Product Catalog

Midrange Self-Contained Unit


3 to 15Ton Water-Cooled and Air-Cooled Conditioners
Remote Air-Cooled Condensers

January 2014 PKG-PRC012Q-EN


Introduction
Deluxe Self-Contained Units
Commercial quality built into each unit.

Figure 1. SCWJ 3-Ton & 12-Ton Units

Revision Summary
PKG-PRC012Q-EN (29 Jan 2014)
Remove corrosion resistant coating option.
PKG-PRC012P-EN (06 Nov 2013)
Updated for increased efficiency project - SCWH to SCWJ.
PKG-PRC012-EN (05 Sep 2012)
Corrected water connection size for SCWH075. Added CTA liquid and discharge line sizes. Added
power entry hole sizes. Miscellaneous minor corrections.

Trademarks
CompleteCoat,Trane and theTrane logo are trademarks ofTrane in the United States and other
countries. All trademarks referenced in this document are the trademarks of their respective
owners.

© 2014Trane All rights reserved PKG-PRC012Q-EN


Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fan Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Pressure Drop Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Water-Cooled Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Air-Cooled Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Heating Coil Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

PKG-PRC012Q-EN 3
Features and Benefits
MidrangeVertical Self-Contained air conditioners, available in 3 to 15-tons, are single package units
designed for low cost installation in the conditioned space or equipment room. Durable
construction, strict quality control, and demanding factory testing ensure reliability from start-up
through years of operation. All units are shipped fully factory assembled and tested — thereby
reducing field labor, installation time, and costs.
Units are easy to convert from vertical to horizontal discharge arrangements. Unit return
convertible for front or rear return air offers flexibility to match most building configurations.
Discharge fan section removable to allow passage through standard height doorway.
Discharge can be either free or ducted. Power and water connections are available from either side
of the unit adding to the unit flexibility.

Standard Features
• 3 through 15-ton commercial self-contained units
• Water-cooled or air-cooled condensing applications
• Fits through standard 36-inch door. Discharge fan section removable to allow passage through
standard height doorway (on 10-15 ton units).
• Single point power connection
• Single point water connection on water-cooled units
• Both water and power connections are available on either side of the unit
• Rugged 1” double wall foamed panel construction
• Positively-sloped stainless steel IAQ drain pan
• Front or rear return air openings
• Vertical and horizontal discharge arrangements
• Decorative front return air grille on 3 - 7.5 tons
• ETL/CETL listing on standard unit
• AHRI certified performance
• All compressors are scroll type
• All remote air-cooled units have crankcase heaters as standard
• Variable pitch sheaves allow field adjustment of airflow
• High and low pressure cutout switches

Optional Features and Accessories


• Hydronic heating coils
• Horizontal discharge plenums
• Water regulating valves provide condensing head pressure control on water-cooled units
• Protective coatings available on both the unit and evaporator coils
• CuNi condensers
• Remote mounted thermostats
• Unit mounted thermostat kit
• Low ambient control operation on air-cooled condenser
• Oversized/2- speed fan motor and drive kits
• Side-mounted fan section kit on 10, 12, & 15-ton units
• Decorative front return grille on 10, 12, & 15-ton units
• Hail Guards on outdoor CTA units

4 PKG-PRC012Q-EN
Application Considerations
CTA Unit Location
Unobstructed condenser airflow is essential to maintain capacity and operating efficiency. When
determining unit placement, give careful consideration to assure sufficient airflow across the
condenser coils. Avoid these two detrimental conditions: warm air recirculation and coil starvation.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity
because of the higher head pressure associated with them. In more severe cases, nuisance unit
shutdowns will result from excessive head pressures.

Clearance
Ensure vertical condenser air discharge is unobstructed. While it is difficult to predict the degree
of warm air recirculation, a unit installed with a ceiling or other obstruction above it will experience
a capacity reduction that will reduce the maximum ambient operation. Nuisance high head
pressure trip outs may also occur.The coil inlet must also be unobstructed. A unit installed closer
than the minimum recommended distance to a wall or other vertical riser will experience a
combination of coil starvation and warm air recirculation.This may result in unit capacity and
efficiency reductions, as well as possible excessive head pressures.
Reference the service clearance section for recommended lateral distances.

Ambient Limitations
Standard ambient control allows operation down to 45°F (7.2°C) with cycling of condenser fans.
Units with the low ambient kit option are capable of starting and operating in ambient temperatures
down to 0°F (-17.8°C). Optional low ambient kit units use a condenser fan motor speed controller
that controls condenser capacity by modulating condenser airflow in response to saturated
condenser temperature or ambient temperature. Maximum cataloged ambient temperature
operation of a standard condenser is 125°F (46.1°C). Operation at design ambient above 125°F can
result in excessive head pressures. For operation above 125°F, contact the localTrane sales office.

PKG-PRC012Q-EN 5
Selection Procedure
Follow this process to select a midrange self-contained unit.

Step 1. Load
Determine the load requirements for heating and cooling, include outside air. UseTrane’s load
estimate program or any standard method.

Step 2. Unit Type


Self-contained air conditioners are available in either water-cooled or remote air-cooled models to
match individual needs.

Step 3. Select the Unit


The conditions under which the unit must operate and the design load will give the final selection.

Selection Example
Design conditions for a water-cooled unit with airflow = 2,000 cfm at 0.5-inch duct static pressure.
Entering air temperature = 80/67°F
Total gross capacity required = 66,400 Btu/h
Entering water temperature = 85°F
Leaving water temperature = 95°F

Unit Selection
Tentatively select a 5-ton unit, model SCWJ050. Refer to Table 19, p. 26 to obtain gross total and
sensible unit capacities, gpm, and leaving water temperature at nominal conditions:
Total capacity = 68.1 MBh
Sensible capacity = 49.2 MBh
Water flow rate = 16.2 gpm
Leaving water temperature = 95°F (all capacity tables assume 10° T)
The SCWJ050 meets the total and sensible capacities and other design requirements.
Refer to the fan data Table 4, p. 12 to determine approximate brake horsepower and fan rpm:
Fan brake horsepower = 0.73 bhp
Fan rpm = 1020 rpm
Determine net capacities by subtracting fan motor heat from gross capacities:
3.98 X 0.73 bhp = 2.9 MBh
Net total capacity = 68.1 MBh – 2.9 MBh = 65.2 MBh
Net sensible capacity = 49.2MBh - 2.9 MBh = 46.3 MBh

6 PKG-PRC012Q-EN
Model Number Descriptions
Midrange Model Remote Air-Cooled
Number Description Condenser
Digit 1 - Unit Model Digits 1, 2, 3 - Product Type
S = Self contained CTA = Remote air-cooled condenser
Digit 2 - Unit Type Digits 4, 5, 6 - Nominal Gross
C = Commercial Cooling Capacity (MBh)
Digit 3 - Condenser Medium 090 = 090 MBh (used with 3 & 5-ton
SCRJ)
R = Remote air-cooled 120 = 120 MBh (used with 7.5
W = Water cooled SCRJ)
Digit 4 - Development Sequence 180 = 180 MBh (used with 10, 12, 15-ton
J = Development series SCW/SCR* SCRJ)

Digit 5, 6, 7- Unit Nominal Digits 7 - Major Development


Capacity Sequence
030 = 3 tons D = 1 refrig cir.(3, 5, 7.5-ton SCRJ)
050 = 5 tons E = 2 refrig cir. (10, 12, 15-ton SCRJ)
075 = 7.5 tons Digits 8 - Electrical
100 = 10 tons Characteristics
120 = 12 tons
150 = 15 tons 1 = 208-230/60/1
2 = 460/60/1
Digit 8 - Unit Voltage 8 = 575/60/1
3 = 208 - 230 volt/60 hz/3 ph Digits 9,10 - Factory Installed
4 = 460 volt/60 hz/3 ph
5 = 575 volt/60 hz/3 ph Options
00 = Packed stock
Digit 9 - Air Flow Configuration 0A = Coated Coil
2 = Vertical discharge / front return 0B = Coated Coil and Cabinet
(3-7.5 ton)
3 = Vertical discharge / rear return Digits 11 - Minor Design
(10-15 ton) Sequence
Digit 10, 11 - Design Sequence * = Factory specified
A0 = Design sequence A0(SCW*/SCR*) Digits 12 - Service Digit
* = Factory specified
Digit 12 - Air Filter Type
1 = One-inch fiberglass throwaway
Digit 13 - Control
0 = Control interface
Digit 14 - Unit Finish
1 = Painted
Digit 15 - Coil Finish
0 = None
E = Evaporator coated + silver solder
braze joints (SCRJ)
J = Cupronickel coated +
evaporator coated + silver solder
braze joints (SCWJ)

PKG-PRC012Q-EN 7
General Data
Table 1. Water-Cooled Midrange General Data

Model SCWJ030 SCWJ050 SCWJ075 SCWJ100 SCWJ120 SCWJ150


Nominal Capacity 3.0 5.0 7.5 10.0 12.0 15.0
Dimensional Data
Height In. 66.93 78.74 78.94 91.54 95.47
Length In. 31.89 36.41 57.68 65.75 65.75 80.31
Depth In. 22.24 24.01 28.74 29.52
Weight (Shipping / Net) Lbs. 494 / 459 592 / 555 803/759 1094/1027 1133/1063 1249 / 1172
Cooling Performance
Net Cooling Capacity(a) btu/h 36000 63000 90000 120000 138000 180000
EER(b) (btu/h)/W 12.1 12.1 12.1 12.1 12.5 12.5
IEER(b) 12.3 12.3 12.3 12.3 12.5 12.5
Rated Air Flow CFM 1200 2000 3000 4000 4800 6000
System Power kW 3.0 5.3 6.91 10.43 12.55 16.36
Compressor
Quantity 1 2
Type Scroll
Manufacturer Copeland
Model ZP32 ZP57 ZP76 ZP57 ZP67 ZP83
Indoor Coil
Tube Size In. 3/8
Face Area Sq Ft 3.19 4.98 10.70 12.12 12.12 14.56
Rows / fpf 4 / 144 4 / 144 4/168 3/168 2 / 168 3 / 168
Water Condenser
Type Tube & Tube
Water Connection In. 3/4 NPT 3/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT 1 1/4 NPT
Minimum Water Flow gpm 3.5 4.5 12 16.5 24.5 25
Maximum Water Flow gpm 11 19 28.5 38.5 44 56
Minimum EWT (w/o water reg. valve) °F 65
Minimum EWT (w/ water reg. valve) °F 35
Indoor Fan
Quantity 1 2
Diameter x Width In. 9x9 10 x 10 9x9 12 x 12
Drive Type Belt
Motor Qt / HP 1 / 0.5 1 / 1.0 1/2.0 1/2.0 1 / 3.0 1 / 3.0
Motor Frame Size Nema 56
Minimum Air Flow CFM 960 1600 2400 3200 3840 4800
Maximum Air Flow CFM 1440 2200 3600 4800 5760 7200
Air Filter
Type Throwaway - 1" Thickness
14 x 20 (1) + 12 x 24 (1) + 12 x 24 (1) + 18 x 24 (3) +
Size / (Quantity) In. 14 x 25 (1) 17 x 24 (3)
20 x 20 (1) 24 x 24 (2) 24 x 24 (2) 24 x 24 (1)
Refrigerant Information
Refrigerant Control TXV
Refrigerant Type R-410A
Refrigerant Charge (Ckt 1 / 2) 3.75 5.56 7.19 5.19/5.44 5.63/5.63 7.0/6.95

8 PKG-PRC012Q-EN
General Data

Table 1. Water-Cooled Midrange General Data (continued)

Model SCWJ030 SCWJ050 SCWJ075 SCWJ100 SCWJ120 SCWJ150


Nominal Capacity 3.0 5.0 7.5 10.0 12.0 15.0
Hot Water Coil
Tube Size 1/2
Face Area 1.42 2.08 5.05 6.20 6.20 7.78
Rows / fpf 2 / 108
(a) Net cooling capacity is rated at 85°F entering water, 80°F entering dry bulb and 67°F entering wet bulb at the rated SCFM air conditio
(b) EER and IEER are rated in accordance with AHRI Standards 210/240 and 340/360.

Table 2. Air-cooled midrange self contained and matching CTA condenser general data

Indoor Unit Model SCRJ030 SCRJ050 SCRJ075 SCRJ100 SCRJ120 SCRJ150


Indoor Unit Nominal Capacity Tons 3.0 5.0 7.5 10.0 12.0 15.0
Matching Outdoor Condenser CTA090 CTA090 CTA120 CTA180 CTA180 CTA180
Condenser Gross Heat of Rejection MBH 121 121 167 272 272 272
Matched System Cooling Performance
AHRI net cooling capacity with matched indoor
33400 55000 78000 121000 135000 172000
unit(a) Btu/h
(S)EER/IEER(b) (Btu/h)/W 13.7 13.0 11.2/11.4 11.84/11.4 11.2/11.2 11.0/11.2
Rated Air Flow CFM 1200 2000 3000 4000 4800 6000
System Power Kw 2.7 4.8 7.0 10.3 12.1 15.8
Condenser Circuits & Refrigerant Lines(c)
No. refrigeration circuits 1 1 1 2 2 2
Discharge line, OD In. .75 .75 .75 .75 .75 .75
Liquid line, OD In. .5 .5 .5 .625 .625 .625
Indoor Unit Compressor
Compressor Quantity 1 2
Type/Refrigerant Scroll/410A
Manufacturer Copeland
Model ZP29 ZP49 ZP67 ZP51 ZP57 ZP76
Indoor Unit Evaporator Coil
Tube Size In. 3/8"
Face Area Sq. Ft. 3.19 4.98 7.13 12.12 14.56
Rows / fpf 4/144 4/168 4/180 4/168 4/168 4/168
Refrigerant Control TXV
Condenser Coil - Micro Channel
Quantity 2 2 2 2 2 2
32x41.5 32x41.5 32x53 40x95 40x95 40x95
Size - in (mm)
(810x1053) (810x1053) (810x1349) (1017x2413) (1017x2413) (1017x2413)
Face Area - ft2 (m2) 18.4 (1.7) 18.4 (1.7) 23.6 (2.2) 52.8 (4.9) 52.8 (4.9) 52.8 (4.9)
Rows/fpi 1/23 1/23 1/23 1/23 1/23 1/23
Refrigerant Charge, Field Supplied
Lbs of R-410A(d) 7.88 8.25 10.6 9.8/9.8 10.1/10.1 10.9/10.4

PKG-PRC012Q-EN 9
General Data

Table 2. Air-cooled midrange self contained and matching CTA condenser general data (continued)

Indoor Unit Model SCRJ030 SCRJ050 SCRJ075 SCRJ100 SCRJ120 SCRJ150


Indoor Unit Nominal Capacity Tons 3.0 5.0 7.5 10.0 12.0 15.0
Matching Outdoor Condenser CTA090 CTA090 CTA120 CTA180 CTA180 CTA180
Condenser Gross Heat of Rejection MBH 121 121 167 272 272 272
Indoor Unit Fan
Quantity 1 2
Diameter x Width In. 9x9 10x10 9x9 12x12
Drive Type Belt
Motor Qt/HP 1/0.5 1/1.0 1/2.0 1/2.0 1/3.0 1/3.0
Motor Frame Size Nema 56
Minimum Air Flow CFM 960 1600 2400 3200 3840 4800
Maximum Air Flow CFM 1440 2200 3600 4800 5760 7200
Condenser Fan
Number/type 1/prop 1/prop 1/prop 1/prop 1/prop 1/prop
Size - in (mm) 26 (660) 26 (660) 28 (711) 28 (711) 28 (711) 28 (711)
Fan drive Direct Direct Direct Direct Direct Direct
Airflow cfm 4500 4500 6800 7500 x 2 7500 x 2 7500 x 2
Motors - Number/hp each 1/.50 1/.50 1/1.00 2/1.0 2/1.0 2/1.0
Motor RPM 1150 1150 1000 1125 1125 1125
Ambient Operating Range
Ambient temperature operating range, °F (°C) 45-125 (7.2 - 51.7)
Low ambient temperature operating range, °F (°C) 0-125 (-17.8 - 51.7)
Indoor Unit Dimensional Data
Height 66.93 78.74 78.94 91.54 95.47
Length 31.89 36.41 40.94 65.75 80.31
Depth 22.24 24.01 28.74 29.52
Weight (Shipping/Net) 474/439 531/494 636/591 1013/946 1034/964 1133/1056
Air Filter
Type Throwaway - 1" Thickness
14 x 20(1) + 18 x 24(3) +
Size/(Quantity) 14 x 25(1) 18 x 24(2) 12 x 24(1) + 24 x 24(2)
20 x 20(1) 24 x 24(1)
Hot Water Coil
Tube Size 1/2
Face Area 1.42 2.08 3.27 6.2 7.78
Rows/fpf 2/108
(a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering the wet bulb. AHRI capacity includes the effect of fan motor
heat. Ratings shown are tested and certified in accordance with AHRI Standard 340/360 or 365 certification program.
(b) (S)EER is rated at AHRI conditions and in accordance with DOE test procedures.
(c) Line sizes listed are for SCRJ units only. See Figure 6, p. 50, Figure 7, p. 51 or Figure 8, p. 52 for CTA discharge and liquid line sizes.
(d) Refrigerant (operating) charge is for condenser unit (all circuits) with matching indoor unit and 33 ft. of interconnecting refrigerant lines. All units
are shipped with a small nitrogen holding charge.

10 PKG-PRC012Q-EN
Fan Performance Data

Table 3. Evaporator fan performance - SCWJ030 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
960 — — — — 960 0.18 1020 0.21 1070 0.23 1130 0.26 1180 0.28
1040 — — 940 0.19 1000 0.21 1050 0.24 1100 0.26 1160 0.29 1210 0.32
1120 920 0.20 980 0.23 1040 0.25 1090 0.28 1140 0.30 1190 0.33 1240 0.36
1200 970 0.24 1020 0.26 1080 0.29 1130 0.32 1180 0.35 1230 0.38 1270 0.40
1280 1020 0.28 1070 0.31 1120 0.34 1170 0.37 1220 0.40 1270 0.43 1310 0.46
1360 1070 0.33 1120 0.36 1170 0.39 1210 0.42 1260 0.45 1300 0.48 1350 0.51
1440 1120 0.38 1160 0.41 1210 0.44 1260 0.48 1300 0.51 1340 0.54 1380 0.57

continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
960 1230 0.31 1280 0.34 1330 0.37 1430 0.43 1520 0.49 1610 0.56
1040 1260 0.35 1310 0.38 1360 0.41 1450 0.47 1530 0.53 1620 0.60
1120 1290 0.39 1340 0.42 1380 0.45 1470 0.51 1550 0.58 1640 0.65
1200 1320 0.44 1370 0.47 1410 0.50 1490 0.56 1580 0.63 1660 0.70
1280 1360 0.49 1400 0.52 1440 0.55 1520 0.62 1600 0.69 1680 0.77
1360 1390 0.55 1430 0.58 1470 0.61 1550 0.68 1630 0.76 1700 0.83
1440 1430 0.61 1470 0.64 1510 0.68 1580 0.75 1660 0.82 1730 0.90
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

PKG-PRC012Q-EN 11
Fan Performance Data

Table 4. Evaporator fan performance - SCWJ050 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b)
1600 740 0.31 780 0.35 830 0.38 880 0.41 920 0.45 960 0.49 1000 0.52
1750 780 0.40 830 0.43 870 0.47 920 0.50 960 0.54 1000 0.58 1040 0.62
1850 820 0.46 860 0.50 900 0.53 940 0.57 980 0.61 1020 0.65 1060 0.69
2000 870 0.56 910 0.60 950 0.64 990 0.68 1020 0.73 1060 0.77 1100 0.81
2150 920 0.69 960 0.73 990 0.77 1030 0.81 1070 0.86 1100 0.90 1130 0.95
2250 960 0.78 990 0.82 1030 0.87 1060 0.91 1100 0.96 1130 1.00 1160 1.05
2400 1010 0.93 1040 0.98 1080 1.02 1110 1.07 1140 1.12 1170 1.17 1200 1.21
Standard Drive(c) Field Installed High Static Pressure Drive(d)

continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
1600 1040 0.56 1080 0.60 1120 0.64 1200 0.72 1270 0.80 1340 0.89
1750 1070 0.66 1110 0.70 1150 0.74 1220 0.83 1290 0.92 1360 1.01
1850 1100 0.73 1130 0.78 1170 0.82 1240 0.91 1310 1.00 1370 1.09
2000 1130 0.86 1170 0.90 1200 0.95 1270 1.04 1330 1.13 1390 1.23
2150 1170 0.99 1200 1.04 1230 1.09 1300 1.19 1360 1.29 — —
2250 1200 1.10 1230 1.15 1260 1.20 1320 1.30 1380 1.40 — —
2400 1240 1.26 1270 1.32 1300 1.37 1350 1.47 — — — —
Field Installed High Static Pressure Drive(d)
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

