Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Configuration - Customer Load

Component And Virtual Name: PQZIP 06-05-2023 11:38:11


Feeder Name: Feeder 1
Network Topology: WYE
Network Nominal: 220kV (LL)
Device Type: PQZIP Based Investigation
Current Short Circuit: 25kA
IL: 557.208A
Report information
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00
GMT: +05:30 Report Version: 1.0.0.22
Summary

Compliance Result
Harmonic Voltage Full Time Range Pass
Total Harmonic Distortion Full Time Range Pass
Harmonic Voltage Daily Pass
Total Harmonic Distortion Daily Pass
Harmonic Current Full Time Range Pass
TDD Full Time Range Pass
Harmonic Current Daily Pass
TDD Daily Pass
Flicker Severity Pass
I T Product Category 1

Event type Number of events Result [% within the limits]


Notches 0 Pass
Interruption 0 Pass
Supply Voltage Dip 0 Pass
Supply Voltage Swell 0 Pass

Page 1 of 18 IEEE519_2022 Report


Harmonic Voltage Full Time Range
At the PCC, during each period of one week, 95% of the 10 min (short time) mean r.m.s. values of each individual harmonic voltage shall be
less than or equal to the regulation max values shown in the table below (values are given as percentage of the fundamental harmonic).
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation
Harmonic V1N V2N V3N V1N V2N V3N
Limit[%] max [%]
2 95 1 0.02 0.02 0.02 Pass (100%) Pass (100%) Pass (100%)
3 95 1 0.41 0.89 0.44 Pass (100%) Pass (99.9%) Pass (100%)
4 95 1 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
5 95 1 0.75 0.8 0.58 Pass (100%) Pass (100%) Pass (100%)
6 95 1 0.01 0.01 0 Pass (100%) Pass (100%) Pass (100%)
7 95 1 0.65 0.55 0.45 Pass (100%) Pass (100%) Pass (100%)
8 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
9 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
10 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
11 95 1 0.21 0.2 0.2 Pass (100%) Pass (100%) Pass (100%)
12 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
13 95 1 0.13 0.14 0.06 Pass (100%) Pass (100%) Pass (100%)
14 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
15 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
17 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
18 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
19 95 1 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
20 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
23 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
24 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
25 95 1 0.01 0 0 Pass (100%) Pass (100%) Pass (100%)
26 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
27 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
28 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
29 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
30 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
31 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
32 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
33 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
34 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
35 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
36 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
37 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
38 95 1 0.01 0.03 0.02 Pass (100%) Pass (100%) Pass (100%)
39 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
40 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
41 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
42 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
Page 2 of 18 IEEE519_2022 Report
42 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
43 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
44 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
45 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
46 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
47 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
48 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
49 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
50 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 3 of 18 IEEE519_2022 Report


Total Harmonic Distortion Full Time Range
The 10min THD of the supply voltage (including all harmonics up to the order 50) shall be less than or equal to the regulation max values
shown in the table below during 95% of each compliance period.
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Parameter Time[%] Regulation max[%] Measured max[%] Result [% within the limits]
V1N 95 1.5 0.97 Pass (100%)
V2N 95 1.5 1.28 Pass (100%)
V3N 95 1.5 0.81 Pass (100%)

