydrated and charged
58 PKG-PRC012Q-EN
Mechanical Specifications
with oil (water-cooled and remote air-cooled) and R410A (water-cooled only, remote air-cooled shall
be charged in field).
Electrical /Controls
Each unit shall have single point power connections with a terminal block.The unit shall come
standard with a control interface that will include terminal strip and 24V transformer.
Agency Listing
The unit has ETL-CETL agency listing.
Evaporator Coil with Corrosion Resistant Treatment and Silver Solder Braze
Joints (SCRJ)
The evaporator coil shall have a phenolic coating applied for protection in harsh environments.
Silver solder braze joints are provided on unit coil and refrigeration piping.
PKG-PRC012Q-EN 59
Mechanical Specifications
Field-Installed Accessories
Remote-Mounted Thermostat
A 1H/1C remote-mounted thermostat shall be provided with 3, 5, and 7.5-ton units. A 2H/2C or 2C
remote-mounted thermostat shall be provided with 10, 12, and 15-ton units. All thermostats are
available with auto, manual, or auto/manual bases.
Unit-Mounted Thermostat
A 1C unit-mounted thermostat shall be provided with 3, 5, and 7.5-ton units. A 2C unit mounted
thermostat shall be provided with 10, 12, and 15-ton units.
Steam Coil
The steam coil shall be designed for use with two (2) to five (5) psig steam.The steam coil shall
be a field-installed item.The coil shall be mounted to the unit with right or left hand connections.
Discharge Plenum
The discharge plenum shall provided with double deflection louvers to provide horizontal
discharge.The plenum shall be constructed of sheet metal with 2" fiberglass insulation to provide
a low sound operation.
60 PKG-PRC012Q-EN
Mechanical Specifications
Anti-Recycle Timer
An anti-recycle timer shall be provided to protect the compressor from excessive cycling.
Compressor will lock out for a determined period of time when either the thermostatic contacts
open or there is a momentary power outage.
PKG-PRC012Q-EN 61
Mechanical Specifications
Unit Casing
Unit casing is constructed of zinc coated heavy gage, galvanized steel. Exterior surfaces are
cleaned, phosphatized and finished with a weather-resistant baked enamel finish. Unit surface is
tested 672 hours in salt spray test. Unit has removable end panels to allow access to all major
components and controls.
Condenser Coil
Coils are microchannel as standard. Also, coils are factory pressure and leak tested to 450 psig.
Refrigeration System
Unit will have a single or dual refrigeration circuit(s). Each refrigeration circuit has an integral
subcooling circuit.
Controls
Condensers will be completely factory wired with necessary controls. Control wiring will be for a
24-volt control circuit.
Hail Guards
Provides condenser protection from hail, vandals, etc. Hail guards are made from perforated,
galvanized steel. Hail guards can be factory or field installed.
62 PKG-PRC012Q-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.