12 PKG-PRC012Q-EN
Fan Performance Data

Table 5. Evaporator fan performance - SCWJ075(a)

External Static Pressure (InWg)


Air Flow
(cfm) 0.1 0.2 0.3 0.4 0.5 0.6 0.7
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
2400 --- --- --- --- 991 0.48 1053 0.53 1115 0.59 1173 0.65 1232 0.71
2600 892 0.44 953 0.49 1015 0.55 1073 0.61 1132 0.67 1188 0.73 1242 0.79
2800 924 0.52 982 0.57 1041 0.63 1096 0.69 1150 0.75 1205 0.82 1257 0.88
3000 958 0.61 1012 0.66 1068 0.73 1120 0.79 1174 0.85 1225 0.92 1274 0.99
3200 992 0.70 1046 0.77 1097 0.83 1149 0.90 1198 0.96 1246 1.03 1295 1.09
3400 1029 0.81 1078 0.88 1128 0.94 1176 1.01 1225 1.08 1271 1.14 1316 1.21
3600 1066 0.93 1113 1.00 1161 1.07 1206 1.13 1253 1.20 1297 1.28 1341 1.35
continued
External Static Pressure (InWg)
Air Flow
(cfm) 0.8 0.9 1.0 1.2 1.4 1.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
2400 1286 0.77 1339 0.84 1393 0.91 1493 1.05 1584 1.18 1672 1.33
2600 1297 0.86 1349 0.93 1401 1.00 1497 1.13 1591 1.28 1679 1.44
2800 1310 0.95 1360 1.02 1409 1.08 1505 1.23 1597 1.39 1684 1.55
3000 1325 1.06 1373 1.12 1422 1.19 1514 1.34 1603 1.50 1690 1.67
3200 1342 1.16 1390 1.24 1436 1.31 1526 1.47 1613 1.63 1696 1.80
3400 1363 1.29 1407 1.37 1453 1.45 1538 1.60 1623 1.77 1706 1.93
3600 1386 1.43 1428 1.51 1472 1.59 1555 1.75 1637 1.91 1717 2.09
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive. Field installed

PKG-PRC012Q-EN 13
Fan Performance Data

Table 6. Evaporator fan performance - SCWJ100 fan performance(a)

External Static Pressure (InWg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
3200 627 0.46 688 0.55 747 0.65 799 0.75 848 0.86 894 0.97 945 1.10
3500 639 0.53 701 0.63 756 0.73 810 0.84 859 0.95 904 1.07 948 1.18
3750 652 0.60 712 0.71 766 0.81 817 0.92 867 1.04 913 1.14 957 1.27
4000 665 0.68 722 0.79 775 0.89 828 1.01 875 1.12 921 1.24 965 1.37
4250 680 0.77 734 0.87 785 0.98 836 1.09 883 1.21 930 1.34 972 1.47
4500 694 0.86 747 0.97 797 1.08 845 1.19 893 1.32 937 1.45 981 1.58
4800 715 0.99 763 1.09 811 1.21 859 1.33 903 1.46 948 1.59 990 1.73
continued
External Static Pressure (InWg)
Air
Flow
(CFM) 0.8 0.9 1.0 1.2 1.4 1.6 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
3200 980 1.20 1020 1.31 1060 1.44 - - - - - - - -
3500 989 1.30 1029 1.43 1067 1.55 1142 1.81 - - - - - -
3750 998 1.39 1036 1.52 1075 1.66 1147 1.92 1216 2.20 - - - -
4000 1006 1.49 1046 1.63 1083 1.77 1154 2.04 1222 2.33 1286 2.62 - -
4250 1013 1.60 1054 1.74 1091 1.87 1162 2.16 1229 2.46 1293 2.76 - -
4500 1021 1.72 1060 1.85 1099 2.00 1171 2.29 1236 2.59 1299 2.91 1418 3.56
4800 1030 1.86 1070 2.01 1108 2.15 1180 2.46 1247 2.77 1310 3.10 1425 3.77
Field Installed High Static Pressure Drive(d)
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive. Field installed

14 PKG-PRC012Q-EN
Fan Performance Data

Table 7. Evaporator fan performance - SCWJ120 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
4000 650 0.69 700 0.79 760 0.89 800 1.00 850 1.11 900 1.23 940 1.35 980 1.48
4300 680 0.83 730 0.93 780 1.04 830 1.15 870 1.27 920 1.39 960 1.52 1000 1.65
4650 720 1.01 770 1.12 820 1.23 860 1.35 900 1.48 940 1.60 990 1.73 1020 1.87
5000 760 1.22 810 1.33 850 1.45 890 1.58 930 1.71 970 1.84 1010 1.98 1050 2.12
5350 810 1.46 850 1.58 890 1.71 930 1.84 970 1.98 1010 2.11 1040 2.26 1080 2.40
5700 850 1.73 890 1.86 930 2.00 960 2.13 1000 2.28 1040 2.42 1070 2.57 1110 2.72
6000 890 1.99 920 2.13 960 2.27 1000 2.41 1030 2.56 1070 2.71 1100 2.86 1140 3.02

continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4000 1020 1.61 1060 1.75 1150 2.10 1240 2.49 1320 2.90 1370 3.22 1440 3.71 — —
4300 1040 1.78 1080 1.92 1170 2.29 1250 2.68 1330 3.09 1380 3.37 1450 3.85 — —
4650 1060 2.01 1100 2.15 1190 2.52 1270 2.93 1350 3.35 1400 3.59 1460 4.05 — —
5000 1090 2.26 1120 2.41 1210 2.80 1290 3.20 1360 3.63 1410 3.85 — — — —
5350 1110 2.55 1150 2.71 1230 3.11 1310 3.53 1380 3.97 1430 4.16 — — — —
5700 1140 2.88 1180 3.04 1260 3.45 1330 3.88 1390 4.10 1450 4.53 — — — —
6000 1170 3.18 1200 3.35 1280 3.77 1340 4.03 1400 4.44 — — — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

PKG-PRC012Q-EN 15
Fan Performance Data

Table 8. Evaporator fan performance - SCWJ150 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
4800 670 0.94 720 1.05 770 1.16 810 1.27 860 1.39 900 1.52 940 1.64 980 1.78
5200 710 1.16 760 1.27 800 1.39 850 1.51 890 1.64 930 1.77 970 1.90 1000 2.04
5600 750 1.41 800 1.53 840 1.66 880 1.78 920 1.91 960 2.05 990 2.19 1030 2.34
6000 800 1.70 840 1.83 870 1.96 910 2.10 950 2.23 990 2.38 1020 2.52 1060 2.67
6400 840 2.03 880 2.16 910 2.30 950 2.44 980 2.58 1020 2.74 1050 2.89 1090 3.05
6800 880 2.40 920 2.54 950 2.68 990 2.83 1020 2.99 — — 1090 3.30 1120 3.46
7200 930 2.81 960 2.96 — — — — — — 1090 3.58 1120 3.75 1150 3.92

Field Installed High Static Pressure Drive(d)

continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4800 1020 1.91 1060 2.05 1150 2.42 1230 2.81 1310 3.22 1390 3.65 1440 3.89 — —
5200 1040 2.18 1080 2.33 1170 2.71 1250 3.11 1330 3.53 1400 3.74 1450 4.18 — —
5600 1070 2.48 1100 2.61 1190 3.02 1260 3.43 1340 3.87 1410 4.08 1460 4.52 — —
6000 1090 2.83 1130 2.98 1210 3.39 1290 3.81 1350 4.08 1420 4.49 — — — —
6400 1120 3.20 1150 3.36 1230 3.78 1300 4.13 1360 4.52 1430 4.94 — — — —
6800 1150 3.62 1180 3.80 1240 4.23 1310 4.62 — — — — — — — —
7200 1160 4.21 1190 4.37 1260 4.76 — — — — — — — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

16 PKG-PRC012Q-EN
Fan Performance Data

Table 9. Evaporator fan performance - SCRJ030 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
960 — — — — 960 0.18 1020 0.21 1070 0.23 1130 0.26 1180 0.28
1040 — — 940 0.19 1000 0.21 1050 0.24 1100 0.26 1160 0.29 1210 0.32
1120 920 0.20 980 0.23 1040 0.25 1090 0.28 1140 0.30 1190 0.33 1240 0.36
1200 970 0.24 1020 0.26 1080 0.29 1130 0.32 1180 0.35 1230 0.38 1270 0.40
1280 1020 0.28 1070 0.31 1120 0.34 1170 0.37 1220 0.40 1270 0.43 1310 0.46
1360 1070 0.33 1120 0.36 1170 0.39 1210 0.42 1260 0.45 1300 0.48 1350 0.51
1440 1120 0.38 1160 0.41 1210 0.44 1260 0.48 1300 0.51 1340 0.54 1380 0.57

continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
960 1230 0.31 1280 0.34 1330 0.37 1430 0.43 1520 0.49 1610 0.56
1040 1260 0.35 1310 0.38 1360 0.41 1450 0.47 1530 0.53 1620 0.60
1120 1290 0.39 1340 0.42 1380 0.45 1470 0.51 1550 0.58 1640 0.65
1200 1320 0.44 1370 0.47 1410 0.50 1490 0.56 1580 0.63 1660 0.70
1280 1360 0.49 1400 0.52 1440 0.55 1520 0.62 1600 0.69 1680 0.77
1360 1390 0.55 1430 0.58 1470 0.61 1550 0.68 1630 0.76 1700 0.83
1440 1430 0.61 1470 0.64 1510 0.68 1580 0.75 1660 0.82 1730 0.90
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

PKG-PRC012Q-EN 17
Fan Performance Data

Table 10. Evaporator fan performance - SCRJ050 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b)
1600 740 0.31 780 0.35 830 0.38 880 0.41 920 0.45 960 0.49 1000 0.52
1750 780 0.40 830 0.43 870 0.47 920 0.50 960 0.54 1000 0.58 1040 0.62
1850 820 0.46 860 0.50 900 0.53 940 0.57 980 0.61 1020 0.65 1060 0.69
2000 870 0.56 910 0.60 950 0.64 990 0.68 1020 0.73 1060 0.77 1100 0.81
2150 920 0.69 960 0.73 990 0.77 1030 0.81 1070 0.86 1100 0.90 1130 0.95
2250 960 0.78 990 0.82 1030 0.87 1060 0.91 1100 0.96 1130 1.00 1160 1.05
2400 1010 0.93 1040 0.98 1080 1.02 1110 1.07 1140 1.12 1170 1.17 1200 1.21
Standard Drive(c) Field Installed High Static Pressure Drive(d)

continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
1600 1040 0.56 1080 0.60 1120 0.64 1200 0.72 1270 0.80 1340 0.89
1750 1070 0.66 1110 0.70 1150 0.74 1220 0.83 1290 0.92 1360 1.01
1850 1100 0.73 1130 0.78 1170 0.82 1240 0.91 1310 1.00 1370 1.09
2000 1130 0.86 1170 0.90 1200 0.95 1270 1.04 1330 1.13 1390 1.23
2150 1170 0.99 1200 1.04 1230 1.09 1300 1.19 1360 1.29 — —
2250 1200 1.10 1230 1.15 1260 1.20 1320 1.30 1380 1.40 — —
2400 1240 1.26 1270 1.32 1300 1.37 1350 1.47 — — — —
Field Installed High Static Pressure Drive(d)
(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

18 PKG-PRC012Q-EN
Fan Performance Data

Table 11. Evaporator fan performance - SCRJ075 fan performance(a),(b)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(c)
2400 — — — — 1050 0.55 1110 0.60 1160 0.66 1220 0.72 1270 0.78
2600 — — 1050 0.60 1100 0.65 1160 0.71 1210 0.77 1260 0.84 1310 0.90
2800 1040 0.65 1100 0.71 1150 0.77 1200 0.84 1250 0.90 1300 0.97 1350 1.04
3000 1100 0.79 1160 0.85 1210 0.92 1260 0.98 1300 1.05 1350 1.12 1390 1.19
3200 1140 0.94 1210 1.00 1260 1.07 1310 1.14 1350 1.21 1400 1.29 1440 1.36
3400 1230 1.11 1270 1.18 1320 1.25 1360 1.33 1410 1.40 1450 1.48 1490 1.55
3600 1290 1.29 1330 1.37 1370 1.45 1420 1.52 1460 1.60 1500 1.68 1540 1.76

Standard Drive(d)

continued
External Static Pressure (In Wg)
Air 0.8 0.9 1.0 1.2 1.4 1.6
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c)
2400 1320 0.84 1370 0.91 1410 0.97 1510 1.11 1590 1.25 1680 1.40
2600 1360 0.97 1400 1.03 1450 1.10 1540 1.25 1620 1.39 1700 1.55
2800 1390 1.10 1440 1.17 1480 1.25 1570 1.39 1650 1.55 1730 1.71
3000 1440 1.26 1480 1.33 1520 1.41 1610 1.56 1680 1.72 1760 1.89
3200 1480 1.44 1520 1.51 1560 1.59 1640 1.75 1720 1.92 1790 2.09(e)
3400 1530 1.63 1570 1.71 1610 1.79 1690 1.96 1760 2.13 — —
3600 1580 1.85 1620 1.93 1650 2.01 1730 2.19 — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE
52.1-1992.
(b) SCWH/SCRJ 7.5T standard and oversize motors are both 2.0 hp motors. Oversize motor is not required for 7.5T unit unless electric
heat is installed in the unit.
(c) Standard Motor - low static pressure drive, field installed
(d) Standard Motor 2.0HP Weg - Frame: Nema A56 ODP
(e) Oversized Motor - high static pressure drive, field installed

PKG-PRC012Q-EN 19
Fan Performance Data

Table 12. Evaporator fan performance - SCRJ100 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
3200 — — 630 0.49 690 0.58 750 0.67 — — 850 0.89 900 1.00 940 1.12
3500 600 0.50 660 0.58 710 0.68 770 0.79 820 0.89 860 1.00 910 1.12 950 1.24
3750 620 0.58 680 0.67 730 0.78 780 0.88 830 0.99 880 1.10 920 1.22 970 1.35
4000 650 0.68 700 0.78 750 0.89 — — 850 1.10 890 1.22 940 1.35 980 1.48
4250 680 0.80 730 0.90 780 1.01 820 1.12 870 1.23 910 1.36 960 1.49 1000 1.62
4500 700 0.92 750 1.02 — — 840 1.25 890 1.38 930 1.50 970 1.63 1010 1.76
4800 740 1.08 780 1.19 830 1.32 870 1.44 910 1.57 960 1.69 1000 1.84 1030 1.97

continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
3200 980 1.24 1020 1.38 1100 1.67 1190 2.07 1270 2.51 1350 3.01 1420 3.54 — —
3500 1000 1.37 1040 1.50 1130 1.85 1200 2.15 1280 2.58 1360 3.05 1430 3.57 — —
3750 1010 1.48 1050 1.61 1140 1.97 1230 2.36 1290 2.67 1370 3.13 1440 3.62 — ---
4000 1020 1.61 1060 1.74 1150 2.11 1240 2.50 1320 2.91 1380 3.22 1450 3.71 — —
4250 1040 1.75 1080 1.90 1170 2.26 1250 2.65 1330 3.07 1390 3.52 1460 3.82 — —
4500 1050 1.91 1090 2.05 1180 2.43 1260 2.83 1340 3.24 1400 3.59 — — — —
4800 1070 2.11 1110 2.26 1200 2.65 1280 3.06 1360 3.49 1410 3.69 — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

20 PKG-PRC012Q-EN
Fan Performance Data

Table 13. Evaporator fan performance - SCRJ120 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
4000 650 0.69 700 0.79 760 0.89 800 1.00 850 1.11 900 1.23 940 1.35 980 1.48
4300 680 0.83 730 0.93 780 1.04 830 1.15 870 1.27 920 1.39 960 1.52 1000 1.65
4650 720 1.01 770 1.12 820 1.23 860 1.35 900 1.48 940 1.60 990 1.73 1020 1.87
5000 760 1.22 810 1.33 850 1.45 890 1.58 930 1.71 970 1.84 1010 1.98 1050 2.12
5350 810 1.46 850 1.58 890 1.71 930 1.84 970 1.98 1010 2.11 1040 2.26 1080 2.40
5700 850 1.73 890 1.86 930 2.00 960 2.13 1000 2.28 1040 2.42 1070 2.57 1110 2.72
6000 890 1.99 920 2.13 960 2.27 1000 2.41 1030 2.56 1070 2.71 1100 2.86 1140 3.02

continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4000 1020 1.61 1060 1.75 1150 2.10 1240 2.49 1320 2.90 1370 3.22 1440 3.71 — —
4300 1040 1.78 1080 1.92 1170 2.29 1250 2.68 1330 3.09 1380 3.37 1450 3.85 — —
4650 1060 2.01 1100 2.15 1190 2.52 1270 2.93 1350 3.35 1400 3.59 1460 4.05 — —
5000 1090 2.26 1120 2.41 1210 2.80 1290 3.20 1360 3.63 1410 3.85 — — — —
5350 1110 2.55 1150 2.71 1230 3.11 1310 3.53 1380 3.97 1430 4.16 — — — —
5700 1140 2.88 1180 3.04 1260 3.45 1330 3.88 1390 4.10 1450 4.53 — — — —
6000 1170 3.18 1200 3.35 1280 3.77 1340 4.03 1400 4.44 — — — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

PKG-PRC012Q-EN 21
Fan Performance Data

Table 14. Evaporator fan performance - SCRJ150 fan performance(a)

External Static Pressure (In Wg)


Air 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Installed Low Static Pressure Drive(b) Standard Drive(c)
4800 670 0.94 720 1.05 770 1.16 810 1.27 860 1.39 900 1.52 940 1.64 980 1.78
5200 710 1.16 760 1.27 800 1.39 850 1.51 890 1.64 930 1.77 970 1.90 1000 2.04
5600 750 1.41 800 1.53 840 1.66 880 1.78 920 1.91 960 2.05 990 2.19 1030 2.34
6000 800 1.70 840 1.83 870 1.96 910 2.10 950 2.23 990 2.38 1020 2.52 1060 2.67
6400 840 2.03 880 2.16 910 2.30 950 2.44 980 2.58 1020 2.74 1050 2.89 1090 3.05
6800 880 2.40 920 2.54 950 2.68 990 2.83 1020 2.99 — — 1090 3.30 1120 3.46
7200 930 2.81 960 2.96 — — — — — — 1090 3.58 1120 3.75 1150 3.92

Field Installed High Static Pressure Drive(d)

continued
External Static Pressure (In Wg)
Air 0.9 1.0 1.2 1.4 1.6 2 2.25 2.5
Flow
(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Drive(c) Field Installed High Static Pressure Drive(d)
4800 1020 1.91 1060 2.05 1150 2.42 1230 2.81 1310 3.22 1390 3.65 1440 3.89 — —
5200 1040 2.18 1080 2.33 1170 2.71 1250 3.11 1330 3.53 1400 3.74 1450 4.18 — —
5600 1070 2.48 1100 2.61 1190 3.02 1260 3.43 1340 3.87 1410 4.08 1460 4.52 — —
6000 1090 2.83 1130 2.98 1210 3.39 1290 3.81 1350 4.08 1420 4.49 — — — —
6400 1120 3.20 1150 3.36 1230 3.78 1300 4.13 1360 4.52 1430 4.94 — — — —
6800 1150 3.62 1180 3.80 1240 4.23 1310 4.62 — — — — — — — —
7200 1160 4.21 1190 4.37 1260 4.76 — — — — — — — — — —

(a) External static pressure includes clean construction throwaway one-inch fiberglass filter, 75% average efficiency filter @ ASHRAE 52.1-1992.
(b) Standard Motor - low static pressure drive, field installed
(c) Standard Motor - standard drive
(d) Oversized Motor - high static pressure drive, field installed

22 PKG-PRC012Q-EN
Pressure Drop Performance Data

Table 15. Waterside pressure drop (ft wc)

SCWJ tons
Waterflow
(gpm) 3 5 7.5 10 12 15
5 4.6
6 6.1
7 7.8
8 9.5 5.3
9 11.4 5.3
10 13.5 7.5 4.7
12 18.9 9.9 6.5
14 23.1 12.7 8.6 6.8
16 28.8 16.0 10.9 7.9
18 35.3 19.2 13.4 9.0
20 43.1 22.5 16.2 10.2 10.2
24 28.1 22.3 12.7 12.7 3.6
28 35.9 29.3 15.3 15.3 5.2
32 44.9 37.0 18.0 18.0 7.0
36 55.5 45.6 20.9 20.9 9.0
40 54.8 23.9 23.9 11.4
45 27.9 27.9 14.7
50 32.1 32.1 18.4
55 36.5 36.5 22.5
60 41.1 41.1 27.0
Note: Water pressure drop values include factory piping and condenser.

