Setting Micom P122 Pelanggan
Setting Micom P122 Pelanggan
Tegangan 20
Ib 288.675135
CT 300
5
Password
gangguan
phasa2
jaraknya
note jauh OCR Trip tI> Yes AAAA
gangguan
yang
jaraknya OCR
dekat Moment
dengan
GI karena
arus
gangguan
besar Trip tI>> Yes Description
P122-1
Trip tI>>> No
Reference
GFR Trip tIe> Yes ALST
Primer
Sekunder
CONFIGURATION
Led Led
tIe> No tIe> Yes
Led Led
Ie>> No Ie>> No
Led Led
tIe>> No tIe>> No
Led Led
Ie>>> No Ie>>> No
Led Led
tIe>>> No tIe>>> No
Led Led
I>>> No I>>> No
Led Led
tI>>> No tI>>> No
Led Led
Ie> No Ie> No
Led Led
tIe> No tIe> No
Led Led
Ie>> No Ie>> No
Led Led
tIe>> Yes tIe>> No
Led Led
Ie>>> No Ie>>> No
Led Led
tIe>>> No tIe>>> No
Phase B Text
S
Phase C Text
T
E/Gnd Text
N
MEASURMENTS COMMUNICATION PROTECTION G1
IN Idmt Idmt
0.00 A IEC SI IEC SI
I1 TMS TMS
0.00 A 0.05 0.05
I2 tReset tReset
0.00 A 40 ms 40
tI>> 0 ms tIe>> 0
tReset tReset
40 ms 40
I>>>? Ie>>>?
No No
[46] Neg Seq OC [49] Therm OL [37] Under Current
Unbalance Overload ID Pel
Nama
1.5 Iset
2 Iset
3 Iset
ms 4 Iset
GROUND FAULT
ms MENURUT RU
Pengujian
1.5 Iset
2 Iset
3 Iset
4 Iset
PENGUJIAN RELAY
I > OCR 1.73 Io > GFR 0.31
49 RMS SETTING OVER LOAD
Curve IEC SI Curve IEC SI Iɵ 0.96 In
Te 13 mn
KVA K 1.05
I >> OCR M 6.93 Io >> GFR M 1.23 ɵ Trip 100 %
Curve DMT Curve DMT ɵ Alarm 84 %
0 5 Delay 0 Delay 0
A Merk Relay MICOM P122
KVA Type
A SN
KSAAN WAKTU KERJA RELAY OVERLOAD HASIL PENGUJIAN
Kriteria Waktu Arus di Relay Arus Injek Arus Uji waktu trip
TDL 2003 (A) (Ampere) (Ampere) (detik)
> 3600 1.05 xI set 303.11 5.05
< 1200 1.2 xI set 346.41 5.77
< 600 1.5 xI set 433.01 7.22
di koordinasikan 4 xI set 1154.70 19.25
KSAAN WAKTU KERJA RELAY OCR/GFR
(.......................................................)