System Power Requirements

Notifier NFS2-3030 Fire Alarm Control Panel

Protected Premises: First Solar M3&M4 Date:


Address:
City: State: Zip:

Prepared By: Phone:


Address: Email:
City: State: Zip:

AC Branch Current Requirements 5.00 AMPS @ 120 VAC


Current required by source to power the fire
alarm system.

Primary Standby Load 0.84 Amps


Current load on the primary power supply during
non-alarm conditions.

Primary Alarm Load 7.10 Amps


Current load on the primary power supply during
alarm conditions.

Secondary Load Requirements 29.50 Amp Hours


Total Secondary Load from the calculation table below.

Current Draw Time (hours) Total (AH)


Secondary Standby Load Required Standby Time
x
0.837 A 24 hours 20.08
Secondary Alarm Load Required Alarm Time
x
4.500 A 1.000 hours 4.50
Total Secondary Load 24.58
Derating factor x 1.2
Secondary Load Requirements 29.50 AH

Battery Selection 55 Amp Hours


Select batteries from the list below.
55 AH BAT-12550 Battery (12 volt)
Two Four (two 12VDC sets in parallel)
TRUE

Page 1 of 2
Battery Distribution Chart
Shows amp-hour distribution of your selections.

Secondary Alarm Load


10% Spare Battery Capacity

Secondary Standby Load

Secondary Alarm Load


Spare Battery
Secondary Capacity
Standby Load 46%
44%

Comments
1. Battery size exceeds FACP capacity. BB-55 or other external battery box
2. Selected battery size meets secondary load requirements.
3. The selected batteries (55AH) are within the charger range of this power supply (55-200AH).

Spare Battery Capacity 25.50 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 24.10 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 5.40 Secondary Alarm Load (AH) * Derating Factor