Professional Documents
Culture Documents
Method of Statement For ROO Project
Method of Statement For ROO Project
Method of Statement For ROO Project
This method statement explains and covers the transformer installation & inspection procedure of cast
resin Transformers, although it is applicable for any other type as well. Transformer is used to transform the
high voltage powers to low voltages, so that it is useful for domestic purpose. There are many types of
transformers like oil type, dry type etc. On arrival at project site, transformer shall be inspected and checked
against the relevant general arrangement drawing, approved material submittals etc. Transformer will be off
loaded to the place nearest to the future installation and protected properly from dust and adverse
environmental impacts. The transformer shall be stored in sheltered, clean and dry ambient temperature.
Transformer shall be checked for any signs of damage occurred probably during the transport. If any damage
is found shall be notified to suppliers or relevant parties. The characteristics of the Transformer detailed on
the rating plate shall be checked to those of the shipping documents and with those of the test report, which
is attached to the transformer. Each transformer shall be checked for the accessories, rating, name plate
details, protection devices, indicators & terminal boxes. Compliance of comments raised during factory
inspection shall be checked if any. The Presence of all identifying and warning levels shall be checked. All
material required at site shall be inspected, handled and store properly. Any discrepancies, damage etc, shall
be notified and reported for corrective action. Material found not suitable as per approved material submittal
shall be removed from site. Proper storage shall be provided as per manufacturer recommendation. An
inspection request shall be raised for consultant approval upon receipt of the material at site.
Installation Procedure
All materials received at site shall be inspected and ensured that the materials are as per approved material
submittal. Any discrepancies, damages etc. shall be notified and reported for further action. Material found
not suitable for the project shall be removed from site immediately.
All the Fire Alarm System Outstations, Modules & Control Panels etc. shall be stored in an air-conditioned
place.
25 mm PVC Conduiting for concealed installation. For surface installation, FP200 cable will be clipped on
the soffit on the slab in false ceiling and non-false ceiling areas.
The containment system for Fire Alarm system is being used wherever required and also near the Fire Alarm
control panels.
Correct type of back boxes for all the outstations should be installed as per approved shop drawings /
material submittals.
The mounting heights for the Junction boxes should be verified with approved shop drawings.
Containment System should be offered for QC verification prior to cabling works.
All the related documents like latest approved shop drawings and schematic etc. should be available with
installation team.
FA System Testing:
Comply with "Test Methods" Table in the "Testing" Section of the "Inspection, Testing and Maintenance"
Chapter in NFPA 72.
• Test audible appliances for the public operating mode according to manufacturer's written instructions.
Perform the test using a portable sound-level meter complying with Type 2 requirements in ANSI S1.4.
• Test audible appliances for the private operating mode according to manufacturer's written instructions.
• Test visible appliances for the public operating mode according to manufacturer's written instructions.
• Factory-authorized service representative shall prepare the "Fire Alarm System Record of Completion" in
the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA 72 and the
"Inspection and Testing Form" in the "Records" Section of the "Inspection, Testing and Maintenance"
Chapter in NFPA 72.
• Re-acceptance Testing: Perform re-acceptance testing to verify the proper operation of added or replaced
devices and appliances. Test all the field loop devices with the control panel.
• Check the detectors with the artificial test smoke spray. Use forms developed for initial tests and
inspections.
• Field tests shall be witnessed by authorities having jurisdiction.