Page 4 of 18 IEEE519_2022 Report


Harmonic Voltage Daily
At the PCC, during each period of one day, 99% of the 3sec (very short time) mean r.m.s. values of each individual harmonic voltage shall be
less than or equal to the regulation max values shown in the table below (values are given as percentage of the fundamental harmonic).
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation
Harmonic V1N V2N V3N V1N V2N V3N
Limit[%] max [%]
2 99 1.5 0.11 0.06 0.06 Pass (100%) Pass (100%) Pass (100%)
3 99 1.5 0.47 0.9 0.39 Pass (99.91%) Pass (100%) Pass (100%)
4 99 1.5 0.03 0.02 0.02 Pass (100%) Pass (100%) Pass (100%)
5 99 1.5 0.55 0.63 0.36 Pass (100%) Pass (100%) Pass (100%)
6 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
7 99 1.5 0.75 0.61 0.51 Pass (100%) Pass (100%) Pass (100%)
8 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
9 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
10 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
11 99 1.5 0.33 0.29 0.28 Pass (100%) Pass (100%) Pass (100%)
12 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
13 99 1.5 0.32 0.32 0.11 Pass (100%) Pass (100%) Pass (100%)
14 99 1.5 0.01 0.01 0 Pass (100%) Pass (100%) Pass (100%)
15 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
17 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
18 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
19 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
20 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
23 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
24 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
25 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
26 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
27 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
28 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
29 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
30 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
31 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
32 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
33 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
34 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
35 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
36 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
37 99 1.5 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
38 99 1.5 0.03 0.06 0.05 Pass (100%) Pass (100%) Pass (100%)
39 99 1.5 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
40 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
41 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
42 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
Page 5 of 18 IEEE519_2022 Report
42 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
43 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
44 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
45 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
46 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
47 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
48 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
49 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
50 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 6 of 18 IEEE519_2022 Report


Total Harmonic Distortion Daily
The 3sec THD of the supply voltage (including all harmonics up to the order 50) shall be less than or equal to the regulation max values
shown in the table below during 99% of each period of one day.
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation V1N V2N V3N V1N V2N V3N
Day
Limit[%] max [%]
21-04-2023 99 2.25 0.94 1.15 0.67 Pass (100%) Pass (100%) Pass (100%)
22-04-2023 99 2.25 0.92 1.3 0.77 Pass (100%) Pass (100%) Pass (100%)
23-04-2023 99 2.25 1.04 1.38 0.9 Pass (100%) Pass (100%) Pass (100%)
24-04-2023 99 2.25 1.13 1.46 0.91 Pass (100%) Pass (100%) Pass (100%)
25-04-2023 99 2.25 1 1.21 0.69 Pass (100%) Pass (100%) Pass (100%)
26-04-2023 99 2.25 0.82 1.15 0.7 Pass (100%) Pass (100%) Pass (100%)
27-04-2023 99 2.25 0.86 1.26 0.78 Pass (100%) Pass (100%) Pass (100%)
28-04-2023 99 2.25 0.83 1.26 0.81 Pass (100%) Pass (100%) Pass (100%)

