Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Device Current Draw

NFS2-3030 Fire Alarm Control Panel


Quantity x [device current draw] = total current draw per device (in amps)
Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm
CPU2-3030 1 x [0.12000] = 0.12000 x [0.12000] = 0.12000 x [0.12000] = 0.12000
NCM-W, NCM-F 1 x [0.11000] = 0.11000 x [0.11000] = 0.11000 x [0.11000] = 0.11000
LCM-320 2 x [0.13000] = 0.26000 x [0.13000] = 0.26000 x [0.13000] = 0.26000
LEM-320 2 x [0.10000] = 0.20000 x [0.10000] = 0.20000 x [0.10000] = 0.20000
NBG-12LX 187 x [0.00038] = 0.07013 x [0.00000] = 0.00000 x [0.00038] = 0.07013
FSP-851 37 x [0.00030] = 0.01110 x [0.00000] = 0.00000 x [0.00030] = 0.01110
XP6-R 1 x [0.00145] = 0.00145 x [0.00000] = 0.00000 x [0.00145] = 0.00145
FMM-101 116 x [0.00035] = 0.04060 x [0.00000] = 0.00000 x [0.00035] = 0.04060
FCM-1 11 x [0.00049] = 0.00534 x [0.00000] = 0.00000 x [0.00049] = 0.00534
FRM-1 71 x [0.00026] = 0.01811 x [0.00000] = 0.00000 x [0.00026] = 0.01811
SLC Loop Device Activation Current 4 x [0.00000] = 0.00000 x [0.20000] = 0.80000 x [0.00000] = 0.00000
Alarm Bell 187 x [0.00000] = 0.00000 x [0.03000] = 5.61000 x [0.00000] = 0.00000

Total (Amperes): 0.8367 A 7.1000 A 0.8367 A

Part Number Qty Secondary Alarm


Total Primary Alarm Load - C2 1 x [4.50000] = 4.50000

Total (Amperes): 4.5000 A