Table 16. Plenum airside pressure drop


Air Flow, Air Pressure Drop, Air Flow, Air Pressure Drop,
Unit Size CFM in.H20 Unit Size CFM in.H20
960 0.09 200 0.15
1080 0.11 3600 0.17
3 ton 10 ton
1200 0.12 4000 0.20
(SCRJ/SCWJ) (SCRJ/SCWJ)
1320 0.14 4400 0.23
1440 0.15 4800 0.25
600 0.14 3840 0.19
1800 0.16 4320 0.22
5 ton 12 ton
2000 0.19 4800 0.25
(SCRJ/SCWJ) (SCRJ/SCWJ)
2200 0.21 5280 0.29
2400 0.24 5760 0.32
2400 0.20 / 0.10 4800 0.19
2700 0.23 / 0.14 5400 0.22
7.5 ton 15 ton
3000 0.27 / 0.16 6000 0.26
(SCRJ/SCWJ) (SCRJ/SCWJ)
3300 0.31 / 0.19 6600 0.29
3600 0.35 / 0.21 7200 0.33
Note: Air pressure drop includes the discharge grill.

PKG-PRC012Q-EN 23
Performance Data
Correction Factor & Heat of Rejection

Table 17. Altitude correction factors


Altitude 2000 4000 6000 8000 10,000
Cooling Capacity Multiplier 0.98 0.95 0.92 0.89 0.86

Figure 2. Gross heat of rejection curve for model CTA

CTA Gross Heat of Rejection

350

300
Heat of Rejection (MBh)

250
CTA180
200
CTA120
150
CTA090
100

50

0
0 10 20 30 40
InItial Temperature Difference (ITD)

24 PKG-PRC012Q-EN
Water-Cooled Performance Data
Table 18. SCWJ030 gross cooling capacity, 10°F T

62 67 70
Entering Air
Water Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F CFM EDB °F MBh MBh Gpm MBh MBh gpm MBh MBh Gpm
70 36.6 22.7 8.4 40.1 17.5 9.1 42.2 14.5 9.5
75 36.6 27.6 8.4 40.0 22.5 9.0 42.2 19.3 9.5
960
80 36.6 32.5 8.4 40.0 27.4 9.0 42.1 24.3 9.5
85 37.0 36.8 8.4 40.0 32.3 9.0 42.1 29.2 9.5
70 38.0 24.5 8.7 41.5 18.3 9.3 43.6 14.6 9.8
75 38.0 30.5 8.6 41.4 24.3 9.3 43.6 20.5 9.7
65 1200
80 38.1 36.3 8.7 41.4 30.3 9.3 43.5 26.5 9.7
85 39.6 39.5 9.0 41.4 36.3 9.3 43.5 32.6 9.7
70 39.0 26.3 8.8 42.4 19.0 9.5 44.6 14.6 9.9
75 38.9 33.3 8.8 42.4 26.0 9.5 44.6 21.6 9.9
1440
80 39.5 39.3 8.9 42.4 33.0 9.5 44.5 28.6 9.9
85 41.7 41.6 9.4 42.5 39.8 9.5 44.5 35.7 9.9
70 34.9 21.9 8.3 38.2 16.7 8.9 40.2 13.7 9.3
75 34.9 26.8 8.3 38.2 21.7 8.9 40.2 18.5 9.3
960
80 34.9 31.7 8.3 38.1 26.6 8.9 40.1 23.5 9.3
85 35.6 35.5 8.4 38.1 31.6 8.9 40.1 28.5 9.3
70 36.2 23.7 8.5 39.4 17.5 9.2 41.5 13.7 9.6
75 36.2 29.7 8.5 39.4 23.5 9.2 41.4 19.7 9.6
75 1200
80 36.4 35.4 8.6 39.4 29.5 9.2 41.4 25.7 9.6
85 38.1 38.0 8.9 39.4 35.4 9.2 41.4 31.8 9.6
70 37.0 25.5 8.7 40.3 18.2 9.4 42.4 13.8 9.8
75 37.0 32.4 8.7 40.3 25.2 9.4 42.3 20.8 9.8
1440
80 37.8 37.7 8.9 40.3 32.2 9.3 42.3 27.8 9.7
85 40.0 39.9 9.3 40.5 38.8 9.4 42.3 34.8 9.7
70 33.0 21.0 8.2 36.1 15.9 8.8 38.0 12.8 9.2
75 33.0 25.9 8.2 36.1 20.8 8.8 38.0 17.7 9.2
960
80 33.1 30.8 8.2 36.0 25.8 8.8 38.0 22.7 9.2
85 34.0 33.9 8.4 36.0 30.7 8.8 37.9 27.6 9.2
70 34.1 22.8 8.4 37.2 16.6 9.0 39.1 12.9 9.4
75 34.1 28.8 8.4 37.2 22.6 9.0 39.1 18.8 9.4
85 1200
80 34.5 34.2 8.5 37.2 28.6 9.0 39.1 24.9 9.4
85 36.3 36.2 8.9 37.3 34.5 9.0 39.1 30.9 9.4
70 34.9 24.6 8.6 38.0 17.3 9.2 39.9 12.9 9.6
75 34.9 31.5 8.6 38.0 24.3 9.2 39.9 19.9 9.6
1440
80 36.0 35.9 8.8 38.0 31.3 9.2 39.9 26.9 9.5
85 38.1 38.0 9.2 38.3 37.7 9.2 39.9 33.9 9.5
70 30.9 20.1 8.1 33.8 14.9 8.7 35.6 11.9 9.0
75 30.9 25.0 8.1 33.8 19.9 8.7 35.6 16.8 9.0
960
80 31.0 29.7 8.1 33.8 24.8 8.7 35.5 21.7 9.0
85 32.3 32.2 8.4 33.8 29.7 8.7 35.5 26.7 9.0
70 31.9 21.9 8.3 34.8 15.7 8.9 36.6 11.9 9.2
75 31.9 27.9 8.3 34.8 21.7 8.9 36.6 17.9 9.2
95 1200
80 32.5 32.4 8.4 34.7 27.7 8.8 36.5 23.9 9.2
85 34.4 34.3 8.8 34.9 33.4 8.9 36.5 30.0 9.2
70 32.6 23.6 8.4 35.5 16.3 9.0 37.3 12.0 9.3
75 32.6 30.4 8.4 35.4 23.4 9.0 37.2 19.0 9.3
1440
80 34.0 33.9 8.7 35.4 30.4 9.0 37.2 26.0 9.3
85 36.0 35.9 9.1 36.0 35.9 9.1 37.2 33.0 9.3
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x
fan motor bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24

PKG-PRC012Q-EN 25
Water-Cooled Performance Data

Table 19. SCWJ050 gross cooling capacity, 10°F T

62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F CFM EDB °F MBh MBh Gpm MBh MBh Gpm Mbh Mbh Gpm
70 66.2 40.7 15.0 72.5 31.7 16.3 76.5 26.2 17.1
75 66.1 49.4 15.0 72.4 40.4 16.3 76.4 34.9 17.0
1800
80 66.1 58.0 15.0 72.4 49.1 16.3 76.4 43.7 17.0
85 66.7 65.9 15.2 72.3 57.8 16.2 76.3 52.4 17.0
70 67.4 42.2 15.3 73.8 32.3 16.5 77.8 26.4 17.3
75 67.4 51.7 15.3 73.8 41.9 16.5 77.8 35.9 17.3
65 2000
80 67.4 61.1 15.3 73.7 51.4 16.5 77.7 45.5 17.3
85 68.7 68.6 15.5 73.7 60.9 16.5 77.7 55.0 17.3
70 68.5 43.6 15.5 74.9 32.9 16.7 78.9 26.5 17.5
75 68.4 53.9 15.5 74.9 43.3 16.7 78.9 36.8 17.5
2200
80 68.6 64.0 15.5 74.8 53.7 16.7 78.8 47.2 17.5
85 70.8 70.7 15.5 74.8 64.0 16.7 78.8 57.5 17.5
70 63.9 39.6 14.9 70.0 30.6 16.1 73.8 25.2 16.8
75 63.9 48.3 14.9 69.9 39.4 16.0 73.7 33.8 16.8
1800
80 63.9 56.9 14.9 69.9 48.1 16.0 73.7 42.6 16.8
85 64.7 64.5 15.0 69.8 56.3 16.0 73.6 51.2 16.8
70 65.1 41.1 15.1 71.2 31.3 16.3 75.0 25.3 17.0
75 65.0 50.6 15.1 71.1 40.8 16.3 75.0 34.8 17.0
75 2000
80 65.1 60.0 15.1 71.1 50.4 16.3 74.9 44.4 17.0
85 66.8 66.7 15.4 71.1 59.9 16.3 74.9 53.9 17.0
70 66.1 42.5 15.3 72.2 31.8 16.5 76.1 25.4 17.2
75 66.0 52.9 15.3 72.2 42.2 16.5 76.0 35.7 17.2
2200
80 66.3 62.8 15.3 72.1 52.6 16.5 76.0 46.1 17.2
85 68.8 68.7 15.8 72.1 62.8 16.5 75.9 56.4 17.2
70 61.3 38.4 14.7 67.1 29.4 15.8 70.8 24.0 16.5
75 61.3 47.1 14.7 67.1 38.2 15.8 70.7 32.7 16.5
1800
80 61.3 55.7 14.7 67.0 46.9 15.8 70.7 41.4 16.5
85 62.5 62.4 14.9 67.0 55.6 15.8 70.6 50.1 16.5
70 62.4 39.9 14.9 68.1 30.0 16.2 71.9 24.1 16.7
75 62.4 49.4 14.9 68.1 39.6 16.2 71.9 33.6 16.7
85 2000
80 62.5 58.7 14.9 68.1 49.2 16.2 71.8 43.2 16.7
85 64.6 64.5 15.3 68.0 58.6 16.2 71.8 52.7 16.7
70 63.3 41.3 15.1 69.2 30.6 16.2 72.9 24.1 16.9
75 63.3 51.6 15.1 69.1 41.0 16.2 72.8 34.5 16.9
2200
80 63.6 61.4 15.1 69.1 51.3 16.2 72.8 44.9 16.9
85 66.5 66.4 15.7 69.1 61.6 16.2 72.7 55.2 16.9
70 58.4 37.1 14.5 63.9 28.1 15.5 67.4 22.6 16.2
75 58.4 45.8 14.5 63.9 36.8 15.5 67.4 31.4 16.2
1800
80 58.5 54.3 14.5 63.9 45.6 15.5 67.3 40.1 16.2
85 60.2 60.1 14.8 63.8 54.2 15.5 67.3 48.8 16.2
70 59.4 38.6 14.7 65.0 28.7 15.7 68.4 22.7 16.4
75 59.4 48.1 14.6 64.9 38.3 15.7 68.4 32.3 16.4
95 2000
80 59.6 57.2 14.7 64.9 47.8 15.7 68.3 41.9 16.4
85 62.1 60.0 15.2 64.9 57.3 15.7 68.3 51.4 16.4
70 60.2 40.0 14.8 65.8 29.3 15.9 69.3 22.8 16.6
75 60.2 50.3 14.8 65.7 39.7 15.9 69.2 33.1 16.6
2200
80 60.7 59.7 14.9 65.7 50.0 15.9 69.2 43.5 16.6
85 63.9 63.8 15.5 65.8 60.1 15.9 69.1 53.9 16.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp
[Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.

26 PKG-PRC012Q-EN
Water-Cooled Performance Data

Table 20. SCWJ075 gross cooling capacity, 10°F T

62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °F Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 92.8 55.3 21.2 100.1 39.7 22.7 104.6 29.9 23.6
75 92.3 68.6 21.1 99.5 53.3 22.6 103.7 42.8 23.5
2400
80 91.0 81.3 20.9 97.8 66.1 22.3 102.6 56.5 23.2
85 91.2 91.2 20.9 96.4 79.0 22.0 100.2 69.5 22.7
70 96.7 60.2 22.0 103.7 40.9 23.4 108.3 28.9 24.4
75 95.2 76.6 21.7 102.2 57.6 23.2 106.7 45.7 24.1
65 3000
80 94.2 92.5 21.5 100.7 73.9 22.9 104.8 62.2 23.7
85 96.6 96.6 22.1 98.8 90.2 22.5 103.1 78.7 23.4
70 98.8 65.1 22.4 106.0 42.5 23.9 111.0 28.2 24.9
75 97.4 84.5 22.2 104.4 62.0 23.6 109.0 48.3 24.5
3600
80 97.6 97.6 22.2 102.7 81.8 23.3 106.9 68.1 24.2
85 100.7 100.7 22.9 101.3 100.3 23.0 104.7 87.8 23.7
70 90.4 54.2 21.1 97.4 38.5 22.5 101.8 28.7 23.4
75 90.1 67.5 21.0 97.1 52.2 22.5 101.4 43.0 23.4
2400
80 88.7 80.3 20.8 95.4 65.1 22.1 99.7 56.2 23.0
85 89.6 89.6 21.0 93.9 78.1 21.9 97.9 68.8 22.7
70 94.1 59.2 21.8 101.1 39.8 23.3 105.3 27.8 24.1
75 93.2 75.6 21.7 99.9 56.8 23.1 103.9 45.1 23.9
75 3000
80 91.9 91.0 21.4 98.0 72.9 22.7 102.1 61.1 23.5
85 94.5 94.5 22.0 96.2 89.4 22.3 100.3 77.9 23.2
70 96.4 64.1 22.3 103.6 41.1 23.8 108.4 27.3 24.8
75 95.0 83.6 22.0 101.8 61.2 23.5 106.4 47.4 24.4
3600
80 95.4 95.4 22.1 101.8 87.0 23.5 104.1 67.3 23.9
85 98.1 98.1 22.7 98.5 98.0 22.8 101.8 87.0 23.5
70 87.0 52.6 20.8 93.9 37.1 22.2 98.1 27.4 23.1
75 87.2 66.3 20.8 93.7 50.8 22.2 97.4 41.8 22.9
2400
80 85.6 79.0 20.5 92.1 63.8 21.8 95.9 54.1 22.6
85 87.1 87.1 20.8 90.4 76.8 21.5 94.3 67.4 22.3
70 90.5 57.8 21.5 97.1 38.5 22.9 101.8 26.5 23.8
75 89.8 74.2 21.4 96.5 55.3 22.7 100.7 43.9 23.6
85 3000
80 88.8 88.6 21.2 94.6 71.7 22.4 98.5 59.9 23.2
85 91.5 91.5 21.8 91.4 87.6 21.7 96.5 76.6 22.8
70 92.6 62.6 21.9 100.0 40.3 23.5 104.4 25.9 24.3
75 91.5 82.2 21.7 98.3 59.8 23.1 102.7 45.9 24.0
3600
80 92.7 92.7 22.0 96.6 79.7 22.8 100.3 66.2 23.6
85 95.2 95.2 22.5 95.0 94.9 22.5 97.7 85.9 23.1
70 83.1 51.0 20.4 89.7 35.5 21.8 93.8 26.0 22.6
75 82.9 64.4 20.4 89.2 48.9 21.7 93.4 39.6 22.5
2400
80 81.6 77.4 20.1 87.5 62.1 21.4 91.3 52.7 22.1
85 83.5 83.5 20.5 85.8 75.2 21.0 89.3 65.7 21.7
70 86.4 56.1 21.1 93.0 37.1 22.4 97.1 24.9 23.3
75 85.6 72.5 20.9 92.0 53.9 22.3 96.5 42.4 23.2
95 3000
80 85.3 85.3 20.9 89.8 70.1 21.8 93.6 58.5 22.6
85 87.7 87.7 21.4 87.9 86.2 21.4 91.2 74.9 22.1
70 88.4 61.0 21.5 95.4 38.7 22.9 99.3 24.3 23.7
75 87.1 80.5 21.3 93.5 58.5 22.6 97.6 44.7 23.4
3600
80 88.3 88.3 21.5 91.2 78.0 22.1 95.1 64.5 22.9
85 90.7 90.7 22.1 90.8 90.8 22.1 92.2 84.0 22.4
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.

PKG-PRC012Q-EN 27
Water-Cooled Performance Data

Table 21. SCWJ100 gross cooling capacity, 10°F T

62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °f Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 124.0 72.2 30.9 133.6 52.6 32.9 139.5 39.4 34.1
75 125.1 89.6 31.1 134.7 70.0 33.1 140.8 57.4 34.2
3200
80 126.5 107.3 31.4 135.6 87.2 33.3 141.7 75.0 34.6
85 128.3 125.4 31.8 137.0 105.0 33.6 142.8 92.7 34.8
70 129.8 78.7 32.1 139.6 54.1 34.1 145.7 38.5 35.4
75 131.2 100.6 32.3 140.7 76.0 34.3 147.0 60.7 35.6
65 4000
80 133.2 123.0 32.8 142.1 97.9 34.6 148.2 82.7 35.9
85 135.8 135.8 33.3 143.5 119.8 34.9 149.7 104.8 36.2
70 134.1 85.2 33.0 144.0 56.3 35.0 150.2 36.6 36.3
75 135.7 111.4 33.3 145.3 82.7 35.3 151.5 64.1 36.6
4800
80 138.4 136.7 33.8 146.9 108.5 35.6 153.0 89.6 36.9
85 143.4 143.4 34.9 149.2 135.3 36.1 154.7 116.9 37.2
70 119.6 70.1 30.7 128.9 50.3 32.6 134.5 37.4 33.8
75 120.7 87.5 30.9 129.7 67.7 32.8 135.6 55.5 34.0
3200
80 122.0 105.2 31.2 130.9 85.2 33.0 136.6 73.0 34.2
85 124.0 122.9 31.6 132.1 102.9 33.3 137.9 90.7 34.5
70 125.0 76.9 31.8 134.4 52.6 33.8 140.2 36.0 35.0
75 126.5 98.5 32.1 135.6 73.4 34.0 141.5 58.8 35.2
75 4000
80 128.5 120.9 32.5 136.9 95.8 34.3 142.8 80.7 35.5
85 131.7 131.7 33.2 138.6 118.0 34.6 144.2 102.7 35.8
70 129.0 83.0 32.6 138.4 54.1 34.6 144.4 34.8 35.8
75 130.6 109.2 33.0 139.8 78.9 34.9 145.9 62.3 36.1
4800
80 133.1 132.5 33.5 141.3 106.3 35.2 147.2 89.1 36.4
85 138.9 138.9 34.7 143.8 133.5 35.7 148.7 114.7 36.7
70 114.9 68.0 30.5 123.8 48.2 32.3 129.1 35.3 33.5
75 115.9 85.3 30.7 124.6 65.7 32.5 130.3 53.4 33.7
3200
80 117.3 103.0 31.0 125.8 83.1 32.7 131.3 70.9 33.9
85 119.2 119.1 31.4 126.9 100.7 33.0 132.4 88.5 34.1
70 119.9 74.4 31.5 128.9 50.2 33.4 134.4 34.4 34.6
75 121.2 95.9 31.8 130.0 71.6 33.6 135.8 56.7 34.8
85 4000
80 123.6 118.8 32.2 131.4 93.6 33.9 137.0 79.2 35.1
85 127.3 127.3 33.0 133.1 116.0 34.2 138.4 100.4 35.3
70 123.6 80.8 32.3 132.6 51.8 34.2 138.0 32.8 35.3
75 125.3 107.1 32.6 134.0 78.2 34.4 139.7 59.9 35.6
4800
80 127.4 127.4 33.1 135.5 104.2 34.7 141.0 86.3 35.9
85 134.1 134.1 34.4 138.1 131.5 35.3 142.6 112.8 36.2
70 109.7 65.5 30.3 118.2 46.1 32.0 123.3 32.7 33.1
75 110.8 82.9 30.5 119.2 63.3 32.2 124.6 51.1 33.4
3200
80 112.2 100.8 30.8 120.2 80.8 32.4 125.6 69.1 33.6
85 114.2 114.2 31.2 121.4 98.4 32.7 126.7 86.5 33.8
70 114.5 72.0 31.2 123.0 47.6 33.0 128.0 31.3 34.1
75 115.7 93.9 31.5 124.2 69.5 33.3 129.6 54.5 34.4
95 4000
80 117.9 116.0 32.0 125.5 91.4 33.5 130.9 76.5 34.6
85 122.5 122.5 32.9 127.3 114.0 33.9 132.0 98.3 34.9
70 117.9 78.5 31.9 126.1 49.3 33.7 131.3 30.5 34.8
75 119.6 104.9 32.3 127.8 75.8 34.0 133.2 58.6 35.1
4800
80 121.8 121.8 32.8 129.3 102.0 34.3 134.5 84.2 35.4
85 128.9 128.9 34.2 131.9 128.7 34.8 136.2 110.8 35.7
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.

28 PKG-PRC012Q-EN
Water-Cooled Performance Data

Table 22. SCWJ120 gross cooling capacity, 10°F T

62 67 70
Entering
Water Air Flow TC SC Flow TC SC Flow TC SC Flow
Temp. °f Cfm EDB °F MBh MBh Gpm MBh MBh Gpm MBh MBh Gpm
70 127.8 71.5 34.9 137.1 47.5 37.1 141.6 30.8 38.2
75 129.6 91.6 35.3 138.8 67.7 37.5 144.8 52.8 38.9
3840
80 131.8 111.8 35.9 140.5 87.8 37.9 146.5 73.1 39.3
85 135.2 131.8 36.7 142.4 107.9 38.4 148.3 93.2 39.7
70 134.8 79.1 36.6 144.4 49.9 38.8 149.4 30.3 40.0
75 136.9 103.9 37.0 146.3 74.8 39.2 152.5 56.7 40.7
65 4800
80 140.2 129.1 37.8 148.3 99.8 39.7 154.4 81.6 41.1
85 142.1 142.0 38.3 151.0 125.2 40.4 156.4 106.8 41.6
70 140.1 86.6 37.8 149.9 52.4 40.1 155.3 30.0 41.3
75 142.6 116.0 38.4 151.9 81.9 40.6 158.3 61.0 42.0
5760
80 146.7 142.9 39.4 154.2 111.7 41.1 160.3 90.6 42.5
85 147.5 147.5 39.6 157.9 141.8 42.0 162.8 120.6 43.1
70 122.9 69.5 34.5 131.9 45.6 36.6 136.2 28.9 37.7
75 124.7 89.5 34.9 133.6 65.8 37.0 139.5 51.0 38.4
3840
80 127.0 109.9 35.5 135.3 85.8 37.4 141.1 71.2 38.8
85 130.5 128.9 36.3 137.2 106.0 37.9 142.8 91.3 39.2
70 129.5 77.0 36.0 138.8 47.9 38.2 143.6 28.4 39.4
75 131.6 101.8 36.5 140.7 72.9 38.7 146.7 54.9 40.1
75 4800
80 134.8 126.7 37.3 142.7 97.8 39.1 148.5 79.9 40.5
85 136.0 136.0 37.6 145.5 123.4 39.8 150.5 104.8 41.0
70 134.4 84.5 37.2 143.9 50.5 39.4 149.1 28.2 40.7
75 137.0 114.0 37.8 145.9 80.0 39.9 152.1 59.2 41.4
5760
80 141.3 139.4 38.8 148.3 109.8 40.4 154.1 88.9 41.8
85 142.7 142.7 39.2 152.1 139.7 41.3 156.7 119.0 42.4
70 117.6 67.2 34.1 126.3 43.6 36.1 130.4 26.9 37.1
75 119.3 87.2 34.5 128.0 63.7 36.5 133.6 49.0 37.8
3840
80 121.8 107.8 35.0 129.7 83.8 36.9 135.3 69.3 38.2
85 124.9 124.4 35.8 131.7 104.1 37.4 137.0 89.3 38.6
70 123.7 74.8 35.5 132.6 45.8 37.6 137.2 26.4 38.7
75 125.8 99.6 36.0 134.6 70.9 38.0 140.4 53.1 39.4
85 4800
80 129.3 124.1 36.8 136.5 95.8 38.5 142.2 78.1 39.8
85 130.2 130.2 37.0 139.5 121.6 9.2 144.2 103.2 40.3
70 128.3 82.3 36.5 137.4 48.3 38.7 142.4 26.2 39.9
75 131.0 111.7 37.2 139.5 78.0 39.2 145.4 57.3 40.6
5760
80 134.8 134.1 38.1 141.8 107.8 39.7 147.4 87.1 41.0
85 137.5 137.5 38.7 145.7 137.1 40.6 150.0 117.3 41.7
70 111.9 64.9 33.6 120.4 41.4 35.6 124.3 24.8 36.5
75 113.7 85.0 34.0 122.0 61.6 36.0 127.5 47.0 37.2
3840
80 116.3 105.7 34.6 123.7 81.7 36.4 129.1 67.3 37.6
85 118.2 118.1 35.0 125.7 102.2 36.8 130.7 87.4 38.0
70 117.6 72.5 34.9 126.2 43.7 36.9 130.6 24.4 38.0
75 119.8 97.4 35.4 128.1 68.9 37.4 133.6 51.0 38.7
95 4800
80 123.3 120.7 36.3 130.0 93.8 37.8 135.5 76.2 39.1
85 125.1 125.1 36.7 133.1 119.6 38.5 137.5 101.4 39.6
70 121.9 79.9 35.9 130.6 46.2 38.0 135.4 24.3 39.1
75 124.6 109.5 36.5 132.6 76.0 38.4 138.2 55.3 39.8
5760
80 127.2 126.9 37.1 135.0 105.9 39.0 140.3 85.2 40.2
85 131.9 131.9 38.3 138.9 133.8 39.9 143.0 115.6 40.8
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor
bhp [Net MBh capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.

PKG-PRC012Q-EN 29
Water-Cooled Performance Data

Table 23. SCWJ150 gross cooling capacity, 10°F T


Entering Air Flow 62 67 70
Water Temp °F Cfm EDB °F TC MBh SC MBh Flow Gpm TC MBh SC MBh Flow Gpm TC MBh SC MBh Flow Gpm
70 171.9 98.6 45.3 184.4 68.9 48.2 192.5 50.5 50.1
75 173.5 123.2 45.7 186.5 94.5 48.7 194.6 76.4 50.6
4800
80 175.1 147.7 46.0 188.1 119.5 49.0 196.6 101.8 51.0
85 177.8 171.7 46.7 189.6 144.3 49.4 198.1 126.9 51.3
70 180.4 107.9 47.3 193.3 71.7 50.2 201.6 49.4 52.1
75 182.1 138.0 47.6 195.6 103.4 50.8 203.7 81.0 52.6
65 6000
80 184.5 168.0 48.2 197.3 134.1 51.1 206.0 112.7 53.1
85 186.7 186.6 48.7 199.3 164.5 51.6 207.5 143.3 53.5
70 186.2 116.4 48.5 199.8 74.8 51.7 208.3 48.5 53.7
75 188.6 152.5 49.1 201.8 111.6 52.1 210.3 85.8 54.1
7200
80 192.1 186.3 49.9 204.0 148.1 52.7 212.3 122.8 54.6
85 194.9 194.9 50.6 206.8 184.2 53.3 214.8 159.8 55.1
70 165.9 95.8 44.9 178.3 66.4 47.7 186.1 48.1 49.5
75 167.6 120.6 45.3 180.2 92.0 48.1 188.0 73.7 50.0
4800
80 169.3 145.1 45.6 182.0 117.0 48.5 189.8 99.2 50.4
85 172.3 168.8 46.3 183.5 141.8 48.9 191.7 124.5 50.8
70 173.9 105.0 46.7 186.6 69.3 49.6 194.7 47.0 51.5
75 175.7 135.1 47.0 188.1 100.3 50.0 196.8 78.7 51.9
75 6000
80 178.4 165.3 47.7 191.1 131.8 50.5 199.1 110.4 52.5
85 180.0 180.0 48.0 192.7 162.1 51.0 200.7 141.1 52.8
70 179.7 113.8 48.0 192.7 72.3 51.0 201.0 46.1 52.9
75 182.1 149.7 48.5 194.3 108.8 51.4 203.4 84.0 53.5
7200
80 185.9 182.7 49.4 197.0 145.7 52.0 204.7 120.1 53.7
85 189.4 189.4 50.2 199.9 181.5 52.6 207.6 157.6 54.4
70 159.2 92.7 44.3 171.4 63.7 47.2 179.0 45.5 48.9
75 161.1 117.7 44.8 173.1 89.0 47.5 181.0 71.3 49.3
4800
80 162.9 142.2 45.2 175.1 114.4 48.0 182.4 96.4 49.7
85 166.2 165.0 45.9 176.7 139.1 48.3 185.0 122.2 50.2
70 166.5 101.8 46.0 179.2 66.5 48.9 187.1 44.4 50.7
75 168.8 132.4 46.5 180.7 97.4 49.2 189.1 76.1 51.2
85 6000
80 171.6 162.2 47.1 183.0 128.7 49.8 190.6 106.8 51.5
85 173.7 173.7 47.6 185.5 159.6 50.3 193.3 138.7 52.1
70 171.9 110.4 47.2 185.0 69.7 50.2 193.0 43.6 52.1
75 174.8 146.9 47.9 186.5 106.0 50.6 195.1 81.0 52.5
7200
80 178.4 177.2 48.7 189.1 142.8 51.2 196.7 117.5 52.9
85 183.2 183.2 49.8 192.5 178.7 51.9 199.5 154.7 53.5
70 152.2 89.7 43.9 164.1 60.9 46.6 171.4 42.8 48.3
75 153.9 114.5 44.2 165.7 86.2 46.9 173.4 68.5 48.7
4800
80 156.1 139.3 44.7 167.0 111.0 47.2 174.8 93.7 49.0
85 158.1 157.9 45.2 169.3 136.4 47.7 176.3 118.7 49.3
70 158.9 98.5 45.4 171.3 63.8 48.2 178.9 41.6 50.0
75 161.2 129.3 45.9 172.8 94.5 48.5 180.7 73.2 50.4
95 6000
80 164.4 158.8 46.6 174.9 125.7 49.0 182.4 104.2 50.7
85 167.4 167.4 47.3 177.6 156.6 49.6 184.6 135.5 51.2
70 164.1 107.3 46.6 176.6 66.9 49.4 184.3 40.8 51.2
75 166.5 143.2 47.1 178.2 103.1 49.8 186.2 78.2 51.6
7200
80 170.0 169.8 47.9 180.6 139.7 50.3 188.1 115.0 52.0
85 176.3 176.3 49.3 184.2 175.2 51.1 190.6 151.8 52.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity - fan motor heat MBh]
3. For capacity data at values other than 10° T, refer to Table 24.

Table 24. Cooling capacity adjustment


Water T GPM Multiplier Multiply by (TC) Multiply (SC)
4.5 2.21 1.01 1.01
7.2 1.39 1.01 1.01
10.0 1.00 1.00 1.00
12.6 0.79 0.99 1.00
15.3 0.66 0.99 1.00
18.0 0.56 0.98 0.99

30 PKG-PRC012Q-EN
Air-Cooled Performance Data

Table 25. SCRJ030 with CTA090 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor Wb Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 30.1 21.3 28.7 20.7 27.1 20.1 25.4 19.3 23.8 18.7
65 32.3 17.6 30.7 16.9 29.1 16.4 27.3 15.4 25.6 14.9
72
67 33.5 15.8 31.9 14.9 30.1 14.1 28.3 13.4 26.5 12.9
71 35.7 11.0 34.0 10.4 32.1 9.9 30.1 9.2 28.3 8.8
61 30.2 23.3 28.7 22.6 27.2 21.9 25.5 21.2 23.9 20.5
65 32.3 19.1 30.8 19.0 29.1 17.7 27.4 17.0 25.6 16.4
74
67 33.5 17.4 31.9 16.8 30.2 16.0 28.3 15.3 26.6 14.9
71 35.9 12.6 34.2 13.0 32.4 11.9 30.4 12.1 28.5 10.8
61 30.2 25.2 28.8 24.5 27.3 23.8 25.6 23.1 23.9 22.4
65 32.4 21.1 30.9 20.7 29.2 19.8 27.4 19.4 25.7 18.6
960 76
67 33.5 19.5 32.0 19.0 30.2 18.1 28.4 17.4 26.6 16.2
71 36.0 15.6 34.3 14.4 32.4 14.2 30.5 13.0 28.6 12.8
61 30.3 27.1 28.9 26.4 27.4 25.7 25.7 25.1 24.1 24.1
65 32.5 23.1 30.9 22.4 29.3 21.8 27.5 21.0 25.7 20.3
78
67 33.6 21.1 32.0 20.5 30.3 19.7 28.5 19.0 26.7 18.4
71 36.0 17.0 34.3 16.4 32.5 15.5 30.5 15.4 28.6 14.7
61 30.4 29.1 28.9 28.3 27.5 27.5 26.0 26.0 24.7 24.7
65 32.5 25.1 31.0 24.3 29.4 23.7 27.6 23.0 25.8 22.3
80
67 33.7 23.1 32.1 22.3 30.4 21.8 28.6 21.0 26.7 20.2
71 36.1 19.0 34.4 18.4 32.6 17.9 30.6 17.3 28.7 16.6
61 31.6 24.2 30.0 23.5 28.4 22.9 26.6 22.0 24.8 21.3
65 33.8 19.6 32.1 18.2 30.3 17.8 28.4 16.9 26.6 16.4
72
67 34.9 16.8 33.2 16.1 31.3 15.2 29.3 14.5 27.5 13.7
71 37.2 11.5 35.4 11.4 33.4 11.2 31.2 10.4 29.3 8.6
61 31.7 26.5 30.1 25.8 28.5 25.2 26.8 24.9 24.9 23.7
65 33.9 21.4 32.2 20.9 30.4 20.2 28.5 19.2 26.6 18.8
74
67 35.0 19.2 33.3 18.5 31.4 17.8 29.4 16.9 27.6 16.3
71 37.5 14.3 35.6 13.2 33.6 12.3 31.5 12.1 29.5 11.7
61 31.8 28.9 30.2 28.2 28.6 27.7 26.8 26.7 25.2 25.2
65 33.9 24.0 32.3 23.2 30.5 22.6 28.6 22.0 26.7 21.1
1200 76
67 35.1 21.4 33.4 20.6 31.5 19.9 29.6 19.5 27.6 18.6
71 37.5 16.9 35.7 16.3 33.7 15.0 31.6 14.1 29.6 13.6
61 31.9 31.4 30.3 30.3 28.9 28.9 27.4 27.4 25.9 25.9
65 34.0 26.3 32.4 25.7 30.6 24.9 28.7 24.3 26.8 23.5
78
67 35.2 23.7 33.5 23.1 31.6 22.5 29.7 21.5 27.7 21.1
71 37.6 18.9 35.8 17.9 33.8 17.7 31.7 16.9 29.7 16.0
61 32.4 32.4 31.1 31.1 29.7 29.7 28.2 28.2 26.5 26.5
65 34.1 28.7 32.5 28.1 30.7 27.3 28.8 26.7 26.9 26.1
80
67 35.3 26.1 33.6 25.5 31.7 24.8 29.8 24.1 27.8 23.4
71 37.7 21.5 35.8 20.7 33.9 19.7 31.8 19.0 29.8 18.5
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net
MBh capacity = gross MBh capacity- fan motor heat MBh]

PKG-PRC012Q-EN 31
Air-Cooled Performance Data

Table 25. SCRJ030 with CTA090 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor Wb Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 32.7 26.9 31.0 26.2 29.3 25.5 27.4 24.7 25.6 24.0
65 34.9 20.9 33.1 20.4 31.2 19.4 29.2 18.8 27.3 18.0
72
67 36.0 17.9 34.2 17.3 32.2 16.6 30.1 15.8 28.2 15.2
71 38.3 11.8 36.3 11.0 34.2 10.3 31.9 10.9 29.8 9.1
61 32.8 29.7 31.1 29.2 29.4 28.5 27.5 27.4 25.8 25.8
65 35.0 23.9 33.2 23.2 31.3 22.4 29.3 21.6 27.4 20.9
74
67 36.1 20.8 34.3 19.7 32.4 19.3 30.3 18.5 28.3 17.8
71 38.5 14.3 36.6 14.4 34.5 14.7 32.2 12.6 30.2 12.1
61 32.9 32.6 31.3 31.3 29.8 29.8 28.2 28.2 26.5 26.5
65 35.1 26.5 33.3 26.0 31.5 25.2 29.5 24.5 27.4 23.7
1440 76
67 36.2 23.6 34.4 23.0 32.5 22.4 30.4 21.2 28.4 20.8
71 38.7 18.7 36.7 16.0 34.7 16.4 32.4 15.3 30.4 14.2
61 33.6 33.6 32.1 32.1 30.6 30.6 28.9 28.9 27.3 27.3
65 35.2 29.5 33.4 28.9 31.6 28.1 29.6 27.3 27.6 26.8
78
67 36.3 26.5 34.5 25.8 32.6 25.1 30.5 24.4 28.5 23.7
71 38.7 20.0 36.8 19.4 34.7 19.1 32.5 18.3 30.5 17.7
61 34.4 34.4 33.0 33.0 31.4 31.4 29.7 29.7 28.0 28.0
65 35.3 32.3 33.6 32.0 31.7 31.1 29.7 29.7 28.0 28.0
80
67 36.4 29.3 34.6 28.7 32.7 28.0 30.7 27.3 28.6 26.7
71 38.8 23.3 36.9 22.6 34.9 21.9 32.7 20.9 30.6 20.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net
MBh capacity = gross MBh capacity- fan motor heat MBh]

Table 26. SCRJ050 with CTA090 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 49.0 34.8 47.1 33.9 44.7 32.9 41.6 31.5 39.2 30.5
65 52.3 27.4 50.2 26.5 47.6 25.4 44.3 24.0 41.7 23.0
72
67 54.0 23.8 51.8 22.9 49.2 21.8 45.8 20.4 43.1 19.2
71 57.7 15.6 55.3 14.6 52.6 13.9 48.9 12.7 46.0 11.2
61 49.2 38.2 47.3 37.4 45.0 36.4 41.9 35.0 39.5 34.0
65 52.4 30.8 50.4 29.9 47.8 28.8 44.9 27.6 42.0 26.5
74
67 54.2 27.0 52.1 26.2 49.4 25.1 46.1 23.8 43.3 22.6
71 57.9 19.7 55.6 18.8 52.7 17.5 49.2 16.2 46.3 15.1
61 49.5 41.7 47.6 40.9 45.3 39.8 42.3 38.6 39.8 37.4
65 52.6 34.2 50.6 33.3 48.1 32.4 44.9 31.0 42.3 29.9
1600 76
67 54.4 30.5 52.2 29.7 49.7 28.6 46.4 27.2 43.6 26.1
71 58.0 23.1 55.8 22.0 53.0 21.2 49.5 19.7 46.5 18.6
61 49.8 45.2 47.9 44.4 45.6 43.3 42.6 41.8 40.2 40.0
65 52.8 37.4 50.8 36.8 48.4 35.8 45.2 34.6 42.5 33.4
78
67 54.5 33.9 52.5 33.0 49.9 32.0 46.7 31.0 43.9 29.8
71 58.2 26.3 56.0 25.4 53.3 24.3 49.7 23.1 46.7 22.0
61 50.0 48.6 48.2 47.5 46.0 45.8 43.2 43.2 41.0 41.0
65 53.1 41.2 51.0 40.2 48.6 39.3 45.5 38.1 42.8 37.0
80
67 54.7 37.3 52.6 36.4 50.1 35.5 46.9 34.3 44.1 33.2
71 58.4 29.8 56.1 28.7 53.4 27.8 50.1 26.4 46.9 25.8
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

32 PKG-PRC012Q-EN
Air-Cooled Performance Data

Table 26. SCRJ050 with CTA090 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 51.2 39.4 49.2 38.5 46.6 37.4 43.3 36.1 40.8 35.1
65 54.4 30.1 52.2 29.1 49.4 28.2 45.9 26.7 43.2 25.5
72
67 56.1 25.5 53.9 24.6 51.0 23.5 47.3 22.0 44.5 21.0
71 59.8 16.1 57.4 14.9 54.3 13.7 50.5 12.5 47.4 11.6
61 51.5 43.7 49.5 42.8 47.0 41.8 43.8 40.5 41.2 39.3
65 54.7 34.5 52.4 33.5 49.8 32.5 46.3 31.2 43.5 30.1
74
67 56.3 29.7 54.1 28.8 51.3 27.8 47.7 26.3 44.9 25.2
71 60.1 20.4 57.6 19.4 54.6 18.3 50.8 17.0 47.7 16.0
61 51.8 48.0 49.9 47.1 47.3 45.9 44.2 43.8 41.6 41.5
65 54.9 38.7 52.7 37.6 50.0 36.8 46.7 35.7 43.9 34.5
2000 76
67 56.6 33.7 54.4 33.2 51.6 32.1 48.1 30.8 45.1 29.6
71 60.3 24.6 57.9 23.6 54.8 22.7 51.1 21.2 48.0 20.1
61 52.2 51.5 50.2 49.9 47.8 47.8 45.0 45.0 42.6 42.6
65 55.2 43.0 53.1 42.1 50.4 41.2 47.1 39.9 44.2 38.9
78
67 56.9 38.4 54.6 37.3 51.9 36.4 48.5 35.2 45.5 34.1
71 60.5 28.8 58.1 27.9 55.1 26.8 51.5 25.8 48.2 24.4
61 52.8 52.8 51.1 51.1 49.0 49.0 46.2 46.2 43.8 43.8
65 55.5 47.3 53.4 46.4 50.9 45.6 47.6 44.3 44.6 43.0
80
67 57.1 42.6 55.0 41.8 52.2 40.8 48.9 39.6 45.8 38.5
71 60.8 33.0 58.4 32.4 55.5 31.3 51.9 30.1 48.5 28.9
61 52.8 43.9 50.6 43.0 48.0 41.9 44.6 40.5 42.0 39.4
65 55.9 32.9 53.6 32.0 50.7 30.7 47.2 29.4 44.3 28.6
72
67 57.7 27.3 55.3 26.5 52.3 25.1 48.5 23.8 45.5 22.6
71 61.4 15.7 58.8 14.9 55.6 14.1 51.5 12.7 48.3 11.2
61 53.2 49.1 51.1 48.1 48.4 46.7 45.1 44.5 42.4 42.2
65 56.2 37.8 54.0 37.2 51.1 36.0 47.5 34.7 44.6 33.4
74
67 57.9 32.3 55.6 31.5 52.6 30.4 48.9 29.0 45.9 27.9
71 61.7 21.4 59.0 19.5 55.9 19.0 51.9 17.6 48.6 16.8
61 53.6 52.9 51.5 51.2 48.9 48.8 45.9 45.9 43.4 43.4
65 56.6 43.2 54.3 42.3 51.5 41.2 48.1 40.0 45.0 38.9
2400 76
67 58.2 37.5 55.9 36.6 53.0 35.7 49.4 34.4 46.3 33.1
71 61.9 26.2 59.4 25.4 56.3 24.3 52.4 23.1 48.9 21.8
61 54.2 54.2 52.4 52.4 50.1 50.1 47.2 47.2 44.6 44.6
65 57.0 48.3 54.8 47.5 52.1 46.5 48.6 45.1 45.5 43.6
78
67 58.6 42.7 56.2 41.8 53.4 41.0 49.9 39.5 46.7 38.6
71 62.2 31.5 59.6 30.2 56.6 29.4 52.8 28.4 49.3 27.1
61 55.6 55.6 53.7 53.7 51.5 51.5 48.5 48.5 45.8 45.8
65 57.4 53.5 55.2 52.5 52.5 51.1 49.1 48.7 46.0 45.9
80
67 59.0 48.1 56.7 47.0 53.9 46.1 50.5 45.2 47.1 43.7
71 62.5 36.7 60.0 35.9 57.0 35.0 53.2 33.6 49.7 32.3
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

PKG-PRC012Q-EN 33
Air-Cooled Performance Data

Table 27. SCRJ075 with CTA120 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 71.4 50.8 68.5 49.5 65.1 48.0 61.1 46.4 57.0 44.6
65 76.1 39.6 73.1 38.4 69.5 36.8 65.4 35.3 61.1 33.7
72
67 78.5 33.8 75.5 32.4 71.9 31.3 67.7 29.9 63.2 28.2
71 83.7 21.8 80.5 20.7 76.7 19.1 72.3 17.9 67.4 15.9
61 71.5 55.7 68.7 54.6 65.2 53.0 61.3 51.3 57.2 49.7
65 76.1 44.6 73.3 43.6 69.7 42.1 65.7 40.4 61.3 39.0
74
67 78.5 38.8 75.6 37.7 72.1 36.4 67.9 35.0 63.4 33.4
71 83.6 26.6 80.6 25.9 76.9 24.7 72.7 23.3 67.7 21.3
61 71.5 60.6 68.8 59.4 65.4 58.0 61.6 56.4 57.5 54.6
65 76.1 49.6 73.3 48.5 69.9 47.2 65.9 45.6 61.5 44.0
2400 76
67 78.5 43.9 75.6 42.6 72.2 41.6 68.2 40.1 63.5 38.5
71 83.5 32.0 80.6 30.8 77.1 30.0 72.9 28.80 67.9 26.8
61 71.5 65.5 68.9 64.4 65.6 62.9 61.8 61.2 57.4 57.3
65 76.0 54.6 73.3 53.5 70.1 52.2 66.1 50.7 61.6 48.9
78
67 78.4 48.9 75.7 47.9 72.3 46.6 68.4 45.1 63.7 43.5
71 83.3 37.1 80.7 36.3 77.1 35.2 73.0 33.8 68.0 32.1
61 71.6 70.2 69.1 68.8 65.5 65.5 62.2 62.2 58.7 58.7
65 75.9 59.5 73.4 58.5 70.2 57.2 66.3 55.7 61.8 53.9
80
67 78.2 53.9 75.7 52.9 72.5 51.7 68.6 50.3 63.8 48.5
71 83.1 41.9 80.5 41.3 77.2 40.0 73.3 38.8 68.2 37.1
52.5
61 74.4 57.0 71.3 55.7 67.7 54.2 63.4 59.2 50.8
38.8
65 79.1 43.3 76.0 41.9 72.3 41.0 67.8 63.3 37.7
72 32.0
67 81.5 36.3 78.4 35.2 74.6 33.8 70.1 65.2 30.2
17.5.
71 86.5 21.4 83.4 20.6 79.3 18.6 74.5 69.3 15.6
7
61 74.4 63.0 71.5 61.8 67.9 60.4 63.8 58.7 59.4 56.8
65 79.1 49.5 76.0 48.4 72.4 46.9 68.2 45.4 63.4 43.6
74
67 81.4 42.4 78.4 41.1 74.8 40.4 70.4 38.6 65.6 37.2
71 86.6 27.8 83.4 27.1 79.7 25.4 75.0 24.0 69.8 22.1
61 74.3 69.1 71.6 67.8 68.2 66.4 64.1 64.0 59.6 59.6
3000 65 78.9 55.7 76.1 54.6 72.6 53.3 68.4 51.8 63.7 50.1
76
67 81.4 48.7 78.4 47.6 74.9 46.5 70.7 45.0 65.8 43.3
71 86.4 34.4 83.4 33.7 79.8 32.2 75.4 30.7 70.0 28.9
61 74.6 74.4 71.7 71.7 68.4 68.4 65.0 65.0 61.2 61.2
65 78.9 61.8 76.2 60.7 72.7 59.4 68.6 57.9 63.8 56.1
78
67 81.2 54.7 78.5 53.9 75.0 52.8 70.9 51.3 65.9 49.4
71 86.2 40.7 83.3 39.8 79.9 38.4 75.6 37.0 70.2 35.5
61 75.2 75.2 72.9 72.9 70.1 70.1 66.7 66.7 62.8 62.8
65 78.8 67.8 76.1 66.8 72.7 65.6 68.9 64.1 64.0 62.3
80
67 81.2 60.9 78.5 60.0 75.1 58.9 71.1 57.4 66.1 55.8
71 86.0 46.8 83.3 46.1 79.6 44.8 75.7 44.0 70.4 41.9
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

34 PKG-PRC012Q-EN
Air-Cooled Performance Data

Table 27. SCRJ075 with CTA120 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 76.4 62.9 73.3 61.6 69.6 60.2 65.2 58.3 60.7 56.5
65 81.2 46.7 78.0 45.7 74.1 44.3 69.6 42.7 64.7 40.9
72
67 83.6 38.6 80.4 37.5 76.5 36.2 71.8 34.6 66.8 32.9
71 88.5 21.6 85.5 20.1 81.1 18.8 75.9 15.8 70.6 15.0
61 76.4 70.1 73.4 68.8 69.8 67.2 65.8 65.4 60.9 60.9
65 81.1 54.2 78.0 53.0 74.4 51.9 70.0 50.3 65.0 48.7
74
67 83.5 46.0 80.5 44.9 76.7 43.6 72.2 42.3 67.1 40.6
71 88.7 29.2 85.6 28.1 81.5 26.5 76.3 24.3 71.2 23.0
61 76.5 76.3 73.6 73.5 70.0 70.0 66.5 66.5 62.5 62.5
65 81.0 61.5 78.1 60.4 74.5 59.2 70.2 57.7 65.2 55.8
3600 76
67 83.4 53.4 80.4 52.4 76.9 51.2 72.5 49.7 67.3 48.0
71 88.6 36.6 85.5 35.4 81.7 34.6 77.1 33.3 71.7 31.2
61 77.2 77.2 74.8 74.8 71.9 71.9 68.3 68.3 64.1 64.1
65 80.9 68.7 77.8 67.6 74.6 66.4 70.5 64.9 65.5 63.1
78
67 83.3 60.7 80.5 59.7 77.0 58.5 72.7 57.0 67.5 55.3
71 88.2 43.9 85.5 43.1 81.8 41.9 77.4 40.8 71.7 38.9
61 78.9 78.9 76.4 76.4 73.6 73.6 70.1 70.1 65.7 65.7
65 80.7 75.8 78.0 74.8 74.8 73.4 70.8 70.7 65.8 65.8
80
67 83.2 67.9 80.4 66.9 77.1 65.9 72.9 64.3 67.6 62.6
71 88.1 51.7 85.2 51.2 81.8 49.5 77.6 48.3 71.9 46.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

Table 28. SCRJ100 with CTA180 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 109.4 76.3 104.6 74.1 99.4 71.9 93.9 69.5 88.0 67.0
65 116.3 60.6 111.5 57.8 105.9 56.3 100.0 53.6 93.7 51.3
72
67 120.2 52.5 114.9 50.5 109.3 48.2 103.2 46.2 96.6 42.9
71 127.9 35.2 122.3 34.6 116.1 30.7 109.7 29.1 102.6 27.0
61 109.7 83.4 104.8 81.3 99.7 79.0 94.2 76.6 88.3 74.1
65 116.5 67.7 111.7 65.7 106.3 63.6 100.3 61.3 94.1 58.8
74
67 120.7 59.7 115.3 57.7 109.7 55.5 103.5 53.1 97.1 51.0
71 128.5 43.4 122.6 41.8 116.6 39.1 110.2 36.9 103.1 33.9
61 110.0 90.5 105.1 88.4 100.1 86.1 94.5 83.8 88.7 81.3
65 116.8 74.7 112.0 72.6 106.6 70.8 100.7 68.3 94.4 65.9
3200 76
67 120.9 67.0 115.6 65.0 110.0 62.8 103.9 60.0 97.4 57.8
71 128.6 50.6 122.7 48.6 116.9 46.3 110.4 44.2 103.5 41.3
61 110.1 97.5 105.5 95.4 100.5 93.3 95.0 90.9 89.2 87.9
65 117.1 82.0 112.2 79.8 106.8 77.8 100.9 75.5 94.7 73.0
78
67 121.0 74.1 115.7 71.8 110.2 69.9 104.2 67.4 97.7 65.3
71 128.9 57.9 123.2 55.8 117.3 53.6 110.8 51.4 103.9 49.3
61 110.6 104.5 106.0 102.5 100.9 99.6 95.4 95.4 90.3 90.3
65 117.4 89.1 112.6 86.9 107.1 84.8 101.2 82.6 95.0 80.2
80
67 121.3 81.0 116.1 79.3 110.5 77.0 104.4 74.7 98.0 72.3
71 129.0 65.0 123.3 62.8 117.5 60.8 111.1 58.6 104.2 55.6
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity - fan motor heat MBh]

PKG-PRC012Q-EN 35
Air-Cooled Performance Data

Table 28. SCRJ100 with CTA180 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 113.9 85.8 109.2 83.7 103.7 81.3 97.7 78.8 91.3 76.2
65 121.3 66.5 116.5 64.2 110.3 61.8 103.9 59.2 97.0 56.8
72
67 125.2 55.7 119.9 53.7 113.7 52.7 107.1 49.4 99.9 46.8
71 132.8 36.5 127.0 34.8 120.4 31.1 113.3 28.6 105.5 25.8
61 114.3 94.5 109.6 92.4 104.3 90.2 98.3 87.7 91.9 85.1
65 121.8 75.3 117.0 73.0 110.8 70.9 104.4 68.4 97.5 66.2
74
67 125.6 64.9 120.3 62.9 114.2 60.7 107.7 58.3 100.4 55.9
71 133.3 44.8 127.5 43.1 121.2 40.5 114.1 37.9 106.3 35.3
61 114.8 103.3 110.1 101.2 105.0 99.0 99.0 96.2 92.4 91.9
65 122.0 84.4 117.2 82.1 111.3 79.9 104.9 77.5 97.8 74.9
4000 76
67 125.9 74.4 120.6 72.4 114.7 70.4 108.2 67.7 100.8 65.1
71 133.8 53.8 128.0 52.1 121.8 51.0 114.9 47.4 106.9 44.7
61 115.5 111.9 110.8 109.8 105.4 105.1 99.7 99.7 94.0 94.0
65 122.4 92.8 117.6 90.5 111.7 88.8 105.4 86.5 98.2 83.9
78
67 126.2 83.2 120.9 81.2 115.2 78.8 108.6 76.7 101.2 74.1
71 133.9 63.1 128.1 61.4 122.4 59.5 115.4 57.5 107.4 54.1
61 116.0 116.0 111.6 111.6 107.4 107.4 102.2 102.2 96.4 96.4
65 122.6 101.9 117.8 99.6 112.4 97.9 106.0 95.5 98.8 92.9
80
67 126.4 92.3 121.7 88.5 115.6 88.1 109.1 85.8 101.5 83.2
71 134.3 72.1 128.3 69.1 122.9 68.9 115.9 65.6 107.7 63.3
61 117.6 94.9 112.5 92.2 106.5 90.4 100.4 88.1 93.9 85.3
65 124.9 72.2 119.2 70.2 113.0 67.4 106.4 65.1 99.4 62.2
72
67 128.7 60.8 122.9 58.9 116.4 55.3 109.6 52.7 102.2 50.3
71 136.4 35.0 130.4 32.7 123.3 31.4 115.8 29.7 107.4 25.1
61 118.1 105.4 112.9 103.4 107.3 100.9 101.1 98.0 94.5 93.6
65 125.4 82.7 119.7 80.7 113.5 78.3 106.8 75.9 99.8 73.4
74
67 129.2 71.1 123.4 69.2 116.9 66.1 110.1 64.1 102.8 61.4
71 137.0 48.2 131.0 45.9 123.8 42.5 116.5 40.0 108.5 37.1
61 118.9 115.4 113.8 112.7 107.7 107.4 101.8 101.8 96.0 96.0
65 125.7 93.2 120.0 91.2 113.9 88.9 107.3 86.6 100.4 84.0
4800 76
67 129.5 81.4 123.7 79.5 117.3 77.3 110.4 75.0 103.3 72.2
71 137.4 57.7 131.1 55.7 124.3 54.2 117.0 51.1 109.2 48.1
61 119.5 119.4 114.4 114.3 109.8 109.8 104.3 104.3 98.3 98.3
65 126.1 103.8 120.4 101.8 114.3 99.6 107.8 97.3 101.0 94.6
78
67 129.8 92.1 124.0 90.2 117.6 88.0 110.8 85.7 103.7 83.2
71 137.7 68.8 131.7 66.5 124.7 64.4 117.4 61.8 109.8 59.4
61 120.1 120.0 115.0 114.9 112.4 112.4 106.7 106.7 100.9 100.9
65 126.5 114.4 120.8 112.4 114.9 109.8 108.5 106.6 101.5 101.2
80
67 130.0 102.8 124.2 100.9 117.9 98.7 111.2 96.4 104.3 93.9
71 137.9 79.7 131.9 77.4 124.9 74.8 117.7 72.9 110.2 70.8
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity - fan motor heat MBh]

36 PKG-PRC012Q-EN
Air-Cooled Performance Data

Table 29. SCRJ120 with CTA180 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 121.7 86.8 116.9 84.6 111.5 82.3 105.6 79.7 99.4 77.1
65 129.8 67.9 124.6 65.8 118.5 62.9 112.1 60.5 105.4 58.1
72
67 134.0 58.3 128.5 56.1 121.4 54.6 115.6 51.3 107.9 47.6
71 143.2 38.7 137.3 36.5 129.1 32.8 121.8 30.2 114.5 28.1
61 122.2 95.4 117.5 93.3 111.9 90.8 106.1 88.4 99.8 85.8
65 130.1 76.5 124.9 74.4 119.0 71.9 112.8 69.5 105.5 66.5
74
67 134.3 66.9 129.0 64.8 122.8 62.4 115.9 59.2 109.4 57.5
71 143.4 47.4 137.7 45.4 130.2 42.7 122.7 39.5 114.8 36.8
61 122.8 104.1 118.0 101.9 112.3 99.7 106.6 97.0 100.4 94.4
65 130.5 85.1 125.3 82.9 119.2 80.5 113.0 78.0 106.0 75.1
3840 76
67 134.8 75.5 129.3 73.3 122.9 70.9 116.6 68.5 109.6 65.9
71 143.6 55.9 137.8 53.9 130.3 51.0 123.0 48.2 115.5 45.9
61 123.4 112.7 118.5 110.5 112.9 107.9 107.0 104.9 101.0 100.7
65 130.9 93.7 125.6 91.3 119.6 89.1 113.4 86.7 106.6 84.1
78
67 135.1 84.1 129.7 82.0 123.2 79.5 116.8 77.1 109.8 74.5
71 143.9 64.6 137.9 62.4 131.0 60.0 123.6 57.2 115.7 54.2
61 124.2 121.1 119.3 118.1 113.9 113.8 108.4 108.4 102.9 102.9
65 131.4 102.3 126.1 100.2 119.9 97.7 113.8 95.4 106.7 92.9
80
67 135.4 92.7 130.4 90.1 123.5 88.0 117.0 85.6 110.1 83.1
71 144.2 73.2 138.5 71.2 131.1 68.5 124.3 66.3 116.8 63.8
61 126.7 98.1 121.5 95.9 115.8 93.6 109.7 91.1 103.0 88.4
65 134.7 74.8 128.8 72.6 122.5 69.7 115.4 66.9 108.1 64.2
72
67 138.9 62.9 133.1 60.8 126.6 57.8 118.5 54.5 111.0 52.0
71 146.9 37.4 139.6 35.1 132.9 33.0 125.1 29.5 117.3 27.2
61 127.4 108.9 122.6 107.7 116.1 104.5 110.3 101.6 103.4 98.7
65 135.0 85.4 129.9 83.9 123.2 80.9 116.6 78.5 109.0 75.4
74
67 139.2 73.6 133.8 72.0 126.7 69.0 120.3 66.8 111.7 62.7
71 148.0 49.5 141.6 47.5 133.7 44.6 126.0 41.9 117.6 39.2
61 128.1 119.6 122.7 117.1 117.0 114.1 110.8 110.1 104.4 104.4
65 135.3 96.1 129.6 94.9 123.6 91.6 117.0 89.2 109.9 86.6
4800 76
67 139.4 84.2 133.4 82.9 127.3 79.8 120.2 78.5 112.5 74.2
71 148.1 60.2 141.4 58.0 134.4 55.7 126.7 53.0 118.7 50.3
61 128.8 127.8 123.6 123.5 118.1 118.1 112.6 112.6 106.7 106.7
65 135.7 106.8 130.1 104.2 124.1 102.4 117.5 100.0 110.5 97.4
78
67 139.7 94.9 133.9 92.8 127.6 90.5 120.7 88.1 113.4 85.6
71 148.3 70.9 142.1 68.8 134.9 66.8 128.0 64.4 118.9 61.0
61 130.5 130.5 125.9 125.3 120.8 120.8 115.3 115.3 109.2 109.2
65 136.4 117.6 130.6 115.2 124.5 113.0 118.1 110.6 110.9 107.4
80
67 140.1 105.6 134.2 103.4 128.0 101.2 121.2 98.9 113.8 96.4
71 148.3 81.5 142.1 79.4 135.4 77.2 127.8 74.6 119.3 71.5
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