Page 7 of 18 IEEE519_2022 Report


Harmonic Current Full Time Range
During each period of one week, 95% and 99% of the 10 min (Short time) mean r.m.s. values of each individual harmonic current shall be
less than or equal to the regulation max values shown in the table below (values are given as percentage of the maximum demand current IL).
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation
Harmonic I1 I2 I3 I1 I2 I3
Limit[%] max [%]
2 95 1 0.03 0.02 0.02 Pass (100%) Pass (100%) Pass (100%)
2 99 1.5 0.06 0.06 0.06 Pass (100%) Pass (100%) Pass (100%)
3 95 2 0.17 0.43 0.39 Pass (100%) Pass (100%) Pass (100%)
3 99 3 0.2 0.44 0.42 Pass (100%) Pass (100%) Pass (100%)
4 95 1 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
4 99 1.5 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
5 95 2 0.28 0.23 0.28 Pass (100%) Pass (100%) Pass (100%)
5 99 3 0.3 0.27 0.3 Pass (100%) Pass (100%) Pass (100%)
6 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
6 99 1.5 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
7 95 2 0.15 0.17 0.15 Pass (100%) Pass (100%) Pass (100%)
7 99 3 0.16 0.19 0.17 Pass (100%) Pass (100%) Pass (100%)
8 95 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
8 99 3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
9 95 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
9 99 3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
10 95 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
10 99 3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
11 95 1 0.01 0.02 0.02 Pass (100%) Pass (100%) Pass (100%)
11 99 1.5 0.05 0.06 0.05 Pass (100%) Pass (100%) Pass (100%)
12 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
12 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
13 95 1 0.06 0.06 0 Pass (100%) Pass (100%) Pass (100%)
13 99 1.5 0.1 0.1 0.02 Pass (100%) Pass (100%) Pass (100%)
14 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
14 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
15 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
15 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 95 1 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
17 95 0.75 0.08 0.07 0.07 Pass (100%) Pass (100%) Pass (100%)
17 99 1.12 0.11 0.08 0.08 Pass (100%) Pass (100%) Pass (100%)
18 95 0.75 0 0 0 Pass (100%) Pass (100%) Pass (100%)
18 99 1.12 0 0 0 Pass (100%) Pass (100%) Pass (100%)
19 95 0.75 0.45 0.45 0.61 Pass (100%) Pass (100%) Pass (100%)
19 99 1.12 0.5 0.49 0.67 Pass (100%) Pass (100%) Pass (100%)
20 95 0.75 0 0 0 Pass (100%) Pass (100%) Pass (100%)
20 99 1.12 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 95 0.75 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 99 1.12 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 95 0.75 0 0 0 Pass (100%) Pass (100%) Pass (100%)
Page 8 of 18 IEEE519_2022 Report
22 95 0.75 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 99 1.12 0 0 0 Pass (100%) Pass (100%) Pass (100%)
23 95 0.3 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
23 99 0.45 0.03 0.03 0 Pass (100%) Pass (100%) Pass (100%)
24 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
24 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
25 95 0.3 0.14 0.12 0.09 Pass (100%) Pass (100%) Pass (100%)
25 99 0.45 0.16 0.14 0.11 Pass (100%) Pass (100%) Pass (100%)
26 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
26 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
27 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
27 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
28 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
28 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
29 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
29 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
30 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
30 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
31 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
31 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
32 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
32 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
33 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
33 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
34 95 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
34 99 0.45 0 0 0 Pass (100%) Pass (100%) Pass (100%)
35 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
35 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
36 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
36 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
37 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
37 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
38 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
38 99 0.22 0 0.01 0 Pass (100%) Pass (100%) Pass (100%)
39 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
39 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
40 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
40 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
41 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
41 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
42 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
42 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
43 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
43 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
44 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
44 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
45 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
45 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
46 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 9 of 18 IEEE519_2022 Report


46 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
46 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
47 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
47 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
48 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
48 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
49 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
49 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)
50 95 0.15 0 0 0 Pass (100%) Pass (100%) Pass (100%)
50 99 0.22 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 10 of 18 IEEE519_2022 Report


TDD Full Time Range
The 10min TDD (including all harmonics up to the order 50) shall be less than or equal to the regulation max values shown in the table below
during 95% and 99% of each period of compliance period.
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Parame
Time[%] Regulation max[%] Measured max[%] Result [% within the limits]
ter
I1 95 2.5 0.56 Pass (100%)
I2 95 2.5 0.65 Pass (100%)
I3 95 2.5 0.77 Pass (100%)
I1 99 3.75 0.6 Pass (100%)
I2 99 3.75 0.7 Pass (100%)
I3 99 3.75 0.83 Pass (100%)

