Protection Maintenance Test Report
Omexom Doc. #: AUT-F-07 Rev.1
A. Relay Data
Date 1/24/2021 Substation HVDC Pole 3 DIA/Bay C36C2+EFA
B. Pre-Requisites
Equipment & Resources: Status
Competent personnel available for the test. OK
All competent persons are EHS certified to work in electrical environment. OK
AC & DC supply availability and security. OK
Test equipment calibrated and suitable for the test. OK
Safety:
Full understanding & electrical risk prevention instruction. OK
PPE safety available. OK
Awareness of electrical hazards precautions. OK
Isolation & Coordination:
Secondary Isolation of Tripping & Inter-tripping. OK
Primary Equipment isolation of Concerned equipment. OK
Coordination With Other Parties (GIS, Transformer, Etc.) OK
2. Visual Inspection
Description Assessment
Relay Visual Inspection: OK
Clock set to GMT time: OK
Communication with PC & DCS: OK
Relay is synchronized by substation GPS: OK
3. CT/VT Data
Phase CT1 (A): 500 / 1 Main VT1 (V): 400000 / 110 LL
Signature: Signature:
GCCIA - Protection Maintenance Test Report
IB CT1 500 A 500.400 A OK
IN CT1 500 A 500.400 A OK
Functionalities Checks
Description Assessment
86 Lockout Relay Trip OK
Final Checks
Description Assessment
Events records extracted and checked NOK
Fault Records Checked NOK
Disturbances records extracted and checked NOK
All Test equipment, leads, shorts and test blocks removed OK
Alarms rest LEDS reset OK
Trip and Lockout Relays reset OK
Disturbed customer wiring re-checked and normalized OK
CT /VT wiring tightness at terminal block checked OK
All relay setting re-checked and normalized OK
IR CT1 NA A OK
IY CT1 NA A OK
IB CT1 0.000 A OK
IN CT1 0.000 A OK
Remarks:
Signature: Signature:
OMICRON AUTOMATIC TESTS
REPORT
GCCIA_HVDC_C36C2_P120_F87F-
B_2021_0
Macro-Enabled
Worksheet
Hardware Configuration
Test Equipment
Type Serial Number
CMC356 GK705N
Hardware Check
Performed At Result Details
OCR_Initial conditions
Instruction Text:
- VR-VY-VB wired
GCCIA_HVDC_C36C2_P120_F87F-
B_2021_0
User Input:
OCR_V.rp:
Test Settings
General
No. of ramp states: 1
Total steps per test: 180
Total time per test: 18.000
No. of test executions: 1
Ramp States
Ramp Ramp 1
U L1-E 41.25 V
0.00 °
60.000 Hz
U L2-E 41.25 V
-120.00 °
60.000 Hz
U L3-E 41.25 V
120.00 °
60.000 Hz
Force abs. Phases Yes
Sig 1 From 41.25 V
Sig 1 To 59.13 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. Out 2 0
Bin. Out 3 0
Bin. Out 4 0
dt per Step 100.0 ms
Ramp Steps 180
Ramp Time 18.000s
Trigger Bin
GCCIA_HVDC_C36C2_P120_F87F-
B_2021_0
Trigger Logic OR
Trip 1
Step back No
Delay Time 0.000 s
Test Module
Name: OMICRON Ramping Version: 4.20
Test Start: 24-Jan-2021 11:17:21 Test End: 24-Jan-2021 11:17:38
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
OCR_V Ramp 1 Trip 0->1 U L1-E, 55.00 V 55.25 V 1.100 V 1.100 V 250.0 mV + 17.70 ms
L2-E,
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
OCR_tV.sq:
Test Settings
State State 1 State 2
60.000 Hz 60.000 Hz
60.000 Hz 60.000 Hz
60.000 Hz 60.000 Hz
Test Module
Name: OMICRON State Sequencer Version: 4.20
Test Start: 24-Jan-2021 11:17:50 Test End: 24-Jan-2021 11:17:53
User Name: Manager:
Company:
Test Results
GCCIA_HVDC_C36C2_P120_F87F-
B_2021_0
Time Assessment
Ignore
Name before Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
Test State:
Test passed