Product data sheet

Specifications

Circuit breaker frame, MasterPact


NW20H2, 2000A, 100kA/440VAC
50/60Hz (Icu), 4 poles, drawout,
without control unit
48295

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product MasterPact NW

Product or component type Basic frame

Device short name MasterPact NW20

Circuit breaker name MasterPact NW20H2

Poles description 4P

Neutral position Left

Network type AC

Breaking capacity code H2

Suitability for isolation Yes conforming to IEC 60947-2

Utilisation category Category B

Complementary
Network frequency 50/60 Hz

Control type Push-button

Mounting mode Drawout

[In] rated current 2000 A at 40 °C

[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 12 kV conforming to IEC 60947-2


voltage

[Icm] rated short-circuit making 187 kA 525 V AC at 50/60 Hz


capacity 187 kA 690 V AC at 50/60 Hz

[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

Circuit breaker CT rating 2000 A

Breaking capacity 85 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2


85 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking 85 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
capacity 85 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2

Protection type Without protection

Mechanical durability 10000 cycles without maintenance conforming to IEC 60947-2


20000 cycles with maintenance conforming to IEC 60947-2

Mar 23, 2023 1


Electrical durability AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
6000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
8000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 6000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 8000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2

Connection pitch 115 mm

[Icw] rated short-time withstand 75 kA 3 s conforming to IEC 60947-2


current 85 kA 1 s conforming to IEC 60947-2

Integral instant protection 171…209 kA

Maximum breaking time 25 ms

Maximum closing response time 70 ms

Height 439 mm

Width 556 mm

Depth 394.5 mm

Environment
Standards IEC 60947-2

Product certifications ASEFA


ASTA

Pollution degree 4 conforming to IEC 60664-1

Ambient air temperature for -25…70 °C


operation

Ambient air temperature for -40…85 °C


storage

Packing Units
Unit Type of Package 1 Db

Number of Units in Package 1 1

Package 1 Height 30.5 cm

Package 1 Width 29.5 cm

Package 1 Length 49.5 cm

Package 1 Weight 49.502 kg

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information Yes

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

PVC free Yes

California proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of
California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or
other reproductive harm. For more information go to www.P65Warnings.ca.gov

2
Mar 23, 2023
Contractual warranty
Warranty 18 months

Recommended replacement(s)

Mar 23, 2023 3