PKG-PRC012Q-EN 37
Air-Cooled Performance Data

Table 29. SCRJ120 with CTA180 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 130.5 109.4 125.5 107.2 119.1 104.7 112.6 101.8 105.1 98.7
65 138.4 81.8 131.8 79.3 125.3 76.5 117.9 73.7 110.2 70.7
72
67 142.6 67.6 135.7 65.1 128.3 61.9 121.6 60.1 113.2 56.5
71 149.4 34.0 142.9 35.9 135.6 30.4 127.5 29.7 119.5 27.6
61 131.4 122.0 126.1 119.2 119.8 116.4 113.2 112.2 106.0 105.9
65 138.6 94.4 133.0 92.7 126.3 89.9 119.4 87.4 111.4 84.4
74
67 142.9 80.5 136.7 77.9 128.9 74.9 121.8 72.5 114.0 69.8
71 150.6 51.2 144.1 49.4 136.4 47.5 128.3 43.8 120.0 40.4
61 131.6 131.0 126.6 122.4 120.8 120.8 114.8 114.8 108.5 108.5
65 139.1 107.2 133.3 105.3 126.8 102.7 119.5 99.9 111.7 96.5
5760 76
67 143.1 93.1 136.9 90.6 129.9 88.1 123.2 86.3 114.9 83.1
71 151.6 64.6 145.2 63.4 136.8 58.0 128.8 56.2 120.5 53.6
61 133.7 133.7 128.6 125.7 123.4 123.4 117.6 117.6 111.2 111.2
65 139.7 120.0 133.7 117.6 127.7 115.4 120.3 112.1 113.2 109.6
78
67 143.5 105.9 137.3 103.7 130.8 101.5 123.5 99.1 115.1 95.4
71 152.0 77.5 145.4 75.4 137.7 73.0 129.5 69.8 121.1 67.0
61 136.8 136.8 131.9 130.8 126.3 126.3 120.4 120.4 113.7 113.7
65 140.5 132.4 134.5 128.2 128.1 126.1 121.1 120.8 114.1 114.1
80
67 144.0 118.8 137.9 116.6 131.4 114.3 124.2 111.7 116.3 108.6
71 152.1 90.2 145.0 87.9 138.0 85.4 130.1 82.8 121.6 80.4
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity- fan motor heat MBh]

Table 30. SCRJ150 with CTA180 gross cooling capacity

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 157.1 109.2 150.1 106.1 142.8 102.7 135.5 99.5 127.2 96.0
65 167.1 86.2 160.3 84.5 152.2 80.0 144.7 77.0 135.6 73.4
72
67 172.5 74.5 165.4 73.0 157.1 68.3 149.4 65.3 140.0 61.8
71 183.8 50.6 176.3 49.1 167.2 44.7 159.5 41.9 148.4 37.3
61 157.3 119.4 150.8 115.8 143.2 113.1 136.0 110.0 127.6 106.4
65 167.5 96.6 160.7 94.7 152.5 90.3 145.1 87.4 136.0 83.8
74
67 172.8 84.9 165.7 83.2 157.3 78.6 149.8 75.8 140.3 72.3
71 184.1 61.0 176.6 59.2 167.5 55.0 160.0 52.4 148.9 48.3
61 158.2 131.3 151.9 127.3 143.7 123.5 136.2 120.3 128.1 117.0
65 168.0 107.0 161.1 104.9 152.8 100.7 144.6 97.4 136.0 94.0
4800 76
67 173.3 95.3 166.2 93.4 157.6 89.1 149.4 86.0 140.5 82.7
71 184.4 71.4 176.8 69.2 167.6 65.3 158.9 62.3 149.6 59.1
61 158.7 140.3 152.2 136.1 144.1 133.8 136.7 130.6 128.8 126.8
65 168.4 117.4 161.5 115.0 153.0 110.9 145.0 107.7 136.4 104.4
78
67 173.6 105.7 166.5 103.5 157.9 99.5 149.5 96.2 140.6 92.9
71 184.7 81.8 177.2 79.4 167.8 75.7 159.2 72.7 149.8 69.6
61 159.2 150.7 152.7 146.2 144.9 143.3 137.7 137.5 130.2 130.2
65 169.1 127.9 162.2 125.4 153.3 121.3 145.3 118.2 136.7 114.9
80
67 174.0 116.1 166.9 113.8 157.9 109.6 149.6 106.4 140.9 103.3
71 185.0 92.2 177.4 89.5 167.9 86.1 159.3 83.1 149.9 80.0
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity - fan motor heat MBh]

38 PKG-PRC012Q-EN
Air-Cooled Performance Data

Table 30. SCRJ150 with CTA180 gross cooling capacity (continued)

85 °F 95 °F 105 °F 115 °F 125 °F


Indoor Ambient
CFM Db Indoor WB Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible
61 163.9 122.9 156.8 119.9 149.2 116.7 141.0 113.3 132.1 109.8
65 174.2 94.7 166.7 92.8 158.8 88.6 150.3 85.4 140.4 81.7
72
67 179.6 80.1 172.1 77.2 163.9 74.2 155.1 71.0 144.5 67.2
71 191.1 50.8 183.3 47.6 174.1 44.2 164.0 41.4 152.4 37.0
61 164.6 135.9 157.9 131.8 150.0 129.7 141.9 126.5 132.8 122.9
65 174.7 107.6 167.3 104.7 159.3 101.6 150.9 98.4 140.6 94.6
74
67 180.0 93.1 172.5 90.3 164.3 87.2 155.6 84.1 145.1 80.5
71 191.3 63.8 183.5 60.9 175.0 58.1 165.8 55.7 153.3 50.8
61 165.3 148.9 158.4 145.9 150.9 142.7 142.9 139.1 133.8 133.2
65 175.0 120.3 167.7 117.5 159.7 114.4 151.2 111.2 141.0 107.5
6000 76
67 180.5 106.0 172.9 103.4 164.8 100.3 156.0 97.1 145.3 93.3
71 191.5 76.2 183.9 74.0 175.3 71.1 166.2 68.2 153.6 63.7
61 166.1 161.4 159.3 153.3 151.7 151.3 144.1 144.1 135.5 135.5
65 174.5 133.3 167.4 130.6 160.3 127.4 151.8 124.3 141.5 120.6
78
67 180.9 119.1 173.4 116.7 165.0 113.0 156.4 110.0 145.5 106.2
71 192.0 89.7 184.2 87.0 175.7 84.2 166.6 81.3 154.5 77.9
61 167.4 167.3 160.9 160.9 154.4 154.4 147.3 147.3 138.6 138.6
65 176.0 146.3 169.0 143.6 161.1 140.6 152.7 137.6 142.0 133.6
80
67 181.3 131.9 173.8 129.1 165.6 126.1 156.9 123.1 145.9 119.3
71 192.3 102.7 184.7 100.1 176.2 97.3 167.0 94.3 154.8 90.6
61 168.9 136.5 161.4 132.4 153.7 130.3 145.3 127.0 135.7 123.3
65 179.2 103.0 171.6 100.0 163.2 96.9 154.3 93.8 143.8 90.1
72
67 184.7 85.8 177.1 83.1 168.3 80.0 159.1 76.8 147.2 72.1
71 196.2 52.1 187.7 47.8 177.2 44.5 166.8 40.5 155.1 37.3
61 169.9 152.0 162.7 149.1 154.9 145.8 146.4 141.9 136.6 135.8
65 179.9 118.5 172.1 116.1 163.6 112.2 154.7 109.0 143.8 105.2
74
67 185.2 101.4 177.4 99.3 168.8 95.5 159.6 92.4 148.1 88.2
71 196.7 66.5 188.0 63.9 178.0 59.7 168.9 57.0 156.5 54.3
61 171.2 166.8 163.8 156.8 156.0 155.6 147.3 147.3 138.3 138.3
65 180.1 133.7 172.5 130.8 164.3 127.8 155.4 124.7 144.5 120.9
7200 76
67 185.6 116.9 177.9 114.1 169.2 110.9 160.0 107.7 148.7 104.0
71 197.0 82.1 188.7 78.8 179.9 76.7 170.2 73.3 157.0 68.3
61 171.8 171.8 164.7 163.2 158.3 158.3 150.8 150.8 141.6 141.6
65 180.8 149.3 173.4 146.3 165.1 143.5 156.5 140.5 145.4 136.6
78
67 185.8 132.0 178.2 129.4 169.7 126.4 160.6 123.3 149.1 119.6
71 197.4 97.7 189.3 94.8 180.3 92.3 170.8 89.3 157.7 85.1
61 175.4 175.4 169.1 169.1 162.1 162.1 154.6 154.6 145.0 145.0
65 181.8 164.9 174.4 162.1 166.0 158.5 157.6 154.8 146.0 145.7
80
67 186.5 147.7 178.7 145.0 170.5 142.2 161.5 139.1 149.8 135.3
71 197.7 113.3 189.7 110.7 180.7 107.8 171.1 104.9 158.6 100.7
Notes:
1. All capacities shown are gross and do not consider indoor fan heat.
2. Use the following equation to compute indoor fan motor heat and calculate the net capacities: Fan motor heat (MBh) = 3.98 x fan motor bhp [Net MBh
capacity = gross MBh capacity - fan motor heat MBh]

PKG-PRC012Q-EN 39
Heating Coil Performance Data

Table 31. Hot water coil heating capacity, 180°F entering water temperature

Water Temperature Drop 20 30 40


Air
Air Pressure WPD WPD WPD
Unit Flow, Drop, EAT, Total LAT Flow Ft. Total LAT Flow Ft. Total LAT Flow Ft.
Size Cfm In H20 °F Capacity °F Gpm H20 Capacity °F Gpm H20 Capacity °F Gpm H20
40 47.2 85.3 4.8 2.9 43.9 82.2 3.0 1.3 40.6 78.9 2.1 0.7
960 0.27 60 39.6 98.0 4.1 2.1 36.3 94.8 2.5 0.9 33.0 91.7 1.7 0.5
80 31.9 110.6 3.3 1.5 28.7 107.5 2.0 0.6 25.4 104.4 1.3 0.3
40 52.4 80.2 5.4 3.5 48.7 77.4 3.3 1.5 44.9 74.5 2.3 0.8
3 ton 1200 0.39 60 43.9 93.7 4.5 2.6 40.2 90.9 2.7 1.1 36.5 88.0 1.9 0.6
80 35.4 107.2 3.6 1.8 31.7 104.4 2.2 0.7 28.0 101.5 1.4 0.4
40 56.7 76.3 5.8 4.1 52.7 73.7 3.6 1.8 48.5 71.1 2.5 0.9
1440 0.53 60 47.5 90.4 4.9 3.0 43.5 87.8 3.0 1.3 39.4 85.2 2.0 0.6
80 38.3 104.5 3.9 2.0 34.3 102 2.3 0.8 30.2 99.3 1.5 0.4
40 75.7 83.6 7.8 10.0 71.1 81.0 4.9 4.4 66.4 78.3 3.4 2.4
1600 0.33 60 63.6 96.6 6.5 7.3 59.0 94.0 4.0 3.1 54.4 91.4 2.8 1.7
80 51.4 109.6 5.3 5.0 47.0 107.1 3.2 2.1 42.4 104.4 2.2 1.1
40 83.7 78.6 8.6 11.9 78.6 76.2 5.4 5.2 73.4 73.8 3.8 2.8
5 ton 2000 0.48 60 70.3 92.4 7.2 8.7 65.2 90.0 4.5 3.8 60.1 87.7 3.1 2.0
80 57.0 106.3 5.8 6.0 51.9 103.9 3.5 2.5 46.7 101.5 2.4 1.3
40 90.4 74.7 9.3 13.7 84.8 72.5 5.8 6.0 79.1 70.4 4.0 3.2
2400 0.65 60 75.9 89.2 7.8 10.1 70.3 87.0 4.8 4.3 64.7 84.9 3.3 2.2
80 61.5 103.6 6.3 6.8 55.9 101.5 3.8 2.8 50.3 99.3 2.6 1.4
40 115.7 84.4 11.9 4.5 108.2 81.5 7.4 2.0 100.4 78.6 5.1 1.0
2400 0.31 60 97.1 97.3 10.0 3.3 89.6 94.4 6.1 1.4 82.0 91.5 4.2 0.7
80 78.5 110.2 8.0 2.2 71.0 107.3 4.8 0.9 63.4 104.4 3.2 0.5
7.5 40 128.3 79.4 13.1 5.4 119.8 76.8 8.2 2.3 111.2 74.1 5.7 1.3
ton 3000 0.44 60 107.6 93.1 11.0 3.9 99.2 90.5 6.8 1.7 90.6 87.8 4.6 0.9
SCRJ 80 87.0 106.7 8.9 2.7 78.6 104.1 5.4 1.1 70.0 101.5 3.6 0.6
40 138.7 75.5 14.2 6.2 129.3 73.1 8.8 2.7 120 70.7 6.1 1.4
3600 0.60 60 116.4 89.8 11.9 4.5 107.0 87.4 7.3 1.9 97.7 85.0 5.0 1.0
80 94.0 104.1 9.6 3.1 84.8 101.7 5.8 1.3 75.4 99.3 3.9 0.6
40 145.3 95.8 14.5 11.9 137.5 92.9 9.2 5.3 129.6 89.8 6.5 2.9
2400 0.14 60 122.4 107.0 12.2 8.8 114.6 104.0 7.6 3.8 106.6 100.9 5.4 2.1
80 99.5 118.2 9.9 6.1 91.64 115.2 6.1 2.6 83.7 112.1 4.2 1.3
7.5 40 164.3 90.5 16.4 14.9 155.4 87.8 10.4 6.6 146.2 85.0 7.3 3.6
ton 3000 0.21 60 138.4 102.5 13.8 10.9 129.4 99.8 8.6 4.8 120.3 97.0 6.1 2.6
SCWJ 80 112.4 114.5 11.2 7.6 103.4 111.8 6.9 3.2 94.3 109.0 4.7 1.7
40 180.1 86.1 18.0 17.6 170.2 83.6 11.4 7.8 160.0 81.0 8.0 4.2
3600 0.28 60 151.6 98.8 15.1 12.9 141.7 96.3 9.4 5.6 131.6 93.7 6.6 3.0
80 123.1 111.5 12.3 88.8 113.2 109.0 7.5 3.8 103.1 106.4 5.2 1.9
40 184.1 93.0 18.9 4.4 172.8 89.8 11.8 1.9 161.3 86.5 8.2 1.1
3200 0.17 60 154.7 104.6 15.8 3.2 143.5 101.3 9.8 1.4 131.9 98.0 6.7 0.7
80 125.3 116.1 12.8 2.2 114.0 112.8 7.8 0.9 102.5 109.5 5.2 0.5
40 206.9 87.7 21.2 5.4 194.0 84.7 13.2 2.4 180.7 81.6 9.2 1.3
10 ton 4000 0.25 60 173.8 100.0 17.8 4.0 160.9 97.1 11.0 1.7 147.7 94.0 7.6 0.9
80 140.7 112.4 14.4 2.7 127.8 109.4 8.7 1.1 114.8 106.4 5.9 0.6
40 226.2 83.4 23.2 6.4 211.8 80.7 14.5 2.8 197.2 77.9 10.1 1.5
4800 0.34 60 189.9 96.5 19.5 4.7 175.6 93.7 12.0 2.0 161.1 90.9 8.2 1.0
80 153.6 109.5 15.8 3.2 139.3 106.8 9.5 1.3 124.9 104.0 6.4 0.7

40 PKG-PRC012Q-EN
Heating Coil Performance Data

Table 31. Hot water coil heating capacity, 180°F entering water temperature (continued)

Water Temperature Drop 20 30 40


Air
Air Pressure WPD WPD WPD
Unit Flow, Drop, EAT, Total LAT Flow Ft. Total LAT Flow Ft. Total LAT Flow Ft.
Size Cfm In H20 °F Capacity °F Gpm H20 Capacity °F Gpm H20 Capacity °F Gpm H20
40 202.6 88.6 20.8 5.2 190.1 85.6 13.0 2.3 177.1 82.5 9.1 1.2
3840 0.23 60 170.2 100.8 17.5 3.8 157.7 97.8 10.8 1.7 144.7 94.7 7.4 0.9
80 137.8 113.1 14.1 2.6 125.2 110 8.5 1.1 112.5 107.0 5.7 0.6
40 226.2 83.4 23.2 6.4 211.8 80.7 14.5 2.8 197.2 77.9 10.1 1.5
12 ton 4800 0.34 60 189.9 96.5 19.5 4.7 175.6 93.7 12.0 2.0 161.1 90.9 8.2 1.0
80 153.6 109.5 15.8 3.2 139.3 106.8 9.5 1.3 124.9 104 6.4 0.7
40 245.8 79.3 25.2 7.4 230.0 76.8 15.7 3.2 213.9 74.2 10.9 1.7
5760 0.45 60 206.4 93.0 21.2 5.4 190.5 90.5 13.0 2.3 174.7 88.0 8.9 1.2
80 166.9 106.7 17.1 3.7 151.2 104.2 10.3 1.5 135.4 101.7 6.9 0.8
40 256.2 89.2 26.3 10.0 241.6 86.4 16.5 4.4 226.4 83.5 11.6 2.4
4800 0.23 60 215.6 101.4 22.1 7.3 200.9 98.6 13.7 3.2 185.7 95.7 9.5 1.7
80 174.9 113.6 17.9 5.0 160.1 110.7 10.9 2.1 145.1 107.9 7.4 1.1
40 285.4 83.8 29.3 12.2 269.3 81.4 18.4 5.4 252.2 78.7 12.9 2.9
15 ton 6000 0.33 60 240.6 97.0 24.7 8.9 223.8 94.4 15.3 3.9 206.8 91.8 10.6 2.0
80 195.1 110.0 20.0 6.1 178.3 107.4 12.2 2.6 161.4 104.8 8.3 1.3
40 311.0 79.8 31.9 14.2 292.6 77.5 20.0 6.2 273.7 75.0 14.0 3.4
7200 0.45 60 261.5 93.5 26.8 10.4 243.0 91.1 16.6 4.5 224.5 88.7 11.5 2.4
80 212.0 107.1 21.7 7.1 193.6 104.8 13.2 3.0 174.9 102.4 8.9 1.5

Table 32. Hot water coil heating capacity, 200°F entering water temperature

Water Temperature Drop 20 30 40


Air
Air Pressure WPD WPD WPD
Unit Flow, Drop, EAT, Total LAT Flow Ft. Total LAT Flow Ft. Total LAT Flow Ft.
Size Cfm In H20 °F Capacity °F Gpm H20 Capacity °F Gpm H20 Capacity °F Gpm H2 0
40 55.1 92.9 5.7 3.8 51.9 89.8 3.6 1.7 48.7 86.8 2.5 0.9
960 0.27 60 47.4 105.5 4.9 2.9 44.3 102.5 3.0 1.3 41.1 99.4 2.1 0.7
80 39.8 118.2 4.1 2.1 36.6 115.2 2.5 0.9 33.5 112.1 1.7 0.5
40 61.2 87.0 6.3 4.6 57.6 84.2 3.9 2.0 54.0 81.5 2.8 1.1
3 ton 1200 0.39 60 52.7 100.5 5.4 3.5 49.1 97.7 3.4 1.5 45.5 94.9 2.3 0.8
80 44.2 113.9 4.5 2.5 40.6 111.2 2.8 1.1 37.0 108.4 1.9 0.6
40 66.3 82.4 6.8 5.3 62.3 79.9 4.3 2.3 58.3 77.3 3.0 1.3
1440 0.53 60 57.0 96.5 5.9 4.0 53.1 94.0 3.6 1.7 49.2 91.5 2.5 0.9
80 47.8 110.6 4.9 2.9 43.9 108.1 3.0 1.2 40.0 105.6 2.1 0.6
40 88.0 90.7 9.1 12.8 83.6 83.6 5.7 5.7 79.1 85.6 4.1 3.1
1600 0.33 60 75.9 103.7 7.8 9.8 71.5 101.2 4.9 4.3 67.0 98.6 3.4 2.3
80 63.9 116.8 6.6 7.2 59.5 114.3 4.1 3.1 55.0 111.7 2.8 1.6
40 97.4 84.9 10.0 15.3 92.4 82.6 6.3 6.8 87.4 80.3 4.5 3.7
5 ton 2000 0.48 60 84.0 98.7 8.7 11.7 79.1 96.4 5.4 5.2 74.0 94.1 3.8 2.8
80 70.7 112.6 7.3 8.6 65.7 110.3 4.5 3.7 60.7 108 3.1 1.9
40 105.2 80.4 10.8 17.6 99.7 78.3 6.8 7.8 94.2 76.2 4.8 4.3
2400 0.65 60 90.7 94.8 9.3 13.5 85.3 92.7 5.8 6.0 79.8 90.6 4.1 3.2
80 76.2 109.3 7.9 9.9 70.8 107.2 4.9 4.2 65.4 105.1 3.4 2.2

PKG-PRC012Q-EN 41
Heating Coil Performance Data

Table 32. Hot water coil heating capacity, 200°F entering water temperature (continued)

Water Temperature Drop 20 30 40


Air
Air Pressure WPD WPD WPD
Unit Flow, Drop, EAT, Total LAT Flow Ft. Total LAT Flow Ft. Total LAT Flow Ft.
Size Cfm In H20 °F Capacity °F Gpm H20 Capacity °F Gpm H20 Capacity °F Gpm H2 0
40 134.8 91.8 13.9 5.8 127.5 89.0 8.7 2.6 120.2 86.1 6.2 1.4
2400 0.31 60 116.3 104.7 12.0 4.4 109.0 101.9 7.5 1.9 101.5 99.0 5.2 1.0
80 97.7 117.5 10.1 3.2 90.4 114.7 6.2 1.4 83.0 111.9 4.3 0.7

7.5 40 149.6 86.0 15.4 6.9 141.3 83.4 9.7 3.2 132.9 80.8 6.8 1.7
ton 3000 0.44 60 128.9 99.6 13.3 5.3 120.7 97.1 8.3 2.3 112.3 94.5 5.8 1.2
SCRJ 80 108.2 113.2 11.1 3.9 100.0 110.7 6.9 1.8 91.8 108.2 4.7 0.9
40 161.7 81.4 16.7 8.0 152.7 79.1 10.5 3.5 143.6 76.8 7.4 1.9
3600 0.60 60 139.3 95.7 14.3 6.1 130.3 93.4 8.9 2.7 121.3 91.1 6.2 1.4
80 117.0 110.0 12.0 4.5 108.0 107.6 7.4 1.9 99.0 105.3 5.1 1.0
40 168.6 104.8 16.8 15.3 161.0 101.9 10.7 6.9 153.3 98.9 7.6 3.8
2400 0.14 60 145.7 116.0 14.5 11.7 138.1 113.1 9.2 5.2 130.4 110.1 6.5 2.9
80 122.7 127.2 12.2 8.6 115.2 124.2 7.7 3.8 107.3 121.2 5.4 2.0
7.5 40 190.7 98.6 19.0 19.1 182.0 95.9 12.1 8.6 173.1 93.2 8.6 4.7
ton 3000 0.21 60 164.7 110.6 16.4 14.7 156.0 108.0 10.4 6.5 147.1 105.2 7.3 3.5
SCWJ 80 138.8 122.7 13.8 10.8 130.0 120.0 8.6 4.7 121.1 117.2 6.0 2.5
40 209.1 93.6 20.8 22.5 199.4 91.1 13.3 10.1 189.6 88.6 9.5 5.6
3600 0.28 60 180.6 106.3 18.0 17.3 170.9 103.8 11.4 7.7 161.0 101.2 8.0 4.2
80 152.1 119.0 15.2 12.7 142.4 116.5 9.5 5.5 132.6 114.0 6.6 2.9
40 214.2 101.7 22.1 5.7 203.3 98.6 13.9 2.5 192.2 95.4 9.9 1.4
3200 0.17 60 184.8 113.2 19.0 4.3 174.0 110.1 11.9 1.9 162.8 106.9 8.4 1.0
80 155.4 124.8 16.0 3.2 144.5 121.6 9.9 1.4 133.3 118.4 6.8 0.7
40 240.8 95.5 24.8 7.0 228.3 92.6 15.7 3.1 215.6 89.7 11.1 1.7
10 ton 4000 0.25 60 207.7 107.9 21.4 5.4 195.3 105.0 13.4 2.4 182.5 102.1 9.4 1.3
80 174.6 120.2 18.0 3.9 162.2 117.4 11.1 1.7 149.4 114.4 7.7 0.9
40 263.3 90.6 27.1 8.2 249.5 87.9 17.1 3.7 235.4 85.2 12.1 2.0
4800 0.34 60 227.1 103.6 23.4 6.3 213.2 100.9 14.6 2.8 199.1 98.2 10.2 1.5
80 190.8 116.6 19.6 4.6 176.9 114.0 12.1 2.0 163 111.3 8.4 1.0
40 235.9 96.6 24.3 6.7 223.7 93.7 15.3 3.0 211.3 90.7 10.9 1.6
3840 0.23 60 203.5 108.8 21.0 5.2 191.3 105.9 13.1 2.3 178.8 102.9 9.2 1.2
80 171.0 121.0 17.6 3.8 158.9 118.1 10.9 1.6 146.3 115.1 7.5 0.9
40 263.3 90.6 27.1 8.2 249.5 87.9 17.1 3.7 235.4 85.2 12.1 2.0
12 ton 4800 0.34 60 227.1 103.6 23.4 6.3 213.2 100.9 14.6 2.8 199.1 98.2 10.2 1.5
80 190.8 116.6 19.6 4.6 176.9 114.0 12.1 2.0 163.0 111.3 8.4 1.0
40 286.4 85.8 29.5 9.6 271.0 83.4 18.6 4.2 255.4 80.9 13.1 2.3
5760 0.45 60 246.9 99.5 25.4 7.3 231.6 97.1 15.9 3.2 216.1 94.6 11.1 1.7
80 207.4 113.2 21.3 5.3 192.2 110.7 13.2 2.3 176.8 108.3 9.1 1.2
40 297.7 97.2 30.7 12.8 283.5 94.4 19.4 5.7 268.9 91.6 13.8 3.2
4800 0.23 60 257.0 109.4 26.5 9.8 242.8 106.6 16.7 4.3 228.2 103.8 11.7 2.4
80 216.4 121.5 22.3 7.2 202.1 118.8 13.9 3.1 187.4 116.0 9.6 1.7
40 332.6 91.1 34.2 15.6 316.3 88.6 21.7 7.0 299.7 86.0 15.4 3.8
15 ton 6000 0.33 60 287.0 104.1 29.6 12.0 270.8 101.6 18.6 5.3 254.2 99.0 13.1 2.9
80 241.6 117.1 24.9 8.8 225.3 114.6 15.4 3.8 208.7 112.1 10.7 2
40 361.7 86.3 37.2 18.2 343.7 84 23.6 8.1 325.4 81.7 16.7 4.4
7200 0.45 60 312.1 100.0 30.2 13.9 294.2 97.7 20.2 6.1 275.9 95.3 14.2 3.3
80 262.5 113.6 27.0 10.2 244.6 111.3 16.8 4.4 227.5 109.1 11.6 2.3

42 PKG-PRC012Q-EN
Heating Coil Performance Data

Table 33. Steam coil heating capacity


Water Temperature Drop 2 Psig Steam 5 Psig Steam
Air Flow, Air Pressure Drop, Capacity, LAT Capacity, LAT
Unit Size Cfm In H20 EAT, °F MBh °F MBh °F
40 42.8 78.0 44.8 80.4
960 0.19 60 37.3 95.0 39.2 96.8
80 32.0 111.2 33.9 113.1
40 47.4 74.2 49.6 75.8
3 ton 1200 0.27 60 41.4 91.0 43.5 92.7
80 35.5 107.7 37.6 109.4
40 51.4 70.9 53.8 72.4
1440 0.37 60 44.8 88.1 47.2 89.5
80 38.5 105.1 40.9 106.6
40 70.9 78.4 74.2 80.2
1600 0.19 60 61.8 94.8 65.1 96.6
80 53.1 111 56.3 112.9
40 78.6 74.0 82.2 75.6
5 ton 2000 0.28 60 68.6 90.9 72.1 92.5
80 58.9 107.5 62.4 109.2
40 85.2 70.7 89.2 72.2
2400 0.38 60 74.4 87.9 78.3 89.4
80 63.9 104.9 67.8 106.4
40 105.9 78.2 110.9 80.0
2400 0.19 60 92.4 94.7 97.3 96.5
80 79.3 110.9 84.1 112.8
40 117.4 73.9 122.9 75.5
7.5 ton SCRJ 3000 0.28 60 102.5 90.7 107.8 92.4
80 88.0 107.4 93.3 109.1
40 127.3 70.6 133.3 72.0
3600 0.38 60 111.1 87.8 116.9 89.3
80 95.5 104.8 101.3 106.3
40 149.6 80.3 156.6 82.1
2400 0.10 60 130.4 96.6 137.3 98.4
80 111.9 112.7 118.7 114.6
40 166.3 75.8 174 77.4
7.5 ton SCWJ 3000 0.14 60 145.1 92.6 152.6 94.3
80 124.5 109.2 132 110.9
40 180.7 72.4 189.2 73.9
3600 0.18 60 157.7 89.5 165.9 91
80 135.5 106.4 143.6 107.9
40 160.8 83.5 168.3 85.5
3200 0.09 60 140.1 99.4 147.4 101.5
80 120.1 115.1 127.4 117.2
40 179.3 78.8 187.7 80.6
10 ton 4000 0.13 60 156.3 95.2 164.5 97.0
80 134.1 111.4 142.2 113.2
40 195.5 75.3 204.6 76.9
4800 0.18 60 170.5 92.0 179.4 93.7
80 146.4 108.5 155.2 110.2

PKG-PRC012Q-EN 43
Heating Coil Performance Data

Table 33. Steam coil heating capacity (continued)


Water Temperature Drop 2 Psig Steam 5 Psig Steam
Air Flow, Air Pressure Drop, Capacity, LAT Capacity, LAT
Unit Size Cfm In H20 EAT, °F MBh °F MBh °F
40 175.8 79.6 184.0 81.5
3840 0.12 60 153.2 95.9 161.3 97.8
80 131.5 112 139.4 113.9
40 195.5 75.3 204.7 76.9
12 ton 4800 0.17 60 170.5 92.0 179.4 93.7
80 146.4 108.5 155.2 110.2
40 212.7 72.0 222.7 73.5
5760 0.24 60 185.6 89.0 195.3 90.5
80 159.4 105.9 169.0 107.4
40 220.3 79.7 230.5 81.6
4800 0.12 60 191.9 96.0 202.0 97.9
80 164.7 112.1 174.6 114
40 244.9 75.3 256.4 77.0
15 ton 6000 0.17 60 213.6 92.0 224.8 93.7
80 183.4 108.6 194.4 110.3
40 266.5 72.0 278.9 73.5
7200 0.24 60 232.5 89.1 244.7 90.6
80 199.7 105.9 211.7 107.5

44 PKG-PRC012Q-EN
Electrical Data
Electrical Data Calculations
RLA = rated load amps.
Compressor LRA = locked rotor amps.
Fan motor LRA = locked rotor amps,
N.E.C.Table 430 - 151.
FLA = Full load amps, N.E.C.Table 430 - 150
Voltage utilization range is ±10%
Minimum circuit ampacity (MCA)
= 1.25 x largest motor amps (FLA or RLA) + the sum of the remaining motor amps.
Maximum fuse size (MFS) and maximum circuit breaker size (MCB) = 2.25 x largest motor amps
(FLA or RLA) + the sum of the remaining motor amps.
Note: If the rating value determined does not equal a standard current rating of over current
protective device, use the next lower standard rating for the marked maximum rating.
Table 34. SCWJ Electrical data
Evaporator Standard Motor Evaporator Oversized Motor
Compressor Evap Fan Motor Evap Fan Motor
Min Ckt MFS/ Min Ckt MFS/
Model Tons Voltage RLA LRA QTY HP FLA Qty Ampacity MCB HP FLA Qty Ampacity MCB
SCWJ0303 208-230V/60Hz/3Ph 12.9 77.0 2.21 18.30 30 3.15 19.3 30
SCWJ0304 3 460V/60Hz/3Ph 5.7 35.0 1 0.5 1.00 1 8.10 15 1 1.42 1 8.5 15
SCWJ0305 575V/60Hz/3Ph 4.8 31.0 0.80 6.80 15 1.14 7.1 15
SCWJ0503 208-230V/60Hz/3Ph 22.9 155.0 5.00 33.6 50 5.81 34.4 50
SCWJ0504 5 460V/60Hz/3Ph 10.7 75.0 1 1 2.50 1 15.9 25 2 2.63 1 16.0 25
SCWJ0505 575V/60Hz/3Ph 8.5 54.0 1.50 12.1 20 2.10 12.7 20
SCWJ0753 208-230V/60Hz/3Ph 25.0 164.0 6.13 37.4 60 6.13 37.4 60
SCWJ0754 7.5 460V/60Hz/3Ph 12.8 100.0 1 2 2.77 1 18.8 30 2 2.77 1 18.8 30
SCWJ0755 575V/60Hz/3Ph 9.6 78.0 2.22 14.2 20 2.22 14.2 25
SCWJ1003 208-230V/60Hz/3Ph 22.9 155.0 6.30 57.8 80 13.7 65.2 80
SCWJ1004 10 460V/60Hz/3Ph 10.7 75.0 2 2 3.10 1 27.2 35 5 6.18 1 30.3 40
SCWJ1005 575V/60Hz/3Ph 8.5 54.0 2.40 21.5 30 4.94 24.1 30
SCWJ1203 208-230V/60Hz/3Ph 25.4 147.7 9.40 66.5 90 13.70 70.8 90
SCWJ1204 12 460V/60Hz/3Ph 11.8 75.0 2 3 4.60 1 31.2 40 5 6.18 1 32.7 45
SCWJ1205 575V/60Hz/3Ph 9.3 59.6 3.40 24.4 30 4.94 25.9 35
SCWJ1503 208-230V/60Hz/3Ph 27.9 164.0 9.40 1 72.2 100 13.70 76.5 100
SCWJ1504 15 460V/60Hz/3Ph 13.6 100.0 2 3 4.60 35.2 45 5 6.18 1 36.8 50
SCWJ1505 575V/60Hz/3Ph 10.9 78.0 3.40 27.9 35 4.94 29.5 35

PKG-PRC012Q-EN 45
Electrical Data

Table 35. Model SCRJ electrical data

Evaporator Standard Evaporator Oversized Evaporator 2-Speed


Motor Motor Motor
Evap. Fan
Evap. Fan Evap. Fan
MFS MFS MFS
Compressor Motor Motor Motor
Model / / /
SCWJ Tons Voltage RLA LRA Qty Hp FLA Qty MCA MCB Hp FLA Qty MCA MCB Hp FLA Qty MCA MCB
0303 208-230/60/3 10.0 71 2.21 14.7 25 3.15 15.7 25
0304 3 460/60/3 6.3 38 1 .5 1.00 1 8.9 15 1 1.42 1 9.3 15 n/a
0305 575/60/3 4.2 37 0.80 6.1 15 1.14 6.4 15
0503 208-230/60/3 17.7 110 5.00 27.1 45 5.81 28.0 45
0504 5 460/60/3 7.9 52 1 1 2.5 1 12.3 20 2 2.63 1 12.5 20 n/a
0505 575/60/3 5.7 40 1.50 8.6 15 2.10 9.2 15
0753 208-230/60/3 25.0 149 6.30 37.6 60 5.81 37.1 60
0754 7.5 460/60/3 11.8 75 1 2 3.10 1 17.8 30 2 2.63 1 17.4 30 n/a
0755 575/60/3 8.6 54 2.40 13.1 20 2.10 12.8 20
1003 208-230/60/3 17.8 110 6.30 46.3 60 13.7 53.7 70 14.9 54.9 70
1004 10 460/60/3 8.6 52 2 2 3.10 1 22.5 30 5 6.18 1 25.6 30 5 7.45 1 26.9 30
1005 575/60/3 6.4 39 2.40 16.7 20 4.94 19.2 25 5.96 20.3 25
1203 208-230/60/3 22.9 155 9.40 60.8 80 13.7 65.1 80 14.9 66.3 80
1204 12 460/60/3 10.7 75.0 2 3 4.60 1 28.7 35 5 6.18 1 30.3 40 5 7.45 1 31.6 40
1205 575/60/3 8.5 54 3.40 22.5 30 4.94 24.1 30 5.96 25.1 30
1503 208-230/60/3 27.9 164.0 9.40 72.1 100 13.70 76.4 100 14.9 77.6 100
1504 15 460/60/3 14.3 100.0 2 3 4.60 1 36.7 50 5 6.18 1 38.3 50 5 7.45 1 39.6 50
1505 575/60/3 10.7 78.0 3.40 27.5 35 4.94 29.0 40 5.96 30.1 40
Notes:
1- Voltage Range:
Nominal Voltage: 208-230v - Acceptable Range: 187 - 253v
Nominal Voltage: 460v - Acceptable Range: 414 - 506v
Nominal Voltage: 575v - Acceptable Range: 518 - 633v
2- Ampacity is calculated per Ul formula: ampacity = (1.25 X compressor RLA) + sum of second compressor RLA (if used)
+ evaporator motor FLA
3- Maximum Fuse Size Is Calculated Per Ul Formula: Mfs = (2.25 X Compressor Rla) + The Sum Of The Second Compressor
Rla (If Used) + Evaporator Motor Fla.

Table 36. CTA condenser electrical data


CTA CTA CTA CTA CTA CTA CTA CTA CTA
Model 090D1 090D2 090D8 120D1 120D2 120D8 180E1 180E2 180E8
Unit Operating Voltage Range 187-254 414-506 518-632 187-254 414-506 518-632 187-254 414-506 518-632
Minimum Circuit Ampacity 6.6 6.6 6.6 9.3 9.3 9.3 11.3 5.6 4.5
Max. Fuse Size Or Max. Circuit
15 15 15 15 15 15 15 15 15
Breaker
Condenser Fan Motor
Qty. 1 1 1 1 1 1 2 2 2
Volts 208-230 208-230 208-230 208-230 208-230 208-230 208-230 460 575
Phase 1 1 1 1 1 1 1 1 1
Amps - FLA (ea.) 4.4-5.3 4.4-5.3 4.4-5.3 7.0-7.4 7.0-7.4 7.0-7.4 5 2.5 2
Amps - LRA (ea.) 0 0 0 0 0 0 14.4 5.8 5.1

46 PKG-PRC012Q-EN
Dimensions and Weights
Figure 3. 3 & 5-tons SCWJ/SCRJ

VERTICAL DISCHARGE

HORIZONTAL DISCHARGE
(FIELD CONVERTED)

From Factory Configured


for Front Return

FIELD REAR
RETURN OPENING

“ NPT

SCWH SCRJ

Note: See Table 2, p. 9 for SCRJ discharge and liquid line sizes.

Table 37. SCWJ/SCRJ dimensions & weight, in-lbs (mm-kg)

Unit Shipping Operating


Size A B C D E F G J K L M N O P Q R S Weight Weight
31.89 64.17 22.24 5.65 11.93 14.31 10.63 18.00 7.80 7.80 15.60 15.63 20.20 6.28 4.33 8.58 4.37 494 459
3
(810) (1630) (565) (3645) (303) (363.5) (270) (457) (198) (198) (396) (397) (513) (159.5) (110) (218) (111) (224.3) (208.4)
36.41 75.98 24.01 7.73 13.03 15.65 11.61 20.31 12.32 8.66 20.98 18.58 24.20 7.10 5.43 6.38 7.12 592 555
5
(925) (1930) (610) (4991) (331) (397.5) (295) (516) (313) (220) (533) (472) (615) (180) (138) (162) (181) (268.8) (252)

Table 38. Power entry hole diameter H (in)

Unit Voltage
Unit Size 208-230V 460V 575V
3 Ton 7/8 7/8 7/8
5 Ton 1 3/8 7/8 7/8

PKG-PRC012Q-EN 47
Dimensions and Weights

Figure 4. 7.5-tons SCWJ/SCRJ

Note: See Table 2, p. 9 for SCRJ discharge and liquid line sizes.

Table 39. SCWJ/SCRJ 7.5 ton dimensions and weights, in-lbs (mm-kg)

Unit Shipping Operating


Size A B C D Weight Weight
40.94 11.93 7.00 5.04 702 657
7.5 - SCRJ
(1040) (303) (178) (128) (318.7) (298.3)
57.68 11.93 7.00 13.41 804 759
7.5 - SCWJ
(1465) (303) (178) (341) (364.6) (344.2)

Table 40. Power entry hole diameter H (in)

Unit Voltage
Unit Size 208-230V 460V 575V
7.5 Ton 1 3/8 7/8 7/8

48 PKG-PRC012Q-EN
Dimensions and Weights

Figure 5. 10, 12 & 15-tons SCWJ/SCRJ

See Table 2, p. 9 for SCRJ discharge and liquid line sizes.

