Summary Performance Report For CH43tr CE 208/230vlt

Project: Aeropuerto de Popayan 04/29/2019


Prepared By: 09:44AM

PackagedChillerReport:DoNotEdit;

AquaSnap TM Air-Cooled Scroll Chiller

Unit Information Performance Information


Tag Name: CH43tr CE 208/230vlt Cooling Capacity: 43.17 Tons
Model Number: 30RAP040 Total Compressor Power: 35.79 kW
Quantity: 1 Total Fan Motor Power: 4.323 kW
Manufacturing Source: Charlotte, NC USA Total Unit Power (without pump): 40.11 kW
ASHRAE 90.1: 2013/2016, 2010, 2007 Efficiency (without pump) (EER): 12.92 BTU/Wh
Refrigerant: R-410A IPLV:.IP: 15.25 BTU/Wh
Independent Refrigerant Circuits: 2
Shipping Weight: 2390 lb Accessories and Installed Options
Operating Weight: 2185 lb Micro Channel
Refrigerant Weight (Circuit A): 16 lb Value Sound
Refrigerant Weight (Circuit B): 16 lb BACnet Communications
Unit Length: 89 in Single Point
Unit Width: 93 in Fixed Speed Condenser Fan
Unit Height: 67 in
Chiller Pressure Drop*: 12.0 ft H2O Electrical Information
*Use Chiller Pressure Drop for sizing pumps. This value Unit Voltage: 208/230-3-60 V-Ph-Hz
includes losses due to chiller piping, fittings, 40 mesh factory Connection Type: Single Point
supplied strainer and BPHX.
Electrical Electrical
Evaporator Information Amps Circuit 1 Circuit 2
Fluid Type: Fresh Water MCA 199.6 ---
Fouling Factor: 0.000100 (hr-sqft-F)/BTU MOCP 225.0 ---
Leaving Temperature: 44.00 °F ICF 396.8 ---
Entering Temperature: 54.00 °F Rec Fuse Size 225.0 ---
Fluid Flow: 103.2 gpm
Evaporator Pressure Drop*: 7.31 ft H2O
*Refer to Chiller Pressure Drop for sizing pumps.

Condenser Information
Altitude: 1,770 ft
Number of Fans: 3
Total Condenser Fan Air Flow: 32,000 CFM
Entering Air Temperature: 80.0 °F

Integrated Pump Information


No Pump Selected

An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be analyzed and
guidance provided by applications engineering and a non-corrosive localized environment.

Packaged Chiller Builder NACO 3.59 Page 1 of 3


Summary Performance Report For CH43tr CE 208/230vlt
Project: Aeropuerto de Popayan 04/29/2019
Prepared By: 09:44AM

Sound power measured in accordance with ANSI/AHRI Standard 370-2015.

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI
Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.59 Page 2 of 3


Summary Performance Report For CH43tr CE 208/230vlt
Project: Aeropuerto de Popayan 04/29/2019
Prepared By: 09:44AM

Unit Parameters
Tag Name: CH43tr CE 208/230vlt
Model Number: 30RAP040
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R-410A
Shipping Weight: 2390 lb
Operating Weight: 2185 lb
Refrigerant Weight (Circuit A): 16 lb
Refrigerant Weight (Circuit B): 16 lb 1 - Chiller Height Above Ground
Unit Length: 89 in 2 - Horizontal Distance From Chiller to Receiver
Unit Width: 93 in 3 - Receiver Height Above Ground
Unit Height: 67 in (See Note 3)

Accessories and Installed Options


Micro Channel Single Point
Value Sound Fixed Speed Condenser Fan
BACnet Communications

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load 39 72 79 85 91 91 89 86 81 97
75% Load 39 72 79 85 91 91 89 86 81 97
50% Load 37 70 77 84 90 90 87 84 79 95
25% Load 37 70 77 84 89 90 87 84 79 95

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load 11 44 51 57 63 63 61 58 53 69
75% Load 11 44 51 57 63 63 61 58 53 69
50% Load 9 42 49 56 61 62 59 56 51 67
25% Load 9 42 49 55 61 62 59 56 51 67

Notes: (1) Measurements performed in accordance with AHRI Standard 370-2015 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft