HP CO2 FLOW CALCULATIONS

Version 1. 0. 3

Data input file name: Y:\LJY\DILA\CADENCE\PAN ENGINEERING\FIRST SOLAR\2) LV SWITCHGEAR 6.hp


FIRST SOLAR

REMARKS: 2) LV SWITCHGEAR 6 (14.6m x 8.4m x 4.23m(h)


SI units (meters, kilograms, kiloPascals) are specified
Total flooding system for Deep Seated hazard
Nozzle Codes are specified

Agent Storage Conditions

Nominal Storage Pressure is 5171 kPa at 21 degrees Celsius


45 kgs of carbon dioxide is stored in each of 17 cylinders.
Total carbon dioxide discharged is 765 kgs
327 kgs discharged during first two minutes of flow

Pressure Drop Results

Sec Sec Nominal Length Equiv Elev Tee/ Start Term Flow
Start End Pipe Size (m) Length(m) (m) Mfld kPa kPa (kgs/min)

1 2 1/2 80 T 1.8 20.1 1.8 Cyl 5171 5137 9.74


2 3 1 80 T 2.4 11.6 0.0 16 cyl 5137 4888 155.92
3 4 1 80 T 2.4 3.1 2.4 4888 4785 165.66
4 5 1 80 T 3.7 4.4 0.0 4785 4675 165.66
5 6 1 80 T 5.0 5.7 0.0 4675 4509 165.66

6 7 3/4 40 T 3.6 4.9 0.0 BHT 4509 4371 108.15


7 8 3/4 40 T 2.2 3.5 0.0 BHT 4371 4357 54.08
8 9 3/4 40 T 2.4 3.7 0.0 BHT 4357 4357 27.04
8 10 3/4 40 T 2.4 3.7 0.0 BHT 4357 4357 27.04

7 11 3/4 40 T 2.2 3.5 0.0 BHT 4371 4357 54.08


11 12 3/4 40 T 2.4 3.7 0.0 BHT 4357 4357 27.04
11 13 3/4 40 T 2.4 3.7 0.0 BHT 4357 4357 27.04
6 14 3/4 40 T 3.6 4.9 0.0 BHT 4509 4475 57.51

14 15 3/4 40 T 2.2 3.5 0.0 BHT 4475 4475 28.75


14 16 3/4 40 T 2.2 3.5 0.0 BHT 4475 4475 28.75
9 301 3/4 40 T 0.2 0.8 -0.2 4357 4357 27.04
10 302 3/4 40 T 0.2 0.8 -0.2 4357 4357 27.04

12 303 3/4 40 T 0.2 0.8 -0.2 4357 4357 27.04


13 304 3/4 40 T 0.2 0.8 -0.2 4357 4357 27.04
15 305 3/4 40 T 0.2 0.8 -0.2 4475 4475 28.75
16 306 3/4 40 T 0.2 0.8 -0.2 4475 4475 28.75

Calculation based on 25 degree Celsius pre-discharge Pipeline Temperature

1 (Continued)
HP CO2 FLOW CALCULATIONS
Version 1. 0. 3

Data input file name: Y:\LJY\DILA\CADENCE\PAN ENGINEERING\FIRST SOLAR\2) LV SWITCHGEAR 6.hp2

Nozzle Performance Summary

Nozzle Nominal Nozzle Weight (kgs) Initial Vapor Liquid End of Discharge
Number Pipe Size Code Discharged Time (sec) Time (sec) Time (sec)
301 3/4 40 T 5.50 124.9 3.0 196.4 199.4
302 3/4 40 T 5.50 124.9 3.0 196.4 199.4
303 3/4 40 T 5.50 124.9 3.0 196.4 199.4
304 3/4 40 T 5.50 124.9 3.0 196.4 199.4
305 3/4 40 T 5.50 132.8 2.9 196.5 199.4

306 3/4 40 T 5.50 132.8 2.9 196.5 199.4


Total carbon dioxide discharged is 765 kgs

Messages

Hydraulic calculation was successful.


Nozzle codes are fixed. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
The system is calculated using nozzle codes rounded and fixed at nearest 1/2 code. Convergence of
nozzle flow rate and pressure to ±2.5%
Calculation performed on 31/1/2020 4:57:56 PM
Calculation by Unique Fire Industry Sdn Bhd
No 9, Jalan Anggerik Mokara 31/55, Seksyen 31, Kota Kemuning,
Shah Alam Selangor 40460 Malaysia
Telephone: 03-5131-1226
Fax: 03-5131-3826
31/1/2020 Time: 4:58:09 PM

2 End of Printout