Table 41. SCWJ/SCRJ dimensions & weight, in-lbs. (mm-kg)

Unit Shipping Operating


Tons A B C D E F G J K M Weight Weight
65.75 88.78 7.04 18.07 57.28 19.01 25.0 5.23 7.48 8.30 984 917
10
(1670) (2255) (179) (459) (1455) (483) (637) (133) (190) (211) (446.7) (416.3)
65.75 92.71 7.04 18.07 61.22 22.95 29.01 5.23 7.48 12.24 977 907
12
(1670) (2255) (179) (459) (1555) (583) (737) (133) (190) (311) (443.6) (411.8)
80.31 92.71 19.83 19.83 61.22 22.95 29.01 5.23 7.48 12.24 1098 1021
15
(2040) (2355) (504) (504) (1555) (583) (737) (133) (190) (311) (498.5) (463.5)

Table 42. Power entry hole diameter H (in)

Unit Voltage
Unit Size 208-230V 460V 575V
10 Ton 13/8 7/8 7/8
12 Ton 1 5/8 1 3/8 7/8
15 Ton 1 5/8 1 3/8 7/8

PKG-PRC012Q-EN 49
Dimensions and Weights

Figure 6. Model CTA090 Air-Cooled Condenser


SEE NOTE 3

NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4
HAIL GUARD
(OPTIONAL)

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE) SEE NOTE 1

35 15/16"
HAIL GUARD (912.8) REFRIGERANT ACCESS
(OPTIONAL) LINE VOLTAGE WITH HAIL GUARD
1 3/8” dia. 33 7/8"
(860.4)
CONTROL WIRING

SERVICE PANEL 39 3/16"


(995.3)
34 1/8" (866.8) 26 15/16"
29 13/16" (684.2)
(757.2) 14 3/8"
16 7/16"
(417.5) (365.1)

1/16"
7 15/16" (1.59) 6" (152.4) 2 7/8"
(201.6) 6" (152.4) (73)
DISCHARGE LINE 1 7/8"
7/8” 21 11/16"
(550.9) (47.6) 40 15/16"
LIQUID LINE (1039.8)
1/2” 33 13/16" 41 15/16"
(858.8) (1065.2)
WITH HAIL GUARD
SERVICE PANEL SIDE

3" (76.2) 7/16" (11.11) DIA. ISOLATOR MOUNTING


HOLES (OUTSIDE HOLES - 4 PLACES)

40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT

4 3/16"
(106.36)
1 13/16" 27 11/16" 2 5/16"
(46) (703.3) (58.7)

Table 43. CTA090 unit weight, lbs

Model Shipping Weight Operating Weight


CTA090*1 230 165
CTA090*2 261 195
CTA090*8 261 195

50 PKG-PRC012Q-EN
Dimensions and Weights

Figure 7. Model CTA120 Air-Cooled Condenser


SEE NOTE 3

NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
SERVICE PANEL WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
HAIL GUARD
SEE NOTE 4 (OPTIONAL)

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE
SEE NOTE 1
39 15/16"
(1014.4) REFRIGERANT ACCESS
HAIL GUARD 4 1/4" WITH HAIL GUARD
(OPTIONAL) (108)
1 1/4" 37 15/16"
(31.7) LINE VOLTAGE
1 3/8” dia (963.6)
CONTROL WIRING

39 1/8"
SERVICE PANEL (993.8)
34 1/16" (865.2)
29 3/4" 26 7/8"
(755.6) (682.6)
14 5/16"
7 1/2" 8 1/4" (363.5)
(190.5) (209.5)
1/16"
DISCHARGE LINE (1.6) 1 7/8"
7/8” 1 15/16" (49.2) 6" 25 11/16" 6" (47.6)
LIQUID LINE (152.4) (652.5) (152.4) 2 7/8" (73)
1/2” 4 15/16" 50 15/16"
(125.4) 37 11/16" (1294)
(957.3)
51 15/16"
(1319.2)
WITH HAIL GUARD

SERVICE PANEL SIDE

7/16" (11.1) DIA. ISOLATOR MOUNTING


3" (76.2)
HOLES (OUTSIDE HOLES - 4 PLACES)

50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)

3 13/16"
(96.8)

2 3/16" 31 11/16" 1 11/16"


(55.6) (804.9) (42.9)

Table 44. CTA120 unit weight, lbs

Model Shipping Weight Operating Weight


CTA120*100 276 205
CTA120*200 306 235
CTA120*800 306 235

PKG-PRC012Q-EN 51
Dimensions and Weights

Figure 8. Model CTA180 Air-Cooled Condenser - use with 12 and 15-ton

SEE NOTE 2 NOTES:


1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

HAIL GUARD
(OPTIONAL)
SEE NOTE 3

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 1
FOR CLEARANCE)

SERVICE PANEL
DETAIL A 46"
95 7/16" (1168.4)
(2424) WITH HAIL GUARD
WITH HAIL GUARD
41 7/16" 44"
(1052.5) (1117.6)

HAIL GUARD
(OPTIONAL) HAIL GUARD
(OPTIONAL)

45 1/8"
(1146.2)

3 3/8" 1/16"
(85.7) 3/16"
SERVICE (1.6)
6 5/8" (4.8)
PANEL
(168.3) 41 3/8"
(1051) 9" 25 11/16" 9"
(228.6) (652.5) (228.6)
93 5/16"
(2370.1)
9 1/4" (235)

6 13/16" (173)
7/16" (11.1) DIA. ISOLATOR MOUNTING 1 3/16" (30.2)
CONTROL
HOLES (OUTSIDE HOLES - 4 PLACES) LINE VOLTAGE WIRING
1 1/4” dia
SERVICE PANEL SIDE
DISCHARGE LINE

REFRIGERANT ACCESS
41 5/8"
39 7/8" (1057.3)
(1012.8)
18 3/4"
BOTTOM OF UNIT
41 1/2" (476.2) 14 5/8"
36 7/8" (1054) (371.5)
(936.6)
12 9/16"
(319.1) LIQUID LINES
5 9/16" 5/8”
4 3/8"
(141.3)
(111.1)
3" (76.2) 2 3/16" 6 13/16" DISCHARGE LINE 6 5/16" (160.3)
87" (55.6) (173) 7/8”
(2210) 3 11/16" (93.7)
93" 15/16" (23.8)
(2362.2)
FRONT DETAIL A
DIMENSIONAL DETAIL

Table 45. CTA180 unit weight, lbs.


Shipping Operating
Weight Weight
551 431

52 PKG-PRC012Q-EN
Dimensions and Weights

Figure 9. Plenum

Table 46. Plenum dimensions & weight, in-lbs (mm-kg)


Unit Size A B Weight
3-ton 31.89 (810) 22.24 (565) 44 (20)
5-ton 36.41 (925) 24.01 (610) 54 (24.5)
7.5-ton (SCRJ) 40.94 (1040) 28.74 (730) 73 (33.1)
7.5-ton (SCWJ) 57.68 (1465) 28.74 (730) 103 (46.6)
10 & 12-ton 65.75 (1670) 29.52 (750) 120 (54.5)
15-ton 80.31 (2040) 29.52 (750) 146 (66.3)

Figure 10. Hot water coil 3 & 5-ton units (coils are field installed)

0.59 (15)
A
3.15 (80)
5.91 (150) B 1.57
(40)
(35)
1.38

2.18
(55)
D

(213)
8.39
G F

0.28
(6.4)
E
2.18
(55)
(35)
1.38

0.59

0.39 0.39
(15)

C
(9.9) (9.9)
1.03 1.03 (26)
(26)
1.08 (27)

1.0 NPT 0.75 (19)


0.75 (19)
(25.4)
5.9
(150)

Table 47. SCWJ/SCRJ Hot water coil dimensions & weights, 3 & 5-ton units, in-lbs (mm-kg)
Size A B C D E F G Weight
3-ton 26.46 (672) 18.98 (482) 25.67 (652) 5.79 (147) 5.79 (147) 10.00 (254) 12.76 (324) 13 (5.9)
5-ton 30.98 (787) 23.50 (597) 30.20 (767) 7.040 (179) 7.040 (179) 12.50 (318) 15.26 (388) 18 (8.2)

PKG-PRC012Q-EN 53
Dimensions and Weights

Figure 11. Hot water coil 7.5-ton units (coils are field installed)

Table 48. SCWJ/SCRJ Hot water coil dimensions & weights, in-lbs. (mm-kg)
Unit Size A B C D E F G Weight
7.5-ton SCRJ 35.5 (902) 28.0 (712) 34.7 (882) 8.5 (215) 8.5 (215) 17 (432) 20.7 (526) 24 (10.9)
7.5-ton SCWJ 52.2 (1327) 44.8 (1137) 51.1 (1299) 8.5 (215) 8.5 (215) 17 (432) 20.7 (526) 30 (13.6)

54 PKG-PRC012Q-EN
Dimensions and Weights

Figure 12. Hot water coil 10 thru 15-ton units (coils are field installed)
1.03 (26)
0.39 (9.9) A 0.39 1.08 (27)
(9.9) 1.03
1.38 (35)

1.38 (35)

2.18 (55)
(26)

0.59
(15)
(242)
9.54

15.89 (404)
17.50 (445)
20.26 (515)

0.28
(7.1)

2.18 (55)
(242)
9.54
8.27 (210)

(230)
9.07
0.59

(190)
1.38
(35)

7.48
0.43 C B 1.57 (40)
(10.9) 3.19
D (81)
BLOCKOFF (SHIPS DISASSEMBLED)

1.00 NPT
(25.4) 0.75 (19.1) 0.75 (19.1)
5.90
(150)

Table 49. SCWJ/SCRJ Hot water coil dimensions & weights, in-lbs. (mm-kg)
Unit Size A B C D Weight
10 & 12-ton 58.72 (1491) 50.98 (1295) 6.95 (177) 59.51 (1512) 49 (22.2)
15-ton 73.29 (1862) 63.98 (1625) 8.52 (216) 74.07 (1881) 55 (25)

PKG-PRC012Q-EN 55
Dimensions and Weights

Figure 13. Steam coil: 10, 12, & 15-ton units (all coils are field installed)
3.15”

C
MPT INLET
B

D
MPT OUTLET
6.89”

Figure 14. Steam coil (all coils are field installed)

3.15”

C
MPT INLET

D
MPT OUTLET

Table 50. Steam coil dimensions & weight, in-lbs (mm-kg)

Unit Size (tons) A B C D Weight


3 26.5 (672) 12.75 (324) 1.5 1 42 (19)
5 31.0 (787) 15.26 (388) 1.5 1 56 (25)
7.5-SCRJ 35.5 (902) 20.70 (526) 1.5 1 68 (31)
7.5-SCWJ 52.5 (1334) 20.70 (526) 1.5 1 100 (45)
10 59.5 (1512) 20.3 (515) 1.5 1 137 (62)
12 59.5 (1512) 20.3 (515) 1.5 1 161 (73)
15 74.1 (1882) 20.3 (515) 2 1.5 161 (73)

56 PKG-PRC012Q-EN
Dimensions and Weights

Figure 15. Service clearance recommendations (top-mounted fan configuration)

Figure 16. Service clearance recommendations (side-mounted fan configuration, field converted on sizes 10, 12, & 15)
RIGHT SIDE

24"

TXV ACCESS
(RIGHT SIDE)
UNIT-MOUNTEDT-STAT
OPENING (BOTH SIDES)

POWER ENTR
(BOTH SIDES)
CONTROL ENTR
FRONT RETURN FAN ACCESS
24" (BOTH SIDES)

18" SERVICE CLEARANCE


REAR
26" SERVICE CLEARANCE MOTOR/DRIVE ACCESS
CONTROL BOX & LEFT SIDE (RIGHT SIDE)
CONDENSER FAN ACCESS
REAR RETURN

26" SERVICE CLEARANCE


RIGHT SIDE
DRAIN CONNECTION
(BOTH SIDES)
AIR FILTER ACCESS
(BOTH SIDES) 42" SERVICE CLEARANCE FRONT

SIGHT GLASS/FILTER DRIER ACCESS COMPRESSOR ACCESS


(RIGHT SIDE) 26" SERVICE CLEARANCE
LEFT SIDE

PKG-PRC012Q-EN 57
Mechanical Specifications
Midrange Self-Contained Models SCWJ/SCRJ
General
The units shall be completely factory assembled, tested, piped, internally wired, and fully charged
with R410A (water-cooled only). Remote air-cooled units shall be charged in field, after refrigerant
interconnecting lines are brazed and the system vacuum pumped.Units are in compliance with
ASHRAE 90.1 equipment efficiency requirements. All units shall go through a factory run test
before shipment. All equipment shall have factory-installed decals and labels to aid in servicing and
indicate caution areas.

Cabinet
The cabinet shall be constructed with galvanized steel with aluminum frame. All exterior panels
shall be 1” double wall foamed panels with allen head fasteners for easy removal and access. All
panels shall be painted with anticorrosive primer and high resistance synthetic enamel.The unit
shall be construct for vertical discharge with front return on 3, 5, and 7.5-ton units or rear return
on 10, 12, and 15-ton units. Air discharge and return is field convertible to different configurations.

Return Air Grill


A decorative return air grill shall be provided and shall be anodized aluminum with vertical blades
on 3, 5, and 7.5-ton units.

Evaporator Coil
The evaporator coil shall be constructed with 3/8”OD, internally enhanced copper tubes, which are
mechanically bonded to aluminum fins. Coils shall be factory leak tested to 600 psig.The drain pan
shall be constructed of stainless steel and positively sloped.

Water Cooled Condenser


The condenser is a tube and tube design, with a finned cooper inner tube and a steel outer tube.
Piping connections are from either side of the unit. Each refrigerant circuit is provided with a
separate condenser. Condenser waterside working pressure cannot exceed 400 psig.

Supply Fan
The evaporator fan shall be statically and dynamically balanced, forward curve centrifugal fans,
and galvanized steel construction.The fans shall be provided with permanently lubricated bearings
with a design life (L10) of at least 200,000 hours. Motors shall be open drip proof type. Drive
assemblies shall consist of V-belts and variable pitch drive sheaves.

Filters
Units shall come standard with one-inch, fiberglass, throwaway filters.The filter rack can
accommodate a one or two-inch filter.

Compressors
The compressors shall all be scroll compressors each with their own independent circuit.
Compressors shall be mounted on rubber isolators for vibration isolation.The 3, 5, and 7.5-ton units
shall have a single compressor.The 10, 12, and 15-ton units shall have dual compressors.
Crankcase heaters shall be provided on remote air-cooled units.

Refrigeration Circuit
Refrigeration circuits shall be independent and completely piped including: filter driers, sight glass,
distributors, thermal expansion valves, and Schrader access valve in the suction / liquid lines. Each
circuit shall be equipped with high and low-pressure switches.The high-pressure switch shall be
rated at 450±10 psig open / 348±14.5 psig close (water cooled, except 12 ton) and 624±17.5 psig open
/ 464±29 psig close (remote air-cooled and 12-ton water-cooled).The low-pressure switch shall be
rated at 51±7 psig open / 94±7 psig close. Each circuit shall be leak tested, dehydrated and charged

58 PKG-PRC012Q-EN
Mechanical Specifications

with oil (water-cooled and remote air-cooled) and R410A (water-cooled only, remote air-cooled shall
be charged in field).

Electrical /Controls
Each unit shall have single point power connections with a terminal block.The unit shall come
standard with a control interface that will include terminal strip and 24V transformer.

Agency Listing
The unit has ETL-CETL agency listing.

Evaporator Coil with Corrosion Resistant Treatment and Silver Solder Braze
Joints (SCRJ)
The evaporator coil shall have a phenolic coating applied for protection in harsh environments.
Silver solder braze joints are provided on unit coil and refrigeration piping.

Cupro-Nickel Condenser, Evaporator Coil with Corrosion Resistant Treatment,


and Silver Solder Braze Joints (SCWJ)
The condenser is a tube and tube design, with a finned 90-10 cupro-nickel inner tube and a steel
outer tube. Piping connections are from either side of the unit. Each refrigerant circuit is provided
with a separate condenser. Condenser waterside working pressure cannot exceed 400 psig.
Evaporator coil shall have a phenolic coating applied for protection in harsh environments. Silver
solder braze joints are provided on unit coil and refrigerant piping.

PKG-PRC012Q-EN 59
Mechanical Specifications

Field-Installed Accessories
Remote-Mounted Thermostat
A 1H/1C remote-mounted thermostat shall be provided with 3, 5, and 7.5-ton units. A 2H/2C or 2C
remote-mounted thermostat shall be provided with 10, 12, and 15-ton units. All thermostats are
available with auto, manual, or auto/manual bases.

Unit-Mounted Thermostat
A 1C unit-mounted thermostat shall be provided with 3, 5, and 7.5-ton units. A 2C unit mounted
thermostat shall be provided with 10, 12, and 15-ton units.

Remote Programmable Thermostat


A 1C remote programmable thermostat shall be provided with 3, 5, and 7.5-ton units. A 2H/2C
remote programmable thermostat shall be provided with 10 and 15-ton units.

Hot Water Coil


The hot water coil shall be designed for use with 180 to 200°F water entering, constructed with
½”OD tube, which are mechanically bonded to aluminum fins.The hot water coil shall be a field-
installed item.The coil shall be mountable to the unit with right or left hand connections.

Steam Coil
The steam coil shall be designed for use with two (2) to five (5) psig steam.The steam coil shall
be a field-installed item.The coil shall be mounted to the unit with right or left hand connections.

Discharge Plenum
The discharge plenum shall provided with double deflection louvers to provide horizontal
discharge.The plenum shall be constructed of sheet metal with 2" fiberglass insulation to provide
a low sound operation.

Return Air Grill


A decorative aluminum return air grill shall be provided for field installation on 10, 12, and 15-ton
units.

Oversized/2-Speed Motor Kit


Oversized/2-speed motor kit and drives shall be provided for those applications where external
static pressure exceeds the capability of the standard fan motor.The 2-speed motor reduces energy
consumption of the equipment when the system is at part load conditions. Approximate turn down
ratio on the 2-speed motor is 66% rated. Oversized/2-speed motors shall be totally-enclosed fan-
cooled (TEFC) type.
Note: The 2-speed motor kit is available only on 10, 12 and 15 ton units.

Low Static Drive Kit


Low static drive kit shall be provided for those applications where low static pressure is required.

Side Mounted Fan Kit


Side mounted fan kit shall be provided for those applications where the fan section must be field
converted to side position due room height limitation.This kit includes brackets, stiffeners,
fasteners, and gaskets.

Water Regulating Valve


A water regulating valve shall be provided for each to control condensing pressure, including a
capillary tube adapter fitting to connect the liquid line Schrader valve.

60 PKG-PRC012Q-EN
Mechanical Specifications

Time Delay Relay


A time delay relay shall provide a delay prior to starting the second compressor on 10, 12, and 15-
ton units to prevent power demand surges.

Anti-Recycle Timer
An anti-recycle timer shall be provided to protect the compressor from excessive cycling.
Compressor will lock out for a determined period of time when either the thermostatic contacts
open or there is a momentary power outage.

PKG-PRC012Q-EN 61
Mechanical Specifications

Remote Air-Cooled Condenser, Model CTA


General
Unit will be assembled on heavy gauge steel mounting/lifting rails and will be weather proofed.
Unit includes a plate fin condenser coil, fan and motor, controls and holding charge of nitrogen.
Operating range is between125°F and 45°F in cooling as standard from the factory. Unit is ETL listed
and rated in accordance with AHRI standards 210/240 or 340/360.

Unit Casing
Unit casing is constructed of zinc coated heavy gage, galvanized steel. Exterior surfaces are
cleaned, phosphatized and finished with a weather-resistant baked enamel finish. Unit surface is
tested 672 hours in salt spray test. Unit has removable end panels to allow access to all major
components and controls.

Condenser Coil
Coils are microchannel as standard. Also, coils are factory pressure and leak tested to 450 psig.

Complete Coat™ Microchannel Condenser Coil


The cathodic epoxy type electrodisposition coating is formulated for high edge build to a
number of different types of heat exchangers.The coating is selected to provide excellent
resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater,
salty air, and other corrosive environments.This coating shall be available on microchannel
condenser coils.

Refrigeration System
Unit will have a single or dual refrigeration circuit(s). Each refrigeration circuit has an integral
subcooling circuit.

Condenser Fan and Motor


Direct drive, statically and dynamically balanced propeller fan(s) with aluminum blade will be used
in draw-through vertical discharge position. Permanently lubricated construction motor(s) will be
provided and will have built in current and thermal overload protection. Motor will be either ball
or sleave bearing type.

Controls
Condensers will be completely factory wired with necessary controls. Control wiring will be for a
24-volt control circuit.

Low Ambient Head Pressure Control Kit


The low ambient kit is a field-installed option for head pressure control. and shall allow down to
0°F (-17.78°C) by utilizing additional fan cycling or speed modulation for head pressure control.The
low ambient kit includes all necessary mounting hardware and instructions; such as the control
module assembly, a liquid temperature sensor assembly, an ambient temperature sensor
assembly, a low voltage pigtail assembly, and all necessary mounting hardware.

Hail Guards
Provides condenser protection from hail, vandals, etc. Hail guards are made from perforated,
galvanized steel. Hail guards can be factory or field installed.

62 PKG-PRC012Q-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2014Trane All rights reserved


PKG-PRC012Q-EN 29 Jan 2014 We are committed to using environmentally
Supersedes PKG-PRC012P-EN (06 Nov 2013) conscious print practices that reduce waste.