Ferro/Rebar Scanning Report of Barishal Airport.
Ferro/Rebar Scanning Report of Barishal Airport.
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Dear Sir,
We are enclosing the NDT reports for the scanning work that has been performed at your site. The scans have been done using
HILTI PS250. Details are mentioned below:
PS250 Scans:
1. Please note that the dimensions per scan is maximum 600mm X 600mm (1 scan)
2. The scan will give an estimate of the following parameters:
Rebar Layout
Rebar Diameter
Rebar Spacing &
Others
3. The Scan surface should be as smooth as possible for optimal results.
4. There should not be any ferrous material/pipes nearby at a distance of at least 30mm which can cause a deviation in the magnetic waves.
5. Results are mentioned, however scans were not clear for accurate estimation of diameter
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Project Name: Barishal Airport.
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
LETTER OF DECLARATION
We do hereby declare that this report is prepared based on the scanning data from different location in the structure
as suggested by the engineer/consultant using Hilti PS 200 under the guidance and supervision of us. We will be
responsible for rationality and verification of any data presented in this report based on scanning only. While scanning
and analyzing, civil engineering knowledge and judgment was applied where necessary.
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Image of Used Apparatus
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: N/A (06-20Ømm)
Location: Ground Floor Stirrup: Ø10 mm @ 12.01” C/C
Ferro scanning no: 01 Remarks: Image not clear due to extra
covering & wet surface.
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: N/A (06-20Ømm)
Location: Ground Floor Stirrup: Ø10 mm @ 10.56” C/C
Ferro scanning no: 02
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: N/A (03-20Ømm)
Location: Ground Floor Stirrup: Ø10 mm @ 10.84” C/C
Ferro scanning no: 03 Remarks: Visible Phase
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: Corner Column (08-20Ømm)
Location: Ground Floor Stirrup: Ø10 mm @ 6.15” C/C
Ferro scanning no.- 04
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: N/A (02-20Ømm)
Location: Ground Floor Stirrup: Ø10 mm @ 10.0” C/C
Ferro scanning no: 05 Remarks: Visible Phase
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: C/A (08-20Ømm)
Location: 1st Floor Stirrup: Ø10 mm @ 8.04” C/C
Ferro scanning no: 06
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Column Main Reinforcement:
Member Type: N/A (08-20Ømm)
Location: 1st Floor Stirrup: Ø10 mm @ 7.15” C/C
Ferro scanning no: 07 Remarks: Image not clear due to extra covering
& uneven surface.
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Beam Main Reinforcement:
Member Type: Floor Beam Side: 02-20Ømm
Location: 1st Floor Bottom: 03-20Ømm
Ferro scanning no: 08 Stirrup: Ø10 mm @ 9.25” C/C
Side Bottom
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Beam (Side) Main Reinforcement:
Member Type: Stair Case Beam Side: 03-20Ømm
Location: 1st Floor Stirrup: Ø10 mm @ 6.89” C/C
Ferro scanning no: 09 & 10 Remarks: 28” beam side in two scan
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Slab Main Reinforcement:
Member Type: Slab Bottom X direction: Ø10 mm @ 6.45” C/C (Average)
Location: 1st Floor Y direction: Ø10 mm @ 7.59” C/C (Average)
Ferro scanning no: 11
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Member Details: Finding & Remarks:
Member: Slab Main Reinforcement:
Member Type: Slab Bottom X direction: Ø10 mm @ 6.64” C/C (Average)
Location: 1st Floor Y direction: Ø10 mm @ 7.15” C/C (Average)
Ferro scanning no: 12
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022
Working Image
This report is prepared based on images can and quick scan only.
Date of reporting: November 2022