Project: Faber Castell 150 kWp
Variant: New simulation variant
PVsyst V7.2.11
VC0, Simulation date:
23/09/22 14:26
with v7.2.11
Project summary
Geographical Site Situation Project settings
Kawasan Industri MM2100 Latitude -6.33 °S Albedo 0.20
Indonesia Longitude 107.10 °E
Altitude 42 m
Time zone UTC+7
Meteo data
Kawasan Industri MM2100
Meteonorm 8.0 (2010-2014), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 272 units Nb. of units 3 units
Pnom total 148 kWp Pnom total 120 kWac
Pnom ratio 1.235
Results summary
Produced Energy 212.5 MWh/year Specific production 1434 kWh/kWp/year Perf. Ratio PR 82.39 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6
PVsyst V7.2.11
VC0, Simulation date:
23/09/22 14:26
with v7.2.11
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / 90 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Jinkosolar Manufacturer Huawei Technologies
Model JKM-545M-72HL4-BDVP Model SUN2000-40KTL-M3-380V
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 545 Wp Unit Nom. Power 40.0 kWac
Number of PV modules 272 units Number of inverters 12 * MPPT 25% 3 units
Nominal (STC) 148 kWp Total power 120 kWac
Modules 16 Strings x 17 In series Operating voltage 200-1000 V
At operating cond. (50°C) Max. power (=>40°C) 44.0 kWac
Pmpp 135 kWp Pnom ratio (DC:AC) 1.24
U mpp 637 V
I mpp 212 A
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 50 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.2.11
VC0, Simulation date:
23/09/22 14:26
with v7.2.11
Main results
System Production
Produced Energy 212.5 MWh/year Specific production 1434 kWh/kWp/year
Performance Ratio PR 82.39 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.11
VC0, Simulation date:
23/09/22 14:26
with v7.2.11
Loss diagram
1756 kWh/m² Global horizontal irradiation
PVsyst V7.2.11
VC0, Simulation date:
23/09/22 14:26
with v7.2.11
Special graphs
Daily Input/Output diagram