Page 11 of 18 IEEE519_2022 Report


Harmonic Current Daily
During each period of one week, 99% of the 3sec (very short time) mean r.m.s. values of each individual harmonic current shall be less than
or equal to the regulation max values shown in the table below (values are given as percentage of the maximum demand current IL).
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation
Harmonic I1 I2 I3 I1 I2 I3
Limit[%] max [%]
2 99 2 0.08 0.05 0.08 Pass (100%) Pass (100%) Pass (99.99%)
3 99 4 0.16 0.42 0.36 Pass (99.98%) Pass (99.98%) Pass (99.98%)
4 99 2 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
5 99 4 0.31 0.26 0.29 Pass (99.99%) Pass (100%) Pass (100%)
6 99 2 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
7 99 4 0.1 0.14 0.14 Pass (100%) Pass (100%) Pass (100%)
8 99 4 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
9 99 4 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
10 99 4 0.01 0.01 0.01 Pass (100%) Pass (100%) Pass (100%)
11 99 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
12 99 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
13 99 2 0.22 0.21 0.07 Pass (100%) Pass (100%) Pass (100%)
14 99 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
15 99 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 99 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
17 99 1.5 0.07 0.07 0 Pass (100%) Pass (100%) Pass (100%)
18 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
19 99 1.5 0.29 0.29 0.35 Pass (100%) Pass (100%) Pass (100%)
20 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 99 1.5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
23 99 0.6 0.07 0.07 0 Pass (100%) Pass (100%) Pass (100%)
24 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
25 99 0.6 0.16 0.14 0.08 Pass (100%) Pass (100%) Pass (100%)
26 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
27 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
28 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
29 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
30 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
31 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
32 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
33 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
34 99 0.6 0 0 0 Pass (100%) Pass (100%) Pass (100%)
35 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
36 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
37 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
38 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
39 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
40 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
41 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
42 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
Page 12 of 18 IEEE519_2022 Report
42 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
43 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
44 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
45 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
46 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
47 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
48 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
49 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)
50 99 0.3 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 13 of 18 IEEE519_2022 Report


TDD Daily
The 3sec TDD (including all harmonics up to the order 50) shall be less than or equal to the regulation max values shown in the table below
during 99% of each period of compliance period.
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Measured max [%] Result [% within the limits]


Time Percent Regulation I1 I2 I3 I1 I2 I3
Day
Limit[%] max [%]
21-04-2023 99 5 0.42 0.51 0.52 Pass (99.82%) Pass (99.91%) Pass (99.82%)
22-04-2023 99 5 0.42 0.56 0.59 Pass (100%) Pass (99.86%) Pass (99.93%)
23-04-2023 99 5 0.61 0.73 0.84 Pass (100%) Pass (100%) Pass (100%)
24-04-2023 99 5 0.64 0.75 0.88 Pass (100%) Pass (100%) Pass (100%)
25-04-2023 99 5 0.65 0.72 0.84 Pass (100%) Pass (100%) Pass (100%)
26-04-2023 99 5 0.63 0.68 0.81 Pass (100%) Pass (100%) Pass (100%)
27-04-2023 99 5 0.61 0.69 0.8 Pass (100%) Pass (100%) Pass (100%)
28-04-2023 99 5 0.63 0.73 0.88 Pass (100%) Pass (100%) Pass (100%)

Page 14 of 18 IEEE519_2022 Report


Flicker Severity
Under normal operating conditions, during each period of one week the long term flicker severity Plt caused by voltage fluctuation should be
less than or equal to 1 for 95% of the time.
Start time: 21-04-2023 04:30:00 End time: 28-04-2023 06:30:00

Parameter Time[%] Regulation max Measured max Result [% within the limits]
V1N 95 1 0.416 Pass (100%)
V2N 95 1 0.416 Pass (100%)
V3N 95 1 0.526 Pass (100%)

Page 15 of 18 IEEE519_2022 Report


I T Product
The use of categories is for illustration purposes only and is provided in the event that it is desirable to assess or compare interference
potentials in multiple areas of a particular electrical system.
Start time: 21-04-2023 05:30:00 End time: 28-04-2023 05:30:00

Parameter Measured max[V] Result


V1N 3.579 Category 1
V2N 3.424 Category 1
V3N 2.787 Category 1

Page 16 of 18 IEEE519_2022 Report


Notches
Phase Start time Duration Deviation [% from ref] Notch area

Page 17 of 18 IEEE519_2022 Report


Event Summary
Type Phase Start time Duration Deviation [% from ref]

Page 18 of 18 IEEE519_2022 Report